Ac Ups Battery Rack Sizes
Ac Ups Battery Rack Sizes
Battery Type BATTERY VOLTAGE Nominal Cell voltage No of Cells End Cell Voltage Battery Ah = SBM 220 1.2 175 1.1 Ni-Cd Volts Volts Nos Volts
Inv kVA x 1000 x PF x BT x TC x AF Inverter Efficiency x No of Cells x V Cell End Ampere Hours Inverter kVA Power Factor Inverter Efficiency Cell end of discharge V Number of Cells Battery back-up time Temperature Compensation Battery aging factor
CALCULATIONS AREA UPS Load (kVA) 50-RIB-01 60-RIB-02 20-RIB-01 30-RIB-01 10-RIB-03 10-RIB-04 30-RIB-02 60-RIB-01 50-RIB-02 60-RIB-03 13.26 13.26 28.57 13.26 28.57 70.4 13.26 13.26 13.26 13.26
Considering Selected Future (kVA) Standard Size (kVA) 16.32 16.32 35.71 16.32 35.71 86.73 16.32 16.32 16.32 16.32 20 20 40 20 40 100 20 20 20 20
Battery Ah Selected (Calculated) Size (Ah) 122 122 244 122 244 611 122 122 122 122 138 138 277 138 277 625 138 138 138 138
BATTERY RACK DETAILS: Battery Block Dimensions Type (Ref Annex I) SBM-138 (H) (W) (L1) (L2) 405 195 115
Rack Total No of Arrangement cells / Step / Tier 2 Tier 2 Step =88/2/2 22 Nos
=22x115 2530 mm
500 mm
Bottom tier 22+22 Top tier 22+22 SBM-277 (H) (W) (L1) (L2) 405 195 228 Bottom tier 11+11+11+11 Top tier 11+11+11+11 SBM-625 (H) (W) (L1) (L2) 405 195 268 2 Tier 3 Step =175/3/2 30 Nos =30x195 (Note 2 940 mm 5850 mm 2 Tier 4 Step =88/4/2 11 Nos =11x228 2508 mm 930 mm
Bottom tier 30+30+30 Top tier 28+28+29 Enclosures 1) Annexure I - Dimensions of M Range batteries
2) Annexure II - Battery Rack Dimensions for 2 tier, standard floor mounted racks - Normal connection 3) Annexure III - Battery Rack Dimensions for 2 tier, standard floor mounted racks -Crosswise connection
4) Annexure IV - Battery Rack diagrams 5) Annexure V Notes: 1 Dimension of Battery Room for 10-RIB-04 is to be re-checked. 2 Due to terminal arrangement of SBM 625 battery, width-to-width connection considered. Other cases the same is length-to-length connection (Ref Annexure V) 3 Above are for 1 Set of batteries. 2 set of Batteries (Dual Redundant) are required as per drg no 3481-8532-70-0030
1 of 6
800 mm
1000 mm
500 mm
800 mm
2 of 6
750 mm
3 of 6
800 mm
4 of 6
Inv kVA x 1000 x PF x BT x TC x AF Inverter Efficiency x No of Cells x V Cell End Ampere Hours Inverter kVA Power Factor Inverter Efficiency Cell end of discharge V Number of Cells Battery back-up time Temperature Compensation Battery aging factor
CALCULATIONS UPS Load Considering AREA (kVA) Future (kVA) CCB - UPS 163.26 208.08
BATTERY RACK DETAILS: Battery Block Dimensions Type (Ref Annex I) SBM-740 (H) (W) (L1) (L2) 405 195
Rack Total No of Arrangement cells / Step / Tier =318/2/2/4 20 Nos 115 (Note 4) Bottom tier 20+20 Top tier 20+20 2 Tier 2 Step
930 mm
4) Annexure IV - Battery Rack diagrams 5) Annexure V Notes: 1 Dimension of Battery Room for CCB is to be re-checked. 2 Due to terminal arrangement of SBM 740 battery, width-to-width connection considered. Other cases the same is length-to-length connection (Ref Annexure V) 3 Above are for 1 Set of batteries. 2 set of Batteries (Dual Redundant) are required as per drg no 3481-8532-70-0030 4 For CCB, due to large no of Cells, each Battery has been considered distributed in 4 racks.
5 of 6
800 mm
6 of 6