Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DB 12-50

12V50Ah

Duration Series SLA Battery


DB Series
DB (Duration) Series batteries utilizes thick grids of modern technology
are adopted so as to guarantee the design life up to 12 years. Advanced
micro porous absorbed glass matt separator - minimizes diffusion of
oxygen into the separator, reducing float charge current which suppressed
the corrosion rate of the positive grid and extends the life of the battery.

Application
Cable Television
Communication Equipment
Security System
UPS

Control Equipment
Medical Equipment
Emergency Power System
Power Plant

General Features
Sealed and maintenance free operation.
Non-Spillable construction design.
ABS containers and covers(UL94HB, UL94V-0) optional.
Safety valve installation for explosion proof.
High quality and high reliability.
Exceptional deep discharge recovery performance.
Low self discharge characteristic.
Flexibility design for multiple install positions.

3mm (0.12inch)

Sealant
........Epoxy Resin
Safety valve .....EPDR
Terminal ........Pb Alloy
Separator ........Fiber glass
Electrolyte ........Sulfuric acid

208mm(8.19inch)

Component ......Raw material


Positive
........Lead dioxide
Negative ........Lead
Container ........ABS
........ABS
Cover

Terminal Dimensions

138mm(5.44inch)

230mm(9.06inch)

Battery Model

DB12-50

Designed Floating Life


Capacity(20oC)

12 Years
20HR(2.63A,1.80V)

10HR(5A,1.80V)

52.6Ah
Dimensions

5HR(9.38A,1.75V)

1HR(33A,1.60V)

46.9Ah

33Ah

50Ah

Length

Width

Height

Total Height

230mm(9.06inch)

138mm(5.44inch)

208mm(8.19inch)

211mm(8.31inch)

Approx. Weight

16.5Kg (36.4 lbs)

Internal Resistance

Full charged at 20 C: 0.0062 Ohm

< 3% of capacity declined per month at (20oC)

Self Discharge
Capacity Affected
by Temp.(10HR)
Charge Voltage(20oC)

M6mm (0.24inch)

211mm(8.31inch)

Construction

14mm (0.55inch)

40oC
102%

20oC

0oC

100%

85%

Cycle use
14.4-14.8V(-30mV/ oC), max. Current: 13A

Page 1 of 2

-15oC
65%
Float use
13.6-13.8V(-20mV/ oC)

DB 12-50

12V50Ah

Charge
Voltage

(CA) (V/Cell)

(%)
120

2.33

100
80

0.25

Constant Charge At 0.25CA-2.30V (20 C)


Charge
Capacity

Charge
Voltage

2.17
100%Discharge
2.00

50%Discharge

0.15

40

0.10
20

1.83

0.05

Discharge Characteristic (20 C)

0.20

60

Charge Characteristic

Charge Current
0

10

Discharge Voltage (V/Cell)

Charge

Current

Charge
Capacity

Duration Series SLA Battery

2.17
2.00
1.83
0.25CA

1.67
3CA

1.50

12

1CA

0.6CA

12

30

60

Min

Time(hour)

10
Hour

20

Self Discharge Characteristics

Relationship of OCV and state of charge


110
105

2.25

2.17

Capacity (%)

Battery Voltage (V/Cell)

2CA

0.1CA 0.05CA

2.08

2.00

100
95
90
85
80
75
70
65
60
55
50

1.92

10

20

30

40

50

60

70

80

90

100

40

20 C

40 C

45

1.83

30 C
3

7 8

9 10 11 12 13 14 15 16 17 18 19 20

Storage time: months

Remained Capacity(%)

Constant current discharge ratings-amperes at 20oC


F . V/Time

5MIN

10MIN

15MIN

30MIN

1HR

3HR

5HR

10HR

20HR

1. 60V

175

120

87. 5

52. 5

33. 0

13. 7

9. 54

5. 30

2. 77

1. 67V

158

110

85. 0

51. 0

33. 0

13. 6

9. 46

5. 22

2. 76

1. 70V

150

106

82. 0

50. 0

32. 9

13. 6

9. 46

5. 18

2. 76

1. 75V

133

97. 5

77. 5

49. 0

32. 5

13. 5

9. 38

5. 09

2. 74

1. 80V

120

90. 5

74. 0

47. 5

32. 1

13. 5

9. 31

5. 00

2. 63

1. 85V

91. 0

74. 5

64. 0

43. 7

31. 8

13. 4

9. 23

4. 92

2. 49

Constant power discharge ratings-watts at 20 C


F . V/Time

5MIN

10MIN

15MIN

30MIN

1HR

3HR

5HR

10HR

20HR

1. 60V

289

199

155

99. 0

65. 0

26. 2

18. 3

10. 6

5. 27

1. 67V

274

197

154

97. 0

62. 9

26. 2

18. 3

10. 4

5. 25

1. 70V

256

192

151

94. 5

61. 2

26. 2

18. 3

10. 4

5. 25

1. 75V

238

179

142

92. 0

60. 7

25. 8

18. 1

10. 2

5. 23

1. 80V

214

167

134

89. 5

59. 6

25. 5

17. 8

10. 0

5. 04

1. 85V

171

138

117

82. 0

59. 1

25. 4

17. 5

9. 83

4. 74

ISO9001

COPYRIGHT BSB POWER COMPANY LIMITED


Page 2 of 2