Professional Documents
Culture Documents
Specification For: Sensitive Earth Fault Relay
Specification For: Sensitive Earth Fault Relay
Specification For: Sensitive Earth Fault Relay
Specification for
CONTENTS Page
1. Scope 1
2.
System Parameters
3. 4. 5. 6. 7. 8. 9. 10.
Service Conditions Applicable Standards Basic Features Minimum Technical Requirements Additional Requirements Information to be Supplied with the offer Technical Literature & Drawings Inspection and Testing 1 2 2 3 4 5
This specification covers the Design and Manufacture & Testing of Sensitive Earth Fault Relay to cater for high resistance earth faults which remain undetected by the main protection and shall comprise a definite time over-current relay. 2.0 SYSTEM PARAMETERS (a) (b) (c) (d) (e) 3.0 Nominal Voltage System Highest Voltage System Frequency Earthing of System Fault Level : 11kV : : : : 12kV 50 Hz. Solidly earthed 13.1 kA
SERVICE CONDITIONS (a) (b) (c) (d) (e) Annual average ambient temperature Maximum ambient temperature Maximum relative humidity Environmental Condition Operational Altitude : : : : : 300C 400C 90% Humid tropical climate with polluted atmosphere
4.0
APPLICABLE STANDARDS IEC IEC 255 68 2-1 2-2 2-3 Electrical Relays Environmental Testing Degrees of protection provided by enclosures (IP Code)
IEC 5.0
529
BASIC FEATURES 5.1 The equipment shall conform to the relevant standards specified in Clause 4.0 above. They shall be intrinsically safe, of compact light weight design and suitable for Indoor use.
5.2
The relays shall be of withdrawable type. When withdrawing the relay from the casing, opening of d.c. auxiliary circuits and shorting of CT inputs shall take place automatically, with auxiliary circuits opening first and shorting of CT inputs subsequently. The relay shall be provided with a test block.
The relay shall be supplied as a single phase unit, suitable for flush mounting on Panel. The relay shall be of non-directional type. For every 10 Nos. of relays one test plug with testing leads shall be supplied. The relay shall be rendered immune to third harmonic components.
MINIMUM TECHNICAL REQUIREMENTS Setting Ranges Reset Current Reset Time Burden Impulse Withstand : : : : Current setting shall be adjustable between 1% and 15% of the rated current. Relay shall reset at greater than 95% of the operating current. Less than 25 ms. : Shall not be mores than .005 VA at setting
The relay shall withstand impulse of 5 kV peak and 1/50 micro-second, wave form applied both transversely and between relay terminals and earth, in accordance with IEC 255-5 Clause. 5A
Rated Current
: : :
50Hz, 0.05 % Third harmonic rejection shall not be less than 25 : 1 0.1 to 9.9 sec. In steps of 0.1
: : :
2 x rated current continuously 50 x rated current for 1 sec. 25 x rated current for 3 sec. The equipment shall withstand 2kV rms for 1 minute between all case terminals connected together and the case. 2 kV rms for 1 minute between independent circuits of the Scheme, including contact circuits. 1 kV rms 1 minute across the contacts of the normally open outgoing contact pairs (IEC 2555).
: The relay shall comply with the requirements of draft IEC test recommendation for the High Frequency Disturbance Test. The accuracy of relay shall not be affected by repetitive 1 MHz bursts having an initial peak of 1.0 kV superimposed across the terminals of each independent circuit and 2.5 kV between independent circuits, and circuit to earth, with a delay time 3 to 6 microseconds and with a repetition rate of 400 bursts per second. The rates shall be performed with the relay energized (IEC 255-22-1 Class III)
7.0
Equipment shall be suitable packed to prevent damage during handling and transport. Each packing shall carry details of the equipment such as name of manufacturer, country of origin and weight etc. 7.2 7.2.1 Markings & Data The following data (with indications of the Units) shall be made available by the Manufacturer; a) b) manufacturers name or trade-mark type designation and serial number
c) d) e) f) g)
rated value of the auxiliary energizing quantity value of the limits of the operative range of the auxiliary energizing quantity frequency for a.c. or the symbol for d.c. contact data (see IEC Publication 255-0-20) rated value or setting range of the specified time either for pick-up or for drop-out and the corresponding accuracy class index data a permit identification of the coil(s) and energizing circuits value of the resistance of winding (s) rated burden (power) dielectric test voltage(s) mechanical durability expressed in number of cycles mounting position data to permit the suitable connection of the relay; including polarity accessories, if essential to the relay performance data concerning the earthing of metal parts duty if the relay has any unusual feature or requirements, it shall be marked prominently with the symbol 1 to indicate that reference to the detailed specification is essential.
h) i) j) k) l) m) n) o) p) q) r)
7.2.2
Requirements for Marking Data a), b) and if applicable r) shall be marked on the relay by a durable method so that they are legible with the relay mounted as in service. Data c) 3), g) and h) if not implicit in b), shall be marked on the relay without necessary being visible, with the relay mounted as in service.
8.0
INFORMATION TO BE SUPPLIED WITH THE OFFER The following shall be furnished with the offer. (a) (b) Catalogues describing the technical features of equipment and indicating the Model Number. Constructional feature Performance Certificates of performance with regard to manufacture, supply and utilization of the relays of same type, and design offered. (d) A list of names and addresses of purchasers giving year of delivery and quantities supplied during the past five years. Type Test Certificates
. (c)
(d)
Test Certificates with performance curves of the Type Tests performed conforming to with the standards specified. The Test Certificates shall clearly identify the equipment concerned showing the Manufacturer's identity, type number and basic technical parameters and shall be issued by an Internationally recognised Independent Testing Authority acceptable to the purchaser. 9.0 TECHNICAL LITERATURE AND DRAWINGS The selected Tenderer shall supply along with the equipment relevant drawings and technical literature including operation, testing, commissioning and maintenance if the relay. 10.0 INSPECTION AND TESTING The selected tenderer may have to make necessary arrangements for inspection by a Representative of the Purchaser if same is deemed necessary and also to carry out in his presence necessary routine tests of the equipment offered, where the purchaser will bear the cost of personnel and travelling expenditure of this representatives.
ANNEX - A
DATE :