Professional Documents
Culture Documents
04 ECE405Tut 2013 Solution PDF
04 ECE405Tut 2013 Solution PDF
0
j16.667
(
(
1.0 ( )
or
j12.5 j12.5
j12.5 j29.167
(
(
V
2
V
3
(
(
=
2.981 j0.608
5.981 j15.556
(
(
.
The solution to this reduced set of equations is
V
2
V
3
(
(
=
1.0185+ j0.0585
0.9698 j0.1800
(
(
=
1.0201Z3.29
0.9864Z10.51
(
(
..
Leaving aside rounding errors in the fourth decimal place for voltage magnitude, and the
second decimal place for voltage angle, this is identical to the solution obtained previously.
The capacitor bank is now removed and an additional smelter potline installed, increasing
the load power from 600MW to 900MW. Assume the additional power requirement is
supplied from the generator at bus 1.
11. With 900MW of load at bus 3, calculate the amount of reactive power that needs to be
supplied or absorbed at bus 3 to maintain the same voltage magnitude as in Question
7. (Hint: use the two-bus load flow formulae from lectures.) If this is provided with a
capacitor or reactor bank, what shunt susceptance B
3
(in per-unit) is required?
In this part of the problem we know the voltage magnitude at every bus, and the active power
flows. The power from the bus 2 generator is fixed at 300MW, so the additional power must
come from the generator at bus 1, which now supplies 600MW.
Knowing the voltage magnitudes and active power flows in a lossless network, one can
determine the reactive power flows from the sine and cosine formulae.
First, use the sine formula to determine the voltage angle differences on each individual line
as before:
Bus 1 to bus 3: sin o
13
= 0.06 x 6 / (1 x 0.9864) = 0.3650, thus o
13
= 0.3736 rad = 21.41
Bus 2 to bus 3: sin o
23
= 0.08 x 3 / (1.02 x 0.9864) = 0.2385, thus o
23
= 0.2409 rad = 13.80
(same as in Question 7)
Now one can use the cosine formula to determine reactive power flows, observing that for a
lossless circuit
= XQ / |V
S
|
2
= (|V
L
| / |V
S
|) cos o (|V
L
| / |V
S
|)
2
, hence
Q = (|V
S
| |V
L
| / X) cos o |V
L
|
2
/ X.
Flow into bus 3 from bus 1:
Q = (1 x 0.9864 / 0.06) cos 0.3736 0.9864
2
/ 0.06 = 0.9105pu = 91.05MVAr
Flow into bus 3 from bus 2:
Q = (1.02 x 0.9864 / 0.08) cos 0.2409 0.9864
2
/ 0.08 = 0.0511pu = 5.11MVAr.
Thus the net reactive power absorbed at bus 3 will be 91.05 + 5.11 = 85.94MVAr, in other
words the load must supply 85.94MVAr at bus 3 to maintain the same voltage magnitude.
By the load convention, the reactive power at bus 3 in per-unit is 0.8594pu and so
corresponds to a capacitor rather than a reactor. To determine the size of capacitor required,
use the formula Q = B |V|
2
as in Question 8. One has:
B = Q / |V
3
|
2
= 0.8594 / 0.9864
2
= 0.8833pu.
(Note this would be described as a nominal 88.33MVAr capacitorwhy?)
12. Under the same conditions as in Question 11, calculate the reactive power supplied
or absorbed at each generator.
Current into bus 3 from bus 1:
|I| = sqrt(P
2
+ Q
2
) / |V| = sqrt(6
2
+ 0.9105
2
) / 0.9864 = 6.1524pu.
Reactive power supplied at bus 1 generator:
Q
1
= 0.9105 + |I|
2
X = 0.9105 + 6.1524
2
x 0.06 = 1.3606pu, or 136.1MVAr.
Current into bus 3 from bus 2:
|I| = sqrt(P
2
+ Q
2
) / |V| = sqrt(3
2
+ 0.0511
2
) / 0.9864 = 3.0418pu.
Reactive power supplied at bus 2 generator:
Q
3
= 0.0511 + |I|
2
X = 0.0511 + 3.0418
2
x 0.08 = 0.7913pu, or 79.1MVAr.
Notice that there is essentially no change in the reactive power supplied from bus 2. This is
to be expected, as the terminal voltage and active power conditions on the line from bus 2 to
bus 3 are entirely unchanged from the situation in Question 7. (Even though the calculation
was done to four decimal places there is still enough accumulated rounding error to give the
final answer as 79.1MVAr instead of 79.2MVAr, but this difference is not normally regarded
as significant in practice.)
13. Under the conditions of Question 11, calculate the voltage angle difference between
the two generators. Is this smaller or larger than the angle difference seen
originally?
The new values o
13
= 21.41 and o
23
= 13.80 were found at Question 11 above. Note again
that o
23
is unchanged from the situation in Question 7.
From these values one calculates o
2
= o
23
+ o
31
= o
23
- o
13
= 13.80 21.41 = 7.61.
Thus a phase lead of 3.28 degrees at bus 2 has now become a phase lag of 7.61 degrees.
Another way to view this is that the generator at bus 1 has advanced its phase angle relative
to bus 2, as a consequence of its greater active power output. This is a generally observed
phenomenon: the greater the active power flow in a network, the greater the phase angle
difference between the bus voltages. Some of the consequences of this for the transient
stability of the system will be explored in later lectures.
ABM, 11/08/2013