Capacity,
Metal Deck
Puddle welds
AISC I3.2c steel deck shall be anchored to all supporting members at a spacing not to exceed 18 (can be from combination of shear studs and puddle welds)
Button-punching deck
http://www.vercodeck.com/index.php?option=com_content&view=article&id=267&Itemid=875
Shear Connectors
Typically 3/4 or 7/8 diameter (3/4 required with metal deck) Height ~ 2 8
Spacing (inches)
May add reinforcement across girders AISC C-I3.2 where longitudinal cracking detrimental to serviceability is likely to occur, slab should be reinforced transverse to the supporting steel section ...
Ar 0.002 Ac
Composite Floor System Design Techniques, 2013 NASCC Will Jacobs, Sam Easterling media.aisc.org/NASCC2013/N14a.mp4
Ideally rigid, no slip Reality stud can deform, concrete crushes, get some slip
Eq. (I8-1)
No metal deck?
Rg 1.0 Rp 0.75
(Easterling, 2007)
wr
Hs
Hs =length of stud after welding
hr
Hs hr + 1-1/2
Hs 4ds AISC I3.2c and I8.2
(Easterling, 2007)
(Easterling, 2007)
(Easterling, 2007)
wr 1.5 hr
; 1.0 if
wr 1.5 hr
Rp = 0.75
emid-ht = distance from edge of stud shank to steel deck web, measured at mid-height of the deck rib, and in the load bearing direction (i.e. direction of max moment for simply supported beam
emid ht 2 in
Rp= 0.75
emid ht 2 in
Rp= 0.6
AISC [16.1-98]
(Easterling, 2007)
(Easterling, 2007)
Composite Floor System Design Techniques, 2013 NASCC Will Jacobs, Sam Easterling media.aisc.org/NASCC2013/N14a.mp4
Limits
wr 2
2 3
1-1/2
Hs
wr 2
When nominal
hr 1-1/2
(AISC I3.2c)
Deck rib permitted to be split longitudinally and separated to form a concrete haunch
AISC I8.2d
Limits, contd.
2 ds (recommended) 4 ds
6 ds (in general)
4 ds
(for ribs perpendicular to beam)
8 ts
and 36
(in any direction)
5 minimum flange width for 2 rows of studs (for stud) 8 minimum flange width for 3 rows of studs (for stud)
AISC I8.1
Limits, contd.
ds 2.5tf
Unless stud placed over web
Limits, contd.
1/2 reqd, ~1 typ.
AISC I8.2d Lateral cover of 1 for shear connectors, except in ribs of formed steel decks
Calculation of fMn
AISC I3.2c Concrete below top of deck (in ribs) shall be neglected for section properties and calculation of Ac (strength, etc.)
Ribs perpendicular to axis of beam
Calculation of fMn
AISC I3.2c Concrete below top of deck (in ribs) is permitted be included for section properties (Ix)
and SHALL be included in calculation of Ac (strength)
on girder filler beam detail Recommend using filler beam spacing as unbraced length at construction stage
Depends
Composite Floor System Design Techniques, 2013 NASCC Will Jacobs, Sam Easterling media.aisc.org/NASCC2013/N14a.mp4