I.

400KV Bus Bar Protection Relay Type : REB500 Make: ABB

Setting Adopted: A Min Fault Current Pick Up Setting (for L1, L2, &L3) i) IKmin = 1100 A ii) Slope = 0.8 (Stabilizing Factor) iii) Diff Current Alarm = 10% of Ikmin. iv) Alarm Time Delay=5s v) Isolator Alarm delay = 15 s

B. Neutral Current System (L0 ) i) IKmin = 50% of Ikmin of L1,L2 ,L3 ii) Slope = 0.8 (Stabilizing Factor) iii) Diff Current Alarm = 10% of Ikmin. iv) Alarm Time Delay=5s v) Isolator Alarm delay = 15 s

II. BREAKER FAILURE PROTECTION (400KV)

i) 10% of In for CT Ratio adopted at 2000/1A

20% of In for CT Ratio adopted at 1000/1A ii) T1 = 180ms, T2 = 200ms with Remote trip.

END FAULT PROTECTION(400KV)

The current pick-up setting can be set the same as for the breaker failure protection

20% more than In,

To avoid false tripping after the circuit-breaker has opened, the delay for the end fault protection must be set longer than the time t1 of the breaker failure protection

Time Delay = 300ms

III. 220KV Bus Bar Protection Relay Type : REB500 Make: ABB

Setting Adopted: A Min Fault Current Pick Up Setting (for L1, L2, &L3) i) IKmin = 900 A ii) Slope = 0.8 (Stabilizing Factor) iii) Diff Current Alarm = 10% of Ikmin. iv) Alarm Time Delay=5s v) Isolator Alarm delay = 15 s

B. Neutral Current System (L0 ) i) IKmin = 50% of Ikmin of L1,L2 ,L3

ii) Slope = 0.8 (Stabilizing Factor) iii) Diff Current Alarm = 10% of Ikmin. iv) Alarm Time Delay=5s v) Isolator Alarm delay = 15 s

IV. BREAKER FAILURE PROTECTION (220Kv)

i) 10% of In for CT Ratio adopted at 1600/1A 20% of In for CT Ratio adopted at 800/1A ii) T1 = 180ms, T2 = 200ms with Remote trip.

END FAULT PROTECTION:

The current pick-up setting can be set the same as for the breaker failure protection

20% more than In,

To avoid false tripping after the circuit-breaker has opened, the delay for the end fault protection must be set longer than the time t1 of the breaker failure protection

Time Delay = 300ms

IV Auto Reclosure Relay RAAAM (of ABB make)

Relay Details: Dead Time Setting : (20ms 99hrs for 1-ph reclosing, Shot 1) (20ms 99hrs for 3-ph reclosing, Shot 1) Adopted Setting : 1 Sec For 1-Ph Autoreclose 3-Ph Autoreclosure to be Blocked

Reclaim time Setting : (2 - 30s) Adopted Setting : 25 Sec

V Check Synchronising Relay - RASC Adopt following Settings in the Relay

In module RXNAA4, U = 4 x 7.5% = 30 = 1 x 5 =5 In Module RXNAC2H for Umin = 80 and Time Delay = 1 Sec

VI) Pole Discrepancy Timer RXKF1

Pole Discrepancy Timer RXKF1 to be set at 3 Sec.