CEILING SYSTEMS
T E C H N I C AL G U I D E
DrywallGridSystem
STUCCO/PLASTER
Grid Systems
Hanging and Framing
Stucco/Plaster Ceilings
8/8/08
12:06 PM
Page 2
TABLE OF CONTENTS
DrywallGridSystem
8/8/08
12:06 PM
Page 3
DrywallGridSystem
Performance
Code Compliance
City of LA RR 25348
Miami/Dade Wind Uplift
NOA #07-0119-02 03/17/10
8/8/08
12:06 PM
Page 4
DrywallGridSystem
Main Beams
Item #
HD8906
HD8906G90
SP135
Length
Face
Dimension
144"
135"
Profile
Height
Duty
Load
1-1/2"
Heavy
1-11/16" duty
1-1/2"
Heavy
1-11/16" duty
Fire
Rated
Routs
Yes
51 routs
starting
2-1/4" from
each end (type
F fixture
compatible)
No
13-1/2" o.c.
starting
6-3/4" from
each end
95.5
Perspective
4'
Cross Tees
Item #
Length
Face
Dimension
Profile
Height
Fire Rated
Routs
XL7936G90
36"
1-1/2"
1-1/2"
No
none
Yes
3 routscenter
rout and 10"
from each end
(type F fixture
compatible)
XL8926
XL8926G90
24"
1-1/2"
1-1/2"
129.0
Perspective
49.96
158.0
Wire Load
9 Gauge Wire Breaking Strength and Technical Data
NOTE:
Per ASTM C 1063 wires must
be plumb and straight.
8/8/08
12:06 PM
Page 5
STUCCO/PLASTER INSTALLATION
DrywallGridSystem
Hanger Wire
Hanger Wire
Main Beam
Wafer Screw
Cross Tee
Stucco or
Plaster
Stop
Main Beam
Space
Main Beam
Wafer
Head
Screw
Wall
3/8'' Min.
Track
Expansion Joint
Isolated Corner
Control Joint
8/8/08
12:06 PM
Page 6
STUCCO/PLASTER DETAILS
DrywallGridSystem
Main Beam
Metal Stud
Vertical Brace
Cross Tee
Hanger Wire
Main Beam
Wafer
Screw
Stucco
Metal Lath
Cross Tee
Stucco
Lighting Troffer
Cross Tee
Adjustable
Arm
Main
Beam
Main Beam
Wall
Metal Lath
Light
Fixture
Metal Lath
Flange
Stucco
"STOP"
Screwed to
Suspension
3/8"
Min.
3' O.C.
Main Beam
Main Beam
Rock Lath
Butterfly Clips
Control Joint
Plaster
8/8/08
12:06 PM
Page 7
WIND LOAD
DrywallGridSystem
6 1
10 3
10 4
15 0
15 1
20 0
Up Lift
Load
(MPH)
Up Lift
Load
(Lbs./Ft.2 )
Stud
Thickness
(Inch)
Stud
Gauge
(Ga. No.)
15
30
45
60
90
120
140
172
15
30
45
60
90
120
140
172
*15
*30
*45
*60
*90
*120
*140
*172
**15
**30
**45
**60
**90
**120
**140
**172
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
22
22
22
22
22
22
22
22
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
16
16
16
16
16
16
16
16
Membrane Substrate
3/8 Ribbed Sheet Lath
3.4 Lbs/SQ. YD., Per ASTM C-847
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
Main Runner
Spacing
(Inch)
Cross Tee
Spacing
(Inch)
Hanger Wire
Spacing
(Feet)
Cross Tee
Length
(Feet)
Compression
Post Spacing
(Feet)
Compression
Post Load
(Lbs.)
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
4 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
2.5 O.C.
2. O.C.
2 O.C.
4 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
2.5 O.C.
2. O.C.
2 O.C.
4 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
2.5 O.C.
2. O.C.
2 O.C.
4 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
2.5 O.C.
2. O.C.
2 O.C.
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
3
2.5
2.
2
4
4
4
4
3
2.5
2.
2
4
4
4
4
3
2.5
2.
2
4
4
4
4
3
2.5
2.
2
6.9
28
63
111
187
184
301
300
6.9
28
63
111
187
184
301
300
6.9
28
63
111
187
184
301
300
6.9
28
63
111
187
184
301
300
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Ceiling System = HD8906G90 Main Beam 12 ft. / XL8945PG90 Cross Tee 4 ft. / XL7936G90 Cross Tee 3 ft. / XL8926G90 Cross Tee 2 ft. / # 9 Ga. H.D.G. Hanger Wire
Control Joints
Shall be installed to delineate areas not more than 100 sq. ft. for all horizontal applications,
that is, ceilings, curves or angle type structures. The distance between control joints shall not
exceed 18 ft. in either direction or a length-to-width ratio of 2-1/2 to 1. Control joints are also
used to minimize stresses in monolithic ceiling membrane that occurs at columns, access
doors, light fixtures, inside and outside corners and other unusual penetrations in ceilings.
Expansion Joints
Ceiling expansion joints are installed to separate the metal suspension system when
expansion joints occur in buildings, or when metal changes direction. Expansion joints
are required to separate a system in T, H, I, and U or circle shaped buildings to eliminate
cracking from expansion.
36"/13.5"
L/240
L/360
HD8906/XL7936G90
(mains 36" O.C.)
21.77
14.51
HD8906/XL8926
(mains 36" O.C.)
26.13
21.77
L/360
SP135/XL7936G90
(mains 36" O.C.)
11.68
For more information call 1 877 ARMSTRONG
6
8/8/08
12:06 PM
Page 8
DrywallGridSystem
For maximum wind speed of 172 MPH. For additional wind speed designs, see page 6.
Fastner Attachment
by Other Manufacturer
Positive Attachment
Structure
3/4"
Hanger
Wire
2' O.C.
18 Gauge 2-1/2"
Studs 2' O.C.
2' O.C.
10'- 3"
Vertical
Drop
Main Beams
3' O.C.
NOTES:
(1) Wind Load Brace 2-1/2" 18 Gauge Steel 2' O.C
(2) From 0' to 6' 22 Gauge 2-1/2" Metal Studs Minimum
From 6' to 10'-3" 18 Gauge 2-1/2" Metal Studs Minimum
(3) From 10'- 4" to 15' 18 Gauge 2-1/2" Metal Studs
Minimum 16 Gauge CRC Mid Span
(4) From 15' to 20' 18 Gauge 2-1/2" Metal Studs Minimum
16 Gauge CRC 1/3 Points
(5) Item 3 and 4 above CRC Bracing Shown on Other
Drawings
(6) Main Beams 3' O.C. / Cross Tees 16" O.C.
(7) Positive Attachment Metal Studs Top and Bottom
(8) #9 Hanger Wire As Shown Above
8/8/08
12:06 PM
Page 9
DrywallGridSystem
Length
Stud Splice
6"
3' O.C.
Maximum
6"
Bracing Clip
Stud Brace
(4) #10 - 16
Fasteners on
each side of
splice point
Minimum
#10 - 16
Screws
4-1/4" 4-1/4"
1" 3/4" 3/4" 1"
Power Actuated
Fastener
Steel Stud
SPLICE DETAIL
(Use stud piece x12" long - same size and gauge
as main studs. Center over splice point.)
3-5/8
362 - CSJ
362 - CSJ
362 - CSJ
362 - CSJ
362 - CSJ
Gauge
20
20
18
16
14
Gauge
4 - SCJ
4 - CSJ
4 - CSJ
20
18
16
4 - CSJ
14
Gauge
6 - CSJ
20
6 - CSJ
18
6 - CSJ
16
6 - CSJ
14
NOTES:
(1) Positive attach with #10 -16 screw - clip
to stud.
(2) Positive attach with Clip to Bar Joist with 2
.145 Dia. x 1/2 long.
(3) Screws: #10 - 16 TEKS/ 3 Buildex or equal.
(4) Power activated Fasteners: .145 Dia. x 1/2
long (X-DNI) Hilti pins.
(5) Clips: All Clips to be made of 50 KSI material.
Spans up to 70 use angle 2 x 5 x 12 gauge
x 0-4 long. Spans 72 x 120 use angle
2 x 5 x 10 gauge x 0-5 long. For studs up
to 4, use 3 flange in lieu of 5.
Gauge
8 - CSJ
18
8 - CSJ
18
8 - CSJ
8 - CSJ
8 - CSJ
16
14
16
(6)
(7)
(8)
(9)
DrywallGridSystem
8/8/08
12:06 PM
Page 10
For maximum wind speed of 172 MPH. For additional wind speed designs, see page 6.
LENGTH
STUD SPLICE
3' O.C.
Hanger
Wire
2'O.C.
Positive
Attachment
Top and Bottom
2' O.C.
18 Gauge 2-1/2"
Studs 2' O.C.
10'- 3"
Vertical
Drop
Main Beams
3' O.C.
NOTES:
(1) 18 Gauge 2-1/2 Steel Studs, 10- 3 Vertical Drop
(2) Positive Attachment Top and Bottom
(3) Hanger Wire 2 O.C.
(4) Main Beams 3 O.C. / Cross Tees 16 O.C 3 Long
8/8/08
12:06 PM
Page 11
DrywallGridSystem
For maximum wind speed of 172 MPH. For additional wind speed designs, see page 6.
LENGTH
STUD SPLICE
3' O.C.
Hanger
Wire
2'O.C.
Positive
Attachment
Top and Bottom
2' O.C.
18 Gauge 3-5/8"
Studs 2' O.C.
Positive
Attachment
Main Beams
3' O.C.
NOTES:
(1) #16 Gauge CRC Channel Bracing Required at
Mid Span for 10 15 Vertical Drop
(2) Positive Attachment Top and Bottom
(3) 18 Gauge 3-5/8 Studs 2 O.C.
(4) Main Beams 3 O.C. / Cross Tees 16 O.C 3 Long
(5) #9 Hanger Wire
8/8/08
12:06 PM
Page 12
DrywallGridSystem
For maximum wind speed of 172 MPH. For additional wind speed designs, see page 6.
LENGTH
STUD BRACE
3' O.C.
Hanger
Wire
2'O.C.
Positive
Attachment
Top and Bottom
16 Gauge U
Channel Bracing
20'
Vertical
Drop
Positive
Attachment
2' O.C.
16 Gauge 3-1/2"
Studs 2' O.C.
16 Gauge U
Channel Bracing
Main Beams
3' O.C.
NOTES:
(1) #16 Gauge CRC Channel Bracing Required at
1/3 Point @ 20 Vertical Drop
(2) Positive Attachment Top and Bottom
(3) 16 Gauge 3-1/2 Studs 2 O.C.
(4) Main Beams 3 O.C. / Cross Tees 16 O.C 3 Long
8/8/08
12:06 PM
Page 13
MAKING A TEMPLATE
DrywallGridSystem
Establishing an Arc
Draw radius on template (plywood, gypsum board, etc)
1. Establish a center line
2. Mark 2 increments on line
perpendicular to center line
20 20 20
5/8 2-1/4
5-1/8
Main Beam
Template under
Main Beam
Cut
Span of Vault
8/8/08
12:06 PM
Page 14
MAKING A TEMPLATE
DrywallGridSystem
2-1/2n or 3-5/8n
flex track
Stop
Work Platform 4b x 12b
Gypsum Wall Board
or Plywood
12b
Cut Main Beam
4b
Flex Track
Radius
Bracing for
span
Saw Horses
8/8/08
12:06 PM
Page 15
RADIUS IN FEET
DrywallGridSystem
Radius Dimension
100
2
4
6
8
2
4
6
8
2
4
6
8
2
4
6
8
2
4
6
8
2
4
6
8
2
10
20
40
110
120
21/4
2
8 1/4
91/8
19 3/8 173/8
35 5/8 30 3/4
250
260
1
3 7/8
8 3/4
133/4
1
7/8
3 3/4
3 5/8
81/2
81/2
131/8 125/8
400
410
5/8
5/8
23/8
51/2
93/4
160
170
180
190
200
210
220
230
240
17/8
13/4
15/8
11/2
75/8
7
6 1/2
6 1/8
15 5/8 14 1/4
13
12
29 1/8 26 1/8 23 3/4 213/4
140
150
11/2
5 3/4
111/8
20
13/8
5 3/8
10 3/8
1101/2
11/4
5 1/8
113/4
191/4
11/4
4 7/8
111/8
18 1/8
11/8
4 5/8
10 1/2
17
11/8
43/8
10
161/8
11/8
4 1/4
9 5/8
15 1/4
1
4
9 1/8
141/2
280
290
300
310
320
330
340
350
360
370
380
390
7/8
7/8
7/8
3/4
3/4
3/4
3/4
3/4
3/4
5/8
5/8
31/2
77/8
12
33/8
71/2
121/2
31/4
31/8
3
71/4
71/8
67/8
111/8 10 5/8 10 1/4
3
65/8
111/2
27/8
63/8
111/2
23/4
61/4
111/8
23/4
61/8
107/8
25/8
57/8
101/2
25/8
53/4
101/4
5/8
21/2
55/8
10
420
430
440
450
460
470
480
490
500
510
520
530
540
5/8
5/8
5/8
5/8
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
23/8
53/8
91/2
23/8
51/4
91/4
21/4
51/8
9
21/8
5
87/8
21/8
47/8
85/8
21/8
43/4
81/2
21/8
45/8
81/4
2
41/2
81/8
2
41/2
77/8
2
43/8
73/4
17/8
41/4
75/8
17/8
41/4
71/2
13/4
41/4
73/8
1/2
13/4
4
71/8
550
560
570
580
590
600
610
620
630
640
650
660
670
680
690
1/2
1/2
1/2
1/2
1/2
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
13/4
4
7
13/4
37/8
67/8
13/4
37/8
63/4
13/4
33/4
65/8
15/8
33/4
65/8
15/8
35/8
61/2
15/8
35/8
63/8
15/8
31/2
61/4
11/2
31/2
61/8
11/2
33/8
6
11/2
33/8
6
11/2
31/4
57/8
11/2
31/4
53/4
11/2
31/4
53/4
3/8
13/8
31/8
55/8
700
710
720
730
740
750
760
770
780
790
800
810
820
830
840
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
13/8
31/8
51/2
13/8
31/8
51/2
13/8
3
53/8
13/8
3
51/4
13/8
3
51/4
11/4
27/8
51/8
11/4
27/8
51/8
11/4
27/8
5
11/4
23/4
5
11/4
23/4
47/8
11/4
23/4
47/8
11/4
23/4
43/4
11/4
25/8
43/4
11/4
25/8
45/8
3/8
11/8
25/8
45/8
850
860
870
880
890
900
910
920
930
940
950
960
970
980
990
3/8
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1
23/8
41/8
1
21/4
41/8
1
21/4
4
1
21/4
4
1
21/4
4
1
21/4
37/8
11/8
25/8
41/2
11/8
21/2
41/2
270
130
11/8
21/2
41/2
11/8
21/2
43/8
11/8
21/2
43/8
11/8
23/8
41/4
11/8
23/8
41/4
11/8
23/8
41/4
11/8
23/8
41/8
1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700
2
4
6
8
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/8
1/8
1
21/4
37/8
1
21/8
33/4
2
31/2
17/8
33/8
17/8
31/4
13/4
31/8
13/4
3
15/8
27/8
15/8
23/4
11/2
23/4
11/2
25/8
13/8
21/2
13/8
23/8
13/8
23/8
7/8
7/8
7/8
3/4
3/4
3/4
3/4
3/4
1750 1800 1850 1900 1950 2000 2100 2200 2300 2400
2
4
6
8
5/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
11/4
21/4
11/4
21/8
11/4
21/8
11/8
2
11/8
2
11/8
2
1
17/8
1
13/4
1
15/8
7/8
7/8
11/2
5/8
1/2
1/2
1/2
1/2
1/2
1/2
3/8
3/8
15/8
5/8
5/8
1/8
5/8
11/4
21/4
250
1/8
5/8
5/8
3/8
8/8/08
12:06 PM
Page 16
Additional Drywall Grid Systems are available. For more information, visit
armstrong.com/drywallgrid or call 877-ARMSTRONG to request literature.
CEILING SYSTEMS
1 877 ARMSTRONG (1 877 276 7876)
Name of your Inner Circle Contractor or Gold Circle
Distributor or Sales Representative
Customer Service Representatives
7:45 a.m. to 5:00 p.m. EST, Monday through Friday
TechLine Technical information
8 a.m. to 5:30 p.m. EST, Monday through Friday
FAX 1-800-572-8324 or email: techline@armstrong.com
Product literature and samples Express service or regular delivery
Request a personal copy of the Armstrong Ceiling Systems
catalog
armstrong.com/drywallgrid
Latest product and program news
Real time selection and specification information
Contacts reps, where to buy, who will install
Submittal pages
Specification writing tool
Literature and samples information
CAD renderings
FPO