SECTION 16011 SPECIAL REQUIREMENTS ELECTRONIC EQUIPMENT REQUIREMENTS :CONSTRUCTION 1.1 1

Electronic components of communication systems, security systems and special systems and electronic components forming part of the power generation and distribution system are to be solid-state integrated construction, unless otherwise .approved :TEMPERATURE LIMITS 1.2

Manufacturer is to indicate maximum and minimum ambient temperatures acceptable for the equipment to operate continuously and normally and beyond .which electronic components may suffer permanent damage ALTERNATIVE ELECTRONIC EQUIPMENT 1.3

May be submitted for approval, provided such equipment meets or exceeds the functional capabilities and/or performance parameters of the equipment specified. Proposals for alternative equipment will be considered only if accompanied by the :following information List of operational characteristics and performance parameters List of differences in operation and performance Between proposed and specified equipment List of changes required and resulting implications Drawings indicating changes required to system wiring Statement of advantages of proposed equipment over that .specified -

Cleopatra Plaza Tower (Nasr City) Specifications

16011/ 1

Rev.0 March.2012

Crown Home Consultants

:PROTECTION

1.4

Solid-state equipment under normal conditions of operation is to withstand any surges which might be produced by sudden mains or standby power switching operations. Protective devices are to be provided to protect against surges, failure .of output stages due to open circuit, short-circuit or miss-match :INDICATOR LIGHTS 1.5

.(Other than LV pilot lamps are to be light emitting diodes (LEDs :ELECTROMAGNETIC RELAYS 1.6

.Control/small power transformers are to be designed to withstand the 500 V a.c .test voltage between winding and winding or winding and core

:DUST COVERS

1.7

Easily removable for inspection and servicing, are to be provided for all relays and .sensitive elements :OUTDOOR EQUIPMENT 1.8

Electronic or other, is to be designed for maximum ambient temperature or direct sun and is to be protected/enclosed, as applicable, against dust and weather .conditions :EXTERNAL INTERFERENCE 1.9

Carry out field investigations and tests to determine possible interference from .outside sources, and design electronic equipment to ensure trouble-free operation :SEGREGATION OF WIRING 1.10

Design wiring so that low current circuits are segregated from power wiring, using different conduits and wire ways for the purpose. Composite wiring will be acceptable for the same system in accordance with the relevant codes; cable .insulation is to be of same grade for all conductors in a common enclosure :POWER SUPPLY UNITS 1.11

For low current systems, which are fed from the LV, supply is to be independently fused on the live conductor and are to have front panel mains indicator light,
Cleopatra Plaza Tower (Nasr City) Specifications 16011/ 2 Rev.0 March.2012

Crown Home Consultants

on/off switch and standard cartridge type fuse holder. Blown fuse indicator lamp is to be provided when fuse does not have indicator. END OF SECTION 16011

Cleopatra Plaza Tower (Nasr City) Specifications

16011/ 3

Rev.0 March.2012