CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 1

CEILING SYSTEMS

T E C H N I C AL G U I D E

DrywallGridSystem

STUCCO/PLASTER
Grid Systems
Hanging and Framing
Stucco/Plaster Ceilings

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 2

TABLE OF CONTENTS

DrywallGridSystem

Features and Benefits


Performance ................................................................................................................................................2
Code Compliance........................................................................................................................................2
Components and Wire Load
Main Beams ................................................................................................................................................3
Cross Tees ..................................................................................................................................................3
Wire Load ....................................................................................................................................................3
Stucco/Plaster Installation
Stucco/Plaster Grid Suspension Installation ..............................................................................................4
Stucco/Plaster Details
Suspended Metal Lath and Stucco............................................................................................................5
Exterior Wind Loaded..................................................................................................................................5
Lighting Troffer ............................................................................................................................................5
Stucco Perimeter Stop ................................................................................................................................5
Rock Lath and Plaster ................................................................................................................................5
Security Metal Lath and Plaster..................................................................................................................5
Wind Load
Wind Load Ceiling Design ......................................................................................................................6
Exterior Wind Load Bracing to Concrete Slab ......................................................................................7
Exterior Wind Load Bracing for T-Bar Installation ..................................................................................8
Templates
Completing the Template Option 1 ....................................................................................................12
Completing the Template Option 2 ....................................................................................................13
Radius Chart..................................................................................................................................................14

For more information call 1 877 ARMSTRONG

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 3

FEATURES AND BENEFITS

DrywallGridSystem

Performance

Code Compliance

PeakForm patented profile


increases strength and stability
for improved performance during
installation

Meets ASTM C 635

SuperLock main beam clip is


engineered for a strong secure
connection and fast accurate
alignment confirmed with an audible
click; easy to remove and relocate

Meets ASTM C 842

Meets ASTM C 645


Meets ASTM C 841
Meets ASTM C 926
Installation per ASTM C 636
Installation per ASTM C 754

ScrewStop reverse hem prevents


screw spin off on 1-1/2 wide face

ICC Evaluation Report Number


ESR-1289

Rotary-stitched Greater torsional


strength and stability

Department of State Architect


DSA PA105

1-1/2" wide face main beams and


cross tees Easy installation of
screw applied gypsum wallboard

City of LA RR 25348
Miami/Dade Wind Uplift
NOA #07-0119-02 03/17/10

G90 hot dipped galvanized coating


Superior corrosion resistance for
exterior applications

Consult local codes for specific


requirements

Heavy-duty load rating Minimum


16 Lbs./LF on main beams and
cross tees
Wind load construction available,
including Miami Dade/Broward
County, Florida
Pre-engineered stucco products
space tees to match lath dimensions

For more information call 1 877 ARMSTRONG


2

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 4

COMPONENTS AND WIRE LOAD

DrywallGridSystem

Main Beams
Item #

HD8906
HD8906G90

SP135

Length

Face
Dimension

144"

135"

Profile
Height

Duty
Load

1-1/2"

Heavy
1-11/16" duty

1-1/2"

Heavy
1-11/16" duty

Fire
Rated

Routs

Yes

51 routs
starting
2-1/4" from
each end (type
F fixture
compatible)

No

13-1/2" o.c.
starting
6-3/4" from
each end

Load Test Data (Lbs./LF)


L/360
L/240
wires at
wires at
2'
3'
4'
2'
3'

95.5

Perspective
4'

35.8 18.76 139.85 52.24 28.14

89.04 43.08 18.0

Cross Tees
Item #

Length

Face
Dimension

Profile
Height

Fire Rated

Routs

XL7936G90

36"

1-1/2"

1-1/2"

No

none

Yes

3 routscenter
rout and 10"
from each end
(type F fixture
compatible)

XL8926
XL8926G90

24"

1-1/2"

1-1/2"

Load Test Data (Lbs./LF)


L/360
L/240
wires at
wires at
2'
3'
4' 2'
3'
4'
33.3

129.0

Perspective

49.96

158.0

Wire Load
9 Gauge Wire Breaking Strength and Technical Data

645 lbs. Maximum


Safe Wire Load
450 lbs.Maximum
Safe Wire Load

NOTE:
Per ASTM C 1063 wires must
be plumb and straight.

For more information call 1 877 ARMSTRONG


3

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 5

STUCCO/PLASTER INSTALLATION

DrywallGridSystem

Stucco/Plaster Grid Suspension Installation


1. Install the main beams with 9 gauge wires
(see page 6 for wire spacing). Space main
beams 36" on center. Hanger wire and
compression post spacing as required for
specific wind load and plenum depth.
2. Install 36" cross tee to required on center spacing.
3. Isolation at perimeters is mandatory when
installing any stucco system. Install perimeter
channel molding at wall/ceiling junctures to
support tees independent of walls. Use
main beam at cut cross tee perimeters and
galvanized track on main beam perimeters.
4. Install 3.4 Lb. 3/8" galvanized diamond mesh
lath with wafer head sharp point screw to
cross tees (use cadmium coated screws on
exterior applications). Lath options:

5. Expansion Joints Installed in accordance


with Metal Lath/Steel Framing Association
Specifications/Standards.
6. Control Joints Installed in accordance
with Metal/Lath Steel Framing Association
Specifications Standards.
7. Plaster stops, grounds, and corner pieces
are attached to system with wafer head
screws and/or 18 gauge tie wire.
8. Plaster or stucco mixture and thickness to
be in accordance with manufacturers
recommendations and applied:
ASTM C 842 For Gypsum Plaster and
ASTM C 926 For Portland Cement-based
Plaster.
9. For exterior application use steel studs for
vertical bracing (see page 6 for wind load).

a. 3/8", 3.4# flat rib diamond mesh lath


27" x 8'-0"
b. 3/8", 3.4# rib diamond mesh lath 27" x 8'-0"
c. 3/8", 3.4# high back rib diamond mesh lath
27" x 8'-0"
d. 3/8", 3.4# paper back diamond mesh lath
27" x 8'-0"

For further information, contact your local


representative or TechLine at 877 ARMSTRONG.

Details of Stucco/Plaster Systems


Main Beam

Hanger Wire
Hanger Wire
Main Beam

Wafer Screw
Cross Tee

Stucco or
Plaster

Stop

3.4 Lb Metal Lath

Main Beam
Space
Main Beam

Wafer
Head
Screw

Wall

3/8'' Min.

Track
Expansion Joint

Isolated Corner

Control Joint

Isolation From Wall

For more information call 1 877 ARMSTRONG


4

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 6

STUCCO/PLASTER DETAILS

DrywallGridSystem

Suspended Metal Lath


and Interior Stucco
Hanger Wire

Exterior Wind Loaded Stucco


(See chart on page 6)

Main Beam

Metal Stud
Vertical Brace

Cross Tee
Hanger Wire

Main Beam

Wafer
Screw

Stucco
Metal Lath

Cross Tee
Stucco

Stucco Perimeter Stop

Lighting Troffer
Cross Tee
Adjustable
Arm

Main
Beam

Main Beam

Wall

Metal Lath
Light
Fixture

Metal Lath

Flange

Stucco

Rock Lath and Plaster

"STOP"
Screwed to
Suspension

3/8"
Min.

Security Metal Lath and Plaster


Hanger Wire

3' O.C.
Main Beam

Main Beam

Rock Lath

Sharp Point Screw

Butterfly Clips
Control Joint

Plaster

For more information call 1 877 ARMSTRONG


5

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 7

WIND LOAD

DrywallGridSystem

Stucco System Exterior Wind Load Design for North America


Plenum
Height
(Ft - In)

6 1

10 3

10 4

15 0

15 1

20 0

Up Lift
Load
(MPH)

Up Lift
Load
(Lbs./Ft.2 )

Stud
Thickness
(Inch)

Stud
Gauge
(Ga. No.)

15
30
45
60
90
120
140
172
15
30
45
60
90
120
140
172
*15
*30
*45
*60
*90
*120
*140
*172
**15
**30
**45
**60
**90
**120
**140
**172

0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75

2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ

22
22
22
22
22
22
22
22
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
16
16
16
16
16
16
16
16

Membrane Substrate
3/8 Ribbed Sheet Lath
3.4 Lbs/SQ. YD., Per ASTM C-847
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb
Lb

Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing
Lathing

&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&

3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1
3/4-1

Main Runner
Spacing
(Inch)

Cross Tee
Spacing
(Inch)

Hanger Wire
Spacing
(Feet)

Cross Tee
Length
(Feet)

Compression
Post Spacing
(Feet)

Compression
Post Load
(Lbs.)

36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

4 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
2.5 O.C.
2. O.C.
2 O.C.
4 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
2.5 O.C.
2. O.C.
2 O.C.
4 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
2.5 O.C.
2. O.C.
2 O.C.
4 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
2.5 O.C.
2. O.C.
2 O.C.

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

4
4
4
4
3
2.5
2.
2
4
4
4
4
3
2.5
2.
2
4
4
4
4
3
2.5
2.
2
4
4
4
4
3
2.5
2.
2

6.9
28
63
111
187
184
301
300
6.9
28
63
111
187
184
301
300
6.9
28
63
111
187
184
301
300
6.9
28
63
111
187
184
301
300

Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco
Stucco

Ceiling System = HD8906G90 Main Beam 12 ft. / XL8945PG90 Cross Tee 4 ft. / XL7936G90 Cross Tee 3 ft. / XL8926G90 Cross Tee 2 ft. / # 9 Ga. H.D.G. Hanger Wire

* Note 1-1/2 16ga. U-Channel Bridging required at Mid Span for 10 4 up to 15 0


** Note 1-1/2 16ga. U-Channel Bridging required at 1/3rd Points for 15 1 up to 20 0
Compression Post and Ceiling system Tested at the Plenum design depth shown here for Positive and Negative Wind Speed Pressure Loads as listed.
Compression Post Assemblies at this Plenum design depth Calculated by Dietrich Design Group
For Heights over 33 feet above ground level, use ( Table 16-G ) in 1997 Uniform Building Code Exposure and Gust Factor Coefficient
IBC Section 1609 Table 1609.6.2.1 and ASCE 7 Figure 6-1. The Exterior Ceiling wind load designs we have shown were tested and approved for the
highest exposure category listed for the continental U.S. as shown in the IBC Section 1609 Wind Exposure Charts.
Stud Products & Properties Based on Dietrich Industries Inc.

Control Joints
Shall be installed to delineate areas not more than 100 sq. ft. for all horizontal applications,
that is, ceilings, curves or angle type structures. The distance between control joints shall not
exceed 18 ft. in either direction or a length-to-width ratio of 2-1/2 to 1. Control joints are also
used to minimize stresses in monolithic ceiling membrane that occurs at columns, access
doors, light fixtures, inside and outside corners and other unusual penetrations in ceilings.

Expansion Joints
Ceiling expansion joints are installed to separate the metal suspension system when
expansion joints occur in buildings, or when metal changes direction. Expansion joints
are required to separate a system in T, H, I, and U or circle shaped buildings to eliminate
cracking from expansion.

Membrane Load Values


Component
Combination

Maximum Load in Lbs./Ft.2 at


Hanger Wire/ Cross Tee Spacing
36"/ 16"

36"/13.5"

L/240

L/360

HD8906/XL7936G90
(mains 36" O.C.)

21.77

14.51

HD8906/XL8926
(mains 36" O.C.)

26.13

21.77

L/360

SP135/XL7936G90
(mains 36" O.C.)

11.68
For more information call 1 877 ARMSTRONG
6

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 8

EXTERIOR WIND LOAD BRACING TO CONCRETE SLAB

DrywallGridSystem

For maximum wind speed of 172 MPH. For additional wind speed designs, see page 6.
Fastner Attachment
by Other Manufacturer
Positive Attachment

Structure

3/4"

Hanger
Wire
2' O.C.
18 Gauge 2-1/2"
Studs 2' O.C.

2' O.C.

10'- 3"
Vertical
Drop

Main Beams
3' O.C.

3 Ft. Cross Tees


16" O.C
3/8" Diamond Mesh
3.4 Galv. Steel Lath

NOTES:
(1) Wind Load Brace 2-1/2" 18 Gauge Steel 2' O.C
(2) From 0' to 6' 22 Gauge 2-1/2" Metal Studs Minimum
From 6' to 10'-3" 18 Gauge 2-1/2" Metal Studs Minimum
(3) From 10'- 4" to 15' 18 Gauge 2-1/2" Metal Studs
Minimum 16 Gauge CRC Mid Span
(4) From 15' to 20' 18 Gauge 2-1/2" Metal Studs Minimum
16 Gauge CRC 1/3 Points
(5) Item 3 and 4 above CRC Bracing Shown on Other
Drawings
(6) Main Beams 3' O.C. / Cross Tees 16" O.C.
(7) Positive Attachment Metal Studs Top and Bottom
(8) #9 Hanger Wire As Shown Above

For more information call 1 877 ARMSTRONG


7

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 9

EXTERIOR WIND LOAD BRACING TO METAL BAR JOISTS

DrywallGridSystem

Length

Stud Splice

6"

3' O.C.
Maximum

6"

Bracing Clip

Stud Brace
(4) #10 - 16
Fasteners on
each side of
splice point

BRACING CLIP SIZES


2"x 3" for studs up to 4"
2"X 5" for studs up to 8"

Minimum
#10 - 16
Screws
4-1/4" 4-1/4"
1" 3/4" 3/4" 1"

12 Gauge Metal Clip

Power Actuated
Fastener

Steel Stud

SPLICE DETAIL
(Use stud piece x12" long - same size and gauge
as main studs. Center over splice point.)

BRACING CLIP DETAIL

STEEL STUD BRACING 2' O.C. ASTMC 645


Span Length
48"
54"
60"
66"
70"
72"
76"
80"
82"
86"
88"
92"
96"
120"

3-5/8
362 - CSJ
362 - CSJ
362 - CSJ
362 - CSJ
362 - CSJ

Gauge
20
20
18
16
14

Gauge

4 - SCJ
4 - CSJ
4 - CSJ

20
18
16

4 - CSJ

14

Gauge

6 - CSJ

20

6 - CSJ

18

6 - CSJ

16

6 - CSJ

14

(For 120" Length Bridging Required @ Midspan (See Note 9)

NOTES:
(1) Positive attach with #10 -16 screw - clip
to stud.
(2) Positive attach with Clip to Bar Joist with 2
.145 Dia. x 1/2 long.
(3) Screws: #10 - 16 TEKS/ 3 Buildex or equal.
(4) Power activated Fasteners: .145 Dia. x 1/2
long (X-DNI) Hilti pins.
(5) Clips: All Clips to be made of 50 KSI material.
Spans up to 70 use angle 2 x 5 x 12 gauge
x 0-4 long. Spans 72 x 120 use angle
2 x 5 x 10 gauge x 0-5 long. For studs up
to 4, use 3 flange in lieu of 5.

Gauge

8 - CSJ

18

8 - CSJ

18

8 - CSJ
8 - CSJ
8 - CSJ

16
14
16

(6)
(7)
(8)
(9)

All spans based on single span.


Wind load - 75 PSF
Dead load - 10 PSF
Spans of 120 require bridging on top flange
at midspan. Use 1-1/2 CRC 16 gauge
attached with (1) #10 - 16 to top flange.
(10) In some cases, angles may need to be welded
to structure.

For more information call 1 877 ARMSTRONG


8

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

DrywallGridSystem

8/8/08

12:06 PM

Page 10

EXTERIOR WIND LOAD BRACING TO METAL BAR JOISTS

For maximum wind speed of 172 MPH. For additional wind speed designs, see page 6.
LENGTH

STUD SPLICE

3' O.C.

Hanger
Wire
2'O.C.

Positive
Attachment
Top and Bottom
2' O.C.

18 Gauge 2-1/2"
Studs 2' O.C.

10'- 3"
Vertical
Drop

Main Beams
3' O.C.

3 Ft. Cross Tees


16" O.C
3/8" Diamond Mesh
3.4 Galv. Steel Lath

NOTES:
(1) 18 Gauge 2-1/2 Steel Studs, 10- 3 Vertical Drop
(2) Positive Attachment Top and Bottom
(3) Hanger Wire 2 O.C.
(4) Main Beams 3 O.C. / Cross Tees 16 O.C 3 Long

For more information call 1 877 ARMSTRONG


9

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 11

EXTERIOR WIND LOAD BRACING TO METAL BAR JOISTS

DrywallGridSystem

For maximum wind speed of 172 MPH. For additional wind speed designs, see page 6.
LENGTH

STUD SPLICE

3' O.C.

Hanger
Wire
2'O.C.

Positive
Attachment
Top and Bottom
2' O.C.

Mid Span Bridging


16 Gauge U Channel
15'
Vertical
Drop

18 Gauge 3-5/8"
Studs 2' O.C.

Positive
Attachment

Main Beams
3' O.C.

3 Ft. Cross Tees


16" O.C
3/8" Diamond Mesh
3.4 Galv. Steel Lath

NOTES:
(1) #16 Gauge CRC Channel Bracing Required at
Mid Span for 10 15 Vertical Drop
(2) Positive Attachment Top and Bottom
(3) 18 Gauge 3-5/8 Studs 2 O.C.
(4) Main Beams 3 O.C. / Cross Tees 16 O.C 3 Long
(5) #9 Hanger Wire

For more information call 1 877 ARMSTRONG


10

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 12

EXTERIOR WIND LOAD BRACING TO METAL BAR JOISTS

DrywallGridSystem

For maximum wind speed of 172 MPH. For additional wind speed designs, see page 6.
LENGTH

STUD BRACE

3' O.C.

Hanger
Wire
2'O.C.

Positive
Attachment
Top and Bottom

16 Gauge U
Channel Bracing

20'
Vertical
Drop

Positive
Attachment

2' O.C.

16 Gauge 3-1/2"
Studs 2' O.C.

16 Gauge U
Channel Bracing

Main Beams
3' O.C.

3 Ft. Cross Tees


16" O.C

3/8" Diamond Mesh


3.4 Galv. Steel Lath

NOTES:
(1) #16 Gauge CRC Channel Bracing Required at
1/3 Point @ 20 Vertical Drop
(2) Positive Attachment Top and Bottom
(3) 16 Gauge 3-1/2 Studs 2 O.C.
(4) Main Beams 3 O.C. / Cross Tees 16 O.C 3 Long

For more information call 1 877 ARMSTRONG


11

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 13

MAKING A TEMPLATE

DrywallGridSystem

Establishing an Arc
Draw radius on template (plywood, gypsum board, etc)
1. Establish a center line
2. Mark 2 increments on line
perpendicular to center line

3. At 2 marks, identify points of arc


below perpendicular line (maintain
consistent spacing of point) See
radius charts on page 14
4. Connect points to form a smooth arc

Example: 43 arc using chart on page 14

20 20 20

5/8 2-1/4

5-1/8

Location of First Row


at Center Line

Completing the Template Option 1


1. Cut along the arc and remove section
of template
2. Cut main beam as required and
position along the cut radius on the
template (use the chart below)

3. Screw RC2 clips to faceted main beam


at all knockout locations *
4. On the template, mark a rout location
reference point to maintain consistent
rout location

Main Beam

Template under
Main Beam

* RC2 Clip placement


Vaults Cross tee placement in routs between cuts
Valleys Cross tee lock into rout on RC2 clip (tight radius installations
may require bending up of the flange at ends of cross tees)
Note: Screw RC2 to cavity side of web

Cut Main Beam(s) to Fit Template

Radius of Vault Plus Thickness of Gypsum


Board (Can Be Partial Radius of Large Spans)
Cut

Cut
Span of Vault

For more information call 1 877 ARMSTRONG


12

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 14

MAKING A TEMPLATE

DrywallGridSystem

Completing the Template Option 2


1-1/2n x 3n Plywood or Blocks
secured by 2 screws
12b
Clamp main beam
to flex track
Main Beam
RC2 Clip

2-1/2n or 3-5/8n
flex track

Screw flex track


to plywood

Stop
Work Platform 4b x 12b
Gypsum Wall Board
or Plywood

12b
Cut Main Beam

4b

Flex Track

Radius

Screw Flex Track


to Plywood

Bracing for
span

Saw Horses

1. Draw radius on board


2. Screw flex track to board along radius line
3. Cut main beams as required and position along
the flex track on the template
4. Screw RC2* clips to faceted main beam at all
knockout locations
5. On the template, mark a rout location reference
point to maintain consistent rout location
* Screw RC2 Clip to cavity side of web

Contractors efficiency and understanding of the suspended grid system construction


provides performance benefits and cost savings.
An unlimited range of vaults and valleys can be constructed using faceted
main beams made on the job to meet design needs
Single and multiple curved ceilings can be framed quickly and easily

For more information call 1 877 ARMSTRONG


13

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 15

RADIUS IN FEET

DrywallGridSystem

Radius Dimension
100
2
4
6
8

2 Increments from Center line

2
4
6
8

2
4
6
8

2
4
6
8

2
4
6
8

2
4
6
8

2
10
20
40

110

120

21/4
2
8 1/4
91/8
19 3/8 173/8
35 5/8 30 3/4

250

260

1
3 7/8
8 3/4
133/4

1
7/8
3 3/4
3 5/8
81/2
81/2
131/8 125/8

400

410

5/8

5/8

23/8
51/2
93/4

160

170

180

190

200

210

220

230

240

17/8
13/4
15/8
11/2
75/8
7
6 1/2
6 1/8
15 5/8 14 1/4
13
12
29 1/8 26 1/8 23 3/4 213/4

140

150

11/2
5 3/4
111/8
20

13/8
5 3/8
10 3/8
1101/2

11/4
5 1/8
113/4
191/4

11/4
4 7/8
111/8
18 1/8

11/8
4 5/8
10 1/2
17

11/8
43/8
10
161/8

11/8
4 1/4
9 5/8
15 1/4

1
4
9 1/8
141/2

280

290

300

310

320

330

340

350

360

370

380

390

7/8

7/8

7/8

3/4

3/4

3/4

3/4

3/4

3/4

5/8

5/8

31/2
77/8
12

33/8
71/2
121/2

31/4
31/8
3
71/4
71/8
67/8
111/8 10 5/8 10 1/4

3
65/8
111/2

27/8
63/8
111/2

23/4
61/4
111/8

23/4
61/8
107/8

25/8
57/8
101/2

25/8
53/4
101/4

5/8
21/2
55/8
10

420

430

440

450

460

470

480

490

500

510

520

530

540

5/8

5/8

5/8

5/8

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/2

23/8
53/8
91/2

23/8
51/4
91/4

21/4
51/8
9

21/8
5
87/8

21/8
47/8
85/8

21/8
43/4
81/2

21/8
45/8
81/4

2
41/2
81/8

2
41/2
77/8

2
43/8
73/4

17/8
41/4
75/8

17/8
41/4
71/2

13/4
41/4
73/8

1/2
13/4
4
71/8

550

560

570

580

590

600

610

620

630

640

650

660

670

680

690

1/2

1/2

1/2

1/2

1/2

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

13/4
4
7

13/4
37/8
67/8

13/4
37/8
63/4

13/4
33/4
65/8

15/8
33/4
65/8

15/8
35/8
61/2

15/8
35/8
63/8

15/8
31/2
61/4

11/2
31/2
61/8

11/2
33/8
6

11/2
33/8
6

11/2
31/4
57/8

11/2
31/4
53/4

11/2
31/4
53/4

3/8
13/8
31/8
55/8

700

710

720

730

740

750

760

770

780

790

800

810

820

830

840

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

13/8
31/8
51/2

13/8
31/8
51/2

13/8
3
53/8

13/8
3
51/4

13/8
3
51/4

11/4
27/8
51/8

11/4
27/8
51/8

11/4
27/8
5

11/4
23/4
5

11/4
23/4
47/8

11/4
23/4
47/8

11/4
23/4
43/4

11/4
25/8
43/4

11/4
25/8
45/8

3/8
11/8
25/8
45/8

850

860

870

880

890

900

910

920

930

940

950

960

970

980

990

3/8

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1
23/8
41/8

1
21/4
41/8

1
21/4
4

1
21/4
4

1
21/4
4

1
21/4
37/8

11/8
25/8
41/2

11/8
21/2
41/2

270

130

11/8
21/2
41/2

11/8
21/2
43/8

11/8
21/2
43/8

11/8
23/8
41/4

11/8
23/8
41/4

11/8
23/8
41/4

11/8
23/8
41/8

1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700
2
4
6
8

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/8

1/8

1
21/4
37/8

1
21/8
33/4

2
31/2

17/8
33/8

17/8
31/4

13/4
31/8

13/4
3

15/8
27/8

15/8
23/4

11/2
23/4

11/2
25/8

13/8
21/2

13/8
23/8

13/8
23/8

7/8

7/8

7/8

3/4

3/4

3/4

3/4

3/4

1750 1800 1850 1900 1950 2000 2100 2200 2300 2400
2
4
6
8

5/8

1/8

1/8

1/8

1/8

1/8

1/8

1/8

1/8

1/8

1/8

11/4
21/4

11/4
21/8

11/4
21/8

11/8
2

11/8
2

11/8
2

1
17/8

1
13/4

1
15/8

7/8

7/8
11/2

5/8

1/2

1/2

1/2

1/2

1/2

1/2

3/8

3/8

15/8

5/8

5/8

1/8

5/8
11/4
21/4

250

1/8
5/8

5/8

3/8

For more information call 1 877 ARMSTRONG


14

CS-3541 Stucco-Plaster_808:CS-3541 Stucco-Plaster rev

8/8/08

12:06 PM

Page 16

Additional Drywall Grid Systems are available. For more information, visit
armstrong.com/drywallgrid or call 877-ARMSTRONG to request literature.

CS-3681 ShortSpan DGS:


What You Need to Know
about Load and Seismic
Testing

CS-3539 Drywall Grid


Systems for
Flat Applications

CS-3540 Drywall Grid


Systems for Curved
Applications

CEILING SYSTEMS
1 877 ARMSTRONG (1 877 276 7876)
Name of your Inner Circle Contractor or Gold Circle
Distributor or Sales Representative
Customer Service Representatives
7:45 a.m. to 5:00 p.m. EST, Monday through Friday
TechLine Technical information
8 a.m. to 5:30 p.m. EST, Monday through Friday
FAX 1-800-572-8324 or email: techline@armstrong.com
Product literature and samples Express service or regular delivery
Request a personal copy of the Armstrong Ceiling Systems
catalog

armstrong.com/drywallgrid
Latest product and program news
Real time selection and specification information
Contacts reps, where to buy, who will install
Submittal pages
Specification writing tool
Literature and samples information
CAD renderings

Printed on recyclable paper


with vegetable-based inks.
Please Recycle.

FPO

AWI Licensing Company, 2007


Printed in United States of America
CS-3541-808

CS-3542 Synthetic Stucco


Grid Systems

CS-3590 Drywall Grid


Systems for
Framing Short
Spans

CS-3950 QuikStix Wall Liner


Drywall Framing
System

Metal suspension manufacturers accept no responsibility


for water damage done to Stucco and Plaster installations
systems by water leaks, misapplication, acts of God or faulty
installation. We do accept responsibility for Metal System
performance in a plum and level surface for attachments
with screws as stated in our literature.
These drawings show typical conditions in which the
Armstrong product depicted is installed. They are not a
substitute for an architects or engineers plan and do
not reflect the unique requirements of local building codes,
laws, statutes, ordinances, rules and regulations (Legal
Requirements) that may be applicable for a
particular installation.
Armstrong does not warrant, and assumes no liability for
the accuracy or completeness of the drawings for a particular installation or their fitness for a particular purpose. The
user is advised to consult with a duly licensed architect or
engineer in the particular locale of the installation to assure
compliance with all Legal Requirements.
Armstrong is not licensed to provide professional architecture or engineering design services.
Engineering data included provided by outside
engineering company.