Force Calculation - 28 Mva
Force Calculation - 28 Mva
1.1.2
1.1.2.1
MEANING OF ABREVIATIONS:
1.1.2.2
CALCULATIONS:
ZT = 12.216
1.1.3
1.1.3.1
MEANING OF ABREVIATIONS:
N= TURN OF WINDING
H = HEIGHT OF WINDING
1.1.3.2
CALCULATIONS:
=4π2 ×0.1387×1334×31652×9122115×10-7
=4.2×106 Newton
=4π2 ×0.1387×241×129572×6762115×10-7
=1.7×106 Newton
1.1.3.3
CONCLUSION:
The result axial imbalance force for winding hv and lv are listed below:
1.1.4
1.1.4.1
MEANING OF ABREVIATIONS:
1.1.4.2
CALCULATIONS:
Fc = 34×KVAHw×%Z×9964×10-3 Newton
=34×50,000211.5×.1221×9964×10-3 Newton
=0.655×106 Newton
1.1.4.3
CONCLUSION:
The result axial compressive force for winding hv and lv are listed below:
1.1.5
1.1.5.1
MEANING OF ABREVIATIONS:
n = NO OF CONDUCTOR RADIALLY
t= THICKNESS OF CONDUCTOR
w= WIDTH OF KEYBLOCK
s = NO OF BLOCK/CIRCLE
1.1.5.2
CALCULATIONS:
Qc = Fcn×t×w×sN/mm 2
1.1.5.3
CONCLUSION:
The result required no of vertical support for winding hv and lv are listed below:
1.1.6
20/28
SHORT MVA, 33/11
CIRCUIT FORCE CALCULATION
KV, Dyn11
1.1.6.1
MEANING OF ABREVIATIONS:
n = NO OF JACKING POINTS
1.1.6.2
CALCULATIONS:
BS(MAX) 6×π×Fc×D8×t2×n2×b
= MT/cm2 = 6×π×399.63×10-
3×1158×62×102×27.5 MT/cm2=0.00109 MT/cm2
1.1.6.3
CONCLUSION:
1.1.7
1.1.7.1
20/28
SHORT MVA, 33/11
CIRCUIT FORCE CALCULATION
KV, Dyn11
MEANING OF ABREVIATIONS:
w= WIDTH OF KEYBLOCK
b= LENGTH OF KEYBLOCK
n = NO OF BLOCK/CIRCLE
1.1.7.2
CALCULATIONS:
continued………………………….
20/28
SHORT MVA, 33/11
CIRCUIT FORCE CALCULATION
KV, Dyn11
1.1.7.3
CONCLUSION:
The result of compressive stress on windings for winding hv and lv are listed below:
1.1.8
1.1.8.1
MEANING OF ABREVIATIONS:
J = CURRENT DENSITY
1.1.8.2
CALCULATIONS:
WCR =1.05×E×m×Iph/cond2t×Dm×J2+4500×As×t3×JIph/cond
WCR(LV)
=1.05×1.13×106×12×72.920.27×67.6×249.62+4500×614.4×0.273×249.672.9kg
cm2
= 252.868×103kgcm2
WCR(HV
=1.05×1.13×106×2×78.920.22×91.2×3072+4500×768×0.223×30778.9kgcm2
=7.818 ×103+143×103kgcm2
20/28
SHORT MVA, 33/11
CIRCUIT FORCE CALCULATION
KV, Dyn11
=151×103kgcm2
the total compressive force of the inner and outer spacers must be less
than these critical resistance to collapse
1.1.8.3
CONCLUSION:
The result of compressive stress on windings for winding hv and lv are listed below:
1.1.9
HOOP STRESS:
1.1.9.1
20/28
SHORT MVA, 33/11
CIRCUIT FORCE CALCULATION
KV, Dyn11
MEANING OF ABREVIATIONS:
2
K(CU) = 0.03 × K x √22.55 = 0.03
1.1.9.2
CALCULATIONS:
1.1.9.2
CONCLUSION:
1.1.10
20/28
SHORT MVA, 33/11
CIRCUIT FORCE CALCULATION
KV, Dyn11
1.1.10.1
MEANING OF ABREVIATIONS:
1.1.10.1
CALCULATIONS:
1.1.10.2
CONCLUSION:
The result required no of vertical support for winding hv and lv are listed below:
HV 40 24 NOT OK
LV 15 16 OK
ANNEXTURE-A:
20/28
SHORT MVA, 33/11
CIRCUIT FORCE CALCULATION
KV, Dyn11
15 mm.
HV
TAP
746
HV M
LV
1490 2115 T = 2x746+623
=H HV
TAP746
d1
=118
d2
=212
X1 = 15mm ; d1x1=11815=7.86