Flare Stack Sizing
Flare Stack Sizing
: CLIENT : UNIT :
S.Rahimi 0
Stack Height Caclulation based on Heat Rediation Intensity Gas G Specification S ifi ti Maximum Flow Rate Tip Inlet Gas Pessure Tip Gas Inlet Temperature Molecular Weight Specific Heat Ratio Gas Comperssibility factor (z) Heat of Combustion kg/hr bara C ---------kJ/kg 260000.0 1.2 41.0 18.9 1.3 1.0 45388
Environment Condition Wind Velocity Air Relative Humidity Ambient Transmitivity Transmitivity to be applied? Air Temperature Atmospheric Pressure m/sec % ------C bara 15.0 30.0 0.78 Yes 55.0 1.0
Sizing Criteria Radiation Heat Release Fraction (F) Maximum Allowable Heat Intensity at Grade Distance from Stack Base to Flare Boundary Maximimum Allowable Mach No. at Stack % kW/m2 m ---13.4 2.15 120.0 1.00
Calculation Results Flare Tip Diameter (Calculated) Flare Tip Diameter (Selected) Heat Liberated Flame Length Volumetric Flow Rate Flare Tip Exit Velocity Wind Velocity / Exit Velocity y/L x/L y x Distance from Flame Center to the Boundary R' Elevation from Flame Center to Grade (H') Flare Stack Height Maximum tip exit velocity for Steam assisted m m Watt m m3/hr m/sec ---0.495 0.495 3.28E+09 105.5 293740.12 424.66 0.035 0.62 0.38 65 75 65.75 40.31 112.96 99.85 52.83 19.96 121.9
m m m m m m m/sec
General Notes
www.chemwork.org
S.Rahimi 0
Stack Height Caclulation based on Heat Rediation Intensity Selected Height Flame Lift off H' R 0 10 20 30 40 50 60 70 80 90 100 120 140 160 32.00 0.00 64.87 R' -20 -10 0 10 20 30 40 50 60 70 80 100 120 140 m m m D (m) 67.9 65.7 64.9 65.6 67.8 71.4 71 4 76.1 81.8 88.3 95.3 102.9 119.1 136.3 154.2 K (Kw/m2) 5.95 6.37 6.52 6.38 5.96 5 5.38 38 4.74 4.10 3.52 3.02 2.59 1.94 1.48 1.15 K (Btu/hr/ft2) 1886 2018 2068 2021 1891 1707 1501 1300 1117 958 822 614 469 366
0 33 66 98 131 164 197 230 262 295 328 394 459 525
5.00 4.00 3.00 2.00 1.00 0.00 0 50 100 Distance from Stack Base (m) 150 200
2000 1500 1000 500 0 0 100 200 300 400 Distance from Stack Base (ft) 500 600