Micom P341: Interconnection Protection Relay
Micom P341: Interconnection Protection Relay
Note:
The technical manual for this device gives instructions for its installation, commissioning, and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate Schneider Electric technical sales office and request the necessary information. Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric including settlements of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the technical manual. This device MUST NOT be modified. If any modification is made without the express permission of Schneider Electric, it will invalidate the warranty, and may render the product unsafe.
The Schneider Electric logo and any alternative version thereof are trademarks and service marks of Schneider Electric. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. This manual is provided for informational use only and is subject to change without notice. 2011, Schneider Electric. All rights reserved.
P341
CONTENTS
1 PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS) 1.1 Introduction 1.2 ACSI basic conformance statement 1.3 ACSI models conformance statement 1.4 ACSI service conformance statement MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) 2.1 Introduction 2.2 Objective 2.3 Logical Device definitions
2.3.1 IEC 61850 Logical Device data model
5 5 5 5 7 11 11 11 11
11
2.4
2.4.1 2.4.2 2.4.3 2.4.4 2.4.5 2.4.6 2.4.7 2.4.8 2.4.9 2.4.10 2.4.11 2.4.12 2.4.13 2.4.14 2.4.15 2.4.16 2.4.17 2.4.18 2.4.19 2.4.20 2.4.21 2.4.22 2.4.23 2.4.24 2.4.25 2.4.26 2.4.27 2.4.28 2.4.29 2.4.30 2.4.31
16
17 17 20 21 22 23 24 25 25 26 26 26 27 27 27 28 28 28 29 29 29 29 30 30 30 30 31 31 31 31 32
P341/EN PM/F74-S
(PM)-1
P341
2.4.32 2.4.33 2.4.34 2.4.35 2.4.36 2.4.37 2.4.38 2.4.39 2.4.40 2.4.41 2.4.42 2.4.43
Logical Node: PTRC_NO_SEG Logical Node: PTTR_NO_SEG_PRIV Logical Node: PTUC_NEU Logical Node: PTUF_NO_SEG Logical Node: PTUV_NO_SEG Logical Node: PVSP_STANDARD Logical Node: RBRF_EXTTRIP Logical Node: RCLI_STANDARD Logical Node: RDRE_BASIC Logical Node: RSYN_DIFCLC Logical Node: RVCS_STANDARD_NO_CT2 Logical Node: XCBR_BASIC_ALL
32 32 33 33 33 33 34 34 34 34 35 35
2.5
2.5.1 2.5.2 2.5.3 2.5.4 2.5.5 2.5.6 2.5.7 2.5.8 2.5.9 2.5.10 2.5.11 2.5.12 2.5.13 2.5.14 2.5.15 2.5.16 2.5.17 2.5.18 2.5.19 2.5.20 2.5.21 2.5.22 2.5.23 2.5.24 2.5.25 2.5.26 2.5.27 2.5.28 2.5.29 2.5.30 2.5.31 2.5.32 2.5.33
36
36 37 37 37 37 38 38 39 39 39 40 40 40 41 41 41 41 42 42 42 42 43 44 44 44 45 45 45 46 46 46 46 47
(PM)-2
P341/EN PM/F74-S
P341
2.5.34 2.5.35
47 47
2.6
2.6.1 2.6.2 2.6.3 2.6.4 2.6.5 2.6.6
47
47 48 48 48 48 49
2.7
2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.7.7 2.7.8 2.7.9 2.7.10 2.7.11 2.7.12 2.7.13
49
49 49 50 50 50 50 50 51 51 51 52 52 52
2.8
54
P341/EN PM/F74-S
(PM)-3
P341
(PM)-4
P341/EN PM/F74-S
P341
1.1
1.2
1.3
P341/EN PM/F74-S
(PM)-5
P341
Client/ subscriber M5 M6 M7 M7-1 M7-2 M7-3 M7-4 M7-5 M7-6 M7-7 M7-8 M7-9 M7-10 M7-11 M8 M8-1 M8-2 M8-3 M8-4 M8-5 M8-6 M8-7 M8-8 M8-9 Logging M9 M9-1 M10 M11 If GSE (B31/32) is supported M12 M13 If SVC (41/42) is supported M14 M15 If Server or Client side (B11/12) is supported M16 M17 Time File Transfer Y Multicast SVC Unicast SVC GOOSE GSSE Y Control Log Log control IntgPd Substitution Setting group control Reporting Buffered report control sequence-number report-time-stamp reason-for-inclusion data-set-name data-reference buffer-overflow entryID BufTim IntgPd GI conf-revision Unbuffered report control sequence-number report-time-stamp reason-for-inclusion data-set-name data-reference BufTim IntgPd GI conf-revision
Server/ publisher Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y
Value/ comments
Y Y
(PM)-6
P341/EN PM/F74-S
P341
Server/ publisher
Value/ comments
1.4
P341/EN PM/F74-S
(PM)-7
P341
Services Setting group control S18 S19 S20 S21 S22 S23 Reporting Buffered report control block (BRCB) S24 S24-1 S24-2 S24-3 S25 S26 Unbuffered report control block (URCB) S27 S27-1 S27-2 S27-3 S28 S29 Logging Log control block S30 S31 Log S32 S33 S34 Generic substation event model (GSE) GOOSE-CONTROLBLOCK S35 S36 S37 SendGOOSEMessage GetReference GetGOOSEElementNumber QueryLogByTime QueryLogByEntry GetLogStatusValues GetLCBValues SetLCBValues Report data-change (dchg) qchg-change (qchg) data-update (dup GetURCBValues SetURCBValues Report data-change (dchg) qchg-change (qchg) data-update (dupd) GetBRCBValues SetBRCBValues SelectActiveSG SelectEditSG SetSGValues ConfirmEditSGValues GetSGValues GetSGCBValues
AA: TP/MC TP TP TP TP TP TP
Client (C)
Server (S) Y
Comments
Y Y
TP
Y Y
TP TP
Y Y
TP
Y Y
TP TP
Y Y
TP TP TP TP TP
MC TP TP
(PM)-8
P341/EN PM/F74-S
P341
Services S38 S39 GSSE-CONTROLBLOCK S40 S41 S42 S43 S44 Transmission of sampled value model (SVC) Multicast SVC S45 S46 S47 Unicast SVC S48 S49 S50 Control S51 S52 S53 S54 S55 S56 File transfer S57 S58 GetFile SetFile Select SelectWithValue Cancel Operate CommandTermination TimeActivated-Operate SendUSVMessage GetUSVCBValues SetUSVCBValues SendMSVMessage GetMSVCBValues SetMSVCBValues SendGSSEMessage GetReference GetGSSEElementNumber GetGsCBValues SetGsCBValues GetGoCBValues SetGoCBValues
AA: TP/MC TP TP
Client (C)
Server (S) Y Y
Comments
MC TP TP TP TP
MC TP TP TP TP TP
Y TP TP TP TP TP Y Y Y Y
TP TP
S59
DeleteFile
TP
S60 Time T1 T2
GetFileAttributeValues
TP
1 ms 1 ms
P341/EN PM/F74-S
(PM)-9
P341
Services
AA: TP/MC
Client (C)
Server (S) T2 T3 T4 T5
Comments
T3
1 ms
Table 3: Service conformance statement AA: Application association type TP: Two part (for MMS) MC: Multicast (for GOOSE and SMV)
(PM)-10
P341/EN PM/F74-S
P341
2.1
2.2
Objective
To provide comprehensive details of the standard data object model elements supported by the device. The MICS is conformant to the devices associated ICD (Substation Configuration Language) file, according to part 6 of the IEC 61850 standards. The layout of the presented tables within this document are conformant to the part 7 series of the IEC 61850 standard specifications with the following exceptions: The "Trigger Options" field is not presented The "M/O" field is not present as the definitions are as deployed within the model An additional column "X" is used to signify Schneider Electric custom attributes
2.3
2.3.1
P341/EN PM/F74-S
(PM)-11
P341
LD Control
LN Instance
LN Type
Description System Checks Check Sync 1 System Checks Check Sync 2 XCBR Interlocking LLN0 for control LD Physical Device Information Circuit Breaker Monitoring for All Module df/dt Measurements Logical Device Physical Device Information Primary C/S Measurements Primary Fourier Derived Measurands P341 only Primary Fixed demand measurements
AscRSYN1 AscRSYN2 CILO1 LLN0 LPHD1 XCBR1 Measurements DfpMMXU1 LLN0 LPHD1 PriCsvMMXU1 PriFouMMXU1
PriFxdMSTA1
MSTA_STANDARD
PriHa3MMXU1
P341/P342 only third harmonic MMXU_THIRD_HARMONIC_NO_VN measurements (no VN) MMTR_PRIV MSTA_STANDARD MMXU_RMS MSTA_STANDARD MMXU_SENSITIVE MSQI_ALL Primary based Energy flow metering quantities Primary Peak demand measurements Primary RMS measurements Primary Rolling demand measurements Primary Sensitive power measurements Primary Sequence measurements Primary Standard MMXU measurements for P341 only Secondary C/S Measurements Secondary Fourier Derived Measurands P341 only
PriStdMMXU1
MMXU_STANDARD_P341
SecCsvMMXU1 SecFouMMXU1
MMXU_CSV MMXU_DERIVED_P341
(PM)-12
P341/EN PM/F74-S
P341
LD
LN Instance SecFxdMSTA1
LN Type MSTA_STANDARD
SecHa3MMXU1
Secondary P341/P342 only Third MMXU_THIRD_HARMONIC_NO_VN Harmonic Measurements MMTR_PRIV Secondary based Energy flow metering quantities Secondary Peak Demand measurements Secondary RMS measurements Secondary Rolling Demand measurements Secondary Sensitive Power measurements Secondary Sequence measurements Secondary Standard MMXU measurements for P341 only CB Fail 1 CB Fail 2 CLIO Input 1 Alarm CLIO Input 2 Alarm CLIO Input 3 Alarm CLIO Input 4 Alarm Current loop input supervision - channel 1 Current loop input supervision - channel 2 Current loop input supervision - channel 3 Current loop input supervision - channel 4 Current Loop Input 1 Trip Current Loop Input 2 Trip Current Loop Input 3 Trip Current Loop Input 4 Trip
SecMMTR1
MMXU_STANDARD_P341
CliRCLI2
RCLI_STANDARD
CliRCLI3
RCLI_STANDARD
P341/EN PM/F74-S
(PM)-13
P341
LD
LN Instance ConPLMP1 DfpPFRC1 DfpPFRC2 DfpPFRC3 DfpPFRC4 EftPTOC1 EftPTOC2 EftPTOC3 EftPTOC4 FrqPTOF1 FrqPTOF2 FrqPTUF1 FrqPTUF2 FrqPTUF3 FrqPTUF4 LLN0 LPHD1 NpsPTOC1 NpsPTOC2 NpsPTOC3 NpsPTOC4 NpsPTOV1 OcpPTOC1 OcpPTOC2 OcpPTOC3 OcpPTOC4 PdpPPWR1 PdpPPWR2 PTRC1 SenPdpPPWR1 PLMP_NEU
LN Type
Description Reconnection timer df/dt> 1 Frequency Rate of Change df/dt> 2 Frequency Rate of Change df/dt> 3 Frequency Rate of Change df/dt> 4 Frequency Rate of Change Earth fault - stage 1 Earth fault - stage 2 Earth fault - stage 3 Earth fault - stage 4 F> 1 Overfrequency F> 2 Overfrequency F< 1 Underfrequency F< 2 Underfrequency F< 3 Underfrequency F< 4 Underfrequency LLN0 for P341 Physical Device Information NPS Overcurrent stage 1 NPS Overcurrent stage 2 NPS Overcurrent stage 3 NPS Overcurrent stage 4 NPS Overvoltage I>1Phase overcurrent I>2 Phase overcurrent I>3 Phase overcurrent I>4 Phase overcurrent Power protection (3phase) stage 1 Power protection (3phase) stage 2 Trip Conditioning Sensitive power (Single phase) stage 1 Sensitive power (Single phase) stage 2 IREF> 1 Restricted Earth Fault ISEF>1 Protection
PFRC_NO_SEG PFRC_NO_SEG PFRC_NO_SEG PFRC_NO_SEG PTOC_NO_SEG PTOC_NO_SEG PTOC_NO_SEG PTOC_NO_SEG PTOF_NO_SEG PTOF_NO_SEG PTUF_NO_SEG PTUF_NO_SEG PTUF_NO_SEG PTUF_NO_SEG LLN0_P341 LPHD_STANDARD PTOC_NEU PTOC_NEU PTOC_NEU PTOC_NEU PTOV_NEU PTOC_NEU PTOC_NEU PTOC_NEU PTOC_NEU PPWR_NORMAL PPWR_NORMAL PTRC_NO_SEG PPWR_NORMAL
(PM)-14
P341/EN PM/F74-S
P341
LD
LN Instance SenSefPTOC2 SenSefPTOC3 SenSefPTOC4 SvnRVCS1 ThmPTTR1 VtpPhsPTOV1 VtpPhsPTOV2 VtpPhsPTUV1 VtpPhsPTUV2 VtpResPTOV1 VtpResPTOV2 VtpResPTOV3 VtpResPTOV4 VvsPVSP1
LN Type PTOC_NO_SEG PTOC_NO_SEG PTOC_NO_SEG RVCS_STANDARD_NO_CT2 PTTR_NO_SEG_PRIV PTOV_NO_SEG PTOV_NO_SEG PTUV_NO_SEG PTUV_NO_SEG PTOV_NO_SEG PTOV_NO_SEG PTOV_NO_SEG PTOV_NO_SEG PVSP_STANDARD
Description ISEF>2 Protection ISEF>3 Protection ISEF>4 Protection Supervision without CTS2. Thermal Overload Phase Overvoltage stage 1 Phase Overvoltage stage 2 Phase Undervoltage Stage 1 Phase Undervoltage Stage 2 Residual Over Voltage - stage 1 Residual Over Voltage - stage 2 Residual Over Voltage - stage 3 Residual Over Voltage - stage 4 Voltage vector shift Records Logical Device Physical Device Information Disturbance Recorder Alarms GOOSE Input Signals GOOSE Output Signals 8 programmable LEDS Sys Logical Device Physical Device Information Opto Inputs (24 off) (64 off)Uniqueness of control "Order Running" indications for Control operations Controllable Inputs
Records LLN0 LPHD1 RDRE1 System AlmGGIO1 GosGGIO1 GosGGIO2 LedGGIO1 LLN0 LPHD1 OptGGIO1 OrdRunGGIO1 PloGGIO1 GGIO_ALM_96 GGIO_IND_64 GGIO_IND_32 GGIO_IND_8 LLN0_SYSTEM LPHD_STANDARD GGIO_IND_24 GGIO_IND_64 GGIO_IND_32_CTRL LLN0_STANDARD LPHD_STANDARD RDRE_BASIC
P341/EN PM/F74-S
(PM)-15
P341
LD
LN Instance RlyGGIO1
LN Type GGIO_IND_24
2.4
Measurements (w.r.t 3rd Harmonic, no VN IEC 61850-7-4:2003 for P341/P342) Sequence and imbalance (w.r.t Pos, Neq, IEC 61850-7-4:2003 Zero) Standard measurements (w.r.t Fourier Derived Values) Differential (w.r.t Neutral) Rate of change of frequency (w.r.t No Phase Segregation) IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003
PLMP_NEU PPWR_NORMAL
(PLMP) (PPWR)
Loss of mains protection, similar to PTOC but without current setting and modified SE-SII:PCS-Px40 meanings for the pick up and drop off timers Power Protection with Pole Dead Inhibit SE-SII:PCS-Px40
(PM)-16
P341/EN PM/F74-S
P341
LN Type PTOC_NEU PTOC_NO_SEG PTOF_NO_SEG PTOV_NEU PTOV_NO_SEG PTRC_NO_SEG PTTR_NO_SEG_PRIV PTUC_NEU PTUF_NO_SEG PTUV_NO_SEG PVSP_STANDARD RBRF_EXTTRIP RCLI_STANDARD RDRE_BASIC RSYN_DIFCLC RVCS_STANDARD_NO_C T2XCBR_BASIC_ALL
(LN (PTOC) (PTOC) (PTOF) (PTOV) (PTOV) (PTRC) (PTTR) (PTUC) (PTUF) (PTUV) (PVSP) (RBRF) (RCLI) (RDRE) (RSYN) (RVCS) (XCBR)
Description Timed Overcurrent (w.r.t Neutral) Timed Overcurrent (w.r.t No Phase Segregation) Overfrequency (w.r.t No Phase Segregation) Overvoltage (w.r.t Neutral) Overvoltage (w.r.t Phase Segregation) Protection trip conditioning (w.r.t No Phase Segregation) Thermal overload for Thermal State and NPS Thermal (w.r.t No Phase Segregation) Models timed under-current protection Underfrequency (w.r.t No Phase Segregation) Undervoltage (w.r.t No Phase Segregation) Voltage Vector Shift protection Breaker Failure (w.r.t External Tripping) Current loop monitoring and reporting Disturbance Recorder function (w.r.t Mandatory Attributes only)
Name Space IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 IEC 61850-7-2:2003 IEC 61850-7-4:2003 IEC 61850-7-4:2003 SE-SII:PCS-Px40 IEC 61850-7-4:2003 SE-SII:PCS-Px40 IEC 61850-7-4:2003
Synchronism-check / Synchronising (w.r.t IEC 61850-7-4:2003 Calculated Differential Measurements) VTS/CTS monitoring and report SE-SII:PCS-Px40 Circuit Breaker (w.r.t Mandatory Attributes IEC 61850-7-4:2003 Only)
2.4.1
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt EnaOpn EnaCls
CILO_INTERLOCK
2.4.2
Logical Node:
Description: LN Class:
Attribute Mod Beh Health
GGIO_ALM_96
P341/EN PM/F74-S
(PM)-17
P341
Attribute NamPlt Alm1 Alm2 Alm3 Alm4 Alm5 Alm6 Alm7 Alm8 Alm9 Alm10 Alm11 Alm12 Alm13 Alm14 Alm15 Alm16 Alm17 Alm18 Alm19 Alm20 Alm21 Alm22 Alm23 Alm24 Alm25 Alm26 Alm27 Alm28 Alm29 Alm30 Alm31 Alm32 Alm33 Alm34 Alm35 Alm36 Alm37 Alm38 Alm39 Alm40 Alm41 Alm42 Alm43 LPL_LN SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D
Explanation General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm
(PM)-18
P341/EN PM/F74-S
P341
Attribute Alm44 Alm45 Alm46 Alm47 Alm48 Alm49 Alm50 Alm51 Alm52 Alm53 Alm54 Alm55 Alm56 Alm57 Alm58 Alm59 Alm60 Alm61 Alm62 Alm63 Alm64 Alm65 Alm66 Alm67 Alm68 Alm69 Alm70 Alm71 Alm72 Alm73 Alm74 Alm75 Alm76 Alm77 Alm78 Alm79 Alm80 Alm81 Alm82 Alm83 Alm84 Alm85 Alm86 Alm87 SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D
Attr. Type
Explanation General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm
P341/EN PM/F74-S
(PM)-19
P341
Attribute Alm88 Alm89 Alm90 Alm91 Alm92 Alm93 Alm94 Alm95 Alm96 SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D
Attr. Type
Explanation General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm General single alarm
2.4.3
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Ind11 Ind12 Ind13 Ind14 Ind15 Ind16 Ind17 Ind18 Ind19 Ind20 Ind21 Ind22 Ind23
GGIO_IND_24
(PM)-20
P341/EN PM/F74-S
P341
Attr. Type
2.4.4
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Ind11 Ind12 Ind13 Ind14 Ind15 Ind16 Ind17 Ind18 Ind19 Ind20 Ind21 Ind22 Ind23 Ind24 Ind25 Ind26 Ind27 Ind28 Ind29 Ind30 Ind31
GGIO_IND_32
P341/EN PM/F74-S
(PM)-21
P341
Attr. Type
2.4.5
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt SPCSO1 SPCSO2 SPCSO3 SPCSO4 SPCSO5 SPCSO6 SPCSO7 SPCSO8 SPCSO9 SPCSO10 SPCSO11 SPCSO12 SPCSO13 SPCSO14 SPCSO15 SPCSO16 SPCSO17 SPCSO18 SPCSO19 SPCSO20 SPCSO21 SPCSO22 SPCSO23 SPCSO24 SPCSO25 SPCSO26 SPCSO27 SPCSO28 SPCSO29 SPCSO30 SPCSO31
GGIO_IND_32_CTRL
(PM)-22
P341/EN PM/F74-S
P341
Attribute SPCSO32
2.4.6
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Ind1 Ind2 Ind3 Ind4 Ind5 Ind6 Ind7 Ind8 Ind9 Ind10 Ind11 Ind12 Ind13 Ind14 Ind15 Ind16 Ind17 Ind18 Ind19 Ind20 Ind21 Ind22 Ind23 Ind24 Ind25 Ind26 Ind27 Ind28 Ind29 Ind30 Ind31 Ind32 Ind33 Ind34
GGIO_IND_64
P341/EN PM/F74-S
(PM)-23
P341
Attribute Ind35 Ind36 Ind37 Ind38 Ind39 Ind40 Ind41 Ind42 Ind43 Ind44 Ind45 Ind46 Ind47 Ind48 Ind49 Ind50 Ind51 Ind52 Ind53 Ind54 Ind55 Ind56 Ind57 Ind58 Ind59 Ind60 Ind61 Ind62 Ind63 Ind64 SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D SPS_D
Attr. Type
Explanation General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input) General indication (binary input)
2.4.7
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Ind1 Ind2 Ind3 Ind4 Ind5
GGIO_IND_8
(PM)-24
P341/EN PM/F74-S
P341
Attr. Type
Explanation General indication (binary input) General indication (binary input) General indication (binary input)
2.4.8
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt AscMod AscBeh
LLN0_CONTROL
2.4.9
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt PdpMod PdpBeh EftMod EftBeh FrqMod SenMod FrqBeh SenBeh DfpMod DfpBeh ThmMod ThmBeh CbfMod CbfBeh SvnBeh SvnMod NvdMod NvdBeh VtpMod VtpBeh
LLN0_P341
P341/EN PM/F74-S
(PM)-25
P341
Attribute VvsMod VvsBeh OcpMod OcpBeh RctMod RctBeh CliMod CliBeh SefMod SefBeh SycMod SycBeh
Attr. Type INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV INC_CTRL_PRIV INS_BEH_D_PRIV
Explanation Voltage vector Shift Mode Voltage vector shift Behaviour Overcurrent Mode Overcurrent Behaviour Reconnection Delay Mode Reconnection Delay Behaviour CLIO Inputs Mode CLIO Inputs Behaviour SEF/REF Mode SEF/REF Behaviour System Checks Mode System Checks Behaviour
2.4.10
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt
LLN0_STANDARD
2.4.11
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt LEDRs OrdRun SyncSt
LLN0_SYSTEM
2.4.12
Logical Node:
Description: LN Class:
Attribute PhyNam PhyHealth Proxy
LPHD_STANDARD
(PM)-26
P341/EN PM/F74-S
P341
Attr. Type
2.4.13
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt SupWh SupVArh DmdWh DmdVArh MTRRs
MMTR_PRIV
Metering MMTR
Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN BCR_PRIV BCR_PRIV BCR_PRIV BCR_PRIV SPC_CTRL_PRIV Mode Behaviour Health Name Plate Real energy supply (Energy flow towards bus bar) Reactive energy supply (Energy flow towards bus bar) Real energy demand (Energy flow from bus bar) Reactive energy demand (Energy flow from bus bar) Reset Energy Measurements X Explanation T X
2.4.14
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt CSVol INS_BEH
MMXU_CSV
2.4.15
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Hz PPV A A2 W VA INS_BEH
MMXU_DERIVED_P341
P341/EN PM/F74-S
(PM)-27
P341
Attr. Type WYE_SEG WYE_SEG_NS DEL_SEG_NS MV_FLOAT_NS WYE_SEG_NS MV_FLOAT_NS MV_FLOAT_NS MV_FLOAT_NS WYE_SEG_NS WYE_SEG_NS WYE_RES_ANG_D_NS
2.4.16
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Dfdt
MMXU_DFDT
2.4.17
Logical Node:
Description: LN Class:
Attribute Beh Mod Health NamPlt PhV A
MMXU_RMS
2.4.18
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt A W INS_BEH
MMXU_SENSITIVE
(PM)-28
P341/EN PM/F74-S
P341
Explanation
X X X
2.4.19
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt VN INS_BEH
MMXU_STANDARD_P341
2.4.20
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt
MMXU_THIRD_HARMONIC_NO_VN
2.4.21
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt SeqA SeqV
MSQI_ALL
2.4.22
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt
MSTA_STANDARD
P341/EN PM/F74-S
(PM)-29
P341
Explanation Total reactive power (Total Q) Total active power (Total P) Phase apparent power (S)
X X X X
2.4.23
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Op
PDIF_NEU
2.4.24
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op
PFRC_NO_SEG
2.4.25
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Op
PLMP_NEU
Loss of mains protection, similar to PTOC but without current setting and modified meanings for the pickup and drop off timers PLMP
Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN_P ACT_NO_SEG Mode Behaviour Health Name Plate Operate (Trip) Explanation T X
2.4.26
Logical Node:
Description: LN Class:
Attribute Mod Beh Health
PPWR_NORMAL
(PM)-30
P341/EN PM/F74-S
P341
Explanation
2.4.27
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op
PTOC_NEU
2.4.28
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op
PTOC_NO_SEG
2.4.29
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op
PTOF_NO_SEG
2.4.30
Logical Node:
Description: LN Class:
Attribute Mod
PTOV_NEU
P341/EN PM/F74-S
(PM)-31
P341
Attr. Type INS_BEH INS_HEALTH LPL_LN ACD_NO_SEG ACT_NO_SEG Behaviour Health Name Plate Start Operate
Explanation
2.4.31
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op
PTOV_NO_SEG
2.4.32
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Tr Str
PTRC_NO_SEG
2.4.33
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt TmpRl Op AlmThm
PTTR_NO_SEG_PRIV
Thermal overload for Thermal State and NPS Thermal (w.r.t No Phase Segregation) PTTR
Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN MV_FLOAT ACT_NO_SEG ACT_NO_SEG Mode Behaviour Health Name Plate Relation between temperature and maximum temperature Operate Thermal alarm T T Explanation T X
(PM)-32
P341/EN PM/F74-S
P341
Attribute MTRRs
X X
2.4.34
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op ModOvA
PTUC_NEU
2.4.35
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op
PTUF_NO_SEG
2.4.36
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Str Op
PTUV_NO_SEG
2.4.37
Logical Node:
Description: LN Class:
Attribute Mod Beh
PVSP_STANDARD
P341/EN PM/F74-S
(PM)-33
P341
2.4.38
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt OpEx
RBRF_EXTTRIP
2.4.39
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Val Blk Min Max
RCLI_STANDARD
2.4.40
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt RcdMade FltNum
RDRE_BASIC
2.4.41
Logical Node:
Description: LN Class:
RSYN_DIFCLC
(PM)-34
P341/EN PM/F74-S
P341
Attribute Mod Beh Health NamPlt Rel VInd AngInd HzInd DifVClc DifHzClc DifAngClc
Attr. Type INC_MOD INS_BEH INS_HEALTH LPL_LN SPS_WD SPS_WD SPS_WD SPS_WD MV_FLOAT MV_FLOAT MV_FLOAT Mode Behaviour Health Name Plate Release
Explanation
Voltage difference indicator Angle difference indicator Frequency difference indicator Calculated difference in voltage Calculated difference in frequency Calculated difference of phase angle
2.4.42
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt SlwVTSBlk FstVTSBlk CTSBlk
RVCS_STANDARD_NO_CT2
2.4.43
Logical Node:
Description: LN Class:
Attribute Mod Beh Health NamPlt Loc EEHealth OpCnt Pos BlkOpn BlkCls CBOpCap INS_BEH
XCBR_BASIC_ALL
P341/EN PM/F74-S
(PM)-35
P341
Attribute Lock
Explanation Prevention, i.e. Lock, Trip/Close Operation of Circuit Breaker over IEC 61850
X X
2.5
2.5.1
ACD_NO_SEG
(PM)-36
P341/EN PM/F74-S
P341
Attribute t
Type TimeStamp
FC ST
Enumeration
2.5.2
ACT_NO_SEG
TimeStamp
ST
2.5.3
ASG_FLOAT
2.5.4
BCR_PRIV
pulsQty
FLOAT32
CF
2.5.5
CMV_MAG_ANG_FLOAT
P341/EN PM/F74-S
(PM)-37
P341
Attribute
Type
FC
Enumeration
Comment Deadbanded complex measured vector. Updated to the current value of instCVal when the value has changed according to the configuration parameter db. Quality of the measurement value Time deadbanded magnitude last exceeded its db configuration parameter Unit of the attribute representing the data Measurement deadband Measurement range configuration attributes
cVal
Vector_MagnitudeAngle_Float
MX
Quality
MX
TimeStamp
MX
units db rangeC
CF CF CF
2.5.6
CMV_MAG_FLOAT
cVal
Vector_Magnitude_Float
MX
Quality
MX
TimeStamp
MX
units db rangeC
CF CF CF
2.5.7
DEL_SEG
Phase to phase measurements for a 3-Phase system (w.r.t Phase Segregation) DEL
(PM)-38
P341/EN PM/F74-S
P341
FC ----
Enumeration
Comment Measurement values for Phase A to Phase B Measurement values for Phase B to Phase C Measurement values for Phase C to Phase A
2.5.8
DEL_SEG_NS
2.5.9
DPC_STATUS_P341
stVal q t
ST ST ST
ctlModel
CF
sboTimeout
CF
2.5.10
DPL_STANDARD
P341/EN PM/F74-S
(PM)-39
P341
FC DC DC DC DC DC
Enumeration
Comment Hardware revision Software revision Serial Number Model Number Physical location of device
2.5.11
INC_CTRL_PRIV
ctlModel d dataNs
CF DC EX
VISIBLE_STRING255 VISIBLE_STRING255
2.5.12
INC_MOD
ctlModel
CF
2.5.13
INS_BASIC
(PM)-40
P341/EN PM/F74-S
P341
Attribute q t Quality
Type
FC ST ST
Enumeration
Comment The quality of the status value Timestamp of the last change in state
TimeStamp
2.5.14
INS_BEH
2.5.15
INS_BEH_D_PRIV
2.5.16
INS_CB_OPCAP
2.5.17
INS_HEALTH
P341/EN PM/F74-S
(PM)-41
P341
Attribute stVal q t
FC ST ST ST
Enumeration Health
Comment The element status The quality of the status value Timestamp of the last change in state
2.5.18
LPL_LLN0
2.5.19
LPL_LN
2.5.20
LPL_LN_P
2.5.21
MV_FLOAT
(PM)-42
P341/EN PM/F74-S
P341
Attribute
Type
FC
Enumeration
Comment Deadbanded magnitude of the instantaneous value of a measured value or harmonic value. Updated to the current value of instMag when the value has changed according to the configuration parameter db. Quality of the measurement value Time deadbanded magnitude last exceeded its db configuration parameter Unit of the attribute representing the data Measurement deadband Measurement range configuration attributes
mag
AnalogueValue_Float
MX
Quality
MX
TimeStamp
MX
units db rangeC
CF CF CF
2.5.22
MV_FLOAT_NS
mag
AnalogueValue_Float
MX
Quality
MX
TimeStamp
MX
units db rangeC
CF CF CF
P341/EN PM/F74-S
(PM)-43
P341
Attribute dataNs
Type VISIBLE_STRING255
FC EX
Enumeration
2.5.23
SEQ_MAG_ANG
c2
CMV_MAG_ANG_FLOAT
--
c3
CMV_MAG_ANG_FLOAT
--
seqT
MX
2.5.24
SPC_CONTROL
ctlModel
CF
sboTimeout
CF
2.5.25
SPC_CTRL_PRIV
(PM)-44
P341/EN PM/F74-S
P341
Type
FC ST ST ST ST
Enumeration
Comment Originator of the last change of the controllable data Status value of the data Quality of the status value Timestamp of the last change in state of status value
ctlModel
CF
ctlModel
Control model (Corresponding to the behaviour of the data) Select Before Operate timeout period (in milliseconds) Data name space
sboTimeout dataNs
CF EX
2.5.26
SPC_STATUS
ctlModel
CF
2.5.27
SPS_D
VISIBLE_STRING255
2.5.28
SPS_WD
P341/EN PM/F74-S
(PM)-45
P341
Attribute stVal q t
FC ST ST ST
Enumeration
Comment The element status (TRUE or FALSE) The quality of the status value Timestamp of the last change in state
2.5.29
SPS_WD_NS
VISIBLE_STRING255
2.5.30
WYE_RES_ANG_D
Phase to ground measurements for a 3-Phase system (w.r.t + Description + Angle) WYE
Type CMV_MAG_ANG_FLOAT VISIBLE_STRING255 FC -DC Enumeration Comment Measurement values for the residual system current Description of the status element X
2.5.31
WYE_RES_ANG_D_NS
Phase to ground measurements for a 3-Phase system (w.r.t + Description + Angle) WYE
Type CMV_MAG_ANG_FLOAT VISIBLE_STRING255 VISIBLE_STRING255 FC -DC EX Enumeration Comment Measurement values for the residual system current Description of the status element Data name space X
2.5.32
WYE_RES_MAG_NS
(PM)-46
P341/EN PM/F74-S
P341
FC -EX
Enumeration
Comment Measurement values for the residual system current Data name space
2.5.33
WYE_SEG
Phase to ground measurements for a 3-Phase system (w.r.t Phase Segregation) WYE
Type CMV_MAG_FLOAT CMV_MAG_FLOAT CMV_MAG_FLOAT FC ---Enumeration Comment Measurement values for Phase A Measurement values for Phase B Measurement values for Phase C X
2.5.34
WYE_SEG_NS
2.5.35
WYE_SEG_PHASEA
2.6
2.6.1
Component:
Comment:
AnalogueValue_Float
P341/EN PM/F74-S
(PM)-47
P341
Attribute f FLOAT32
Type
Enumeration
2.6.2
Component:
Comment: Parent Type:
Attribute orIdent
Originator
Originator of the last change of data attribute representing the value of a controllable data object
Type OCTET_STRING64
Enumeration
Comment Originator identification (Null value indicates unknown or not reported) Originator category (Notsupported, bay-control, station-control, remotecontrol, automatic-bay, automatic-station, automaticremote, maintenance or process)
orCat
orCategory
2.6.3
Component:
Comment:
RangeConfig_Deadband
2.6.4
Component:
Comment: Parent Type: Unit
Attribute SIUnit multiplier
Unit_multiplier
SI Unit definitions
Comment
2.6.5
Component:
Comment: Parent Type: Vector
Vector_Magnitude_Float
(PM)-48
P341/EN PM/F74-S
P341
Attribute mag
Type AnalogueValue_Float
Enumeration
2.6.6
Component:
Comment: Parent Type: Vector
Attribute mag ang
Vector_MagnitudeAngle_Float
Enumeration
Comment The magnitude of the complex value The angle of the complex value (the unit is degrees)
2.7
2.7.1
Add Cause
Semantic
2.7.2
Behaviour
Semantic
P341/EN PM/F74-S
(PM)-49
P341
Semantic
2.7.3
2.7.4
CB Operating Capability
Semantic
2.7.5
Control Model
Semantic
2.7.6
2.7.7
(PM)-50
P341/EN PM/F74-S
P341
Semantic
2.7.8
Health
Semantic
2.7.9
Mode
Semantic
2.7.10
P341/EN PM/F74-S
(PM)-51
P341
Ordinal 21 24 Z Y
Semantic
2.7.11
or Category
Semantic
2.7.12
2.7.13
(PM)-52
P341/EN PM/F74-S
P341
Ordinal 3 4 5 6 7 8 9 10 11 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 41 42 43 44 45 46 47 48 49 50 51 52 53 54 61 62 kg s A K mol cd deg rad sr Gy q C Sv F C S H V ohm J N Hz lx Lm Wb T W Pa m m m/s m/s m/s m/m M kg/m m/s W/m K J/K ppm 1/s rad/s VA Watts
Semantic
P341/EN PM/F74-S
(PM)-53
P341
Semantic
2.8
(PM)-54
P341/EN PM/F74-S
P341
Part 7 Description 255 character string 64 character string 65 character string 97 character string
P341/EN PM/F74-S
(PM)-55
P341
(PM)-56
P341/EN PM/F74-S