Professional Documents
Culture Documents
Lecture4 Power Flow Analysis
Lecture4 Power Flow Analysis
Lecture4 Power Flow Analysis
ECE4334
Bus admittance matrix
It provides the relationship governing the behavior of the node
voltages and currents.
Widely used in various power system analysis tools.
It finds widespread application in determining the network solution
and forms an integral part of most modern-day power system
analysis
Bus impedance matrix, Z
bus
is the inverse of Y
bus
and mainly used in
fault analysis.
In the bus admittance matrix representation, the injected currents at
nodes of the interconnected network are related to the voltages at the
nodes via an admittance representation.
Y
bus
of an interconnected power system is large and has a large
number of zero entities (sparse matrix). This is because each node
in the physical power system is connected to at most three or five
other buses. However the bus impedance matrix, Z
bus
is a full matrix.
Dr. C.Y. Evrenosoglu
ECE4334
Per phase bus admittance matrix
In developing this representation the neutral is taken as
the reference node. The relationship between the injected
node currents and the node voltages is
where I
is the vector of injected node currents (from generators
and to loads) and V is the vector of node voltages.
Each component element of the interconnected network is
referred to as a branch (line and xfmr).
For the purpose of modeling we will represent a branch
by the branch admittance, y which is also referred to as
primitive admittance. Sometimes we will also use the
branch impedance, z (primitive impedance).
Dr. C.Y. Evrenosoglu
ECE4334
Construct Y
bus
Convert the network impedances into admittances
Use Norton equivalent for the generators and the loads
Use Kirchhoffs Current Law to construct the bus Y
bus
Dr. C.Y. Evrenosoglu
Thanks to Dr. Thomas Baldwin, FAMU/FSU for slide content
ECE4334
Example Regulating XFMR
Dr. C.Y. Evrenosoglu
I
p
a*
/||
/
/
1
x
2
x
1
y/a
1 /
1/
ECE4334
Example LTC
Dr. C.Y. Evrenosoglu
I
p
a
/
/
/
1
ECE4334
Example
The parameters for the branch data is provided. The series
impedance and total line charging susceptance for each branch are
in pu on an appropriately chosen base. A generator with emf equal
to 0.90 pu and a reactance of j1.25 pu is connected to bus 1 while
a motor with internal voltage equal to 0.8 70 pu and a
reactance of j1.25 pu is connected to bus 5. Write the nodal
equations.
Dr. C.Y. Evrenosoglu
From To R X B
1 2 0.004 0.0533 0
2 3 0.02 0.25 0.22
3 4 0.02 0.25 0.22
2 4 0.01 0.15 0.11
4 5 0.006 0.08 0
ECE4334
Example
Dr. C.Y. Evrenosoglu
From To R X B
1 2 0.004 0.0533 0
2 3 0.02 0.25 0.22
3 4 0.02 0.25 0.22
2 4 0.01 0.15 0.11
4 5 0.006 0.08 0
0.80
0.72 90
0.80
0.64 160
ECE4334
Example
Dr. C.Y. Evrenosoglu
jB
24
/2
jB
23
/2
jB
34
/2
0.72 90
0
0
0
0.64 160
1.4 19.457
1.4 18.657
0
0
0
1.4 18.657
2.16 29.104
0.318 3.975
0.442 6.637
0
0
0.318 3.975
0.636 7.73
0.318 3.975
0
0
0.442 6.637
0.318 3.975
1.692 22.877
0.932 12.43
0
0
0
0.932 12.43
0.932 13.23
1/0.04 0.0533
ECE4334
Power flow
When analyzing power systems we know neither the
complex bus voltages nor the complex current
injections
Rather, we know the complex power being consumed
by the load, and the power being injected by the
generators plus their voltage magnitudes
Therefore we can not directly use the Y
bus
equations,
but rather must use the power balance equations.
We want to know the voltage profile of the network
that is the nodal (bus) voltages for a given load and
generation schedule.
Dr. C.Y. Evrenosoglu
Thanks to Dr. Tom Overbye, University of Illinois for the content
ECE4334
Power flow bus types
There three main types of network buses
1. Load bus (PQ bus)
The power injection is known real power, P and
reactive power, Q injections are known
2. Generator bus (PV bus)
The real power (P) injection is known and the voltage
magnitude, |V| is known.
3. Slack bus (swing bus)
Reference bus; voltage angle is set to 0
Takes up the losses in the network.
We will assume that there is one slack bus.
In practice distributed slack and generator
participation factors are in use.
Dr. C.Y. Evrenosoglu
ECE4334
P
Dk
Q
Dk
Power flow bus types
The power delivered (injected) to bus k is
Since I = Y
bus
V then;
||
| |
| |
OR Y
ik
is in polar form
| |
||
| |
||
| |
||
)
Dr. C.Y. Evrenosoglu
ECE4334
Power flow equations
||
||
1
For the first iteration, k=0 we guess that x
(0)
=1 and we start iterating:
Dr. C.Y. Evrenosoglu
k x
(k)
k x
(k)
0 1 5 2.61185
1 2 6 2.61612
2 2.41421 7 2.61744
3 2.55538 8 2.61785
4 2.59805 9 2.61798
Thanks to Dr. Tom Overbye, University of Illinois for the content
ECE4334
Gauss iteration
ECE4334
Gauss iteration
Stopping criteria is a key problem When to stop the
iteration?
With Gauss iteration we stop when
Common norms are the two-norm (Euclid) and infinity norm;
b 0.25 0.25
Unknown complex voltage at bus 2.
Slack bus is bus 1
10.
Slack bus will pick up the losses.
S
G1
will be calculated at the end once V
2
is determined.
Dr. C.Y. Evrenosoglu
V
1
V
2
S
D2
Z
Line
S
G1
Y
cap
ECE4334
Two-bus example solution
Determine Y
bus
S
2
= S
G2
S
D2
= 0 S
D2
= 1 j0.5
Dr. C.Y. Evrenosoglu
V
1
V
2
S
D2
=1+j0.5
y
12
S
G1
Y
cap
=j0.25
1
0.02 0.06
5 15
5 15 0.05 5 15
5 15 5 15 0.05 0.25
5 14.95 5 15
5 15 5 14.70
y/2=j0.05 y/2=j0.05
ECE4334
Two-bus example solution
Dr. C.Y. Evrenosoglu
V
1
V
2
S
D2
y
12
S
G1
Y
cap
5 14.95 5 15
5 15 5 14.70
ECE4334
Two-bus example solution
Dr. C.Y. Evrenosoglu
V
1
V
2
S
D2
y
12
S
G1
Y
cap
5 14.95 5 15
5 15 5 14.70
102.12
23.96
2
25 23.2
1.0212 0.2396
ECE4334
Power flow
Study Example 6.9 in 5
th
edition.
Dr. C.Y. Evrenosoglu
ECE4334
Gauss acceleration factor
The procedure for finding a solution to x = h(x)
can be accelerated by using
0
If >>1 or 0 < << 1; the iteration might
diverge.
Dr. C.Y. Evrenosoglu
ECE4334
Gauss Multivariable
k = 0, 1, 2,
, ,
, ,
, ,
. This
modification is called Gauss-Seidel iteration
Dr. C.Y. Evrenosoglu
ECE4334
Gauss-Seidel Multivariable
k = 0, 1, 2,
, ,
, ,
, ,
, ,
Easier to program.
Faster than Gauss.
Acceleration factor is used.
Dr. C.Y. Evrenosoglu
ECE4334
Power flow Multi-bus with Gauss-Seidel
Load Bus Generator Bus
Given
|
Find |
and
ECE4334
Power flow Multi-bus with Gauss-Seidel
Dr. C.Y. Evrenosoglu
Generation Bus
| by
but
keep the new angle
. If
hits one of
the limits. It is assigned to the limit; the bus type is changed to PQ and
the
Q
G2
is not known; once it is calculated then you can calculate
S
D2
= 1 + j0.5
Z
line
= j0.5
S
G1
S
G2
= 0.25 + jQ
G2
S
D1
ECE4334
Example
Dr. C.Y. Evrenosoglu
V
1
=10 V
2
=1
S
D2
= 1 + j0.5
Z
line
= j0.5
S
G1
S
G2
= 0.25 + jQ
G2
S
D1
Bus 2: PV (Generator) Bus
ECE4334
Example
Dr. C.Y. Evrenosoglu
V
1
=10 V
2
=1
S
D2
= 1 + j0.5
Z
line
= j0.5
S
G1
S
G2
= 0.25 + jQ
G2
S
D1
Bus 2: PV (Generator) Bus
0.75
2 and
10
ECE4334
Example
Dr. C.Y. Evrenosoglu
V
1
=10 V
2
=1
S
D2
= 1 + j0.5
Z
line
= j0.5
S
G1
S
G2
= 0.25 + jQ
G2
S
D1
0.75 j0.1459
ECE4334
Power flow
Study Example 6.10 in 5
th
edition.
Dr. C.Y. Evrenosoglu
ECE4334
Newton-Raphson
Quadratic convergence
Mathematically superior to Gauss-Seidel method
More efficient for large networks
Number of iterations required for solution is independent of
system size
The Newton-Raphson (NR) equations are cast in natural
power system form
Solving for voltage magnitude and angle, given real and reactive
power injections.
General form of the problem is to find an x such that f() = 0
Use 1
st
order Taylor expansion around a point; x
0
1
2
. . . 0
NR iterations
f( x
k
) is known as the mismatch and we are trying to
drive it to zero.
The stopping criteria is |f( x
k
)| <
ECE4334
NR non-linear algebraic equations
Dr. C.Y. Evrenosoglu
. . .
. . .
. . .
h. o. t.
H.o.t. (higher order terms) are neglected.
NR iterations
ECE4334
NR non-linear algebraic equations
In power flow analysis flat start is used as initial guess; however,
to improve the initial guess a few steps of Gauss-Seidel iteration
may be used.
A disadvantage of NR is the need to update the Jacobian (J) every
iteration. Sometimes we can update less often and still get good
results.
In practice we do not evaluate the inverse matrix. Taking inverses is
computationally expensive and not really needed. Instead we use;
solve for
0.5
For NR formulation we need the equations in the form of
f(x)=0. The easiest way is to subtract the left sides from the
right sides and use the slack bus information as V
1
= 1.
ECE4334
Example
Dr. C.Y. Evrenosoglu
x
1
= V
2
and x
2
= V
3
Now that we have our Jacobian, we start the iteration with flat
profile
ECE4334
Example
Dr. C.Y. Evrenosoglu
ECE4334
Example
Dr. C.Y. Evrenosoglu
0.991667
0.993333
ECE4334
Example
Dr. C.Y. Evrenosoglu
0.991667
0.993333
The accuracy is acceptable. Two iterations are enough! Our
objective to find and x for which f(x)=0 is met.
Now, find P
1
:
P
1
=1.511800
2.011800.
Losses in the transmission system is
0.011800
ECE4334
Dr. C.Y. Evrenosoglu
NR Application to Power Flow
=
V
x
V
V
V
N N
... , ...
2 2
( )
( )
( ) ( )
( ) ( )
( )
( )
=
=
=
=
=
=
=
x Q
x P
x f
x Q Q x Q
x P P x P
x Q Q
x P P
Q Q Q
P P P
i
i
i i i
i i i
i i
i i
Di Gi i
Di Gi i
) (
Power system
state vector
ECE4334
Dr. C.Y. Evrenosoglu
NR Application to Power Flow
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
( )
( )
( )
( )
( )
( )
( )
( )
( )
=
=
+ =
=
=
x Q Q
x Q Q
x P P
x P P
x Q
x Q
x P
x P
x f
B G V V x Q
B G V V x P
N N
N N
N
N
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
...
...
...
...
cos sin
sin cos
2 2
2 2
2
2
1
1
ECE4334
Dr. C.Y. Evrenosoglu
NR Application to Power Flow
( ) [ ] ( )
( ) [ ] ( )
( ) [ ] ( )
[ ]
( )
( )
( )
( )
=
= =
=
+
k
i i
k
i i
k
k
k
k
k k k
k k k k k
k k k k
x Q Q
x P P
x Q
x P
V
J
x f x x J
x f x J x x x
x f x J x x
1
1
1
1
The right side represent the mismatch between the
specified values of P and Q and the corresponding values
obtained with the trial value
. We
can update the mismatch vector and the Jacobian matrix and
continue iterating.
ECE4334
Dr. C.Y. Evrenosoglu
NR Application to Power Flow
( )
( )
k
k
k
k
k k
k k
x Q
x P
V
J J
J J
22 21
12 11
( )
( ) ( ) [ ]
( )
( ) ( ) [ ]
( )
( ) ( ) [ ]
( )
( ) ( ) [ ]
ij ij ij ij i
j
i
ij 22
ij ij ij ij j i
j
i
ij 21
ij ij ij ij i
j
i
ij 12
ij ij ij ij j i
j
i
ij 11
cos B sin G V
V
x Q
J
sin B cos G V V
x Q
J
sin B cos G V
V
x P
J
cos B sin G V V
x P
J
=
+ =
=
+ =
=
=
i j
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
1 k
i i
k i ik k i ik k
N
1 k
i i
cos B sin G V V x Q
sin B cos G V V x P
=
+ =
=
=
Partition the Jacobian into block sub-matrices.
||
||
i
th
and j
th
bus
(ith row and jth column)
ECE4334
Dr. C.Y. Evrenosoglu
NR Application to Power Flow
( )
( )
( ) ( )
( )
( )
( ) ( )
i ii
i
i
i
i
ii 22
2
i ii i
i
i
ii 21
i ii
i
i
i
i
ii 12
2
i ii i
i
i
ii 11
V B
V
x Q
V
x Q
J
V G x P
x Q
J
V G
V
x P
V
x P
J
V B x Q
x P
J
=
=
=
=
+ =
=
=
i = j
( )
( )
k
k
k
k
k k
k k
x Q
x P
V
J J
J J
22 21
12 11
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
1 k
i i
k i ik k i ik k
N
1 k
i i
cos B sin G V V x Q
sin B cos G V V x P
=
+ =
=
=
ECE4334
NR Application to Power Flow
Dr. C.Y. Evrenosoglu
PV buses
As long as the reactive power generated at the bus is
within the reactive power limit specified at the bus, we do
not solve for the |V
i
| since |V
i
| is specified.
This reduces the dimensions of the problem.
We exclude the voltage magnitudes of the PV buses from
the state vector, corresponding entries in the Jacobian
matrix and the mismatch vector.
If during an iteration a PV bus violates the reactive power
limit at the bus, then the reactive power is held at the
limit, and the bus is treated as PQ bus. The voltage
magnitude has to be reintroduced to the state vector and
the corresponding entries have to be reintroduced to the J
and the mismatch vector.
ECE4334
NR Application to Power Flow
Dr. C.Y. Evrenosoglu
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ] ( )
ij shunt ij i j i ij j i ij j i ij
i ij j i ij j i ij j i ij
b B V B G V V x Q
V G B G V V x P
,
2
2
cos sin
sin cos
+ =
+ =
Once the voltage magnitudes and angles at each bus is
known, the slack bus power injections and the line flows
can be calculated. For line flows the following equations
can be used:
Line losses can be easily calculated as follows:
ECE4334
Example
Find
2
, |V
2
|,
3
, S
G1
and Q
G2
. All the transmission line impedances
are same and j0.1 and the shunt admittances are same and j0.01.
Ignore the generator reactive limits at bus 2.
Dr. C.Y. Evrenosoglu
Bus 1: Slack
10
Bus 2: PV bus
Bus 3: PQ bus
ECE4334
Example
Dr. C.Y. Evrenosoglu
unknowns knowns
ECE4334
Example
Dr. C.Y. Evrenosoglu
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
B G V V x Q
B G V V x P
=
+ =
=
=
cos sin
sin cos
1
1
ECE4334
Example
Dr. C.Y. Evrenosoglu
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
B G V V x Q
B G V V x P
=
+ =
=
=
cos sin
sin cos
1
1
ECE4334
Example
Dr. C.Y. Evrenosoglu
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
B G V V x Q
B G V V x P
=
+ =
=
=
cos sin
sin cos
1
1
ECE4334
Example
Dr. C.Y. Evrenosoglu
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
B G V V x Q
B G V V x P
=
+ =
=
=
cos sin
sin cos
1
1
ECE4334
Example
Dr. C.Y. Evrenosoglu
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
B G V V x Q
B G V V x P
=
+ =
=
=
cos sin
sin cos
1
1
We are ready to start iterating.
0.6661
2.8653
1.2244
Initial guess Flat start
For angles:
0
For voltage magnitude:
1
ECE4334
Example
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
B G V V x Q
B G V V x P
=
+ =
=
=
cos sin
sin cos
1
1
Big mismatch!
Dr. C.Y. Evrenosoglu
ECE4334
Example
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
B G V V x Q
B G V V x P
=
+ =
=
=
cos sin
sin cos
1
1
Dr. C.Y. Evrenosoglu
After 1 iteration:
Better mismatch!
ECE4334
Example
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
B G V V x Q
B G V V x P
=
+ =
=
=
cos sin
sin cos
1
1
Dr. C.Y. Evrenosoglu
After 2 iterations:
Sufficient mismatch!
STOP
ECE4334
Example
( ) ( ) ( ) [ ]
( ) ( ) ( ) [ ]
k i ik k i ik k
N
k
i i
k i ik k i ik k
N
k
i i
B G V V x Q
B G V V x P
=
+ =
=
=
cos sin
sin cos
1
1
Dr. C.Y. Evrenosoglu
Now; calculate S
G1
and Q
G2
1.6396
ECE4334
NR in power flow analysis
Advantages
fast convergence as long as initial guess is close to
solution
large region of convergence
Disadvantages
each iteration takes much longer than a Gauss-Seidel
iteration
more complicated to code, particularly when
implementing sparse matrix algorithms
Newton-Raphson algorithm is very common in
power flow analysis
Dr. C.Y. Evrenosoglu
Thanks to Dr. Tom Overbye, University of Illinois for the content
ECE4334
Power flow control
A major problem with power system operation is
the limited capacity of the transmission system
lines/transformers have limits (usually thermal)
no direct way of controlling flow down a
transmission line (e.g., there are no valves to close to
limit flow)
open transmission system access associated with
industry restructuring is stressing the system in new
ways
We need to indirectly control transmission line
flow by changing the generator outputs
Dr. C.Y. Evrenosoglu
Thanks to Dr. Tom Overbye, University of Illinois for the content
ECE4334
Dr. C.Y. Evrenosoglu
Real-sized Power Flow Cases
Real power flow studies are usually done with
cases with many thousands of buses
Buses are usually group in to various balancing
authority areas, with each area doing its own
interchange control
Cases also model a variety of different automatic
control devices, such as generator reactive power
limits, load tap changing transformers, phase
shifting transformers, switched capacitors,
HVDC transmission lines, and (potentially)
FACTS devices
Thanks to Dr. Tom Overbye, University of Illinois for the content
ECE4334
Dr. C.Y. Evrenosoglu
Indirect Transmission Line Control
What we would like to determine is how a change in
generation at bus k affects the power flow on a line
from bus i to bus j (Sensitivities).
The assumption is
that the change
in generation is
absorbed by the
slack bus
System
i
j
P
G-k
P
ij
Thanks to Dr. Tom Overbye, University of Illinois for the content
ECE4334
Dr. C.Y. Evrenosoglu
Power flow simulation before
One way to determine the impact of a generator change
is to compare a before/after power flow.
For example below is a three bus case with an overload
Z for all lines = j0.1
One Two
200 MW
100 MVR
200.0 MW
71.0 MVR
Three 1.000 pu
0 MW
64 MVR
131.9 MW
68.1 MW
68.1 MW
124%
Thanks to Dr. Tom Overbye, University of Illinois for the content
ECE4334
Dr. C.Y. Evrenosoglu
Power flow simulation after
Z for all lines = j0.1
Limit for all lines = 150 MVA
One Two
200 MW
100 MVR
105.0 MW
64.3 MVR
Three
1.000 pu
95 MW
64 MVR
101.6 MW
3.4 MW
98.4 MW
92%
100%
Increasing the generation at bus 3 by 95 MW (and hence
decreasing it at bus 1 by a corresponding amount), results
in a 31.3 drop in the MW flow on the line from bus 1 to 2.
Thanks to Dr. Tom Overbye, University of Illinois for the content
ECE4334
More
There are different types of power flow under certain
assumptions based on NR:
Decoupled Power Flow
Fast Decoupled Power Flow
DC Power Plow
Sensitivities are calculated by using DC power flow
Contingency analysis
Dr. C.Y. Evrenosoglu
ECE4334
Homework 6.1 (due Thursday, 10/27)
Find one of the roots of the equation
9 4 0
by using Gauss iteration. You can assume the initial guess
for x
(0)
= 2. Observe the number of iterations.
Upload your file to the assignment area.
Name your file as ECE4334_HW6_1_lastname.m
Dr. C.Y. Evrenosoglu
ECE4334
Homework 6.2 (due Tuesday, 11/1)
A. Repeat Homework 6.1 by using an acceleration factor of
1.25.
B. Repeat 6.1 by using an acceleration factor of 2.
C. Repeat 6.1 by using an acceleration factor of 0.1.
Upload your file(s) to the assignment area.
Name your file as ECE4334_HW6_2_lastname.m
Dr. C.Y. Evrenosoglu
ECE4334
Homework 6.3 (due Tuesday, 11/1)
Solve the class (Slide 46) example using Gauss-Seidel and an
acceleration factor.
Find S
1
, Q
2
and
2
. Ignore the Q generation limits at bus 2.
Dr. C.Y. Evrenosoglu
V
1
=10 V
2
=1
S
D2
= 1 + j0.5
Z
line
= j0.5
S
G1
S
G2
= 0.25 + jQ
G2
S
D1
ECE4334
Homework 7.1 (due Thursday11/3)
Use the Newton-Raphson method to solve
1 0
1 0
A.
1
B.
1
Exact solution is x
1
= x
2
= 1.618 and another solution is
x
1
= x
2
= -0.618.
Observe the number of iterations in both cases.
Upload your file to the assignment area.
Name your file as ECE4334_HW7_1_lastname.m
Dr. C.Y. Evrenosoglu
ECE4334
Homework 7.2 (due Tuesday 11/8)
In the following network;
a) Find V
2
exactly (take the larger of two possible values) Hint: Use
power circle
b) Find V
2
by Gauss iteration and use flat start for initial condition. If
you use hand calculation; stop after one iteration. If you use
MATLAB; please provide your code (print-out).
c) Find S
1
.
Dr. C.Y. Evrenosoglu
V
1
=10
V
2
S
D2
= 0.3 + j1.0
Z
line
=j0.4
S
G1
jQ
G2
= j1.1
S
D1
ECE4334
Homework 7.3 (due Tuesday 11/8)
In the following network S
D1
=1.0, S
D2
=1.0 j0.8 and S
D3
= 1.0+j0.6.
Z
line
= j0.4 for all lines and line charging susceptances are neglected.
P
G2
= 0.8 and |V
2
| = 1.0
Bus 1 is slack.
Use Gauss-Seidel to find V
2
and V
3
. Use flat start for iterations.
If you do hand calculations do one iteration only. If you use
MATLAB please provide your code (print-out).
Dr. C.Y. Evrenosoglu
1 2
3
ECE4334
Homework 7.4 (due Tuesday 11/8)
For the system on Slide 69, assume that P
G2
= 0.3, |V
2
|=0.95 and
S
D3
=0.5+j0.2. Use flat start for the iterations. Carry out one NR
iteration and find
and |V
3
|
1
. Evaluate the mismatch vector
after single iteration.
Dr. C.Y. Evrenosoglu