MiCOM P341

Interconnection Protection Relay P341/EN PM/F74


Version 36

PICS & MICS

Note:

The technical manual for this device gives instructions for its installation, commissioning, and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate Schneider Electric technical sales office and request the necessary information. Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric including settlements of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the technical manual. This device MUST NOT be modified. If any modification is made without the express permission of Schneider Electric, it will invalidate the warranty, and may render the product unsafe.

The Schneider Electric logo and any alternative version thereof are trademarks and service marks of Schneider Electric. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. This manual is provided for informational use only and is subject to change without notice. 2011, Schneider Electric. All rights reserved.

P341

PICS & MICS

CONTENTS
1 PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS) 1.1 Introduction 1.2 ACSI basic conformance statement 1.3 ACSI models conformance statement 1.4 ACSI service conformance statement MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) 2.1 Introduction 2.2 Objective 2.3 Logical Device definitions
2.3.1 IEC 61850 Logical Device data model

5 5 5 5 7 11 11 11 11
11

2.4
2.4.1 2.4.2 2.4.3 2.4.4 2.4.5 2.4.6 2.4.7 2.4.8 2.4.9 2.4.10 2.4.11 2.4.12 2.4.13 2.4.14 2.4.15 2.4.16 2.4.17 2.4.18 2.4.19 2.4.20 2.4.21 2.4.22 2.4.23 2.4.24 2.4.25 2.4.26 2.4.27 2.4.28 2.4.29 2.4.30 2.4.31

Logical Node definitions


Logical Node: CILO_INTERLOCK Logical Node: GGIO_ALM_96 Logical Node: GGIO_IND_24 Logical Node: GGIO_IND_32 Logical Node: GGIO_IND_32_CTRL Logical Node: GGIO_IND_64 Logical Node: GGIO_IND_8 Logical Node: LLN0_CONTROL Logical Node: LLN0_P341 Logical Node: LLN0_STANDARD Logical Node: LLN0_SYSTEM Logical Node: LPHD_STANDARD Logical Node: MMTR_PRIV Logical Node: MMXU_CSV Logical Node: MMXU_DERIVED_P341 Logical Node: MMXU_DFDT Logical Node: MMXU_RMS Logical Node: MMXU_SENSITIVE Logical Node: MMXU_STANDARD_P341 Logical Node: MMXU_THIRD_HARMONIC_NO_VN Logical Node: MSQI_ALL Logical Node: MSTA_STANDARD Logical Node: PDIF_NEU Logical Node: PFRC_NO_SEG Logical Node: PLMP_NEU Logical Node: PPWR_NORMAL Logical Node: PTOC_NEU Logical Node: PTOC_NO_SEG Logical Node: PTOF_NO_SEG Logical Node: PTOV_NEU Logical Node: PTOV_NO_SEG

16
17 17 20 21 22 23 24 25 25 26 26 26 27 27 27 28 28 28 29 29 29 29 30 30 30 30 31 31 31 31 32

P341/EN PM/F74-S

(PM)-1

PICS & MICS

P341

2.4.32 2.4.33 2.4.34 2.4.35 2.4.36 2.4.37 2.4.38 2.4.39 2.4.40 2.4.41 2.4.42 2.4.43

Logical Node: PTRC_NO_SEG Logical Node: PTTR_NO_SEG_PRIV Logical Node: PTUC_NEU Logical Node: PTUF_NO_SEG Logical Node: PTUV_NO_SEG Logical Node: PVSP_STANDARD Logical Node: RBRF_EXTTRIP Logical Node: RCLI_STANDARD Logical Node: RDRE_BASIC Logical Node: RSYN_DIFCLC Logical Node: RVCS_STANDARD_NO_CT2 Logical Node: XCBR_BASIC_ALL

32 32 33 33 33 33 34 34 34 34 35 35

2.5
2.5.1 2.5.2 2.5.3 2.5.4 2.5.5 2.5.6 2.5.7 2.5.8 2.5.9 2.5.10 2.5.11 2.5.12 2.5.13 2.5.14 2.5.15 2.5.16 2.5.17 2.5.18 2.5.19 2.5.20 2.5.21 2.5.22 2.5.23 2.5.24 2.5.25 2.5.26 2.5.27 2.5.28 2.5.29 2.5.30 2.5.31 2.5.32 2.5.33

Common Data Class definitions


Common Data Class: ACD_NO_SEG Common Data Class: ACT_NO_SEG Common Data Class: ASG_FLOAT Common Data Class: BCR_PRIV Common Data Class: CMV_MAG_ANG_FLOAT Common Data Class: CMV_MAG_FLOAT Common Data Class: DEL_SEG Common Data Class: DEL_SEG_NS Common Data Class: DPC_STATUS_P341 Common Data Class: DPL_STANDARD Common Data Class: INC_CTRL_PRIV Common Data Class: INC_MOD Common Data Class: INS_BASIC Common Data Class: INS_BEH Common Data Class: INS_BEH_D_PRIV Common Data Class: INS_CB_OPCAP Common Data Class: INS_HEALTH Common Data Class: LPL_LLN0 Common Data Class: LPL_LN Common Data Class: LPL_LN_P Common Data Class: MV_FLOAT Common Data Class: MV_FLOAT_NS Common Data Class: SEQ_MAG_ANG Common Data Class: SPC_CONTROL Common Data Class: SPC_CTRL_PRIV Common Data Class: SPC_STATUS Common Data Class: SPS_D Common Data Class: SPS_WD Common Data Class: SPS_WD_NS Common Data Class: WYE_RES_ANG_D Common Data Class: WYE_RES_ANG_D_NS Common Data Class: WYE_RES_MAG_NS Common Data Class: WYE_SEG

36
36 37 37 37 37 38 38 39 39 39 40 40 40 41 41 41 41 42 42 42 42 43 44 44 44 45 45 45 46 46 46 46 47

(PM)-2

P341/EN PM/F74-S

P341

PICS & MICS

2.5.34 2.5.35

Common Data Class: WYE_SEG_NS Common Data Class: WYE_SEG_PHASEA

47 47

2.6
2.6.1 2.6.2 2.6.3 2.6.4 2.6.5 2.6.6

Common data attribute type definitions


Component: AnalogueValue_Float Component: Originator Component: RangeConfig_Deadband Component: Unit_multiplier Component: Vector_Magnitude_Float Component: Vector_MagnitudeAngle_Float

47
47 48 48 48 48 49

2.7
2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.7.7 2.7.8 2.7.9 2.7.10 2.7.11 2.7.12 2.7.13

Enumerated type definitions


Enumerated type: AddCause Enumerated type: Beh Enumerated type: Bypass Enumerated type: CBOpCap Enumerated type: ctlModel Enumerated type: Dbpos Enumerated type: dir Enumerated type: Health Enumerated type: Mod Enumerated type: multiplier Enumerated type: orCategory Enumerated type: seqT Enumerated type: SIUnit

49
49 49 50 50 50 50 50 51 51 51 52 52 52

2.8

MMS data-type conversions

54

P341/EN PM/F74-S

(PM)-3

PICS & MICS

P341

(PM)-4

P341/EN PM/F74-S

P341

PICS & MICS

PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS)


Introduction
This specification is the Protocol Implementation Conformance Statement (PICS) and presents the ACSI conformance statements as defined in Annex A of Part 7-2 of the IEC 61850 standard specifications.

1.1

1.2

ACSI basic conformance statement


The basic conformance statement shall be as defined in Table 1.
Client-Server roles B11 B12 SCSMs supported B21 B22 B23 B24 Generic substation event model (GSE) B31 B32 Transmission of sampled value model (SVC) B41 B42 Y = supported N or empty = not supported Publisher side Subscriber side Publisher side Subscriber side Y Y SCSM: IEC 6185-8-1 used SCSM: IEC 6185-9-1 used SCSM: IEC 6185-9-2 used SCSM: other Y Server side (of TWO-PARTYAPPLICATION-ASSOCIATION) Client side of (TWO-PARTYAPPLICATION-ASSOCIATION) Client/ subscriber Y Server/ publisher Value/ comments

Table 1: Basic conformance statement

1.3

ACSI models conformance statement


The ACSI models conformance statement shall be as defined in Table 2.
Client/ subscriber If Server or Client side (B11/12) is supported M1 M2 M3 M4 Logical Device Logical Node Data Data set Y Y Y Y Server/ publisher Value/ comments

P341/EN PM/F74-S

(PM)-5

PICS & MICS

P341

Client/ subscriber M5 M6 M7 M7-1 M7-2 M7-3 M7-4 M7-5 M7-6 M7-7 M7-8 M7-9 M7-10 M7-11 M8 M8-1 M8-2 M8-3 M8-4 M8-5 M8-6 M8-7 M8-8 M8-9 Logging M9 M9-1 M10 M11 If GSE (B31/32) is supported M12 M13 If SVC (41/42) is supported M14 M15 If Server or Client side (B11/12) is supported M16 M17 Time File Transfer Y Multicast SVC Unicast SVC GOOSE GSSE Y Control Log Log control IntgPd Substitution Setting group control Reporting Buffered report control sequence-number report-time-stamp reason-for-inclusion data-set-name data-reference buffer-overflow entryID BufTim IntgPd GI conf-revision Unbuffered report control sequence-number report-time-stamp reason-for-inclusion data-set-name data-reference BufTim IntgPd GI conf-revision

Server/ publisher Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y

Value/ comments

Y Y

Time source with required accuracy shall be available.

(PM)-6

P341/EN PM/F74-S

P341

PICS & MICS

Client/ subscriber Y = service is supported N or empty = service is not supported

Server/ publisher

Value/ comments

Table 2: Models conformance statement

1.4

ACSI service conformance statement


The ACSI service conformance statement shall be as defined in Table 3 (depending on the statements in Table 1).
Services Server S1 Application association S2 S3 S4 Logical Device S5 Logical Node S6 S7 Data S8 S9 S10 S11 Data set S12 S13 S14 S15 S16 Substitution S17 SetDataValues TP GetDataSetValues SetDataSetValues CreateDataSet DeleteDataSet GetDataSetDirectory TP TP TP TP TP Y Y GetDataValues SetDataValues GetDataDirectory GetDataDefinition TP TP TP TP Y Y Y Y LogicalNodeDirectory GetAllDataValues TP TP Y Y LogicalDeviceDirectory TP Y Associate Abort Release Y Y Y ServerDirectory TP Y AA: TP/MC Client (C) Server (S) Comments

P341/EN PM/F74-S

(PM)-7

PICS & MICS

P341

Services Setting group control S18 S19 S20 S21 S22 S23 Reporting Buffered report control block (BRCB) S24 S24-1 S24-2 S24-3 S25 S26 Unbuffered report control block (URCB) S27 S27-1 S27-2 S27-3 S28 S29 Logging Log control block S30 S31 Log S32 S33 S34 Generic substation event model (GSE) GOOSE-CONTROLBLOCK S35 S36 S37 SendGOOSEMessage GetReference GetGOOSEElementNumber QueryLogByTime QueryLogByEntry GetLogStatusValues GetLCBValues SetLCBValues Report data-change (dchg) qchg-change (qchg) data-update (dup GetURCBValues SetURCBValues Report data-change (dchg) qchg-change (qchg) data-update (dupd) GetBRCBValues SetBRCBValues SelectActiveSG SelectEditSG SetSGValues ConfirmEditSGValues GetSGValues GetSGCBValues

AA: TP/MC TP TP TP TP TP TP

Client (C)

Server (S) Y

Comments

Y Y

TP

Y Y

TP TP

Y Y

TP

Y Y

TP TP

Y Y

TP TP TP TP TP

MC TP TP

IED supports GOOSE publish & subscription.

(PM)-8

P341/EN PM/F74-S

P341

PICS & MICS

Services S38 S39 GSSE-CONTROLBLOCK S40 S41 S42 S43 S44 Transmission of sampled value model (SVC) Multicast SVC S45 S46 S47 Unicast SVC S48 S49 S50 Control S51 S52 S53 S54 S55 S56 File transfer S57 S58 GetFile SetFile Select SelectWithValue Cancel Operate CommandTermination TimeActivated-Operate SendUSVMessage GetUSVCBValues SetUSVCBValues SendMSVMessage GetMSVCBValues SetMSVCBValues SendGSSEMessage GetReference GetGSSEElementNumber GetGsCBValues SetGsCBValues GetGoCBValues SetGoCBValues

AA: TP/MC TP TP

Client (C)

Server (S) Y Y

Comments

MC TP TP TP TP

MC TP TP TP TP TP

Y TP TP TP TP TP Y Y Y Y

TP TP

Y Only from /dr_unextracted/ Operation may only be performed on .cfg files.

S59

DeleteFile

TP

S60 Time T1 T2

GetFileAttributeValues

TP

Time resolution of internal clock Time accuracy of internal clock

1 ms 1 ms

Nearest negative power of 2 in seconds. T0 T1

P341/EN PM/F74-S

(PM)-9

PICS & MICS

P341

Services

AA: TP/MC

Client (C)

Server (S) T2 T3 T4 T5

Comments

T3

Supported TimeStamp resolution

1 ms

Nearest negative power of 2 in seconds.

Table 3: Service conformance statement AA: Application association type TP: Two part (for MMS) MC: Multicast (for GOOSE and SMV)

(PM)-10

P341/EN PM/F74-S

P341

PICS & MICS

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)


Introduction
This specification is the Model Implementation Conformance Statement (MICS) and presents the top-level IEC 61850 data model that has been implemented. The definitions of all used Logical Nodes and their associated Common Data Classes, components and associated enumerated values are also included for completeness. The reader is expected to be conversant with the terminology presented within the IEC 61850 part 7 series of specifications.

2.1

2.2

Objective
To provide comprehensive details of the standard data object model elements supported by the device. The MICS is conformant to the devices associated ICD (Substation Configuration Language) file, according to part 6 of the IEC 61850 standards. The layout of the presented tables within this document are conformant to the part 7 series of the IEC 61850 standard specifications with the following exceptions: The "Trigger Options" field is not presented The "M/O" field is not present as the definitions are as deployed within the model An additional column "X" is used to signify Schneider Electric custom attributes

2.3

Logical Device definitions


The MiCOM relay implements an IEC 61850 server that can contain one or more Logical Devices. Each Logical Device contains a data model built from instances of specific Logical Nodes and must consist of at least an instance of the LPHD Logical Node (which is responsible for providing physical device information) and an instance of the LLN0 Logical Node (for addressing common issues across the Logical Device). The IEC 61850 data model is contained within the Logical Devices detailed in the table below. All MiCOM devices will name the supported Logical Devices consistently to ensure that data model variables with the same purpose will have the same name within each MiCOM server.
Logical Device Control Measurements Protection Records System P341 Control P341 Measurements P341 Protection P341 Records P341 System Comment/Usage

2.3.1

IEC 61850 Logical Device data model


The IEC 61850 Logical Device top-level data model consists of instances of Logical Nodes. The data model name for a Logical Node instance is constructed from an optional prefix (known as the wrapper), the Logical Node name, and an instance ID (or suffix). The presented data model is in an alphabetically sorted order, rather than a logical order, because this is the natural order of the data when presented by a native MMS browser. (Higher level browsers can of course impart any ordering that they desire).

P341/EN PM/F74-S

(PM)-11

PICS & MICS

P341

LD Control

LN Instance

LN Type

Description System Checks Check Sync 1 System Checks Check Sync 2 XCBR Interlocking LLN0 for control LD Physical Device Information Circuit Breaker Monitoring for All Module df/dt Measurements Logical Device Physical Device Information Primary C/S Measurements Primary Fourier Derived Measurands P341 only Primary Fixed demand measurements

AscRSYN1 AscRSYN2 CILO1 LLN0 LPHD1 XCBR1 Measurements DfpMMXU1 LLN0 LPHD1 PriCsvMMXU1 PriFouMMXU1

RSYN_DIFCLC RSYN_DIFCLC CILO_INTERLOCK LLN0_CONTROL LPHD_STANDARD XCBR_BASIC_ALL

MMXU_DFDT LLN0_STANDARD LPHD_STANDARD MMXU_CSV MMXU_DERIVED_P341

PriFxdMSTA1

MSTA_STANDARD

PriHa3MMXU1

P341/P342 only third harmonic MMXU_THIRD_HARMONIC_NO_VN measurements (no VN) MMTR_PRIV MSTA_STANDARD MMXU_RMS MSTA_STANDARD MMXU_SENSITIVE MSQI_ALL Primary based Energy flow metering quantities Primary Peak demand measurements Primary RMS measurements Primary Rolling demand measurements Primary Sensitive power measurements Primary Sequence measurements Primary Standard MMXU measurements for P341 only Secondary C/S Measurements Secondary Fourier Derived Measurands P341 only

PriMMTR1 PriPkdMSTA1 PriRmsMMXU1 PriRodMSTA1 PriSenMMXU1 PriSeqMSQI1

PriStdMMXU1

MMXU_STANDARD_P341

SecCsvMMXU1 SecFouMMXU1

MMXU_CSV MMXU_DERIVED_P341

(PM)-12

P341/EN PM/F74-S

P341

PICS & MICS

LD

LN Instance SecFxdMSTA1

LN Type MSTA_STANDARD

Description Secondary Fixed demand Measurements

SecHa3MMXU1

Secondary P341/P342 only Third MMXU_THIRD_HARMONIC_NO_VN Harmonic Measurements MMTR_PRIV Secondary based Energy flow metering quantities Secondary Peak Demand measurements Secondary RMS measurements Secondary Rolling Demand measurements Secondary Sensitive Power measurements Secondary Sequence measurements Secondary Standard MMXU measurements for P341 only CB Fail 1 CB Fail 2 CLIO Input 1 Alarm CLIO Input 2 Alarm CLIO Input 3 Alarm CLIO Input 4 Alarm Current loop input supervision - channel 1 Current loop input supervision - channel 2 Current loop input supervision - channel 3 Current loop input supervision - channel 4 Current Loop Input 1 Trip Current Loop Input 2 Trip Current Loop Input 3 Trip Current Loop Input 4 Trip

SecMMTR1

SecPkdMSTA1 SecRmsMMXU1 SecRodMSTA1 SecSenMMXU1 SecSeqMSQI1

MSTA_STANDARD MMXU_RMS MSTA_STANDARD MMXU_SENSITIVE MSQI_ALL

SecStdMMXU1 Protection CbfRBRF1 CbfRBRF2 CliAlmPTUC1 CliAlmPTUC2 CliAlmPTUC3 CliAlmPTUC4 CliRCLI1

MMXU_STANDARD_P341

RBRF_EXTTRIP RBRF_EXTTRIP PTUC_NEU PTUC_NEU PTUC_NEU PTUC_NEU RCLI_STANDARD

CliRCLI2

RCLI_STANDARD

CliRCLI3

RCLI_STANDARD

CliRCLI4 CliTrpPTUC1 CliTrpPTUC2 CliTrpPTUC3 CliTrpPTUC4

RCLI_STANDARD PTUC_NEU PTUC_NEU PTUC_NEU PTUC_NEU

P341/EN PM/F74-S

(PM)-13

PICS & MICS

P341

LD

LN Instance ConPLMP1 DfpPFRC1 DfpPFRC2 DfpPFRC3 DfpPFRC4 EftPTOC1 EftPTOC2 EftPTOC3 EftPTOC4 FrqPTOF1 FrqPTOF2 FrqPTUF1 FrqPTUF2 FrqPTUF3 FrqPTUF4 LLN0 LPHD1 NpsPTOC1 NpsPTOC2 NpsPTOC3 NpsPTOC4 NpsPTOV1 OcpPTOC1 OcpPTOC2 OcpPTOC3 OcpPTOC4 PdpPPWR1 PdpPPWR2 PTRC1 SenPdpPPWR1 PLMP_NEU

LN Type

Description Reconnection timer df/dt> 1 Frequency Rate of Change df/dt> 2 Frequency Rate of Change df/dt> 3 Frequency Rate of Change df/dt> 4 Frequency Rate of Change Earth fault - stage 1 Earth fault - stage 2 Earth fault - stage 3 Earth fault - stage 4 F> 1 Overfrequency F> 2 Overfrequency F< 1 Underfrequency F< 2 Underfrequency F< 3 Underfrequency F< 4 Underfrequency LLN0 for P341 Physical Device Information NPS Overcurrent stage 1 NPS Overcurrent stage 2 NPS Overcurrent stage 3 NPS Overcurrent stage 4 NPS Overvoltage I>1Phase overcurrent I>2 Phase overcurrent I>3 Phase overcurrent I>4 Phase overcurrent Power protection (3phase) stage 1 Power protection (3phase) stage 2 Trip Conditioning Sensitive power (Single phase) stage 1 Sensitive power (Single phase) stage 2 IREF> 1 Restricted Earth Fault ISEF>1 Protection

PFRC_NO_SEG PFRC_NO_SEG PFRC_NO_SEG PFRC_NO_SEG PTOC_NO_SEG PTOC_NO_SEG PTOC_NO_SEG PTOC_NO_SEG PTOF_NO_SEG PTOF_NO_SEG PTUF_NO_SEG PTUF_NO_SEG PTUF_NO_SEG PTUF_NO_SEG LLN0_P341 LPHD_STANDARD PTOC_NEU PTOC_NEU PTOC_NEU PTOC_NEU PTOV_NEU PTOC_NEU PTOC_NEU PTOC_NEU PTOC_NEU PPWR_NORMAL PPWR_NORMAL PTRC_NO_SEG PPWR_NORMAL

SenPdpPPWR2 SenRefPDIF1 SenSefPTOC1

PPWR_NORMAL PDIF_NEU PTOC_NO_SEG

(PM)-14

P341/EN PM/F74-S

P341

PICS & MICS

LD

LN Instance SenSefPTOC2 SenSefPTOC3 SenSefPTOC4 SvnRVCS1 ThmPTTR1 VtpPhsPTOV1 VtpPhsPTOV2 VtpPhsPTUV1 VtpPhsPTUV2 VtpResPTOV1 VtpResPTOV2 VtpResPTOV3 VtpResPTOV4 VvsPVSP1

LN Type PTOC_NO_SEG PTOC_NO_SEG PTOC_NO_SEG RVCS_STANDARD_NO_CT2 PTTR_NO_SEG_PRIV PTOV_NO_SEG PTOV_NO_SEG PTUV_NO_SEG PTUV_NO_SEG PTOV_NO_SEG PTOV_NO_SEG PTOV_NO_SEG PTOV_NO_SEG PVSP_STANDARD

Description ISEF>2 Protection ISEF>3 Protection ISEF>4 Protection Supervision without CTS2. Thermal Overload Phase Overvoltage stage 1 Phase Overvoltage stage 2 Phase Undervoltage Stage 1 Phase Undervoltage Stage 2 Residual Over Voltage - stage 1 Residual Over Voltage - stage 2 Residual Over Voltage - stage 3 Residual Over Voltage - stage 4 Voltage vector shift Records Logical Device Physical Device Information Disturbance Recorder Alarms GOOSE Input Signals GOOSE Output Signals 8 programmable LEDS Sys Logical Device Physical Device Information Opto Inputs (24 off) (64 off)Uniqueness of control "Order Running" indications for Control operations Controllable Inputs

Records LLN0 LPHD1 RDRE1 System AlmGGIO1 GosGGIO1 GosGGIO2 LedGGIO1 LLN0 LPHD1 OptGGIO1 OrdRunGGIO1 PloGGIO1 GGIO_ALM_96 GGIO_IND_64 GGIO_IND_32 GGIO_IND_8 LLN0_SYSTEM LPHD_STANDARD GGIO_IND_24 GGIO_IND_64 GGIO_IND_32_CTRL LLN0_STANDARD LPHD_STANDARD RDRE_BASIC

P341/EN PM/F74-S

(PM)-15

PICS & MICS

P341

LD

LN Instance RlyGGIO1

LN Type GGIO_IND_24

Description Output Contacts (24 off)

2.4

Logical Node definitions


The definition tables for each of the Logical Nodes in the top-level data model are presented in the following sub-sections. The following table presents a summary of the Logical Node templates used across the Logical Devices within the overall IEC 61850 product data model:
LN Type CILO_INTERLOCK GGIO_ALM_96 GGIO_IND_24 GGIO_IND_32 GGIO_IND_32_CTRL GGIO_IND_64 GGIO_IND_8 LLN0_STANDARD LLN0_SYSTEM LLN0_P341 LLN0_CONTROL LPHD_STANDARD MMTR_PRIV MMXU_CSV MMXU_DERIVED_P341 MMXU_DFDT MMXU_RMS MMXU_SENSITIVE MMXU_STANDARD_P341 MMXU_THIRD_HARMONIC _NO_VNMSQI_ALL MSTA_STANDARD PDIF_NEU PFRC_NO_SEG (LN (CILO) (GGIO) (GGIO) (GGIO) (GGIO) (GGIO) (GGIO) (LLN0) (LLN0) (LLN0) (LLN0) (LPHD) (MMTR) (MMXU) (MMXU) (MMXU) (MMXU) (MMXU) (MMXU) (MMXU) (MSQI) (MSTA) (PDIF) (PFRC) Description Control Interlocking Generic Process I/O (w.r.t 96 Alarm Elements) Generic Process I/O Generic Process I/O (w.r.t 32 Indication Elements) Generic Process I/O Generic Process I/O(w.r.t 64 Indication Elements) Generic Process I/O (w.r.t 8 Indication Elements) General Logical Node 0 System Logical Node 0 Logical Node 0 Control Domain Logical Node 0 Px40 Physical Device Information Metering Measurements for C/S Standard measurements (w.r.t Standard Values - P341) Standard measurements(for dfdt only) Measurements (RMS values) Sensitive measurements Standard measurements (w.r.t Fourier Derived Values - P341) Name Space IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003

Measurements (w.r.t 3rd Harmonic, no VN IEC 61850-7-4:2003 for P341/P342) Sequence and imbalance (w.r.t Pos, Neq, IEC 61850-7-4:2003 Zero) Standard measurements (w.r.t Fourier Derived Values) Differential (w.r.t Neutral) Rate of change of frequency (w.r.t No Phase Segregation) IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003

PLMP_NEU PPWR_NORMAL

(PLMP) (PPWR)

Loss of mains protection, similar to PTOC but without current setting and modified SE-SII:PCS-Px40 meanings for the pick up and drop off timers Power Protection with Pole Dead Inhibit SE-SII:PCS-Px40

(PM)-16

P341/EN PM/F74-S

P341

PICS & MICS

LN Type PTOC_NEU PTOC_NO_SEG PTOF_NO_SEG PTOV_NEU PTOV_NO_SEG PTRC_NO_SEG PTTR_NO_SEG_PRIV PTUC_NEU PTUF_NO_SEG PTUV_NO_SEG PVSP_STANDARD RBRF_EXTTRIP RCLI_STANDARD RDRE_BASIC RSYN_DIFCLC RVCS_STANDARD_NO_C T2XCBR_BASIC_ALL

(LN (PTOC) (PTOC) (PTOF) (PTOV) (PTOV) (PTRC) (PTTR) (PTUC) (PTUF) (PTUV) (PVSP) (RBRF) (RCLI) (RDRE) (RSYN) (RVCS) (XCBR)

Description Timed Overcurrent (w.r.t Neutral) Timed Overcurrent (w.r.t No Phase Segregation) Overfrequency (w.r.t No Phase Segregation) Overvoltage (w.r.t Neutral) Overvoltage (w.r.t Phase Segregation) Protection trip conditioning (w.r.t No Phase Segregation) Thermal overload for Thermal State and NPS Thermal (w.r.t No Phase Segregation) Models timed under-current protection Underfrequency (w.r.t No Phase Segregation) Undervoltage (w.r.t No Phase Segregation) Voltage Vector Shift protection Breaker Failure (w.r.t External Tripping) Current loop monitoring and reporting Disturbance Recorder function (w.r.t Mandatory Attributes only)

Name Space IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-2:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 SE-SII:PCS-Px40 IEC 61850-7-4:2003 SE-SII:PCS-Px40 IEC 61850-7-4:2003

Synchronism-check / Synchronising (w.r.t IEC 61850-7-4:2003 Calculated Differential Measurements) VTS/CTS monitoring and report SE-SII:PCS-Px40 Circuit Breaker (w.r.t Mandatory Attributes IEC 61850-7-4:2003 Only)

2.4.1

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt EnaOpn EnaCls

CILO_INTERLOCK

Control Interlocking CILO


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SPS_WD SPS_WD Mode Behaviour Health Name Plate Enable OPEN Commands Enable CLOSE Commands Explanation T X

2.4.2

Logical Node:
Description: LN Class:
Attribute Mod Beh Health

GGIO_ALM_96

Generic Process I/O (w.r.t 96 Alarm Elements) GGIO


Attr. Type INC_MOD INS_BEH INS_HEALTH Mode Behaviour Health Explanation T X

P341/EN PM/F74-S

(PM)-17

PICS & MICS

P341

Attribute NamPlt Alm1 Alm2 Alm3 Alm4 Alm5 Alm6 Alm7 Alm8 Alm9 Alm10 Alm11 Alm12 Alm13 Alm14 Alm15 Alm16 Alm17 Alm18 Alm19 Alm20 Alm21 Alm22 Alm23 Alm24 Alm25 Alm26 Alm27 Alm28 Alm29 Alm30 Alm31 Alm32 Alm33 Alm34 Alm35 Alm36 Alm37 Alm38 Alm39 Alm40 Alm41 Alm42 Alm43 LPL_LN SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D

Attr. Type Name Plate

Explanation General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm

(PM)-18

P341/EN PM/F74-S

P341

PICS & MICS

Attribute Alm44 Alm45 Alm46 Alm47 Alm48 Alm49 Alm50 Alm51 Alm52 Alm53 Alm54 Alm55 Alm56 Alm57 Alm58 Alm59 Alm60 Alm61 Alm62 Alm63 Alm64 Alm65 Alm66 Alm67 Alm68 Alm69 Alm70 Alm71 Alm72 Alm73 Alm74 Alm75 Alm76 Alm77 Alm78 Alm79 Alm80 Alm81 Alm82 Alm83 Alm84 Alm85 Alm86 Alm87 SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D

Attr. Type

Explanation General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm

P341/EN PM/F74-S

(PM)-19

PICS & MICS

P341

Attribute Alm88 Alm89 Alm90 Alm91 Alm92 Alm93 Alm94 Alm95 Alm96 SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D

Attr. Type

Explanation General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm

2.4.3

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Ind11 Ind12 Ind13 Ind14 Ind15 Ind16 Ind17 Ind18 Ind19 Ind20 Ind21 Ind22 Ind23

GGIO_IND_24

Generic Process I/O GGIO


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D Mode Behaviour Health name Plate General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication General Indication Explanation T X

(PM)-20

P341/EN PM/F74-S

P341

PICS & MICS

Attribute Ind24 SPS_D

Attr. Type

Explanation General Indication

2.4.4

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Ind11 Ind12 Ind13 Ind14 Ind15 Ind16 Ind17 Ind18 Ind19 Ind20 Ind21 Ind22 Ind23 Ind24 Ind25 Ind26 Ind27 Ind28 Ind29 Ind30 Ind31

GGIO_IND_32

Generic Process I/O (w.r.t 32 Indication Elements) GGIO


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D Mode Behaviour Health Name Plate General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) Explanation T X

P341/EN PM/F74-S

(PM)-21

PICS & MICS

P341

Attribute Ind32 SPS_D

Attr. Type

Explanation General indication (binary input)

2.4.5

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt SPCSO1 SPCSO2 SPCSO3 SPCSO4 SPCSO5 SPCSO6 SPCSO7 SPCSO8 SPCSO9 SPCSO10 SPCSO11 SPCSO12 SPCSO13 SPCSO14 SPCSO15 SPCSO16 SPCSO17 SPCSO18 SPCSO19 SPCSO20 SPCSO21 SPCSO22 SPCSO23 SPCSO24 SPCSO25 SPCSO26 SPCSO27 SPCSO28 SPCSO29 SPCSO30 SPCSO31

GGIO_IND_32_CTRL

Generic Process I/O GGIO


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL SPC_CONTROL Mode Behaviour Health Name Plate Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Single point controllable status output Explanation T X

(PM)-22

P341/EN PM/F74-S

P341

PICS & MICS

Attribute SPCSO32

Attr. Type SPC_CONTROL

Explanation Single point controllable status output

2.4.6

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Ind11 Ind12 Ind13 Ind14 Ind15 Ind16 Ind17 Ind18 Ind19 Ind20 Ind21 Ind22 Ind23 Ind24 Ind25 Ind26 Ind27 Ind28 Ind29 Ind30 Ind31 Ind32 Ind33 Ind34

GGIO_IND_64

Generic Process I/O(w.r.t 64 Indication Elements) GGIO


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D Mode Behaviour Health Name Plate General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) Explanation T X

P341/EN PM/F74-S

(PM)-23

PICS & MICS

P341

Attribute Ind35 Ind36 Ind37 Ind38 Ind39 Ind40 Ind41 Ind42 Ind43 Ind44 Ind45 Ind46 Ind47 Ind48 Ind49 Ind50 Ind51 Ind52 Ind53 Ind54 Ind55 Ind56 Ind57 Ind58 Ind59 Ind60 Ind61 Ind62 Ind63 Ind64 SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D

Attr. Type

Explanation General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input)

2.4.7

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Ind1 Ind2 Ind3 Ind4 Ind5

GGIO_IND_8

Generic Process I/O (w.r.t 8 Indication Elements) GGIO


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SPS_D SPS_D SPS_D SPS_D SPS_D Mode Behaviour Health Name Plate General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) Explanation T X

(PM)-24

P341/EN PM/F74-S

P341

PICS & MICS

Attribute Ind6 Ind7 Ind8 SPS_D SPS_D SPS_D

Attr. Type

Explanation General indication (binary input) General indication (binary input) General indication (binary input)

2.4.8

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt AscMod AscBeh

LLN0_CONTROL

Control Domain Logical Node 0 LLN0


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LLN0 INC_CTRL_PRIV INS_BEH_D_PRIV Mode Behaviour Health Name Plate Check Synchronisation Check Synchronisation X X Explanation T X

2.4.9

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt PdpMod PdpBeh EftMod EftBeh FrqMod SenMod FrqBeh SenBeh DfpMod DfpBeh ThmMod ThmBeh CbfMod CbfBeh SvnBeh SvnMod NvdMod NvdBeh VtpMod VtpBeh

LLN0_P341

Logical Node 0 LLN0


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LLN0 INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV Mode Behaviour Health Name Plate Power Protection Mode Power Protection Behaviour Earth Fault 1 (Measured) Mode Earth Fault 1 (Measured) Behaviour Overfrequency/Underfrequency Mode Sensitive Power Mode Overfrequency/Underfrequency Behaviour Sensitive Power Behaviour df/dt Mode df/dt Behaviour Thermal Overload Mode Thermal Overload Behaviour CB Fail Mode Circuit Breaker Fail Behaviour VTS/CTS Supervision Behaviour VTS/CTS Supervision Mode Residual Overvoltage NVD Mode Residual Overvoltage NVD Behaviour Overvoltage/Undervoltage Mode Overvoltage/Undervoltage Behaviour Explanation T X

P341/EN PM/F74-S

(PM)-25

PICS & MICS

P341

Attribute VvsMod VvsBeh OcpMod OcpBeh RctMod RctBeh CliMod CliBeh SefMod SefBeh SycMod SycBeh

Attr. Type INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV

Explanation Voltage vector Shift Mode Voltage vector shift Behaviour Overcurrent Mode Overcurrent Behaviour Reconnection Delay Mode Reconnection Delay Behaviour CLIO Inputs Mode CLIO Inputs Behaviour SEF/REF Mode SEF/REF Behaviour System Checks Mode System Checks Behaviour

2.4.10

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt

LLN0_STANDARD

General Logical Node 0 LLN0


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LLN0 Mode Behaviour Health Name Plate Explanation T X

2.4.11

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt LEDRs OrdRun SyncSt

LLN0_SYSTEM

System Logical Node 0 LLN0


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LLN0 SPC_CONTROL SPS_WD_NS SPS_WD_NS Mode Behaviour Health Name Plate LED reset Indicate the IED is operating a control object (Order Running) Indicate time synchronisation in the IED is active or inactive T X X Explanation T X

2.4.12

Logical Node:
Description: LN Class:
Attribute PhyNam PhyHealth Proxy

LPHD_STANDARD

Px40 Physical Device Information LPHD


Attr. Type DPL_STANDARD INS_HEALTH SPS_D Explanation Physical device name plate Physical device health Indicates if this LN is a proxy T X

(PM)-26

P341/EN PM/F74-S

P341

PICS & MICS

Attribute PwrUp SPS_D

Attr. Type

Explanation Power up detected

2.4.13

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt SupWh SupVArh DmdWh DmdVArh MTRRs

MMTR_PRIV

Metering MMTR
Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN BCR_PRIV BCR_PRIV BCR_PRIV BCR_PRIV SPC_CTRL_PRIV Mode Behaviour Health Name Plate Real energy supply (Energy flow towards bus bar) Reactive energy supply (Energy flow towards bus bar) Real energy demand (Energy flow from bus bar) Reactive energy demand (Energy flow from bus bar) Reset Energy Measurements X Explanation T X

2.4.14

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt CSVol INS_BEH

MMXU_CSV

Measurements for C/S MMXU


Attr. Type INC_MOD INS_HEALTH LPL_LN WYE_RES_ANG_D_NS Mode Behaviour Health Name Plate C/S Voltage X Explanation T X

2.4.15

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Hz PPV A A2 W VA INS_BEH

MMXU_DERIVED_P341

Standard measurements (w.r.t Standard Values - P341) MMXU


Attr. Type INC_MOD INS_HEALTH LPL_LN MV_FLOAT DEL_SEG WYE_SEG WYE_RES_ANG_D WYE_SEG WYE_SEG Phase-Phase Magnitudes IN-I derived magnitude IN Derived Magnitude Angle Phase watts VA 3 phase Mode Behaviour Health Name Plate Explanation T X

P341/EN PM/F74-S

(PM)-27

PICS & MICS

P341

Attribute PF AngA AngPPV AvgPF AngV AvgWatts AvgVArs AvgVA V VArs VN

Attr. Type WYE_SEG WYE_SEG_NS DEL_SEG_NS MV_FLOAT_NS WYE_SEG_NS MV_FLOAT_NS MV_FLOAT_NS MV_FLOAT_NS WYE_SEG_NS WYE_SEG_NS WYE_RES_ANG_D_NS

Explanation IN-I Derived magnitude angle Phase-Phase Angles VN derived angle

3 phase Average VA VN derived magnitude Phase VArs VN Derived Magnitude Angle

2.4.16

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Dfdt

MMXU_DFDT

Standard measurements(for dfdt only) MMXU


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN MV_FLOAT_NS Mode Behaviour Health Name Plate df/dt X Explanation T X

2.4.17

Logical Node:
Description: LN Class:
Attribute Beh Mod Health NamPlt PhV A

MMXU_RMS

Measurements (RMS values) MMXU


Attr. Type INS_BEH INC_MOD INS_HEALTH LPL_LN WYE_SEG WYE_SEG Behaviour Mode Health Name Plate Phase to Ground voltages RMS Current Explanation T X

2.4.18

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt A W INS_BEH

MMXU_SENSITIVE

Sensitive measurements MMXU


Attr. Type INC_MOD INS_HEALTH LPL_LN WYE_SEG_PHASEA WYE_RES_MAG_NS Mode Behaviour Health Name Plate Current Sensitive watts Explanation T X

(PM)-28

P341/EN PM/F74-S

P341

PICS & MICS

Attribute PwrAng VArs

Attr. Type MV_FLOAT_NS MV_FLOAT_NS Power angle VArs

Explanation

X X X

2.4.19

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt VN INS_BEH

MMXU_STANDARD_P341

Standard measurements (w.r.t Fourier Derived Values - P341) MMXU


Attr. Type INC_MOD INS_HEALTH LPL_LN WYE_RES_ANG_D_NS Mode Behaviour Health Name Plate Explanation T X

2.4.20

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt

MMXU_THIRD_HARMONIC_NO_VN

Measurements (w.r.t 3rd Harmonic, no VN for P341/P342) MMXU


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN Mode Behaviour Health Name Plate Explanation T X

2.4.21

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt SeqA SeqV

MSQI_ALL

Sequence and imbalance (w.r.t Pos, Neq, Zero) MSQI


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SEQ_MAG_ANG SEQ_MAG_ANG Mode Behaviour Health Name Plate Positive, Negative and Zero sequence current Positive, Negative and Zero sequence voltage Explanation T X

2.4.22

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt

MSTA_STANDARD

Standard measurements (w.r.t Fourier Derived Values) MSTA


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN Mode Behaviour Health Name Plate Explanation T X

P341/EN PM/F74-S

(PM)-29

PICS & MICS

P341

Attribute TotRtPwr TotPwr PhApPwr

Attr. Type MV_FLOAT_NS MV_FLOAT_NS WYE_SEG_NS

Explanation Total reactive power (Total Q) Total active power (Total P) Phase apparent power (S)

X X X X

2.4.23

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Op

PDIF_NEU

Differential (w.r.t Neutral) PDIF


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACT_NO_SEG Mode Behaviour Health Name Plate Operate T Explanation T X

2.4.24

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op

PFRC_NO_SEG

Rate of change of frequency (w.r.t No Phase Segregation) PFRC


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG Mode Behaviour Health Name Plate Start Operate T Explanation T X

2.4.25

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Op

PLMP_NEU

Loss of mains protection, similar to PTOC but without current setting and modified meanings for the pickup and drop off timers PLMP
Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN_P ACT_NO_SEG Mode Behaviour Health Name Plate Operate (Trip) Explanation T X

2.4.26

Logical Node:
Description: LN Class:
Attribute Mod Beh Health

PPWR_NORMAL

Power Protection with Pole Dead Inhibit PPWR


Attr. Type INC_MOD INS_BEH INS_HEALTH Mode Behaviour Health Explanation T X

(PM)-30

P341/EN PM/F74-S

P341

PICS & MICS

Attribute NamPlt Str Op

Attr. Type LPL_LN_P ACD_NO_SEG ACT_NO_SEG Name Plate Start Trip

Explanation

2.4.27

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op

PTOC_NEU

Timed Overcurrent (w.r.t Neutral) PTOC


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG Mode Behaviour Health Name Plate Start Operate T Explanation T X

2.4.28

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op

PTOC_NO_SEG

Timed Overcurrent (w.r.t No Phase Segregation) PTOC


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG Mode Behaviour Health Name Plate Start Operate T Explanation T X

2.4.29

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op

PTOF_NO_SEG

Overfrequency (w.r.t No Phase Segregation) PTOF


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG Mode Behaviour Health Name Plate Start Operate T Explanation T X

2.4.30

Logical Node:
Description: LN Class:
Attribute Mod

PTOV_NEU

Overvoltage (w.r.t Neutral) PTOV


Attr. Type INC_MOD Mode Explanation T X

P341/EN PM/F74-S

(PM)-31

PICS & MICS

P341

Attribute Beh Health NamPlt Str Op

Attr. Type INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG Behaviour Health Name Plate Start Operate

Explanation

2.4.31

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op

PTOV_NO_SEG

Overvoltage (w.r.t Phase Segregation) PTOV


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG Mode Behaviour Health Name Plate Start Operate T Explanation T X

2.4.32

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Tr Str

PTRC_NO_SEG

Protection trip conditioning (w.r.t No Phase Segregation) PTRC


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACT_NO_SEG ACD_NO_SEG Mode Behaviour Health Name Plate Trip Sum of all starts of all connected Logical Nodes Explanation T X

2.4.33

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt TmpRl Op AlmThm

PTTR_NO_SEG_PRIV

Thermal overload for Thermal State and NPS Thermal (w.r.t No Phase Segregation) PTTR
Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN MV_FLOAT ACT_NO_SEG ACT_NO_SEG Mode Behaviour Health Name Plate Relation between temperature and maximum temperature Operate Thermal alarm T T Explanation T X

(PM)-32

P341/EN PM/F74-S

P341

PICS & MICS

Attribute MTRRs

Attr. Type SPC_CTRL_PRIV

Explanation Reset Thermal State

X X

2.4.34

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op ModOvA

PTUC_NEU

Models timed under-current protection PTUC


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG SPS_WD_NS Mode Behaviour Health Name Plate Started Operate Overcurrent Mode Indication T X Explanation T X

2.4.35

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op

PTUF_NO_SEG

Underfrequency (w.r.t No Phase Segregation) PTUF


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG Mode Behaviour Health Name Plate Start Operate T Explanation T X

2.4.36

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op

PTUV_NO_SEG

Undervoltage (w.r.t No Phase Segregation) PTUV


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG Mode Behaviour Health Name Plate Start Operate T Explanation T X

2.4.37

Logical Node:
Description: LN Class:
Attribute Mod Beh

PVSP_STANDARD

Voltage Vector Shift protection PVSP


Attr. Type INC_MOD INS_BEH Mode Behaviour Explanation T X

P341/EN PM/F74-S

(PM)-33

PICS & MICS

P341

Attribute Health NamPlt Op StrVal

Attr. Type INS_HEALTH LPL_LN_P ACT_NO_SEG ASG_FLOAT Health

Explanation name plate with namespace Trip status V Shift Angle

2.4.38

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt OpEx

RBRF_EXTTRIP

Breaker Failure (w.r.t External Tripping) RBRF


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN ACT_NO_SEG Mode Behaviour Health Name Plate Breaker failure trip ("External trip") T Explanation T X

2.4.39

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Val Blk Min Max

RCLI_STANDARD

Current loop monitoring and reporting RCLI


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN_P MV_FLOAT SPS_WD ASG_FLOAT ASG_FLOAT Mode Behaviour Health Name Plate curent loop input measured value Block (TRUE = current loop blocked) Minimum input of current loop Maximum input of current loop Explanation T X

2.4.40

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt RcdMade FltNum

RDRE_BASIC

Disturbance Recorder function (w.r.t Mandatory Attributes only) RDRE


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SPS_WD INS_BASIC Mode Behaviour Health Name Plate Recording made Fault number Explanation T X

2.4.41

Logical Node:
Description: LN Class:

RSYN_DIFCLC

Synchronism-check / Synchronising (w.r.t Calculated Differetial Measurements) RSYN

(PM)-34

P341/EN PM/F74-S

P341

PICS & MICS

Attribute Mod Beh Health NamPlt Rel VInd AngInd HzInd DifVClc DifHzClc DifAngClc

Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SPS_WD SPS_WD SPS_WD SPS_WD MV_FLOAT MV_FLOAT MV_FLOAT Mode Behaviour Health Name Plate Release

Explanation

Voltage difference indicator Angle difference indicator Frequency difference indicator Calculated difference in voltage Calculated difference in frequency Calculated difference of phase angle

2.4.42

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt SlwVTSBlk FstVTSBlk CTSBlk

RVCS_STANDARD_NO_CT2

VTS/CTS monitoring and report RVCS


Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN_P SPS_D SPS_D SPS_D Mode Behaviour Health Name Plate slow VTS block status fast VTS block status CTS block status Explanation T X

2.4.43

Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Loc EEHealth OpCnt Pos BlkOpn BlkCls CBOpCap INS_BEH

XCBR_BASIC_ALL

Circuit Breaker (w.r.t Mandatory Attributes only) XCBR


Attr. Type INC_MOD INS_HEALTH LPL_LN SPS_WD INS_HEALTH INS_BASIC DPC_STATUS_P341 SPC_STATUS SPC_STATUS INS_CB_OPCAP Mode Behaviour Health Name Plate Local operation External equipment health Operation counter Switch position Block opening Block closing Circuit Breaker operating capability Explanation T X

P341/EN PM/F74-S

(PM)-35

PICS & MICS

P341

Attribute Lock

Attr. Type SPC_CTRL_PRIV

Explanation Prevention, i.e. Lock, Trip/Close Operation of Circuit Breaker over IEC 61850

X X

2.5

Common Data Class definitions


The definition tables for each of the Common Data Classes used in the Logical Node definitions are presented in the following sub-sections. From an application point-of-view the data attributes of a Common Data Class are classified according to their specific use. The characterization of data attributes, and the services that they support/provide, will be through the use of 'Functional Constraints'. The Functional Constraints are specified by the table below:
FC Name BR CF CO DC EX GO GS LG MS MX RP SE SG SP ST SV US XX Buffered reports Configuration Control Description Extended Definition GOOSE Control GSSE Control (UCA2 GOOSE) Logging Multicast sampled value control Measurands (Analogue values) Unbuffered reports Setting Group Editable Setting Group Set Point Status Information Substitution Values Unicast sampled value control Data attribute service parameters Semantic Source Definition IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2 IEC 61850-7-2

2.5.1

Common Data Class:


Description: CDC Class:
Attribute general dirGeneral q BOOLEAN ENUMERATED8 (MMS Type: INT8) Quality

ACD_NO_SEG

Directional Protection Activation Information (w,r,t No Phase Segregation) ACD


Type FC ST ST ST dir Enumeration Comment Trip or start has happened General direction (unknown, forward, backward or both) Quality of the protection activation information X

(PM)-36

P341/EN PM/F74-S

P341

PICS & MICS

Attribute t

Type TimeStamp

FC ST

Enumeration

Comment Timestamp of the last change in state of protection activation information

2.5.2

Common Data Class:


Description: CDC Class:
Attribute general q

ACT_NO_SEG

Protection Activation Information (w.r.t No Phase Segregation) ACT


Type BOOLEAN Quality FC ST ST Enumeration Comment Trip or start has happened Quality of the protection activation information Timestamp of the last change in state of protection activation information X

TimeStamp

ST

2.5.3

Common Data Class:


Description: CDC Class:
Attribute setMag d units

ASG_FLOAT

Analogue Setting ASG


Type AnalogueValue_Float VISIBLE_STRING255 Unit_multiplier FC SE DC CF Enumeration Comment Setting value Description of the status element Unit of the attribute representing the data X

2.5.4

Common Data Class:


Description: CDC Class:
Attribute actVal q t INT128 Quality TimeStamp

BCR_PRIV

Binary Counter Reading BCR


Type FC ST ST ST Enumeration Comment Binary counter status represented as an integer Quality of counter value Time of last counter change Magnitude of the counted value 'per count' (value = actVal x pulsQty) X

pulsQty

FLOAT32

CF

2.5.5

Common Data Class:


Description: Angle) CDC Class:

CMV_MAG_ANG_FLOAT

Complex Measured value (w.r.t Floating Point Magnitude and CMV

P341/EN PM/F74-S

(PM)-37

PICS & MICS

P341

Attribute

Type

FC

Enumeration

Comment Deadbanded complex measured vector. Updated to the current value of instCVal when the value has changed according to the configuration parameter db. Quality of the measurement value Time deadbanded magnitude last exceeded its db configuration parameter Unit of the attribute representing the data Measurement deadband Measurement range configuration attributes

cVal

Vector_MagnitudeAngle_Float

MX

Quality

MX

TimeStamp

MX

units db rangeC

Unit_multiplier INT32U RangeConfig_Deadband

CF CF CF

2.5.6

Common Data Class:


Description: CDC Class:
Attribute

CMV_MAG_FLOAT

Complex Measured value (w.r.t Floating Point Magnitude) CMV


Type FC Enumeration Comment Deadbanded complex measured vector. Updated to the current value of instCVal when the value has changed according to the configuration parameter db. Quality of the measurement value Time deadbanded magnitude last exceeded its db configuration parameter Unit of the attribute representing the data Measurement deadband Measurement range configuration attributes X

cVal

Vector_Magnitude_Float

MX

Quality

MX

TimeStamp

MX

units db rangeC

Unit_multiplier INT32U RangeConfig_Deadband

CF CF CF

2.5.7

Common Data Class:


Description: CDC Class:

DEL_SEG

Phase to phase measurements for a 3-Phase system (w.r.t Phase Segregation) DEL

(PM)-38

P341/EN PM/F74-S

P341

PICS & MICS

Attribute phsAB phsBC phsCA

Type CMV_MAG_FLOAT CMV_MAG_FLOAT CMV_MAG_FLOAT

FC ----

Enumeration

Comment Measurement values for Phase A to Phase B Measurement values for Phase B to Phase C Measurement values for Phase C to Phase A

2.5.8

Common Data Class:


Description: CDC Class:
Attribute phsAB phsBC phsCA dataNs

DEL_SEG_NS

DEL_SEG with namespace DO dataNs DEL


Type CMV_MAG_FLOAT CMV_MAG_FLOAT CMV_MAG_FLOAT VISIBLE_STRING255 FC ---EX Enumeration Comment Measurement values for Phase A to Phase B Measurement values for Phase B to Phase C Measurement values for Phase C to Phase A Data name space X

2.5.9

Common Data Class:


Description: CDC Class:
Attribute ctlVal origin

DPC_STATUS_P341

Controllable Double Point (w.r.t Status only) DPC


Type BOOLEAN Originator CODED_ENUM (MMS Type: _BSTR2) Quality TimeStamp ENUMERATED8 (MMS Type: INT8) INT32U FC CO ST Enumeration Comment Control value (Off FALSE, On - TRUE) Originator of the last change of the controllable data Dbpos Status value of the data (Intermediate state, Off, On or Bad-state) Quality of the status value Timestamp of the last change in state of status value ctlModel Control model (Corresponding to the behaviour of the data) Select Before Operate timeout period (in milliseconds) X

stVal q t

ST ST ST

ctlModel

CF

sboTimeout

CF

2.5.10

Common Data Class:


Description: CDC Class:
Attribute vendor

DPL_STANDARD

Standard Device Name Plate DPL


Type VISIBLE_STRING255 FC DC Enumeration Comment Name of the vendor X

P341/EN PM/F74-S

(PM)-39

PICS & MICS

P341

Attribute hwRev swRev serNum model location

Type VISIBLE_STRING255 VISIBLE_STRING255 VISIBLE_STRING255 VISIBLE_STRING255 VISIBLE_STRING255

FC DC DC DC DC DC

Enumeration

Comment Hardware revision Software revision Serial Number Model Number Physical location of device

2.5.11

Common Data Class:


Description: CDC Class:
Attribute ctlVal stVal q t INT32 INT32 (MMS Type: INT8) Quality TimeStamp ENUMERATED8 (MMS Type: INT8)

INC_CTRL_PRIV

Controllable Integer Status INC


Type FC CO ST ST ST Mod Enumeration Comment Control value Status value of the data Quality of the status value Timestamp of the last change in state of status value ctlModel Control model (Corresponding to the behaviour of the data) Description of the status element Data name space X

ctlModel d dataNs

CF DC EX

VISIBLE_STRING255 VISIBLE_STRING255

2.5.12

Common Data Class:


Description: CDC Class:
Attribute stVal q t

INC_MOD

Controllable Integer Status (w.r.t Mode) INC


Type INT32 (MMS Type: INT8) Quality TimeStamp ENUMERATED8 (MMS Type: INT8) FC ST ST ST Enumeration Mod Comment Status value of the data Quality of the status value Timestamp of the last change in state of status value ctlModel Control model (Corresponding to the behaviour of the data) X

ctlModel

CF

2.5.13

Common Data Class:


Description: CDC Class:
Attribute stVal INT32

INS_BASIC

Integer Status (w.r.t Mandatory Options only) INS


Type FC ST Enumeration Comment The element status X

(PM)-40

P341/EN PM/F74-S

P341

PICS & MICS

Attribute q t Quality

Type

FC ST ST

Enumeration

Comment The quality of the status value Timestamp of the last change in state

TimeStamp

2.5.14

Common Data Class:


Description: CDC Class:
Attribute stVal q t

INS_BEH

Integer Status (w.r.t Behaviour) INS


Type INT32 (MMS Type: INT8) Quality TimeStamp FC ST ST ST Enumeration Beh Comment The element status The quality of the status value Timestamp of the last change in state X

2.5.15

Common Data Class:


Description: CDC Class:
Attribute stVal q t d dataNs

INS_BEH_D_PRIV

Integer Status (w.r.t Behaviour, with Description (Private DO)) INS


Type INT32 (MMS Type: INT8) Quality TimeStamp VISIBLE_STRING255 VISIBLE_STRING255 FC ST ST ST DC EX Enumeration Beh Comment The element status The quality of the status value Timestamp of the last change in state Description of the status element Data name space X

2.5.16

Common Data Class:


Description: CDC Class:
Attribute stVal q t

INS_CB_OPCAP

Integer Status (w.r.t CB Operating capability) INS


Type INT32 (MMS Type: INT8) Quality TimeStamp FC ST ST ST Enumeration CBOpCap Comment The element status The quality of the status value Timestamp of the last change in state X

2.5.17

Common Data Class:


Description: CDC Class: INS

INS_HEALTH

Integer Status (w.r.t health)

P341/EN PM/F74-S

(PM)-41

PICS & MICS

P341

Attribute stVal q t

Type INT32 (MMS Type: INT8) Quality TimeStamp

FC ST ST ST

Enumeration Health

Comment The element status The quality of the status value Timestamp of the last change in state

2.5.18

Common Data Class:


Description: CDC Class:
Attribute vendor swRev d configRev ldNs

LPL_LLN0

Logical Node 0 Name Plate LPL


Type VISIBLE_STRING255 VISIBLE_STRING255 VISIBLE_STRING255 VISIBLE_STRING255 VISIBLE_STRING255 FC DC DC DC DC EX Enumeration Comment Name of the vendor Software revision Description Uniquely identifies the configuration of a local device instance Logical Device name space X

2.5.19

Common Data Class:


Description: CDC Class:
Attribute vendor swRev d

LPL_LN

Standard Logical Node Name Plate LPL


Type VISIBLE_STRING255 VISIBLE_STRING255 VISIBLE_STRING255 FC DC DC DC Enumeration Comment Name of the vendor Software revision Description X

2.5.20

Common Data Class:


Description: CDC Class:
Attribute vendor swRev d lnNs

LPL_LN_P

Logical Node Name Plate for Propriety LN LPL


Type VISIBLE_STRING255 VISIBLE_STRING255 VISIBLE_STRING255 VISIBLE_STRING255 FC DC DC DC EX Enumeration Comment Name of the vendor Software revision Description Logical Node name space X

2.5.21

Common Data Class:


Description: CDC Class: MV

MV_FLOAT

Measured value (w.r.t. Floating Point value)

(PM)-42

P341/EN PM/F74-S

P341

PICS & MICS

Attribute

Type

FC

Enumeration

Comment Deadbanded magnitude of the instantaneous value of a measured value or harmonic value. Updated to the current value of instMag when the value has changed according to the configuration parameter db. Quality of the measurement value Time deadbanded magnitude last exceeded its db configuration parameter Unit of the attribute representing the data Measurement deadband Measurement range configuration attributes

mag

AnalogueValue_Float

MX

Quality

MX

TimeStamp

MX

units db rangeC

Unit_multiplier INT32U RangeConfig_Deadband

CF CF CF

2.5.22

Common Data Class:


Description: CDC Class:
Attribute

MV_FLOAT_NS

MV_FLOAT with dataNs for extra Dos MV


Type FC Enumeration Comment Deadbanded magnitude of the instantaneous value of a measured value or harmonic value. Updated to the current value of instMag when the value has changed according to the configuration parameter db. Quality of the measurement value Time deadbanded magnitude last exceeded its db configuration parameter Unit of the attribute representing the data Measurement deadband Measurement range configuration attributes X

mag

AnalogueValue_Float

MX

Quality

MX

TimeStamp

MX

units db rangeC

Unit_multiplier INT32U RangeConfig_Deadband

CF CF CF

P341/EN PM/F74-S

(PM)-43

PICS & MICS

P341

Attribute dataNs

Type VISIBLE_STRING255

FC EX

Enumeration

Comment Data name space

2.5.23

Common Data Class:


Description: CDC Class:
Attribute c1

SEQ_MAG_ANG

Sequence components of a measurement value (w.r.t Magnitudes + Angles) SEQ


Type CMV_MAG_ANG_FLOAT FC -Enumeration Comment Sequence component 1 (For semantic meaning see seqT) Sequence component 2 (For semantic meaning see seqT) Sequence component 3 (For semantic meaning see seqT) seqT Sequence quantity measurement type (Pos-Neg-Zero or DirQuad-Zero) X

c2

CMV_MAG_ANG_FLOAT

--

c3

CMV_MAG_ANG_FLOAT

--

seqT

ENUMERATED8 (MMS Type: INT8)

MX

2.5.24

Common Data Class:


Description: CDC Class:
Attribute ctlVal origin stVal q t

SPC_CONTROL

Controllable Single Point SPC


Type BOOLEAN Originator BOOLEAN Quality TimeStamp ENUMERATED8 (MMS Type: INT8) INT32U FC CO ST ST ST ST Enumeration Comment Control value (Off FALSE, On - TRUE) Originator of the last change of the controllable data Status value of the data Quality of the status value Timestamp of the last change in state of status value ctlModel Control model (Corresponding to the behaviour of the data) Select Before Operate timeout period (in milliseconds) X

ctlModel

CF

sboTimeout

CF

2.5.25

Common Data Class:


Description: CDC Class:
Attribute ctlVal BOOLEAN

SPC_CTRL_PRIV

Controllable Single Point SPC


Type FC CO Enumeration Comment Control value (Off FALSE, On - TRUE) X

(PM)-44

P341/EN PM/F74-S

P341

PICS & MICS

Attribute origin stVal q t Originator BOOLEAN Quality

Type

FC ST ST ST ST

Enumeration

Comment Originator of the last change of the controllable data Status value of the data Quality of the status value Timestamp of the last change in state of status value

TimeStamp ENUMERATED8 (MMS Type: INT8) INT32U VISIBLE_STRING255

ctlModel

CF

ctlModel

Control model (Corresponding to the behaviour of the data) Select Before Operate timeout period (in milliseconds) Data name space

sboTimeout dataNs

CF EX

2.5.26

Common Data Class:


Description: CDC Class:
Attribute stVal q t

SPC_STATUS

Controllable Single Point (w.r.t Status only) SPC


Type BOOLEAN Quality TimeStamp ENUMERATED8 (MMS Type: INT8) FC ST ST ST Enumeration Comment Status value of the data Quality of the status value Timestamp of the last change in state of status value ctlModel Control model (Corresponding to the behaviour of the data) X

ctlModel

CF

2.5.27

Common Data Class:


Description: CDC Class:
Attribute stVal q t d BOOLEAN Quality TimeStamp

SPS_D

Standard Single Point Status (with Description) SPS


Type FC ST ST ST DC Enumeration Comment The element status (TRUE or FALSE) The quality of the status value Timestamp of the last change in state Description of the status element X

VISIBLE_STRING255

2.5.28

Common Data Class:


Description: CDC Class: SPS

SPS_WD

Single Point Status (without Description)

P341/EN PM/F74-S

(PM)-45

PICS & MICS

P341

Attribute stVal q t

Type BOOLEAN Quality TimeStamp

FC ST ST ST

Enumeration

Comment The element status (TRUE or FALSE) The quality of the status value Timestamp of the last change in state

2.5.29

Common Data Class:


Description: CDC Class:
Attribute stVal q t dataNs BOOLEAN Quality TimeStamp

SPS_WD_NS

Single Point Status (without Description, with namespace) SPS


Type FC ST ST ST EX Enumeration Comment The element status (TRUE or FALSE) The quality of the status value Timestamp of the last change in state Data name space X

VISIBLE_STRING255

2.5.30

Common Data Class:


Description: Residual CDC Class:
Attribute res d

WYE_RES_ANG_D

Phase to ground measurements for a 3-Phase system (w.r.t + Description + Angle) WYE
Type CMV_MAG_ANG_FLOAT VISIBLE_STRING255 FC -DC Enumeration Comment Measurement values for the residual system current Description of the status element X

2.5.31

Common Data Class:


Description: Residual CDC Class:
Attribute res d dataNs

WYE_RES_ANG_D_NS

Phase to ground measurements for a 3-Phase system (w.r.t + Description + Angle) WYE
Type CMV_MAG_ANG_FLOAT VISIBLE_STRING255 VISIBLE_STRING255 FC -DC EX Enumeration Comment Measurement values for the residual system current Description of the status element Data name space X

2.5.32

Common Data Class:


Description: CDC Class:

WYE_RES_MAG_NS

Phase to ground measurements for a 1-Phase system, magnitude only WYE

(PM)-46

P341/EN PM/F74-S

P341

PICS & MICS

Attribute res dataNs

Type CMV_MAG_FLOAT VISIBLE_STRING255

FC -EX

Enumeration

Comment Measurement values for the residual system current Data name space

2.5.33

Common Data Class:


Description: CDC Class:
Attribute phsA phsB phsC

WYE_SEG

Phase to ground measurements for a 3-Phase system (w.r.t Phase Segregation) WYE
Type CMV_MAG_FLOAT CMV_MAG_FLOAT CMV_MAG_FLOAT FC ---Enumeration Comment Measurement values for Phase A Measurement values for Phase B Measurement values for Phase C X

2.5.34

Common Data Class:


Description: CDC Class:
Attribute phsA phsB phsC dataNs

WYE_SEG_NS

WYE_SEG with dataNs DO WYE


Type CMV_MAG_FLOAT CMV_MAG_FLOAT CMV_MAG_FLOAT VISIBLE_STRING255 FC ---EX Enumeration Comment Measurement values for Phase A Measurement values for Phase B Measurement values for Phase C Data name space X

2.5.35

Common Data Class:


Description: CDC Class:
Attribute phsA

WYE_SEG_PHASEA

Phase to ground measurements for a 3-Phase system WYE


Type CMV_MAG_ANG_FLOAT FC -Enumeration Comment Measurement values for Phase A X

2.6

Common data attribute type definitions


Common data attribute types, known herein as components, are defined for use in the Common Data Classes defined in the sections above.

2.6.1

Component:
Comment:

AnalogueValue_Float

General analogue value (w.r.t Floating Point value)

Parent Type: AnalogueValue

P341/EN PM/F74-S

(PM)-47

PICS & MICS

P341

Attribute f FLOAT32

Type

Enumeration

Comment Floating point value

2.6.2

Component:
Comment: Parent Type:
Attribute orIdent

Originator

Originator of the last change of data attribute representing the value of a controllable data object

Type OCTET_STRING64

Enumeration

Comment Originator identification (Null value indicates unknown or not reported) Originator category (Notsupported, bay-control, station-control, remotecontrol, automatic-bay, automatic-station, automaticremote, maintenance or process)

orCat

ENUMERATED8 (MMS Type: INT8)

orCategory

2.6.3

Component:
Comment:

RangeConfig_Deadband

Measurement range configuration

Parent Type: RangeConfig


Attribute min Type AnalogueValue_Float Enumeration Comment Minimum process measurement for which values of i and f are considered within limits Maximum process measurement for which values of i and f are considered within limits Low Low range limit Low range limit High range limit High High range limit X

max llLim lLim hLim hhLim

AnalogueValue_Float AnalogueValue_Float AnalogueValue_Float AnalogueValue_Float AnalogueValue_Float

2.6.4

Component:
Comment: Parent Type: Unit
Attribute SIUnit multiplier

Unit_multiplier

SI Unit definitions

Type ENUMERATED16 (MMS Type: INT8) ENUMERATED16 (MMS Type: INT8)

Enumeration SIUnit multiplier SI Unit

Comment

Multiplier value, the default of which is 0 (i.e. multiplier = 1)

2.6.5

Component:
Comment: Parent Type: Vector

Vector_Magnitude_Float

Complex vector (w.r.t Floating Point Magnitude value)

(PM)-48

P341/EN PM/F74-S

P341

PICS & MICS

Attribute mag

Type AnalogueValue_Float

Enumeration

Comment The magnitude of the complex value

2.6.6

Component:
Comment: Parent Type: Vector
Attribute mag ang

Vector_MagnitudeAngle_Float

Complex vector (w.r.t Floating Point Magnitude and Angle values)

Type AnalogueValue_Float AnalogueValue_Float

Enumeration

Comment The magnitude of the complex value The angle of the complex value (the unit is degrees)

2.7

Enumerated type definitions


The following sub-sections specify the enumerations that are associated to some Common Data Class attributes. The definition of the enumerations are according to IEC 61850-7-3 and IEC 61850-7-4 unless otherwise stated.

2.7.1

Enumerated type: AddCause


Description:
Ordinal 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Unknown Not-supported Blocked-by-switching-hierarchy Select-failed Invalid-position Position-reached Parameter-change-in-execution Step-limit Blocked-by-Mode Blocked-by-process Blocked-by-interlocking Blocked-by-synchrocheck Command-already-in-execution Blocked-by-health 1-of-n-control Abortion-by-cancel Time-limit-over Abortion-by-trip Object-not-selected

Add Cause
Semantic

2.7.2

Enumerated type: Beh


Description:
Ordinal 1 on

Behaviour
Semantic

P341/EN PM/F74-S

(PM)-49

PICS & MICS

P341

Ordinal 2 3 4 5 blocked test test/blocked off

Semantic

2.7.3

Enumerated type: Bypass


Description:
Ordinal 0 1 2 3 4 5 locking-bypass mode-bypass automation-bypass uniqueness-bypass select-bypass status-bypass Semantic

2.7.4

Enumerated type: CBOpCap


Description:
Ordinal 1 2 3 4 5 None Open Close-Open Open-Close-Open Close-Open-Close-Open

CB Operating Capability
Semantic

2.7.5

Enumerated type: ctlModel


Description:
Ordinal 0 1 2 3 4 status-only direct-with-normal-security sbo-with-normal-security direct-with-enhanced-security sbo-with-enhanced-security

Control Model
Semantic

2.7.6

Enumerated type: Dbpos


Description:
Ordinal 0 1 2 3 intermediate off on bad

Circuit Breaker position


Semantic

2.7.7

Enumerated type: dir


Description: Direction

(PM)-50

P341/EN PM/F74-S

P341

PICS & MICS

Ordinal 0 1 2 3 unknown forward backward both

Semantic

2.7.8

Enumerated type: Health


Description:
Ordinal 1 2 3 Ok Warning Alarm

Health
Semantic

2.7.9

Enumerated type: Mod


Description:
Ordinal 1 2 3 4 5 on blocked test test/blocked off

Mode
Semantic

2.7.10

Enumerated type: multiplier


Description:
Ordinal -24 -21 -18 -15 -12 -9 -6 -3 -2 -1 0 1 2 3 6 9 12 15 18 da h k M G T P E y z a f p n m c d

Exponents of the multiplier value in base 10.


Semantic

P341/EN PM/F74-S

(PM)-51

PICS & MICS

P341

Ordinal 21 24 Z Y

Semantic

2.7.11

Enumerated type: orCategory


Description:
Ordinal 0 1 2 3 4 5 6 7 8 not-supported bay-control station-control remote-control automatic-bay automatic-station automatic-remote maintenance process

or Category
Semantic

2.7.12

Enumerated type: seqT


Description:
Ordinal 0 1 pos-neg-zero dir-quad-zero

Sequence Measurement Type


Semantic

2.7.13

Enumerated type: SIUnit


Description:
Ordinal -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 1 2 years months weeks V/s mins hours days F ratio miles inches feet df/dt Hz/s % pu none m

SI Units derived from ISO/IEC 1000


Semantic

(PM)-52

P341/EN PM/F74-S

P341

PICS & MICS

Ordinal 3 4 5 6 7 8 9 10 11 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 41 42 43 44 45 46 47 48 49 50 51 52 53 54 61 62 kg s A K mol cd deg rad sr Gy q C Sv F C S H V ohm J N Hz lx Lm Wb T W Pa m m m/s m/s m/s m/m M kg/m m/s W/m K J/K ppm 1/s rad/s VA Watts

Semantic

P341/EN PM/F74-S

(PM)-53

PICS & MICS

P341

Ordinal 63 64 65 66 67 68 69 70 71 72 73 74 VAr phi cos(phi) Vs V As A At VAh Wh VArh V/Hz

Semantic

2.8

MMS data-type conversions


The following table shows the relationships between the Part 7 and Part 8-1 data types. The definitions presented above use Part 7 data types, however these are subject to 'translation' when exposed over an MMS (Part 8-1) interface:
Part 7 Type BOOLEAN BSTR16 BVstring13 Check CODED_ENUM CODED_ENUM2 EntryTime ENUMERATED16 ENUMERATED8 FLOAT32 FLOAT64 INT128 INT16 INT16U INT24U INT32 INT32U INT8 INT8U OCTET_STRING6 OCTET_STRING64 OCTET_STRING8 Quality TimeStamp UNICODE_STRING255 UTC_TM Bool Bstring16 BVstring13 BVstring2 Byte Byte Btime6 Short Byte Float Double Int64 Short Ushort Ulong Long Ulong Byte Ubyte Ostring6 OVstring64 OVstring8 BVstring13 Utctime UTF8Vstring255 Utctime MMS Type Part 7 Description Logical TRUE/FALSE value Bit String 16 Variable bit string (upto 13 bits) Control Object check flags Coded enumeration Coded enumeration (2) 8.1 Section 8.1.3.7 16 bit enumerated value 8 bit enumerated value 32 bit floating point value 64 bit floating point value 128 bit signed integer value 16 bit signed integer value 16 bit unsigned integer value 24 bit unsigned integer value 32 bit signed integer value 32 bit unsigned integer value 8 bit signed integer value 8 bit unsigned integer value 6 character string (8 bits per character) 64 character string (8 bits per character) 8 character string (8 bits per character) IEC 61850 Quality IEC 61850 Time stamp 255 character string (16 bits per unicode character) UTC Timestamp

(PM)-54

P341/EN PM/F74-S

P341

PICS & MICS

Part 7 Type VISIBLE_STRING255 VISIBLE_STRING64 VISIBLE_STRING65 VISIBLE_STRING97

MMS Type Vstring255 Vstring64 Vstring65 Vstring97

Part 7 Description 255 character string 64 character string 65 character string 97 character string

P341/EN PM/F74-S

(PM)-55

PICS & MICS

P341

(PM)-56

P341/EN PM/F74-S