Vitosolic 200
VITOSOLIC 200
for systems with dual mode DHW heating or dual mode DHW
and swimming pool water heating or space heating backup
using solar panels and oil-/gas-fired boilers
Vitosolic 200
400 mm / 15¾”
with
H Tank temperature sensor
H Collector temperature sensor
H Temperature sensor (swimming pool /
space heating water tank)
267 mm / 10½” 52 mm
2”
72 mm / 2¾”
Construction and function To improve the start-up characteristics of Systems with dual mode DHW heating:
the system or for systems with several The temperature in the DHW tank is limited
Construction collector arrays, operation with a bypass by the electronic temperature limiter (safety
circuit is feasible. This requires the use of shutdown at 90ºC / 194ºF) in Vitosolic 200
Vitosolic 200 comprises: the optional solar cell. or by the high limit safety cut-out (if
Electronics, digital display and setting keys. required.
Reheating by the boiler will be suppressed if This device switches the solar circuit pump
Vitosolic 200 offers terminals for the the solar circuit pump is already active. OFF when the set temperature has been
connection of power supply, solar loop HSystems with Vitotronic control units and exceeded.
pump, bypass circuit pump, circulation KM BUS:
pump for heating up the pre-heat stage, A third set DHW temperature is encoded Systems with dual mode DHW and
swimming pool / space heating tank pump at the boiler control unit. The DHW tank
swimming pool water heating:
will only be heated by the boiler, if this set
switching output for suppressing reheating DHW heating has priority. When the
value cannot be achieved by the solar
by the boiler, additional DHW heating swimming pool water is heated (consumer
heating system.
function, thermostat function and central HSystems with additional Viessmann control with the lower set temperature), the
fault messages. An additional solar cell can units: circulation pump will be switched OFF in
be installed to measure radiation intensity. An actual DHW temperature which is accordance with a timer, to establish
10ºC / 18ºF higher is simulated via a whether the DHW tank (consumer with the
resistor in the connection extension, higher set temperature) can be reloaded.
Function which should be installed on site. The
If it is being heated or if the temperature of
DHW tank will only be heated by the boiler
the solar fluid is insufficient for heating the
if this actual temperature cannot be
Vitosolic 200 starts the solar circuit pump DHW tank, the system continues to heat the
achieved by the solar heating system.
for DHW heating and (if installed) the solar swimming pool water.
circuit pump for heating swimming pool Additional function for DHW heating:
water and/or pump for space heating In systems with a capacity above 400 litres, Refer to Vitosolic 200
storage tank, when the respective the entire water content must be heated to Installation and Service
differential temperature has been reached. 60ºC / 140ºF once every day. Instructions for detailed
HSystems with Vitotronic control units and descriptions of all functions
Optional safety shutdown of collectors and KM BUS: and possible system
DHW tank in case of excessive A second set DHW temperature is configurations.
temperatures. encoded at the boiler control unit, and the
fourth DHW phase is activated. This signal
is transferred to the solar control unit, and
Calculation of the energy production of
the circulation pump (reheating) will be
solar system is achieved by measuring the
started.
temperature differential between the solar HSystems with additional Viessmann control
collector sensor and the storage tank units:
sensor, and by input of the solar fluid The circulation pump (reheating) is started
volume flow rate. The energy production is at the adjustable time, if the DHW cylinder
displayed in kW/h. has not been heated to 60ºC / 140ºF at
least once every day. A DHW temperature
of approx. 35ºC / 95ºF is simulated via an
Accumulative run hours run the solar circuit
on-site resistor.
pump can be displayed.
5345 075 v1.0
2
Technical Data
Vitosolic 200
3
Accessories
Accessories