Rovinari Latitude Legal Time Albedo 45.0N Time zone UT+2 0.20
Simulation parameters Collector Plane Orientation Horizon Near Shadings PV Array Characteristics Si-poly Model Manufacturer Number of PV modules In series Total number of PV modules Nb. modules Array global power Nominal (STC) Array operating characteristics (50C) U mpp Total area Module area PV module Inverter Characteristics Model Manufacturer Operating Voltage Phono Solar 20 modules 3400 884 kWp 630 V 6597 m Tilt Free Horizon Linear shadings 25 Azimuth 0
535-850 V
800 kW AC
PV Array loss factors Thermal Loss factor Uc (const) 20.0 W/mK => Nominal Oper. Coll. Temp. (G=800 W/m, Tamb=20C, Wind=1 m/s.) Wiring Ohmic Loss Global array res. Module Quality Loss Module Mismatch Losses Incidence effect, ASHRAE parametrization IAM = 8.3 mOhm
1 - bo (1/cos i - 1)
User's needs :
PVSYST V5.70
PV Rovinari 1
System type Linear shadings tilt Mode Nb. of modules Model Unlimited load (grid) Grid-Connected 25 3400 azimuth 0 Pnom 260 Wp Pnom total 884 kWp Pnom 800 kW ac
East
West
South
Iso-shadings diagram
90
1 2
13h 14h
1: 22 june 2: 22 may - 23 july 3: 20 apr - 23 aug 4: 20 mar - 23 sep 5: 21 feb - 23 oct 6: 19 jan - 22 nov 7: 22 december
3 15h
45
9h
16h
8h 30 7h
17h
6 7
18h
15
6h
19h
PVSYST V5.70
PV Rovinari 1
System type Linear shadings tilt Model Nb. of modules Model Unlimited load (grid) Produced Energy Performance Ratio PR Grid-Connected 25 3400 azimuth 0 Pnom 260 Wp Pnom total 884 kWp Pnom 800 kW ac
Specific prod.
1540 kWh/kWp/year
Performance Ratio PR
1.0 PR : Performance Ratio (Yf / Yr) : 0.802
Performance Ratio PR
0.6
0.4
2 0.2 1
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
0.0
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
Horizontal global irradiation Ambient Temperature Global incident in coll. plane Effective Global, corr. for IAM and shadings
Effective energy at the output of the array Energy injected into grid Effic. Eout array / rough area Effic. Eout system / rough area
PVSYST V5.70
PV Rovinari 1
System type Linear shadings tilt Model Nb. of modules Model Unlimited load (grid) Grid-Connected 25 3400 azimuth 0 Pnom 260 Wp Pnom total 884 kWp Pnom 800 kW ac
1585 kWh/m
Horizontal global irradiation +21.1% Global incident in coll. plane -2.8% -3.0% Near Shadings, "linear" IAM factor on global Effective irradiance on collectors PV conversion Array nominal energy (at STC effic.) -2.9% -6.4% -1.6% -2.1% -1.0% PV loss due to irradiance level PV loss due to temperature Module quality loss Module array mismatch loss Ohmic wiring loss Array virtual energy at MPP Inverter Loss during operation (efficiency) Inverter Loss over nominal inv. power Inverter Loss due to power threshold Inverter Loss over nominal inv. voltage Inverter Loss due to voltage threshold Available Energy at Inverter Output Energy injected into grid
1385 MWh -1.7% 0.0% -0.0% 0.0% -0.0% 1362 MWh 1362 MWh