Reactive Power and Harmonic Filter - ABB

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 49

Power Systems HVDC / Dipti Khare

Reactive Power Compensation and Harmonic Filters for HVDC Classic


ABB Group Slide 1 09MR0163

CONTENTS

Reactive Power Requirement Harmonic Generation Harmonic Control


AC Filters DC Filters

Reactive Power Requirement

Reactive Power Requirement


HVDC

converters absorb reactive power, approximately 50% to 60% of their active power.
Harmonic

filters are installed on the AC side for filtering the AC current and for generation of reactive power.
The

reactive power absorption of a converter increases with the transmitted active power. Also the need for filtering of harmonics is increased.
The

need for reactive power grows slowly at low power, and more pronounced at high power, whereas the filter needs behave in the opposite fashion.
The

reactive power compensation scheme has to take care of the unbalances for the AC system requirement, by switching of filters
Q 0,5

Classic

0,13

filter

converter

1,0

Id

Purpose of the Reactive Power Control

The purpose of the Reactive Power Control (RPC) is to control the properties in the AC network that are connected to the converter station. The RPC will also make sure that the required filters are connected to prevent excessive harmonics that may enter into the AC system. These tasks are performed by switching of the filter banks.

Reactive Power Control


The

reactive power balance of each side of the HVDC transmission will normally be performed by reactive power controller (RPC).
Each

RPC is located in the pole control level and operates independently from the RPC in the other end of the HVDC transmission.
Switching

of filter banks or sub-banks is ordered by the RPC or by protections.


Switching

priority restrictions are determined by limits in the reactive power compensation study for the different control modes.

Selection of AC filter configurations due to reactive power requirements

The a.c. filters, PLC-filters and shunt capacitor banks generate reactive power to compensate the reactive power consumption by the converter The consumption of reactive power varies linearly with the active power, but the generation can only be changed in steps by switching in or out of filter banks. Therefore there will be a net interchange of reactive power with the network Maximum size of the filter bank may also be influenced by the permitted voltage step size at the switching of a bank

Reactive power for typical AC filter switching sequence

0.8 0.6 0.4

3 2 1: qexchng 2: qdc 3: qf 4: qac(limit) 1 4

q (=Q/PdN)

0.2 0 -0.2 -0.4 -0.6 -0.8 0.00 0.20 0.40 0.60 0.80 1.00

1.20

p (pu)

Main components of a converter station


Converter station Transmission Converter line or cable station
Smoothing reactor Converter

AC bus

DC filter

Shunt capacitors or other reactive equipment

AC filters Telecommunication Control system

~~

Harmonic Generation

Characteristic Harmonic currents on the AC side of a converter

Idealized converter

The supply (AC) voltage is exactly symmetrical The direct current is perfectly constant without ripple (Infinite smoothing reactor). The firing angles of each phase are perfectly equal The commutation impedances are equal in the three phases

Characteristic Harmonic currents on the AC side of a converter


i1 i1 + i2 Y D

i2

i1

T/4

T/2 3T/4

Phase current
i2

i1 +

i2

[%]

In I1

10 5 5 7 11 13 17 19 2 3 25

In i 2

[%] 5 11 13 23 25

Neglecting

the commutating reacta pulses

i1 +

n Rectangular

Harmonic generation Characteristic Harmonic currents on AC side of a converter


Y-Y 6-pulse: i1 = Y-? 6-pulse: i2 =
2 3 1 1 1 I d (cos t cos5t + cos7t cos11t + L) 5 7 11 2 3 1 1 1 I d (cost + cos5t cos 7t cos11t + L) 5 7 11
4 3 1 1 1 I d (cost cos11t + cos13t cos 23t + L) 11 13 23

12-pulse:

i1 + i2 =

Id: d.c. current The fundamental current The n:th harmonic

2 6 I1 = Id

In =

I1 n

n = 11, 13, 23, 25L

ABB Group Slide 13 09MP0163

Characteristic AC-side harmonics


n

= 12k ? 1
11 23 35 47

k = 1, 2, 3, ...
13 25 37

49 In = Kn * I 1/n
In

= harmonic current

Kn=

reduction factor due to overlap


I1

= fundamental AC current

Characteristic converter ac harmonic currents


Converter ac harmonic currents as a function of direct current (Id nom = 1500 A)
200 180 160 140
11

120 Amps
13

100
23

80 60 40 20 0

35

Direct current (A)

Characteristic Harmonic currents on the AC side of a converter

The inductive reactance of converter transformers gives a gradual transfer of current from one phase to another and so rounds the steps of the current waveforms The characteristic harmonics will decrease with increasing commutation reactance

Current Pulses with Overlap

Imperfections of the converter

The odd 6-pulse harmonics that are supposed to cancel perfectly in a 12-pulse converter, may not do so because of some small difference in the reactance or in turn ratio between the wye-wye and wye-delta connected transformers There is always some difference in the transformer reactance of each phase due to manufacturing tolerances The phase voltages are not exactly symmetrical, for example contain a small negative sequence component There may be a spread in the firing angles for the different valves due to imperfections in the control system

Non-characteristic harmonics

Imperfections
AC system Negative sequence th th 5 and 7 distortion Transformer reactance Difference between Y/Y and Y/D Difference between phases Firing asymmetry

AC-side harmonics
3 th th (5 , 7 )
rd

DC-side harmonics
2 th 6
nd

5 ,7 odd All

th

th

6 even All

th

Converter ac harmonic currents as a function of direct current (Id nom = 1500 A) - non-characteristic harmonics
25

20
3 5

15
Amps

9 15

10

0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 Direct current (A)

Impact of Non-characteristic harmonics on a.c. side

The magnitude of non-characteristic harmonics is small comparing to the characteristic harmonics Most of them have a minor influence on the total harmonic distortion and filter design However,if the short circuit impedance of the AC network is high, it could result in high distortion of the lower order non-characteristic harmonics(orders 2-7) on a.c. bus voltage due to parallel resonance between the network and filter banks

Characteristic DC side harmonics 12-pulse n=12k k=1, 2, 3, ...


12 24 36 48 etc U d (n ) 1 = C 2 + D 2 2CD cos( 2 + u ) U dio 2
C= cos((n + 1) u / 2) n +1

D=

cos(( n 1) u / 2) n 1

The characteristic harmonic voltage across a converter as a function of overlap angle u at firing angle of 15 deg.

The characteristic harmonic voltage across a converter as a function of overlap angle u at firing angle of 15 deg.

As the overlap increases from a very low value at minimum current to a value in the range 15 25 o at nominal current, it can be seen for the 12th harmonic that the harmonic generation is high at low load operation, then decreases to a minimum before rising again to a value eventually greater than that at low-load operation For higher order harmonics, the maximum generation does not occur at full load. There are several local maxima, progressively increasing in peak magnitude, within the feasible range of overlap angle

Harmonic Control

Why do we need filters?


To compensate the reactive power consumption of the converter (classic)

Q 0,5

Classic

0,13

filter

converter unbalance

1,0

Id

To clean up the harmonics that are generated from the converter. These may otherwise cause

Increased losses / overload of system equipment Telephone disturbances Source of misbehavior of control equipment

ABB Group Slide 26 09MP0163

AC Filter capacitors

Performance requirements

The basic requirement for the design of a.c. filter is a set of interference disturbance criteria valid for the voltage of converter a.c. bus or in special cases for the currents in the outgoing a.c. lines It is difficult to specify limits on disturbing current (requiring very precise knowledge about the impedance of the a.c. network at all harmonics of interest) even though it would seem justified to specify limits on the disturbing currents in the outgoing a.c. lines The requirements related to the a.c. bus voltage are commonly used disturbance criteria:

Individual harmonic voltage distortion Dn Total harmonic voltage distortion THD Telephone interference factor TIF (B.T.S. - EEI) Telephone harmonic form factor THFF (CCITT) (never used with TIF simultaneously)

Requirement specification

Voltage distortion

Specified limits on Dn are in the range of 0.5% to 1.5% (most typically 1%) Specified limits on THD are in the range of 1% to 4%

Telephone interference

Specified limits on TIF are typically between 30 and 50 Required limit of THFF is typically 1%

Equivalent circuit for AC filter calculations

Converter harmonic current generation

AC filters C1 L1

AC network impedance

Network Impedance

Network harmonic impedance is of critical importance to the design of the AC filters The a.c. network harmonic impedance varies with varying network conditions. It is customary to present limit curves (impedance envelope diagrams) for the network impedance in an R-X plane; make filter design manageable and easier Network harmonic impedance sector diagram Network harmonic impedance circle diagram

Sector limits for the AC network impedance (CIGR WG 14.30)


X
Zmax
2

Zmin =
Zmin
max min

UL Smax s.c.
2

Zmax =
UL

UL Smin s.c.

= line to line AC network voltage

Smax s.c. Smin s.c. n

= a.c.network maximum short-circuit capacity = a.c.network minimum short-circuit capacity

=0- 80 el for n < 5 = 75 el for 5 n<11 = 70 el for 11 n 50

= harmonic number

Circle limits for the AC network impedance


X

max Rmin min

Rad ius

AC filter types

Single-tuned filter High-pass filter Double-tuned filter C-type filter

Single-tuned bandpass filter


C 1

4 1 10 Impedance (ohms)

L 1

Q 1 C1 = ( 1 ) 2 2 2 f1U n

3 1 10 100 10 1

R 1

L1 =

1 ( 2 f1n ) 2 C 1

R1 = 2f1n L1 / q

10

20

30

Harmonic number

Very low impedance in resonance frequency Efficient filtering in a narrow frequency band Single-tuned filter normally used for the largest harmonics, 11th and 13th

Quality Factor

The Quality factor is a measurement of the sharpness of a filter Q-value normally lie in the range between 40 and 90 for tuned filter branchs High Q-value filter is sensitive with the frequency 0L variation (detuning)

q=

High-pass filter, HP24


4 1 10 Impedance (ohms) 3 1 10

C 1

L 1

R 1

Q 1 C1 = ( 1 ) 2 f1U 2 n2 1 L1 = ( 2 f1n ) 2 C1

100

R1 = 2f1n L1 q
10 0 20 40 60

Harmonic number

Broadband filter to take care of all harmonics from the 23rd and upwards, tuned to near the 24th harmonics Q-value of the filter branch normally lie within the range of 2-10 This type filter can be designed with high Q-values for 11th and 13th with lower fundamental losses, but the parallel connected resistor is more expensive

Double-tuned filter, 11/13


C 1

3 1 10 Impedance (ohms)

L 1

100

C 2

L 2

R 2

10

10

15

Harmonic number

Commonly used in modern HVDC station At high system voltage the larger main capacitor is easier to optimize to a lower cost/kvar lower reactive power generation in the filter branch to fullfil the requirement under lower power transmission Each switched filter attenuates two harmonics to reduce filter branch types and facilitate filter redundancy

Double-tuned high pass filter


3 1 10 Impedance (ohms)

C1 L1 C2 L2 R1 R2

100

10

20

40 Harmonic number

60

Tuned to 12th and 24th with relatively low resistive impedance for higher order harmonics; The efficiency of filtering at characteristic harmonics is not high,but it does cover the whole spectrum of interest with only one branch Tuned to 24th and 36th with a lower resistive impedance for higher frequencies for stringent requirement on TIF or THFF

C-type filter
Impedance (ohms)

C1 C2 R L

1 ) 2 Q n C1 = 2f1U 2 (1 1 1 ) 2 2 na nb 1 L = ( 2 f1na ) 2 C1 1 C2 = ( 2f1nb ) 2 L (1

1 . 10

1 . 10

100

R=

L q C1

5 10 15 Harmonic number

20

Low-order high-pass filter for 3rd,5th,7th harmonic filtering The lower L-C is series resonant at the fundamental frequency and so bypassed the resistor to greatly reduce the filter losses

DC harmonic filter capacitor

Cancellation of harmonic currents between poles

Harmonic current - pole 1

Harmonic current - pole 2

In a balanced bipolar operation, the harmonic currents in the two pole conductors will partially cancel lower level of disturbing current of bipolar operation than of monopolar ground return operation

Typical DC filter arrangement


Ldc Pole

Bus

C 1

C 1

L 1

L 1

C 2

L 2

C 2

L 2

Neutral Cnb

Bus

n n n

The large smoothing reactor plays a major role in mitigating harmonic current flow DC filter tuned to characteristic harmonics connected on the line side of the smoothing reactor, between pole and neutral bus Neutral bus capacitor providing a return pass for the harmonic current through stray capacitances in the converter transformers to ground

DC filters
The filter types used on the d.c. side are essentially the same as those used on the a.c. side Double-tuned 12/24 filter Triple-tuned 12/24/36 filter Hybrid passive plus active filter

Double-tuned 12/24 filter

Pole bus
C 1

5 1 10 Impedance (ohms) 4 1 10 3 1 10 100 10 1

L 1

C 2

L 2

R 2

Neutral bus

0.1

10

20

30

Harmonic number

Triple-tuned filter
Pole Bus

1 .10
C1

R1 F1 L1

Impedance (ohms)

1 .10

100

10
C2 L2 F2 R2

10

20 30 Harmonic order

40

50

F3

L3

C3

Maximum use of high-voltage capacitor unit size Tuned to 3 harmonics for stringent Ieq requirement

Neutral Bus

Modeling of DC side for harmonic calculation,bipolar


Ldc L3p PT

C6p 2L3p

DC

Filter

DC

Filter

PT:

Pole Line Transmission

C6p L3p

ETL: Electrode Line Transmission, ETZ: Electrode Line Transmission

Cnb

ETL

ETZ

DC

Filter

Re

DC

Filter

3GG Jingzhou station


AC-filters

Harmonics and Filter in Line Commutated Converter (HVDC Classical)

DC-filters

ABB Group Slide 48 09MP0163

www.abb.com/hvdc

You might also like