Setting Adopted: A Min Fault Current Pick Up Setting (for L1, L2, &L3) i) IKmin = 1100 A ii) Slope = 0.8 (Stabilizing Factor) iii) Diff Current Alarm = 10% of Ikmin. iv) Alarm Time Delay=5s v) Isolator Alarm delay = 15 s
B. Neutral Current System (L0 ) i) IKmin = 50% of Ikmin of L1,L2 ,L3 ii) Slope = 0.8 (Stabilizing Factor) iii) Diff Current Alarm = 10% of Ikmin. iv) Alarm Time Delay=5s v) Isolator Alarm delay = 15 s
20% of In for CT Ratio adopted at 1000/1A ii) T1 = 180ms, T2 = 200ms with Remote trip.
The current pick-up setting can be set the same as for the breaker failure protection
To avoid false tripping after the circuit-breaker has opened, the delay for the end fault protection must be set longer than the time t1 of the breaker failure protection
III. 220KV Bus Bar Protection Relay Type : REB500 Make: ABB
Setting Adopted: A Min Fault Current Pick Up Setting (for L1, L2, &L3) i) IKmin = 900 A ii) Slope = 0.8 (Stabilizing Factor) iii) Diff Current Alarm = 10% of Ikmin. iv) Alarm Time Delay=5s v) Isolator Alarm delay = 15 s
ii) Slope = 0.8 (Stabilizing Factor) iii) Diff Current Alarm = 10% of Ikmin. iv) Alarm Time Delay=5s v) Isolator Alarm delay = 15 s
i) 10% of In for CT Ratio adopted at 1600/1A 20% of In for CT Ratio adopted at 800/1A ii) T1 = 180ms, T2 = 200ms with Remote trip.
The current pick-up setting can be set the same as for the breaker failure protection
To avoid false tripping after the circuit-breaker has opened, the delay for the end fault protection must be set longer than the time t1 of the breaker failure protection
Relay Details: Dead Time Setting : (20ms 99hrs for 1-ph reclosing, Shot 1) (20ms 99hrs for 3-ph reclosing, Shot 1) Adopted Setting : 1 Sec For 1-Ph Autoreclose 3-Ph Autoreclosure to be Blocked
In module RXNAA4, U = 4 x 7.5% = 30 = 1 x 5 =5 In Module RXNAC2H for Umin = 80 and Time Delay = 1 Sec