BTS3012

Product Description(for 18TRX) 7 BTS3012 Power Subsystem

7 BTS3012 Power Subsystem

About This Chapter

The BTS3012 power subsystem consists of the power distribution units in the cabinet. It provides
stable power supply for the BTS3012 through mechanisms such as lightning protection and E1
filtering.

7.1 Components of the BTS3012 Power Subsystem


The functions of the BTS3012 power subsystem are performed by the power distribution units.
The power distribution units consist of the DC lightning arrester, EMI filter, PGND bar, busbar
terminal socket on top of the cabinet, and the busbar at the right of the cabinet.
7.2 Power Distribution of the BTS3012
The BTS3012 power subsystem provides the input power with lightning protection and filtering,
and then distributes the power to the equipment in the BTS3012 cabinet through the busbar.

Issue 02 (2007-08-15) Huawei Technologies Proprietary 7-1


BTS3012
7 BTS3012 Power Subsystem Product Description(for 18TRX)

7.1 Components of the BTS3012 Power Subsystem


The functions of the BTS3012 power subsystem are performed by the power distribution units.
The power distribution units consist of the DC lightning arrester, EMI filter, PGND bar, busbar
terminal socket on top of the cabinet, and the busbar at the right of the cabinet.

Figure 7-1 shows the BTS3012 power subsystem.

Figure 7-1 BTS3012 power subsystem

-48 V DC DC lighting
EMI filter Busbar Load
arrester

BTS3012 power subsystem

7.2 Power Distribution of the BTS3012


The BTS3012 power subsystem provides the input power with lightning protection and filtering,
and then distributes the power to the equipment in the BTS3012 cabinet through the busbar.

DC Power Distribution
Figure 7-2 shows the power distribution in the BTS3012 when the external –48 V DC power
input is used.

Figure 7-2 BTS3012 power distribution (–48 V DC)


User
Power subsystem
interface

DC lightning arrester
DAFU
subrack
DTRU
PGND

+
V-

B subrack
V+

u
s
-48V -48V GND GND
-48V -48V GND GND

Common
b subrack
-48V DC a
r
Fan

- BBU
EMI filter

PGND cable
GND cable
- 48 V DC power cable

7-2 Huawei Technologies Proprietary Issue 02 (2007-08-15)


BTS3012
Product Description(for 18TRX) 7 BTS3012 Power Subsystem

The external power input is processed through the DC lightning arrester and the EMI filter, and
then sent to the equipment in the cabinet through the 13 power switches on the busbar.
Table 7-1 lists the relation between the power switches on the Busbar and the equipment in the
cabinet.

Table 7-1 Relation between the power switches and the equipment
Power Switch Equipment

SW1 DAFU subrack

SW2–SW7 DTRU 0–DTRU 5 in DTRU subrack 1

SW 8 Fan subrack

SW9–SW11 DTRU 6–DTRU 8 in DTRU subrack 0

SW 12 Common subrack

SW13 Transmission subrack

When the external +24 V DC power input is used, a DC/DC Sidepower power cabinet should
be configured with the BTS3012 to convert the external +24 V DC to –48 V DC. Figure 7-3
shows the power distribution in the BTS3012.

Figure 7-3 BTS3012 power distribution (+24 V DC)

User interface Power subsystem

DC lightning arrester
DAFU
subrack

DTRU
PGND

+
V-

B subrack
V+

u
-48V -48V GND GND

s Common
-48V -48V GND GND

+24V DC DC/DC
Sidepower b subrack
cabinet -48V DC a
r
Fan

- BBU
EMI filter

PGND cable
GND cable
- 48 V DC power cable

AC Power Distribution
When the external 220 V AC or 110 V AC power input is used, an AC/DC Sidepower power
cabinet should be configured with the BTS3012 to convert the 220 V AC or 110 V AC to –48
V DC. Figure 7-4 shows the power distribution in the BTS3012.

Issue 02 (2007-08-15) Huawei Technologies Proprietary 7-3


BTS3012
7 BTS3012 Power Subsystem Product Description(for 18TRX)

Figure 7-4 BTS3012 power distribution (220 V AC or 110 V AC)

User interface Power subsystem

DC lightning arrester
DAFU
subrack

DTRU

PGND
V-
+ B subrack

V+
u

-48V -48V GND GND


s Common

-48V -48V GND GND


AC/DC
220V AC b subrack
Sidepower
110V AC cabinet -48V DC a
r
Fan

- BBU
EMI filter

PGND cable
GND cable
- 48 V DC power cable

7-4 Huawei Technologies Proprietary Issue 02 (2007-08-15)