Relay Settings Tables - 12mar12

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 5

HT MOTOR RELAY SETTINGS TABLE Motor Feeder Feeder (breaker) Rating (Motor Feeder) Relay / Release Make Alstom

Relay / Release Type MiCOM P241

JOB NO : CLIENT : DOC NO : REV NO : Range Available

DATE : Remarks

Breaker No.

Panel No

Feeder CT Ratio Nos 400/5A

Setting Function Rated current Rated frequency Line CT Primary Line CT Secondary Line VT Primary Line VT Secondary

Setting Parameter

Recommended Settings 5A 50Hz 400A 5A 6600 Volt 110 Volt

IN fN

1 or 5A 50 or 60Hz

Ith> K Coefficient Thermal constant T1 Thermal constant T2 Thermal constant Tr Thermal Trip Thermal Alarm Alarm Threshold Thermal Lockout Lockout Thresh Inh Trip Dur St

0.2 to 1.5 In 0 to 10 1 - 180 min. 1 - 360 min. 1 - 999 min. Disabled/Enabled Disabled/Enabled 0.2% to 100% Disabled/Enabled 0.2% to 100% Disabled/Enabled

0.82 In 2 20 min. 20 min. 100 min. Enabled Enabled 80% Enabled 20% Disabled

Thermal Overload Protection (49)

Page 1 of 5

HT MOTOR RELAY SETTINGS TABLE Motor Feeder Feeder (breaker) Rating Relay / Release Make Relay / Release Type

JOB NO : CLIENT : DOC NO : REV NO : Range Available Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse 0.2 to 15 In 0.04 to 100 0.025 to 1.2 0.01 to 100 0.1 to 10 DT/Inverse 0.0 to 100 Disabled/Enabled 0.2 to 15 In 0.04 to 100

DATE : Remarks

Breaker No.

Panel No

Feeder CT Ratio Nos

Setting Function

Setting Parameter

Recommended Settings

I>1 Fuction

DT

I>1 Current set Short circuit protection I>1 Time Dealy I>1 TMS I>1 Time Dial I>1 K (RI) I>1 Reset Charac. I>1 t RESET I>2 set as I>1 I>3 Status I>3 Current set I>3 Time Dealy I>4 Set as I>3

4.3 0.05 DT 0 Disabled Disabled Disabled

Page 2 of 5

HT MOTOR RELAY SETTINGS TABLE Motor Feeder Feeder (breaker) Rating Relay / Release Make Relay / Release Type

JOB NO : CLIENT : DOC NO : REV NO : Range Available

DATE : Remarks

Breaker No.

Panel No

Feeder CT Ratio Nos

Setting Function

Setting Parameter

Recommended Settings

Blocked Rotor Protection (50 L/R)

I> Time Delay (T)

1-5 x 49 Pickup 0.1 - 60 sec

3.5 11.5

ISEF>1 Fuction

Earth Fault Protection ISEF>1 Current ISEF>1 Time Delay ISEF>1 TMS ISEF>1 Time dial ISEF>1 Reset Charac ISEF>1 tReset ISEF>2 Fuction V<1 Function Under voltage protection [27] V<1 Voltage set V< 1 Time delay V<1 TMS V<2 Status

Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, UK Rectifier, RI, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse 0.005 to 1 In 0.04 - 200 s 0.025 to 1.2 0.5 to 15 DT/Inverse 0 to 100 sec Disabled/Enabled Disabled/DT/IDMT 15 - 120 V 0.04 - 7200 S 0.05 - 100 Disabled/DT

DT

0.076 0.1 DT 0 Disabled DT 88 5 Disabled

Page 3 of 5

HT MOTOR RELAY SETTINGS TABLE Motor Feeder Feeder (breaker) Rating Relay / Release Make Relay / Release Type

JOB NO : CLIENT : DOC NO : REV NO : Range Available Disabled/DT/IDMT 50 - 200 V 0.04 - 7200 S Disabled/DT Disabled / DT 0.05 to 0.8 In 0.04 - 200 s Disabled / IMDT Disabled / DT 45.65 Hz 0.1 - 100 s Disabled / IMDT 45.65 Hz 0.1 - 100 s 1In - 120In W 0.04 - 100 sec 0.05 - 300 sec Disabled / Enabled 15 - 75 0.00 - 100.0 sec Disabled / Enabled 0 - 40.0/In 25 - 325.0/In 0 - 100 sec 0 - 100 sec Disabled / Enabled 0 - 40.0/In 25 - 325.0/In

DATE : Remarks

Breaker No.

Panel No

Feeder CT Ratio Nos

Setting Function Over voltage protection [59] Negative sequence overcurrent (46)

Setting Parameter V> Status V>1 Voltage Set V< 1 Time delay V>2 Status I2>1 Status I2>1 Current I2>1 Time delay I2>2 Status F<1 Status F<1 Setting

Recommended Settings DT 126.5 5 Disabled DT 0.44 In 10 Disabled DT 48.5 5 DT 51.5 5 10In 5 17 Enabled 25 12 Enabled 38 67.3 10 0 Disabled -

Under Frequency (81)

F<1 Time delay F<2 Status F<2 Setting F<2 Time delay Rev P < Power set Rev P < Time delay Rev P < Drop-of time FFail Alarm status FFail Alarm angle FFail Alarm delay FFail 1 status FFail 1 -Xa1 FFail 1 -Xb1 FFail 1 Time delay FFail 1 DO Timer FFail 2 status FFail 2 -Xa1 FFail 2 -Xb1

Reverse power relay (32)

Field failure relay (40)

Page 4 of 5

Field failure SETTINGS TABLE HT MOTOR RELAY relay (40) Feeder Motor Feeder (breaker) Rating Relay / Release Make Relay / Release Type

JOB NO : CLIENT : DOC NO : REV NO : Range Available 0 - 100 sec 0 - 100 sec Disabled / DT 0.1 - 0.9 0.05 - 100 sec Disabled / DT 0.1 - 0.9 0.05 - 100 sec 0.05 - 300 sec

DATE : Remarks

Breaker No.

Panel No

Feeder CT Ratio Nos

Setting Function

Setting Parameter FFail 2 Time delay FFail 2 DO Timer PF<Status Lead Power Fact lead

Recommended Settings DT 0.9 50 msec DT 0.9 50 msec 17

Out of step protection (78)

PF < Lead TD PF<Status Llag Power Fact lag PF < Lag TD PF < Drop-off time

Page 5 of 5