Confidential and Proprietary AB-7118

PARAMATRIX4
Pump/Chiller Controller
Parameter Description







Notice

This document contains proprietary information of Azbil Corporation. Information contained herein is
to be used solely for the purpose submitted, and no part of this document or its contents shall be
reproduced, published or disclosed to a third party without the express permission of Azbil
Corporation.
While this information is presented in good faith and believed to be accurate, Azbil Corporation
disclaims the implied warranties of merchantability and fitness for purpose and makes no express
warranties except as may be stated in its written agreement with and for its customer.
In no event is Azbil Corporation liable to anyone for any direct, special or consequential damages.
The information and specifications in this document are subject to change without notice.

PARAMATRIX, PARACONDUCTOR are registered trademark of Azbil Corporation.
2012 Azbil Corporation All Rights Reserved.
Safety Precautions
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
3
Safety precautions are aimed at protecting users or any other person from injury or loss of property, by
instructing the safe and correct use of the product. Please observe them strictly. In this manual, the
safety precautions are described in the following forms. Be sure to understand the context of the
precautions clearly before going on to the main text.

Restrictions on use
This product is targeted for general air conditioning. Do not use this product in situations where human
life may be at risk from air conditioning applications. For applications such as in clean rooms or other
spaces where reliability or control accuracy are critical, please contact your Azbil Corporation sales
representatives. Azbil Corporation bears no responsibility for any benefit, or lack of benefit, derived
from the operation by the customer.



Safety Precautions
Introduction
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
4
This manual describes the panel parameter of PARAMATRIX 4 (hereafter PMX-4) model WY5130 series
pump controller and chiller controller.
This manual is intended for engineering and service personnel.


Related documents
AB-7118 PARAMATRIX 4 Pump/Chiller Controller Parameter Description (this manual)

Following manuals other than this manual may be required for engineering work.
Please refer to them as required.

AB-7115 PARAMATRIX 4 Pump/Chiller Controller Engineering Manual


Notations
The following notations are used in this manual.

Notation Description

Things you should take special notice of.

Supplementary explanation for your convenience.

The section or the name of the manual you may refer to.
[ ]
Buttons or menu items that can be selected on screens and dialog boxes.
< >
Represents the keys of the keyboard.
>
Result of operation in a procedure.


Introduction
Contents
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
5

Safety Precautions........................................................................................................ 3

Introduction................................................................................................................... 4
Related documents............................................................................................................................. 4
Notations............................................................................................................................................. 4


Contents ....................................................................................................................... 5


Chapter 1 Overview...................................................................................................... 7
1. How to Use This Manual ............................................................................................................. 8
2. Before Parameter Setting (Preset by OI or Data Setter) ............................................................. 9
2.1 Pump controller .................................................................................................................... 9
2.2 Chiller controller.................................................................................................................. 16


Chapter 2 Engineering Work Associated with Operation Change............................... 25
1. Group Command Usage Change.............................................................................................. 26
1.1 How to change the setting.................................................................................................. 26
1.2 Operation example............................................................................................................. 28
2. Night Mode, Cooling Mode Operation Change ......................................................................... 29
2.1 Without upper communication equipment, operated by OI ................................................ 29
2.2 With upper communication equipment, operated by OI ..................................................... 30
3. Sequence Control Method Change (Flow/Energy/Supply Water Temp.) - only Chiller Controller
................................................................................................................................................... 31
3.1 How to change the method to control by energy, flow ....................................................... 31
3.2 How to change the method to control by temperature....................................................... 32
3.3 Notes .................................................................................................................................. 32
4. Upper Communication Implementation Changeover ................................................................ 33
4.1 How to change the settings................................................................................................ 33


Chapter 3 Parameter Description ............................................................................... 35
1. Panel 1 - Pressure Control Interlock ......................................................................................... 36
2. Panel 2 - Supply Water Pressure Control (Without Bypass Valve Control/Chiller) <Item001>. 37
3. Panel 2 - Supply Water Pressure Control
(With Bypass Valve Control/Chiller) <Item002> ........................................................................ 38
4. Panel 2 - Supply Water Pressure Control
(Without Proportional Bypass Valve Control/Pump) <Item003> ............................................... 39
5. Panel 2 - Supply Water Pressure Control
(With Proportional Bypass Valve Control/Pump) <Item004>..................................................... 40
6. Panel 2 - Supply Water Pressure Control
(Inverter All Units + ONOFF Bypass Valve/Pump) <Item005>.................................................. 41
7. Panel 2 - Supply Water Pressure Control
(Inverter 1 Unit + Proportional Bypass Valve/Pump) <Item006>............................................... 45
8. Panel 4 - Operation Management ............................................................................................. 48
Contents
Contents
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
6
9. Panel 6 - Start Load................................................................................................................... 49
10. Panel 7 - Sequence Control Load Preprocess
(Single-pump/Dual-pump Chiller 1 System) <Item001>............................................................ 50
11. Panel 7 - Sequence Control Load Preprocess (Dual-pump Chiller 4 System) <Item002>....... 51
12. Panel 8 - Sequence Control Load Preprocess (Flow 1 System) <Item001> ............................ 52
13. Panel 8 - Sequence Control Load (Energy 1 System) <Item002>............................................ 53
14. Panel 8 - Sequence Control Load (Energy 4 System) <Item003>............................................ 54
15. Panel 8 - Sequence Control Load (Flow 4 System) <Item004>................................................ 55
16. Panel 9 - Energy Monitoring (Chiller Flow 1 System) <Item001> ............................................. 56
17. Panel 9 - Energy Monitoring (Chiller Energy 1 System) <Item002> ......................................... 57
18. Panel 9 - Energy Monitoring (Chiller Energy 4 System) <Item003> ......................................... 58
19. Panel 9 - Energy Monitoring (Chiller Flow 4 System) <Item004> ............................................. 59
20. Panel 9 - Energy Monitoring (Pump Flow 1 System) <Item005>.............................................. 60
21. Panel 9 - Energy Monitoring (Pump Flow 4 System) <Item006>.............................................. 61
22. Panel 10 - Units Adjustment (Temperature) <Item001>............................................................ 62
23. Panel 10 - Units Adjustment (Pressure) <Item002>.................................................................. 63
24. Panel 14 - Power Demand Process (No.1 - No.8) .................................................................... 64
25. Panel 16 - Thermal Source Startup Timer Reset....................................................................... 65
26. Panel 18 - Power Failure Process (No.1 - No.8) ....................................................................... 66
27. Panel 20 - Sequence Control (Thermal Source) <Item001>..................................................... 67
28. Panel 20 - Sequence Control (Pump) <Item002>..................................................................... 84
29. Panel 22 - Commander Changeover (No.1 - 8) ...................................................................... 101
30. Panel 23 - Failure Auto Reset Output...................................................................................... 102
31. Panel 24 - ON/OFF Equipment (No.1 - 8) ............................................................................... 103
32. Panel 28 - Power Restoration Process (No.1 - 8) ................................................................... 104
33. Panel 29 - ON/OFF Decision................................................................................................... 105
34. Panel 30 - Caution Output ....................................................................................................... 106
35. Panel 1 to 33 - Free Panel....................................................................................................... 107




Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
7

Chapter 1

Overview



Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
8
This manual is written in the format shown below. The detail description of each item follows.







<<General>>
This panel controls the bypass valve of single-pump system.
Affected Instrumentation Code
WY5130Q1**1**1W
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
2 FIL T1 sec 0
Pressure filter delay time
When pressure changes so rapidly that the control is not
stable, adjust this parameter. Normally set it 0 (no delay).

GP
3 PID PB kPa 200
Bypass valve control proportional band
Take care the unit.


No. Item Name Descriptions
Q Panel No. Panel No.
, Panel Name Panel name
Panel Overview Describes the general operational information of the panel.
{ Instrumentation Code Instrumentation code of the PMX-4 including the panel.
Severity
Severity to check parameter of the panel.
: Parameter must be checked
: May be required to check
: Must be checked when the function is used
No mark : Not required to check
( Classification
Shows parameter classification.
Meter Classification GP, GPX, LPX
Execution Order Shows execution order of the module.
( Module Shows the module ID.
No.
Shows consecutive number of the parameter GPX and LPX. Parameter GP does
not have it.
j Input Symbol Shows global input ID of the module.
j Unit Shows unit of the parameter value.
( Default Value The default parameter of the factory preset.
( Changed Value Fill in the value when it is changed at site.
(
Parameter Name and
Descriptions
Describes the parameter name, usage, setting method etc.
When you set the parameter, please check the item with the mark on the Severity column.
The parameter with No mark on the Severity column is not required to check, so don't change it.



1. How to Use This Manual


{
( ( j j ( (
(
Q ,
3. Panel 2 - Supply Water Pressure Control
(With Bypass Valve Control/Chiller) <Item002>
Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
9
There are items to be set for PMX-4 other than the parameters in the Panel. These parameters are
shown below with their set point. Before setting the panel parameter, firstly define the parameters listed
below.
If the OI is not used at the site, please set it using PC-MMI.

2.1 Pump controller

1) Pump Information

Pump Information
Operation Sequence (Sequential) Group Setting
No. Name
Capacity
Setting
Cooling
Daytime
Cooling
Nighttime
Heating
Daytime
Heating
Nighttime
Cooling Heating
Remarks
1 Pump No.1 m
3
/h
2 Pump No.2 m
3
/h
3 Pump No.3 m
3
/h
4 Pump No.4 m
3
/h
5 Pump No.5 m
3
/h
6 Pump No.6 m
3
/h
7 Pump No.7 m
3
/h
8 Pump No.8 m
3
/h
Set the Group Setting
only when program
method is specified.
If PC-MMI is used to set, set the operation sequence (sequential) and the group setting according to
the GPX and LPX of "28. Panel 20 - Sequence Control (Pump) <Item002>" respectively.

2) Level Setting (Program Method)

Level Setting (Program Method)
Cooling Daytime Cooling Nighttime Heating Daytime Heating Nighttime
Level
Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6
1
2
3
4
5
6
7
8
If PC-MMI is used to set, set it according to the GPX and LPX of "28. Panel 20 - Sequence Control
(Pump) <Item002>". (Gr1-4 is set by GPX, Gr5-1 is set by LPX.)


Important
In the program method, all the unused levels must be set as "0-0-0-0-0-0".
In the program method, operation sequence of the equipment in a same group is rotated.


2. Before Parameter Setting (Preset by OI or Data Setter)
Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
10
3) Operation sequence setting when PARACON optional software
"Thermal Source Operating Sequence Changeover Function" is
used.
If "Thermal Source Operation Sequence Changeover Function" of PARACONDUCTOR is not
implemented, the following settings are not required.

Changeover Conditions
Select Seasonal Changeover Program
No. (0 - 16)
Set 0 when it is not used.
Schedule No. (0 - 150) Set 0 when it is not used.
Interlock Point No. (Point ID) Set 0 when it is not used.

Changeover Setting
Fill the operation sequence pattern No. (1 to 8) in the following table.
Season Mode
Interlock Point Schedule No.
Cooling Heating Fan Cooling/Heating
OFF
ON OFF
AUTO
OFF
ON ON
AUTO
When the Select Seasonal Changeover Program is not used, set the operation sequence pattern as
"Heating". .
When the Schedule is not used, set the operation sequence pattern as "Schedule OFF". .
When the Interlock point is not used, set the operation sequence pattern as "Interlock Point OFF". .

Operation sequence pattern setting
When PMX Sequential/Rotation method is used

Operation
Sequence
Pattern No.
Cooling/Heating

Pump
No.1
Pump
No.2
Pump
No.3
Pump
No.4
Pump
No.5
Pump
No.6
Pump
No.7
Pump
No.8
1 Cooling/Heating
2 Cooling/Heating
3 Cooling/Heating
4 Cooling/Heating
5 Cooling/Heating
6 Cooling/Heating
7 Cooling/Heating
8 Cooling/Heating
9 (Manual
only)
Cooling/Heating
10 (Manual
only)
Cooling/Heating
"Cooling/Heating" means that either Cooling or Heating of PMX should be selected and assigned to
the operation sequence pattern by PARACON.
Operation sequence pattern No.9 and 10 are Manual operation mode only.
Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
11
When PMX program method is used
Operation sequence pattern setting
Fill the operation sequence for each level in the following table.

.
Operation Sequence Pattern
1
Operation Sequence Pattern
2
Operation Sequence Pattern
3
Operation Sequence Pattern
4
Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating
Level
Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6
1
2
3
4
5
6
7
8
9
10
11
12


.
Operation Sequence Pattern
5
Operation Sequence Pattern
6
Operation Sequence Pattern
7
Operation Sequence Pattern
8
Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating
Level
Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6
1
2
3
4
5
6
7
8
9
10
11
12


.
Operation Sequence Pattern
9
(Manual only)
Operation Sequence Pattern
10
(Manual only)
Cooling/Heating Cooling/Heating
Level
Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6
1
2
3
Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
12
4
5
6
7
8
9
10
11
12



Important
All the unused levels must be set as "0-0-0-0-0-0".


Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
13
4) Waiting effect time, Restart prevent time (pump controller)

<Set point (OI screen)>: Main Menu - Thermal Source Control - Sequence Control parameter
No. Name Restart Prevent Time Minimum Stop Time
Thermal Source Startup
Time
Remain run time
1 Pump No.1 minute minute minute minute
2 Pump No.2 minute minute minute minute
3 Pump No.3 minute minute minute minute
4 Pump No.4 minute minute minute minute
5 Pump No.5 minute minute minute minute
6 Pump No.6 minute minute minute minute
7 Pump No.7 minute minute minute minute
8 Pump No.8 minute minute minute minute
If PC-MMI is used to set, set it according to the LPX of "28. Panel 20 - Sequence Control (Pump)
<Item002>".

Description and recommended value of the setting item are as follows:

Recommended
Value
Setup Items Description
Pump
Restart Prevent Time
The minimum interval time that should be secured from turning ON the
Thermal Source to the next turning ON.
0 minute
Minimum Stop Time
The minimum interval time that should be secured from turning OFF the
Thermal Source to the next turning ON.
0 minute
Thermal Source Startup
Time
The waiting time that the Thermal Source shows its capability from turning
ON.
5 minute
Remain run time
The dilution operation time to stop the pump after the Thermal Source has
been stopped.
0 minute

Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
14
5) Setting items by OI or Data Setter (pump controller)

Setting items by OI or Data Setter (pump controller)
Severity Name
Set Point (OI
screen)
Changed
Value
Remarks
Operation Sequence Method 1BS40th record
Set the Operation Sequence Method
0: Sequential, 1: Rotation, 2: Program

Cooling Daytime Max.
Number of Operating Units

Cooling Nighttime Max.
Number of Operating Units

Heating Daytime Max.
Number of Operating Units

Heating Nighttime Max.
Number of Operating Units
Max. Number of
Operating Units
setting screen
Set the maximum number of Thermal Source
that is allowed to operate by the Units
Control.
If PC-MMI is used to set, set it according to
the LP of "28. Panel 20 - Sequence Control
(Pump) <Item002>"
Daytime Start Time minute
Nighttime Start Time
Start load setting
screen
minute
Set the period of time to control with the start
load.
If PC-MMI is used to set, set it according to
the GP of "9. Panel 6 - Start Load".
Discharge pressure setting Point kPa Set with the actual value when it is used.
System 1 Flow Meter Range -
System 2 Flow Meter Range -
System 3 Flow Meter Range -
System 4 Flow Meter Range
Linearization Table
-
Set the range using BESS/PC-MMI/Data
Setter.
System 1 Totalized flow RTIO
System 2 Totalized flow RTIO
System 3 Totalized flow RTIO
System 4 Totalized flow RTIO
Point Parameter
Set it using the point parameter of
BESS/PC-MMI/Data Setter.




Important
When the symbol or the decimal position of flow point is changed, the Totalize IO Ratio
(RTIO) of Totalized Flow must be recalculated.

Unit of Totalized Flow
RTIO =
Unit of Flow x Minute
x 10
(DA-DT)


DA: Decimal position of Flow point
DT: Decimal position of Totalized flow point

Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
15
6) Start load (pump controller)

<Setting point (OI screen)>: Main Menu Thermal Source Control Start Load Setting
Weekday Holiday Special day 1 Special day 2
Daytime m
3
/h m
3
/h m
3
/h m
3
/h
Cooling
Nighttime m
3
/h m
3
/h m
3
/h m
3
/h
Daytime m
3
/h m
3
/h m
3
/h m
3
/h
Heating
Nighttime m
3
/h m
3
/h m
3
/h m
3
/h
The start load is weekday's 4 patterns when the Calendar function is no used, so fill in at the weekday
column.
If PC-MMI is used to set, set it according to the GP of "9. Panel 6 - Start Load".

< Reference >
Pressure: kPa (1 kgf/cm = 98 kPa)
Energy: J (1 kcal/h = 4.186 KJ/h Chilled water)
(1 kcal/h = 4.123 KJ/h Hot water)
(1 USRT = 3024 kcal/h = 12.66 MJ/h)


Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
16
2.2 Chiller controller

1) Thermal Source equipment information

Thermal Source equipment information (Cooling) Common parameter with PARACON
Operation Sequence (Sequential)
No. Name
Capacity
Setting
Cooling Daytime Cooling Nighttime
Group Setting Remarks
1
No.1 Thermal
Source equipment
m
3
/hGJ/h
2
No.2 Thermal
Source equipment
m
3
/hGJ/h
3
No.3 Thermal
Source equipment
m
3
/hGJ/h
4
No.4 Thermal
Source equipment
m
3
/hGJ/h
5
No.5 Thermal
Source equipment
m
3
/hGJ/h
6
No.6 Thermal
Source equipment
m
3
/hGJ/h
7
No.7 Thermal
Source equipment
m
3
/hGJ/h
8
No.8 Thermal
Source equipment
m
3
/hGJ/h
Set the Group Setting
only when program
method is specified.

Thermal Source equipment information (Heating)
Operation Sequence (Sequential)
No. Name
Capacity
Setting
Heating Daytime Heating Nighttime
Group Setting Remarks
1
No.1 Thermal
Source equipment
m
3
/hGJ/h
2
No.2 Thermal
Source equipment
m
3
/hGJ/h
3
No.3 Thermal
Source equipment
m
3
/hGJ/h
4
No.4 Thermal
Source equipment
m
3
/hGJ/h
5
No.5 Thermal
Source equipment
m
3
/hGJ/h
6
No.6 Thermal
Source equipment
m
3
/hGJ/h
7
No.7 Thermal
Source equipment
m
3
/hGJ/h
8
No.8 Thermal
Source equipment
m
3
/hGJ/h
Set the Group Setting
only when program
method is specified.
If PC-MMI is used to set, set the operation sequence (sequential) and the group setting according to
the GPX and LPX of "27. Panel 20 - Sequence Control (Thermal Source) <Item001>" respectively.
Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
17
2) Level Setting (Program Method)

Level Setting (Program Method)
Level Level Level Level
Level
Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6
1
2
3
4
5
6
7
8
9
10
11
12
If PC-MMI is used to set, set it according to the GPX and LPX of "27. Panel 20 - Sequence Control
(Thermal Source) <Item001>". (Gr1-4 is set by GPX, Gr5-1 is set by LPX.)


Important
In the program method, all the unused levels must be set as "0-0-0-0-0-0".
In the program method, operation sequence of the equipment in a same group is rotated.


Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
18
3) Operation sequence setting when PARACON optional software
"Thermal Source Operating Sequence Changeover Function" is
used.
If "Thermal source operation sequence changeover function" of PARACONDUCTOR is not
implemented, the following settings are not required.

Changeover Conditions
Select Seasonal Changeover Program
No. (0 - 16)
Set 0 when it is not used.
Schedule No. (0 - 150) Set 0 when it is not used.
Interlock Point No. (Point ID) Set 0 when it is not used.

Changeover Setting
Fill the operation sequence pattern No. (1 to 8) in the following table.
Season Mode
Interlock Point Schedule.
Cooling Heating Fan Cooling/Heating
OFF
ON OFF
AUTO
OFF
ON ON
AUTO
When the Select Seasonal Changeover Program is not used, set the operation sequence pattern as
"Heating".
When the Schedule is not used, set the operation sequence pattern as "Schedule OFF". .
When the Interlock point is not used, set the operation sequence pattern as "Interlock Point OFF". .

Operation sequence pattern setting
When PMX Sequential/Rotation method is used
"Cooling/Heating" means that either Cooling or Heating of PMX should be selected and assigned to
the operation sequence pattern by PARACON.
Operation Sequence Pattern No.9 and 10 are Manual operation mode only.
Operation
Sequence
Pattern
No.
Cooling/Heating
Thermal
Source
equipment
No.1
Thermal
Source
equipment
No.2
Thermal
Source
equipment
No.3
Thermal
Source
equipment
No.4
Thermal
Source
equipment
No.5
Thermal
Source
equipment
No.6
Thermal
Source
equipment
No.7
Thermal
Source
equipment
No.8
1 Cooling/Heating
2 Cooling/Heating
3 Cooling/Heating
4 Cooling/Heating
5 Cooling/Heating
6 Cooling/Heating
7 Cooling/Heating
8 Cooling/Heating
9 (Manual
only)
Cooling/Heating
10
(Manual
only)
Cooling/Heating
Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
19
When PMX program method is used
Operation sequence pattern setting
Fill the operation sequence for each level in the following table.

.
Operation Sequence Pattern
1
Operation Sequence Pattern
2
Operation Sequence Pattern
3
Operation Sequence Pattern
4
Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating
Level
Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6
1
2
3
4
5
6
7
8
9
10
11
12


Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
20

.
Operation Sequence Pattern
5
Operation Sequence Pattern
6
Operation Sequence Pattern
7
Operation Sequence Pattern
8
Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating
Level
Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6
1
2
3
4
5
6
7
8
9
10
11
12

.
Operation Sequence Pattern
9
(Manual Only)
Operation Sequence Pattern
10
(Manual Only)
Cooling/Heating Cooling/Heating
Level
Gr1 Gr2 Gr3 Gr4 Gr5 Gr6 Gr1 Gr2 Gr3 Gr4 Gr5 Gr6
1
2
3
4
5
6
7
8
9
10
11
12



Important
In the program method, all the unused levels must be set as "0-0-0-0-0-0".


Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
21
4) Waiting effect time, Restart prevent time (pump controller)

< Set Point (OI screen) > Main Menu - Thermal Source Control - Sequence Control Parameter
No. Name Restart Prevent Time Minimum Stop Time
Thermal Source
Startup Time
Remain run time
1
Thermal Source
equipment No. 1
minute minute minute minute
2
Thermal Source
equipment No. 2
minute minute minute minute
3
Thermal Source
equipment No. 3
minute minute minute minute
4
Thermal Source
equipment No. 4
minute minute minute minute
5
Thermal Source
equipment No. 5
minute minute minute minute
6
Thermal Source
equipment No. 6
minute minute minute minute
7
Thermal Source
equipment No. 7
minute minute minute minute
8
Thermal Source
equipment No. 8
minute minute minute minute
If PC-MMI is used to set, set it according to the LPX of "27. Panel 20 - Sequence Control (Thermal
Source) <Item001>".

Description and recommended value of the setting item are as follows:

Recommended Value
Setup Items Description
Heat Pump
Chiller
Turbo Chiller
Chilled/Hot
Water
Generator
Heat
Exchanger
Restart Prevent
Time
The minimum interval time that should
be secured from turning ON the
Thermal Source to the next turning
ON.
30 minutes 30 minutes 30 minutes 0 minute
Minimum Stop Time
The minimum interval time that should
be secured from turning OFF the
Thermal Source to the next turning
ON.
30 minutes 20 minutes 20 minutes 0 minute
Thermal Source
Startup Time
The waiting time that the Thermal
Source shows its capability from
turning ON.
5 minutes 10 minutes 30 minutes 5 minutes
Remain run time
The dilution operation time to stop the
pump after the Thermal Source has
been stopped.
5 minutes 10 minutes 30 minutes 0 minute

Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
22
5) Setting items by OI or Data Setter (Chiller controller)

Setting items by OI or Data Setter (Chiller controller)
Severity Name Set Point (OI screen)
Changed
Value
Remarks

Operation Sequence Method
1BS40th record
Set the Operation Sequence Method
0: Sequential, 1: Rotation,
2: Program

Cooling Daytime Max. Number
of Operating Units

Cooling Nighttime Max. Number
of Operating Units

Heating Daytime Max. Number
of Operating Units

Heating Nighttime Max. Number
of Operating Units
Max. Number of
Operating Units
setting screen
Set the maximum number of Thermal Source
that is allowed to operate by the Units
Control.
If PC-MMI is used to set, set it according to
the LP of "27. Panel 20 - Sequence Control
(Thermal Source) <Item001>".

Daytime Start Time
minute

Nighttime Start Time
Start Load setting
screen
minute
Set the period of time to control with the start
load.
If PC-MMI is used to set, set it according to
the GP of "9. Panel 6 - Start Load".

Pressure (Differential) Setting
kPa Set with the actual value when it is used.

Supply Water Temperature
Setting (Cooling)
C

Supply Water Temperature
Setting (Heating)
Point
C
This value is used as criteria of
increase/decrease adjustment, so basically it
should be set as same as the temperature of
the Thermal Source outlet.

System 1 Flow Meter Range
-

System 2 Flow Meter Range
-

System 3 Flow Meter Range
-

System 4 Flow Meter Range
Linearization Table
-
Set the range using BESS/PC-MMI/Data
Setter.

System 1 Totalized Flow RTIO

System 2 Totalized Flow RTIO

System 3 Totalized Flow RTIO

System 4 Totalized Flow RTIO

System 1 Totalized Energy
RTIO

System 2 Totalized Energy
RTIO

System 3 Totalized Energy
RTIO

System 4 Totalized Energy
RTIO

Total Totalized Flow RTIO

Total Totalized Energy RTIO
Point Parameter
Set the range using BESS/PC-MMI/Data
Setter.

Important
When the symbol or the decimal position of flow point is changed, the Totalize IO Ratio
(RTIO) of Totalized Flow must be recalculated.

Unit of Totalized Flow
RTIO =
Unit of Flow x Minute
x 10
(DA-DT)


DA: Decimal position of Flow point
DT: Decimal position of Totalized flow point
Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
23
6) Start load (Chiller controller)

<Setting point (OI screen)>: Main Menu Thermal Source Control Start Load Setting
Weekday Holiday Special day 1 Special day 2
Daytime m
3
/h, GJ/h m3/h, GJ/h m3/h, GJ/h m3/h, GJ/h
Cooling
Nighttime m3/h, GJ/h m3/h, GJ/h m3/h, GJ/h m3/h, GJ/h
Daytime m3/h, GJ/h m3/h, GJ/h m3/h, GJ/h m3/h, GJ/h
Heating
Nighttime m3/h, GJ/h m3/h, GJ/h m3/h, GJ/h m3/h, GJ/h
The start load is weekday's 4 patterns when the Calendar function is no used, so fill in at the weekday
column.
If PC-MMI is used to set, set it according to the GP of "9. Panel 6 - Start Load".

< Reference >
Pressure (Differential) Setting kPa (1 kgf/cm = 98 kPa)
Energy: J (1 kcal/h = 4.186 KJ/h Chilled water)
(1 kcal/h = 4.123 KJ/h Hot water)
(1 USRT = 3024 kcal/h = 12.66 MJ/h)



Chapter 1 Overview
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
24
This blank page is added for page layout purposes.

Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
25

Chapter 2

Engineering Work Associated with
Operation Change


Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
26
There are two Group command points; "Unit group command (PT1): COPl (Dummy)" and "Group
command DI (PT2): SOP (Actual)".
It is designed that the Group command is performed by "Unit group command (PT1)" or by "Group
command DI (PT2)" if the upper communication is implemented or it is not implemented respectively.
(Default setting)

1.1 How to change the setting

The Group command operation can be changed as follows:
Upper communication implemented (Yes) - Q => , or
Upper communication not implemented (No) - { => or (.
To change the operation mode, the shaded portions in the following table should be modified. For
example, in order to change Q =>,, Group command DI must be "DEL => ASN", OI operation must be
"Enable => Disable", Upper connection information must be "Yes => No".

Upper
communication
Operation pattern (Group command and
Freeze proofing)
Group
command
DO
(Dummy)
Group
command
DI (Actual)
Freeze
proofing
Yes/No
(GP)
OI operation
Enable/Disable
Upper
connection
information
(1BS41)
Basic
Q
Group command DO is used as
Group command. (Freeze proofing
is not performed.)
ASN DEL No Enable
Yes
,
Group command DI is used as
Group command. (Freeze proofing
is not performed.)
ASN
DEL =>
ASN
No
Enable =>
Disable
Yes => No Yes

Group command DO is used as
Group command. Group command
DI is used for Freeze proofing or so.
ASN
DEL =>
ASN
No =>
Yes
Enable
Yes
Basic
{
Group command DI is used as
Group command. (Freeze proofing
is not performed.)
ASN ASN No Disable

No

Group command DO is used as
Group command. (Freeze proofing
is not performed.)
ASN
ASN =>
DEL
No
Disable =>
Enable
No No
(
Group command DO is used as
Group command. Group command
DI is used for Freeze proofing or so.
ASN ASN
No =>
Yes
Disable =>
Enable
No
* If OI is not used at the site, it is not required to change.

1) Group command DI Assign/Delete
Points can be assigned or deleted by BESS (or Data Setter, PC-MMI).


Important
If Group command DO is deleted and the central control is disabled, the control panel will be
error, so the Group command DO must be "assigned" and the central control must be enabled.


2) Global parameter of SW (S of step 9), Freeze proofing Yes/No (GP)
panel 4 (Operation management)
Chang it as 0 (No) => 1 (Yes).

Refer to "Chapter 3, 8. panel 4 Operation management" for the detail.
1. Group Command Usage Change
Can be
Changed
Can be
Changed
Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
27
3) OI operation Enable/Disable
When Group command is operated by DI only, the Group command operation should be disabled by OI
screen touch panel.
When you operate the group command (dummy DO) using OI, you have to enable the group command
operation on the OI touch panel screen.
* If OI is not used at the site, it is not required to change.
If the Group command is used as Dummy DO (operation by OI or Central monitor) and as DI, the
Group command OI operation is enabled as shown on the table above (Upper communication: Yes),
( (Upper communication: No).
OI operation Enable/Disable can be altered by PC-MMI.

PC-MMI Operation

Select PMX-4 on the "Service tool" tab, and then change to the "Configuration tool" tab.

Upload the PMX-4 files.
Select "Upload", it completes when completed successfully message appears.

Select "Edit" on the "DDC Screen" of the function list, and then select "Display Data
Information" from the menu.

If the "Setting enabled" box of #1 and #2 block is checked, the setting is enabled. If it is
unchecked, the setting is disabled. Modify the settings as shown on the table above and click
[OK].
#1 block is set for the sequential/rotation mode, #2 block is set for the program mode.


Important
Don't change any items not described above.


















Change here
Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
28
If you want to restore Totalization, Setpoint to the original value, uncheck the "TDA copy" check
box on the function list and download it.

4) Upper connection information
The 41st record on the basic parameter should be changed.

Data Setter Operation
Access to the 41st record on (), and enter (: Yes, : No) then click .

PC-MMI Operation
Keep the service tool opened, select "Search - NC-BUS search" and search PMX-4.

Select PMX-4 and right-click the mouse and select "Basic data" or select "Basic data" from the
menu bar.

Enter (0: Yes, 1: No) on the 41st record from "FIX changeover".


1.2 Operation example

The upper communication equipment has been ordered, however you want to operated with the
group command DI until the central station is delivered. Change Q => , on the operation pattern
shown on the previous page.
Normally you operate group command from the central station, and you want to have group startup
by DI for freeze proofing control.
Set the operation pattern on the previous page as Upper communication: Yes Q =>, or Upper
communication: No { =>(.
Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
29
If a model No. that does not have upper communication is selected, point type of Night mode and
Cooling mode is SOP (Actual). If this point is changed to dummy DO point, you can operate from OI. If a
model No. that has upper communication is selected, point type of Night mode and Cooling mode is
CCPl (Dummy). If this point is changed to actual SOP point and assigned to IO, you can change it by the
contact.
The change procedure follows.


2.1 Without upper communication equipment, operated by OI

1) Point type change
Change the point type of Night mode and Cooling mode as SOP (Actual) => CCPl (Dummy) by BESS (or
Data Setter, PC-MMI), and then perform BESS error check.


Important
At this time, the uninterruptible power and the batch restoration disabled (NRCV) must be set.


2) OI operation Enable/Disable
If you operate the Night mode and Cooling mode by OI, it is required to enable the operation by OI
screen touch panel.
OI operation Enable/Disable is altered by PC-MMI.

PC-MMI Operation
Keep PMX-4 is selected on the "Service tool" tab, change to the "Configuration tool" tab.

Upload the PMX-4 files.
Select "Upload", it completes when completed successfully message appears.

Select "Edit" on the "DDC Screen" of the function list, and then select "Display Data
Information" from the menu. For the night mode, if the "Setting Enabled" check box of #2 of the
block #1 and block #2 are checked, the setting gets enabled. For the cooling mode, if the
"Setting Enabled" check box of #3 of block #1 and block #2 are checked, the setting gets
enabled. After modification, click [OK].
#1 block is set for the sequential/rotation mode, #2 block is set for the program mode.


Important
Don't change any items not described above.


2. Night Mode, Cooling Mode Operation Change
Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
30



















2.2 With upper communication equipment, operated by OI

1) Point type change
Assign the point type of Night mode and Cooling mode as CCPl (Dummy) => SOP (Actual) by BESS (or
Data Setter, PC-MMI), and then perform BESS error check.

2) OI operation Enable/Disable
If you operate the Night mode and Cooling mode by DI, it is required to disable the operation by OI
screen touch panel.
Group command OI operation Enable/Disable is altered by PC-MMI.
Uncheck the setting enabled check that corresponds to each point by OI operation Enable/Disable of "In
this chapter, 2.1 Without upper communication equipment, operated by OI"
* If OI is not used at the site, it is not required to change.

Night mode
Cooling mode
Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
31
The sequence control method is defined by the instrumentation code for PMX-4.
(Pump controller, single-pump system chiller controller: Sequential control by flow load, Dual-pump
system chiller controller: Sequential control by energy load)

The sequence control has three methods; "control by flow", "control by energy", and "control by
temperature", these control methods can be changed.


3.1 How to change the method to control by energy, flow

1) Sequence control method change
Change the 45th record on the basic parameter.

Data Setter Operation
Access to the 45th record on (), and enter (: Energy, : Flow) then click
.

PC-MMI Operation

Keep the service tool opened, select "Search - NC-BUS search" and search PMX-4.

Select PMX-4 and right-click the mouse and select "Basic data" or select "Basic data" from the
menu bar.

Select "FIX Changeover", enter (0: Energy, 1: Flow) on the 45th record.

2) Change the point parameter IPD
Change the point IPD of "**Start load", "Decrease criteria", "Operating unit total capacity", "Heating
capacity", and "Cooling capacity". Set [m
3
/h or L/min] for flow, [GJ/h or MJ/h] for energy.
After the change operation, perform BESS error check.

3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) - only Chiller Controller -
Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
32
3.2 How to change the method to control by temperature

The sequence control by temperature is attained by:
- Increase adjustment by the supply water temperature
- Decrease adjustment by the return water temperature. By applying dummy load (chiller total capacity)
to the sequence control load, units adjustment control by the supply/return water temperature is enabled.

1) Control parameter change
Change the MAX global parameter of panel 8 (sequence control load) as -1=>59999.
For the details, refer to "Chapter 3, 12. Panel 8 Sequence Control Load (Flow 1 system) <Item001>", "Chapter
3, 13. Panel 8 Sequence Control Load (Energy 1 system) <Item002>", "Chapter 3, 14. Panel 8 Sequence
Control Load (Energy 4 system) <Item003>", "Chapter 3, 15. Panel 8 Sequence Control Load (Flow 1 system)
<Item004>".


3.3 Notes

Sequence control method of the pump controller can't be changed.
Sequence control change to temperature can be done for the chiller controller (Single-pump/
Dual-pump).
However, performance of the sequence control by temperature will be degraded when number of unit
increases, so the number of unit should be limited to 2 or 3.If many units are installed, perform the
sequence control with a flow meter equipped.
The sequence control by energy for the single-pump system chiller controller is disabled at the site
where there is less temperature difference since it may cause insufficient flow.
The dual-pump system chiller controller can be changed to the sequence control by flow.
If it is decided to adopt the flow control before ordering, it is better to order the single-pump system
chiller controller because of less engineering works.

Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
33
Configuration of the upper communication is defined by the instrumentation code for PMX-4.
When a central station is installed at the site where the upper communication is not implemented, in
order to connect the PMX-4 to the system, the settings of PMX-4 can be changed from "Upper
communication not implemented" to "Implemented" at the site.
In this case, if number of Thermal Source (pump) or control details is to be changed, customization is
required because the changes can not be applied at the site. (Only the configuration of the upper
communication can be changed from "Not implemented" to "Implemented".)

4.1 How to change the settings

The configuration change from "Upper communication not implemented" to "Implemented" is as follows.

1) Change the Point type, UPS setting, and No batch restoration
allowed
Check the configuration of the upper communication is "Not implemented" or "Implemented" with the
instrumentation sheet, and change the Point type, UPS setting, and No batch restoration allowed.
The change point is "Night mode" and "Cooling mode".
After the change operation, assign IO, and then perform BESS error check

2) Change the group command settings
The usage of the group command differs according to the configuration of the upper communication "Not
implemented" or "Implemented".(Not implemented: use it as DI, Implemented: use it as Dummy COP)
As shown in this chapter, "1. Group Command Usage Change", change the operation pattern { => Q.
For the details, refer to "Chapter 2, 1. Group Command Usage Change".

Set the "Group command DI(PT2)" as ASN => DEL.
Set the Group command OI operation Enable/Disable as Disable => Enable.
Change the Upper connection information (1BS41) 1: No => 0: Yes.

3) Change power failure related parameter
To detect power failure status from the power feeding signal from the upper system, set the followings.
Power supply input setting
Change 1BS37: 17 (Power failure detection by point) => 0 (Power failure detection by power supply
signal from the upper controller)
Power restoration delay time
Change 1BS38: 15 => 0 (Upper communication is implemented)

"AB-7115 PARAMATRIX Pump/Chiller Controller Engineering Manual, Chapter 5, 9 Power Restoration Control.

4. Upper Communication Implementation Changeover
Chapter 2 Engineering Work Associated with Operation Change
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
34
This blank page is added for page layout purposes.




Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
35

Chapter 3

Parameter Description


Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
36

<<General>>
This panel generates control signals to start or end control of Inverter, Bypass valve etc.
Affected Instrumentation Code
All Pump Controllers

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions






























1. Panel 1 - Pressure Control Interlock
No parameter to be updated.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
37

<<General>>
This panel controls the bypass valve of single-pump system.
Affected Instrumentation Code
WY5130Q1**00**1W
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions






























2. Panel 2 - Supply Water Pressure Control
(Without Bypass Valve Control/Chiller) <Item001>
No parameter to be updated.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
38

<<General>>
This panel controls the bypass valve of single-pump system.
Affected Instrumentation Code
WY5130Q1**1**1W
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
2 FIL T1 sec 0
Pressure filter delay time
When pressure changes so rapidly that the control is not
stable, adjust this parameter. Normally set it 0 (no delay).
PB kPa 200
Bypass valve control proportional band
Take care the unit.
TI min 0.5
Bypass valve control Integral time
When the unit of value is second, set it with a decimal
number less than 1.
TD min 0 Bypass valve control differential time
UR % 0 Bypass valve control reset value

3 PID
GAP kPa 0
Bypass valve control deviation gap
Take care the unit.
4 LMT CR % 100.0
PID output limit value
Adjust this parameter to change the output
gradually. .Normally set it 100 (no change ration limit).
5 SEL V1 % 50
Bypass valve forced open position
When Thermal Source is increased, this parameter is used
to open the bypass valve forcibly in order to secure the flow
of the Thermal Source.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 0
Y2 % 100
Y3 % 0

6 SC4
Y4 % 0
Bypass valve output adjustment schedule
When flow characteristic of the bypass valve is not linear,
adjust this table.

<< E.g. >>
A valve whose characteristic is equal percentage is used.











GP
7 SEL V2 % 100
Position during off
Set the position of valve during Thermal Source is off.





3. Panel 2 - Supply Water Pressure Control
(With Bypass Valve Control/Chiller) <Item002>
100
300
10 100 X
Y
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
39

<< General >>
This panel controls the secondary pump's bypass valve in the dual-pump system.
Affected Instrumentation Code
WY5130P1**00*1W
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 FIL T1 sec 600
Flow filter delay time
When the pressure setting is corrected by the flow, apply a
filter because flow changes so rapidly that the pressure
setting is not stable.
X1 m
3
/h 0
X2 m
3
/h 1000
X3 m
3
/h 0
X4 m
3
/h 0
Y1 1.0
Y2 1.0
Y3 0

GP
2 SC4
Y4 0
Pressure setting adjustment schedule
Adjust this table in order to change the correction factor of
pressure setpoint.


























4. Panel 2 - Supply Water Pressure Control (Without
Proportional Bypass Valve Control/Pump) <Item003>
Flow
SC4
MUL
Pressure
Setting


Rated pressure setting
Point to set manually from
the central station. Point
type is PRA.


Pressure setting
The actual setpoint used
for pressure control. Point
type is AI dummy.
Rated pressure
setting
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
40

<< General >>
This panel controls the secondary pump's bypass valve in the dual-pump system.
Affected Instrumentation Code
WY5130P1**1**1W
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 FIL T1 sec 600
Flow filter delay time
When the pressure setting is corrected by the flow, apply a
filter because flow changes so rapidly that the pressure
setting is not stable.
X1 m
3
/h 0
X2 m
3
/h 1000
X3 m
3
/h 0
X4 m
3
/h 0
Y1 1.0
Y2 1.0
Y3 0

2 SC4
Y4 0
Pressure setting adjustment schedule
Adjust this table in order to change the correction factor of
pressure setpoint.













PB kPa 200 Proportional band (take care the unit)
TI min 0.5
Integral time (When the unit of value is second, set it with a
decimal number less than 1.)
TD min 0 Differential time
UR % 0 Reset value

4 PID
GAP kPa 0 Deviation gap
5 TMR OND sec 180
Bypass valve stabilization waiting time at start
A timer to switch the Normal PID output limit value and
Startup PID output limit value.
V1 100.0 Normal PID output limit value

6 SEL
V2 100.0 Startup PID output limit value
Limit is not applied for the default
value. There is no difference in
operation at normal and at startup.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 0
Y2 % 100
Y3 % 0

GP
8 SC4
Y4 % 0
Bypass valve output adjustment schedule
When flow characteristic of the bypass valve is not linear,
adjust this table.

<< E.g. >>
A valve whose characteristic is equal percentage is used.












5. Panel 2 - Supply Water Pressure Control
(With Proportional Bypass Valve Control/Pump) <Item004>
100
300
10 100 X
Y
Flow
SC4
MUL
Pressure
Setting


Rated pressure setting
Point to set manually from
the central station. Point
type is PRA.


Pressure setting
The actual setpoint used
for pressure control. Point
type is AI dummy.
Rated pressure
setting
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
41
(1/4)
<< General >>
This panel controls the secondary pump's bypass valve and rotational speed in the dual-pump
system.
Affected Instrumentation Code
WY5130P1**20*1W
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 FIL T1 sec 600
Flow filter delay time
When the pressure setting is corrected by the flow, apply a
filter because flow changes so rapidly that the pressure
setting is not stable.
X1 m
3
/h 0
X2 m
3
/h 1000
X3 m
3
/h 0
X4 m
3
/h 0
Y1 1.0
Y2 1.0
Y3 0

2 SC4
Y4 0
Pressure setting adjustment schedule
Adjust this table in order to change the correction factor of
pressure setpoint.












PB kPa 200 Proportional band (take care the unit)
TI min 0.5
Integral time (When the unit of value is second, set it with a
decimal number less than 1.)
TD min 0 Differential Time
UR % 0 Reset value

4 PID
GAP kPa 0 Deviation gap
5 TMR OND sec 180
Bypass valve stabilization waiting time at start
A timer to switch the Normal PID output limit value and
Startup PID output limit value.
V1 100.0 Normal PID output limit value

6 SEL
V2 100.0 Startup PID output limit value
Limit is not applied for the default
value.
R m
3
/h 24
ON/OFF bypass valve ON
flow

8 CMP
HYS m
3
/h 6
ON/OFF bypass valve ON
flow hysteresis
Take care the unit of flow.
Set the ON flow as 20% of the
pump's rated flow.
OND sec 60 Low flow decision ON delay

9 TMR
OFD sec 60 Low flow decision OFF delay
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP
12 SC4
Y4 % 0
Inverter output adjustment schedule (for Batch dummy output)
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 14 SC4
Y4 % 0
No.1 Inverter output adjustment schedule
Set the low limit of inverter to Y2.

6. Panel 2 - Supply Water Pressure Control
(Inverter All Units + ONOFF Bypass Valve/Pump) <Item005>
Flow
SC4
MUL
Pressure
Setting


Rated pressure setting
Point to set manually from
the central station. Point
type is PRA.


Pressure setting
The actual setpoint used
for pressure control. Point
type is AI dummy.
Rated pressure
setting
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
42
(2/4)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 15 SC4
Y4 % 0
No.1 Inverter output display adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 16 SC4
Y4 % 0
No.2 Inverter output adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 17 SC4
Y4 % 0
No.2 Inverter output display adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 18 SC4
Y4 % 0
No.3 Inverter output adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 19 SC4
Y4 % 0
No.3 Inverter output display adjustment schedule
Set the low limit of inverter output to Y2.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
43
(3/4)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 20 SC4
Y4 % 0
No.4 Inverter output adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 21 SC4
Y4 % 0
No.4 Inverter output display adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 22 SC4
Y4 % 0
No.5 Inverter output adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 23 SC4
Y4 % 0
No.5 Inverter output display adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 24 SC4
Y4 % 0
No.6 Inverter output adjustment schedule
Set the low limit of inverter output to Y2.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
44
(4/4)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 25 SC4
Y4 % 0
No.6 Inverter output display adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 26 SC4
Y4 % 0
No.7 Inverter output adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 27 SC4
Y4 % 0
No.7 Inverter output display adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 28 SC4
Y4 % 0
No.8 Inverter output adjustment schedule
Set the low limit of inverter output to Y2.
X1 % 0
X2 % 100
X3 % 0
X4 % 0
Y1 % 100
Y2 % 0
Y3 % 0

GP 29 SC4
Y4 % 0
No.8 Inverter output display adjustment schedule
Set the low limit of inverter output to Y2.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
45
(1/2)
<< General >>
This panel controls the secondary pump's bypass valve and rotational speed in the dual-pump
system.
Affected Instrumentation Code
WY5130P1**3**1W
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 FIL T1 sec 600
Flow filter delay time
When the pressure setting is corrected by the flow, apply a
filter because flow changes so rapidly that the pressure
setting is not stable.
X1 m
3
/h 0
X2 m
3
/h 1000
X3 m
3
/h 0
X4 m
3
/h 0
Y1 1.0
Y2 1.0
Y3 0

2 SC4
Y4 0
Pressure setting adjustment schedule
Adjust this table in order to change the correction factor of
pressure setpoint.












PB kPa 200 Proportional band (take care the unit)
TI min 0.5
Integral time (When the unit of value is second, set it with a
decimal number less than 1.)
TD min 0 Differential Time
UR % 0 Reset value

4 PID
GAP kPa 0 Deviation gap
5 TMR OND sec 180
Bypass valve stabilization waiting time at start
Set the waiting time to stabilize the pressure control by bypass
valve.
V1 % 100.0 Normal PID output limit value

6 SEL
V2 % 100.0 Startup PID output limit value
Limit is not applied for the default
value. There is no difference in
operation at normal and at startup.
X1 % 50

Pump 1 unit: Bypass valve/Inverter control operation
changeover point
Y1 % 0

Pump 1 unit: Bypass valve minimum position

9 SC2
Y2 % 100

Pump 1 unit: Bypass valve maximum position
X1 % 37.5

Pump 2 units or more: Bypass valve/Inverter control
operation changeover point
Y1 % 0

Pump 2 units or more: Bypass valve minimum
position

10 SC2
Y2 % 100

Pump 2 units or more: Bypass valve maximum
position
X2 % 50

Pump 1 unit: Bypass valve/Inverter control operation
changeover point
Y1 % 100

Pump 1 unit: Inverter maximum output

11 SC2
Y2 % 80

Pump 1 unit: Inverter minimum output
X2 % 37.5

Pump 2 units or more: Bypass valve/Inverter control
operation changeover point
Y1 % 100

Pump 2 units or more: Inverter maximum output

GP
12 SC2
Y2 % 85

Pump 2 units or more: Inverter minimum output
For the
details, refer
to the
operation
diagram on
the below
page.


7. Panel 2 - Supply Water Pressure Control (Inverter 1 Unit +
Proportional Bypass Valve/Pump) <Item006>
Flow
SC4
MUL
Pressure
Setting


Rated pressure setting
Point to set manually from
the central station. Point
type is PRA.


Pressure setting
The actual setpoint used
for pressure control. Point
type is AI dummy.
Rated pressure
setting
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
46
(2/2)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
X1 0
X2 100
X3 0
X4 0
Y1 % 0
Y2 % 100
Y3 % 0

GP 16 SC4
Y4 % 0
Bypass valve output adjustment schedule
When flow characteristic of the bypass valve is not linear,
adjust this table.
<< E.g. >>
A valve whose characteristic is equal percentage is used.











X1 0
X2 100
X3 0
X4 0
Y1 % 0
Y2 % 100
Y3 % 0

17 SC4
Y4 % 0
Inverter output adjustment schedule
X1 0
X2 100
X3 0
X4 0
Y1 0
Y2 100
Y3 0

18 SC4
Y4 0
Inverter output display adjustment schedule
R m
3
/h 24
Valve-closed operation
prevention: Minimum flow

21 CMP
HYS m
3
/h 6
Valve-closed operation
prevention: Minimum flow
hysteresis
Valve-closed operation prevention:
Minimum flow
Valve-closed operation prevention:
Minimum flow hysteresis
OND sec 60 Valve-closed operation prevention: Flow decision ON delay


22 TMR
OFD sec 60 Valve-closed operation prevention: Flow decision ON delay
V1 % 30
Valve-closed operation prevention at 1 unit operation: Bypass
valve open position
When pump is 1 unit and the flow is lower than 24 m/h, output
this open position.


24 SEL
V2 % 0
Valve-closed operation prevention at 2 units or more operation:
Bypass valve open position

100
300
10 100 X
Y
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
47
<< Bypass valve and Inverter control operation diagram >>

Bypass valve and Inverter control operation diagram is shown below.





















Pressure SP
PID
Output
Discharge
Pressure
50.0
80
Operation at pump 1
PID Output
Bypass Valve
Inverter
Operation at pump 2 or more
37.5
85

Bypass Valve
Inverter
Output
PID Output
Output
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
48

<< General >>
This panel generates the control signals according to Auto/Manual changeover or Power
supplying decision. Group command is input from the group command DO or DI, Power
Failure Restoration is input from the system or the target unit's power supply status, so this
panel generates the Power supplying/Group command signal that matches with them.
Affected Instrumentation Code
All machine types


Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
GP 9 SW S 0
Freeze proofing flag
0: No, 1: Yes
If Group command dummy DO is used and Group command
DO is used as freeze proofing, set the value as 1. .
When the freeze proofing is applied, there are other items to
be changed. For the details, refer to "Chapter 2, 1. Group
Command Usage Change".






























8. Panel 4 - Operation Management
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
49

<< General >>
This panel defines the start load used at startup timing and updates the start load point.
Affected Instrumentation Code
All machine types
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
T1 min 30 Daytime Start Runtime
After group startup, the period of time to
control with the start load.
Set the value on the Start Load setting
screen of OI.
When OI is not used, set the
parameter using PC-MMI.
T2 min 30 Nighttime Start Runtime
L11 0
Weekday Heating
Daytime Start Load
L12 0
Holiday Heating
Daytime Start Load
L13 0
Special 1 Heating
Daytime Start Load
L14 0
Special 2 Heating
Daytime Start Load
L21 0
Weekday Heating
Nighttime Start Load
L22 0
Holiday Heating
Nighttime Start Load
L23 0
Special 1 Heating
Nighttime Start Load
L24 0
Special 2 Heating
Nighttime Start Load
L31 0
Weekday Cooling
Daytime Start Load
L32 0
Holiday Cooling
Daytime Start Load
L33 0
Special 1 Cooling
Daytime Start Load
L34 0
Special 2 Cooling
Daytime Start Load
L41 0
Weekday Cooling
Nighttime Start Load
L42 0
Holiday Cooling
Nighttime Start Load
L43 0
Special 1 Cooling
Nighttime Start Load

GP 1 SLD
L44 0
Special 2 Cooling
Nighttime Start Load
Set the start value used at startup timing
on the Start Load setting screen of OI.

The start load that was set by OI will be
distributed to the parameters here
automatically, so it is not required to set
the start load on the Parameter setting
screen.

Also there is Start load point. The start
load set by OI will be distributed to the
point at the day change timing.
The start load used by the actual control
is given by the point, so it is required to
set the start load on both OI and point
when PMX-4 starts up initially.
When it is operated by Group
command DI, do not register Group
command DO on the calendar.
When OI is not used, set the
parameter using PC-MMI.













9. Panel 6 - Start Load
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
50

<< General >>
This panel sets the sequence control load after waiting effect time period as the actual load.


Affected Instrumentation Code
All pump controllers
WY5130Q1*****1W
WY5130Q2*2***1W
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions


































10. Panel 7 - Sequence Control Load Preprocess
(Single-pump/Dual-pump Chiller 1 System) <Item001>
No parameter to be updated.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
51

<< General >>
This panel prepares required operations before the sequence control load decision. Also, it
adds flow to perform the sequence control load by the flow.
Affected Instrumentation Code
WY5130Q2*6***1W

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
6 FIL T1 sec 0
System 1 Flow filter delay time

Use it when the sequence control is performed by flow.
Apply filter to change the flow gradually.
The default is not filtered value.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".
T1 time 10

7 MEN
T2 sec 30
Moving average process parameter
Use it when the sequence control is performed by flow.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".
8 FIL T1 sec 0
System 2 Flow filter delay time

Use it when the sequence control is performed by flow.
Apply filter to change the flow gradually.
The default is not filtered value.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".
T1 time 10

9 MEN
T2 sec 30
Moving average process parameter
Use it when the sequence control is performed by flow.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".
10 FIL T1 sec 0
System 3 Flow filter delay time

Use it when the sequence control is performed by flow.
Apply filter to change the flow gradually.
The default is not filtered value.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".
T1 time 10

11 MEN
T2 sec 30
Moving average process parameter
Use it when the sequence control is performed by flow.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".
12 FIL T1 sec 0
System 4 Flow filter delay time

Use it when the sequence control is performed by flow.
Apply filter to change the flow gradually.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".
T1 time 10

GP
13 MEN
T2 sec 30
Moving average process parameter
Use it when the sequence control is performed by flow.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".






11. Panel 7 - Sequence Control Load Preprocess
(Dual-pump Chiller 4 System) <Item002>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
52

<< General >>
This panel uses the flow as the sequence control load. During start operation/Overtime
transition, an adequate load is selected comparing the start load and the actual load set
separately.
Affected Instrumentation Code
WY5130P1*3***1W
WY5130Q1*3***1W
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 FIL T1 sec 0
Flow filter delay time
Apply filter to change the flow gradually. The default is not
filtered value.
T1 time 10

GP
2 MEN30
T2 sec 30
Moving average process parameter
T1: Quantity of data processed by moving average process
T2: Sampling cycle of the source data processed by moving
average process
Therefore the default setting is to calculate the moving average
using 10 data that is sampled every 30 seconds.
GP 3 MAX V2 -1
Sequential control change by temperature
To set the sequence control change by temperature, set 59999.
Pump controller should not be changed.
To change the sequence control method by temperature,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".



























12. Panel 8 - Sequence Control (Flow 1 System) <Item001>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
53

<< General >>
This panel calculates to use energy as load. Also the load can be changed to flow. During
start operation/Overtime transition, an adequate load is selected comparing the start load and
the actual load set separately.
Affected Instrumentation Code
WY5130Q2*2***1W


Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
V1 0.06 Conversion coefficient (L/min). Can't be changed.

2 SEL
V2 1 Conversion coefficient (m
3
/h). Can't be changed.
V1 1 Conversion coefficient (MJ/h). Can't be changed.

4 SEL
V2 0.001 Conversion coefficient (GJ/h). Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

6 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
8 FIL T1 sec 0
Energy filter delay time

Use it when the sequence control is performed by energy.
Apply filter to change the energy gradually.
The default is not filtered value.
T1 time 10
Moving average count
Use it when the sequence control is performed by energy.

9 MEN
T2 sec 30
Moving average cycle
Use it when the sequence control is performed by energy.
10 MAX V2 -1
Sequential control change by temperature (energy)
To set the sequence control by temperature, set 59999.
To change the sequence control method by temperature,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".
12 FIL T1 sec 0
Flow filter delay time
Use it when the sequence control is performed by flow.

To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".
Apply filter to change the flow gradually.
The default is not filtered value.
T1 time 10
Moving average count
Use it when the sequence control is performed by flow.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".

13 MEN
T2 sec 30
Moving average cycle
Use it when the sequence control is performed by flow.
To change the sequence control method from energy to flow,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".

GP
14 MAX V2 -1
Sequential control change by temperature (energy)
To set the sequence control by temperature, set 59999.
To change the sequence control method by temperature,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".







13. Panel 8 - Sequence Control Load (Energy 1 System)
<Item002>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
54

<< General >>
This panel calculates the load energy of 4 systems and sums up these load energy. The
summed up value is used as the sequence control load. Also the summed up value can be
considered as the sequence control load. During start operation/Overtime transition, an
adequate load is selected comparing the start load and the actual load set separately.
Affected Instrumentation Code
WY5130Q2*6***1W



Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
V1 0.06 Conversion coefficient (L/min). Can't be changed.

2 SEL
V2 1 Conversion coefficient (m
3
/h). Can't be changed.
V1 1 Conversion coefficient (MJ/h). Can't be changed.

4 SEL
V2 0.001 Conversion coefficient (GJ/h). Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

6 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

9 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

12 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

15 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
17 FIL T1 sec 0
System 1 Energy filter delay time*
Apply filter to change the energy gradually. The default is not
filtered value.
T1 time 10

18 MEN30
T2 sec 30
System 1 Moving average process parameter
T1: Quantity of data processed by moving average process
T2: Sampling cycle of the source data processed by moving
average process
Therefore the default setting is to calculate the moving average
using 10 data that is sampled every 30 seconds.
19 FIL T1 sec 0 System 2 Energy filter delay time (same as above*)
T1 time 10

20 MEN30
T2 sec 30
System 2 Moving average process parameter (same as above*)
21 FIL T1 sec 0 System 3 Energy filter delay time (same as above
*
)
T1 time 10

22 MEN30
T2 sec 30
System 3 Moving average process parameter (same as above
*
)
23 FIL T1 sec 0 System 4 Energy filter delay time (same as above
*
)
T1 time 10


24 MEN30
T2 sec 30
System 4 Moving average process parameter (same as above
*
)
27 MAX V2 -1
Sequential control change by temperature (energy)
To set the sequence control by temperature, set 59999.
To change the sequence control method by temperature,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".


* To change the sequence control method from energy to flow, change the parameter at Panel 7. Refer to "Panel 7 - Sequence
Control Load Preprocess (Dual-pump Chiller 4 System) <Item002>".
14. Panel 8 - Sequence Control Load (Energy 4 System)
<Item003>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
55

<< General >>
This panel is to use the summed up value of 4 systems as the sequence control load. During
start operation/Overtime transition, an adequate load is selected comparing the start load and
the actual load set separately.
Affected Instrumentation Code
WY5130P1*4***1W
WY5130Q1*4***1W

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 FIL T1 sec 0
Flow filter delay time
Apply filter to change the flow gradually. The default is not
filtered value.
T1 time 10

2 MEN30
T2 sec 30
Moving average process parameter
T1: Quantity of data processed by moving average process
T2: Sampling cycle of the source data processed by moving
average process
Therefore the default setting is to calculate the moving average
using 10 data that is sampled every 30 seconds.
3 FIL T1 sec 0
Flow filter delay time
Apply filter to change the flow gradually. The default is not
filtered value.
T1 time 10

4 MEN30
T2 sec 30
Moving average process parameter
T1: Quantity of data processed by moving average process
T2: Sampling cycle of the source data processed by moving
average process
Therefore the default setting is to calculate the moving average
using 10 data that is sampled every 30 seconds.
5 FIL T1 sec 0
Flow filter delay time
Apply filter to change the flow gradually. The default is not
filtered value.
T1 time 10

6 MEN30
T2 sec 30
Moving average process parameter
T1: Quantity of data processed by moving average process
T2: Sampling cycle of the source data processed by moving
average process
Therefore the default setting is to calculate the moving average
using 10 data that is sampled every 30 seconds.
7 FIL T1 sec 0
Flow filter delay time
Apply filter to change the flow gradually. The default is not
filtered value.
T1 time 10

8 MEN30
T2 sec 30
Moving average process parameter
T1: Quantity of data processed by moving average process
T2: Sampling cycle of the source data processed by moving
average process
Therefore the default setting is to calculate the moving average
using 10 data that is sampled every 30 seconds.

GP
10 MAX V2 -1
Sequential control change by temperature
To set the sequence control change by temperature, set 59999.
Pump controller should not be changed.
To change the sequence control method by temperature,
refer to "Chapter 2, 3. Sequence Control Method Change
(Flow/Energy/Supply Water Temp.) (only Chiller Controller)".






15. Panel 8 - Sequence Control Load (Flow 4 System)
<Item004>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
56

<< General >>
This panel is to calculate the energy for monitoring when the sequence control load (Panel 8)
is performed by flow.
Affected Instrumentation Code
WY5130Q1*3***1W

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
V1 0.06 Conversion coefficient (L/min). Can't be changed.

2 SEL
V2 1 Conversion coefficient (m
3
/h). Can't be changed.
V1 1 Conversion coefficient (MJ/h). Can't be changed.

4 SEL
V2 0.001 Conversion coefficient (GJ/h). Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

GP
6 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.






















16. Panel 9 - Energy Monitoring (Chiller Flow 1 System)
<Item001>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
57

<< General >>
This panel is to set the flow for monitoring when the sequence control load (Panel 8) is
performed by energy. Also this panel is to calculate the energy for monitoring when the
sequence control load (Panel 8) is performed by flow.
Affected Instrumentation Code
WY5130Q2*2***1W

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
V1 0.06 Conversion coefficient (L/min). Can't be changed.

2 SEL
V2 1.0 Conversion coefficient (m
3
/h). Can't be changed.
V1 1.0 Conversion coefficient (MJ/h). Can't be changed.

4 SEL
V2 0.001 Conversion coefficient (GJ/h). Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

GP
6 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.























17. Panel 9 - Energy Monitoring (Chiller Energy 1 System)
<Item002>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
58

<< General >>
This panel is to calculate the totalized flow of system 4 for monitoring when the sequence control
load (Panel 8) is performed by the totalized energy of system 4. Also this panel is to calculate the
totalized energy of each system and system 4 for monitoring when the sequence control load
(Panel 8) is performed by the totalized flow of system 4.
Affected Instrumentation Code
WY5130Q2*6***1W


Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
V1 0.06 Conversion coefficient (L/min). Can't be changed.

4 SEL
V2 1.0 Conversion coefficient (m
3
/h). Can't be changed.
V1 1.0 Conversion coefficient (MJ/h). Can't be changed.

6 SEL
V2 0.001 Conversion coefficient (GJ/h). Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

8 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

11 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

14 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

GP
17 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.

















18. Panel 9 - Energy Monitoring (Chiller Energy 4 System)
<Item003>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
59

<< General >>
This panel is to calculate the totalized energy of each system and system 4 for monitoring when
the sequence control load (Panel 8) is performed by the totalized flow of system 4.
Affected Instrumentation Code
WY5130Q1*4***1W

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
V1 0.06 Conversion coefficient (L/min). Can't be changed.

2 SEL
V2 1.0 Conversion coefficient (m
3
/h). Can't be changed.
V1 1.0 Conversion coefficient (MJ/h). Can't be changed.

4 SEL
V2 0.001 Conversion coefficient (GJ/h). Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

6 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

9 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

12 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

GP
15 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
















19. Panel 9 - Energy Monitoring (Chiller Flow 4 System)
<Item004>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
60

<< General >>
This panel is to calculate the energy for monitoring when the sequence control load (Panel 8) is
performed by flow.
Affected Instrumentation Code
WY5130P1*3***1W

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
V1 0.06 Conversion coefficient (L/min). Can't be changed.

2 SEL
V2 1.0 Conversion coefficient (m
3
/h). Can't be changed.
V1 1.0 Conversion coefficient (MJ/h). Can't be changed.

4 SEL
V2 0.001 Conversion coefficient (GJ/h). Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

GP
6 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.

















20. Panel 9 - Energy Monitoring (Pump Flow 1 System)
<Item005>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
61

<< General >>
This panel is to calculate the totalized energy of each system and system 4 for monitoring
when the sequence control load (Panel 8) is performed by the totalized flow of system 4.
Affected Instrumentation Code
WY5130P1*4***1W

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
V1 0.06 Conversion coefficient (L/min). Can't be changed.

2 SEL
V2 1.0 Conversion coefficient (m
3
/h). Can't be changed.
V1 1.0 Conversion coefficient (MJ/h). Can't be changed.

4 SEL
V2 0.001 Conversion coefficient (GJ/h). Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

6 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

9 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

12 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
PC 4.186 Cooling Energy Calculation Constant. Can't be changed.

GP
15 CAL
PH 4.123 Heating Energy Calculation Constant. Can't be changed.
















21. Panel 9 - Energy Monitoring (Pump Flow 4 System)
<Item006>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
62

<< General >>
This panel is to adjust the number of operating units that is defined by the load (flow or
energy) by referring supply water temperature or return water temperature.
Affected Instrumentation Code
All chiller controllers

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
3 ADD2 V2 C 1.5
Increase Capacity Adjustment Setting deviation (Cooling)
Increase capacity if following condition meets:
(Hi limit > Load > Lo limit) and
(Supply water temperature > Supply water temperature
setting + Increase capacity adjustment setting deviation)
When the Thermal Source is chiller, set a larger value.
4 CMP HYS C 0.5 Increase Capacity Adjustment Decision hysteresis (Cooling)
5 SUB V2 C 1.5
Increase Capacity Adjustment Setting deviation (Heating)
Increase capacity if following condition meets:
(Hi limit > Load > Lo limit) and
(Supply water temperature < Supply water temperature
setting - Increase capacity adjustment setting deviation)
When the Thermal Source is chiller, set a larger value.
6 CMP HYS C 0.5 Increase Capacity Adjustment Decision hysteresis (Heating)
9 TMR OND sec 300 Increase Capacity Adjustment Decision time
12 ADD2 V2 C 1.5
Forced increase capacity/Increase capacity relative deviation
(Cooling)
Increase capacity forcibly if following condition meets:
(Hi limit > Load > Lo limit) and
(Supply water temperature > Supply water temperature
setting + Increase capacity adjustment setting deviation +
Forced increase capacity/Increase capacity relative
deviation)
When the Thermal Source is chiller, set a larger value.
13 CMP HYS C 0.5 Forced increase capacity decision hysteresis (Cooling)
14 SUB V2 C 1.5
Forced increase capacity/Increase capacity relative deviation
(Heating)
Increase capacity forcibly if following condition meets:
(Hi limit > Load > Lo limit) and
(Supply water temperature < Supply water temperature
setting - Increase capacity adjustment setting deviation -
Forced increase capacity/Increase capacity relative
deviation)
When the Thermal Source is chiller, set a larger value.
15 CMP HYS C 0.5 Forced increase capacity decision hysteresis (Heating)
18 TMR OND sec 360 Forced increase capacity decision time
21 ADD2 V2 C 2.0
Decrease Capacity Request Setting deviation(Cooling)
Decrease capacity forcibly if following condition meets:
(Supply water temperature setting + Decrease capacity request
setting deviation) > Return water temperature
20 SEL V2 C 0.5 Decrease Capacity Request Decision hysteresis (Cooling)
24 SUB V2 C 2.0
Decrease Capacity Request Setting deviation (Heating)
Decrease capacity forcibly if following condition meets:
(Supply water temperature setting - Decrease capacity request
setting deviation) < Return water temperature
23 SEL V2 C 0.5 Decrease Capacity Request Decision hysteresis (Heating)
29 TMR OND sec 180 Decrease Capacity Request Decision time
39 TMR OFD sec 300 Decrease capacity interval
34 TMR OFD sec 600 Low load off minimum duration time
20 SEL V1 C 2.0 Low load decrease capacity hysteresis (Cooling)

GP
23 SEL V1 C 2.0 Low load decrease capacity hysteresis (Heating)

Important
The increase/decrease adjustment by temperature is based on the data of PMX-4 "Supply Water
Temperature Setting" point. Set the same data for "Supply Water Temperature Setting" point as the
outlet temperature of Thermal Source equipment.
22. Panel 10 - Units Adjustment (Temperature) <Item001>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
63

<< General >>
This panel is to adjust the number of operating units that is defined by the load (flow).
Affected Instrumentation Code
All pump controllers
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
3 SUB V2 kPa 59999
Forced increase capacity pressure setting deviation
Can't be changed
4 CMP HYS kPa 20
Forced increase capacity decision hysteresis
Can't be changed
6 TMR OND sec 300
Forced increase capacity decision time
Can't be changed
9 SUB V2 kPa 59999
Increase capacity adjustment pressure setting deviation
Can't be changed
10 CMP HYS kPa 20
Increase capacity adjustment decision hysteresis
Can't be changed
12 TMR OND sec 300
Increase capacity adjustment decision time
Can't be changed
14 ADD V2 kPa 59999
Decrease capacity request setting deviation
Can't be changed
15 CMP HYS kPa 20
Decrease capacity request decision hysteresis
Can't be changed
17 TMR OND sec 180
Decrease capacity request decision time
Can't be changed
20 TMR OFD sec 300
Decrease capacity interval time
Can't be changed

















23. Panel 10 - Units Adjustment (Pressure) <Item002>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
64

<< General >>
This panel is to control the Thermal Source so that it does not start up immediately when
returning from the power demand stop status.
Affected Instrumentation Code
All machine types

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
































24. Panel 14 - Power Demand Process (No.1 - No.8)
No parameter to be updated.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
65

<< General >>
This panel is to detect the thermal equipment starts up by monitoring the outlet temperature
and reset the timer that waits effect of Thermal Source equipment during startup.
Affected Instrumentation Code
All chiller controllers

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 ADD2 V2 C 1.0
Thermal Source startup detection deviation (Cooling)
Reset the waiting effect timer when the deviation between
the supply water temperature of each Thermal Source and
its target temperature gets within 1 C (default). The timer
will be reset when the supply water temperature of all the
Thermal Sources settles to the target temperature.
If each Thermal Source does not have the supply water
temperature sensor, set it as "- 59999".
2 SUB V2 C 1.0
Thermal Source startup detection deviation (Heating)
Reset the waiting effect timer when the deviation between
the supply water temperature of each Thermal Source and
its target temperature gets within 1 C (default). The timer
will be reset when the supply water temperature of all the
Thermal Sources settles to the target temperature.
If each Thermal Source does not have the supply water
temperature sensor, set it as "- 59999".
4 CMP HYS C 0.5 Outlet temperature compare hysteresis (Cooling)
5 CMP HYS C 0.5 Outlet temperature compare hysteresis (Heating)

GP
51 TMR OND sec 300
Thermal Source startup detection time
Reset the waiting effect timer when the deviation of the
supply water temperature gets within 1 C (default) for 300
seconds (default).


















25. Panel 16 - Thermal Source Startup Timer Reset
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
66

<< General >>
This panel is to control that the equipments don't restart simultaneously with the recovery
command after the commercial power is recovered.
Affected Instrumentation Code
All machine types

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

































26. Panel 18 - Power Failure Process (No.1 - No.8)
No parameter to be updated.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
67
(1/17)
<< General >>
This panel is main part of sequence control; it defines the number of operating units according
to the load, suspends ON/OFF decision until the Thermal Source starts up.
Affected Instrumentation Code
All chiller controllers

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
GP 5 SW V1 min 0
Forced Rotation time (0 - 2880)
Set the timing of the forced increase capacity when rotation
with forced increase capacity is selected.
Q Forced Rotation by the set time (PMX-III method)
Set the interval time (min) to activate the forced increase
capacity.
, Forced Rotation by the specified time
Set the time to activate the forced increase capacity.
To plan the forced Rotation at 23:30:
Set as 1410 (23 x 60 (min) + 30).
(0: Forced Rotation is disabled, at 1440:24 (0:00 AM), 1440
or more is regarded as 1440.)
Q and , can be changed by LP:12 (CRT).
MIN unit 1 Minimum number of operating units (0 - 12)
TON sec 30
Sequential start time (0 - 15300)
Interval of start command the to Thermal Sources that are
recovered from power failure simultaneously.
TOF sec 30
Sequential stop time (0 - 15300)
Interval of stop command to the Thermal Sources that are
ordered to stop simultaneously.
TWW sec 300
Water round time (0 - 15300)
Set the time in which water goes round in the pipe.
TIM min 0
Failure auto reset time (0 - 1440)
Send OFF command to the failed Thermal Source after
the preset time pass has passed and reset the alarm
automatically. This function can't be used for the Thermal
Sources that don't have the failure reset function by OFF
command. When it is set as "0", reset manually.
When point type is changed from CAPf to CAPl and then
the thermal source (pump) is recovered form failure status,
the thermal source may start automatically. To avoid the
automatic start, set this parameter.
TIC sec
Single
pump
=60,
Dual
pump =0

Increase notice time (0 - 15300)
The interval time between when the increase command is
issued and when the Thermal Source receives startup
command actually. For the single-pump system, within the
interval time, open the valve to secure the path in which
cold/hot water flows when Thermal Source is increased.
ABP GJ/H 59999
ON/OFF simultaneous process (59999 - 59999)
According to the difference of ON/OFF simultaneous
process, change the value. If ON priority process is
adopted, set a positive number (can be set as default). If
OFF priority process is adopted, set to "- 1". The ON/OFF
simultaneous process can be changed by this setting. "0" is
regarded as a positive number.
SWJ 0
Operating sequence adjustment method (0 - 1)
Set the operating sequence adjustment method when
returning from failed condition.
0: Sequence setting priority method, 1: Operating unit priority
method
SPR01 5 No.1 Thermal Source type (0 - 5)
SPR02 5 No.2 Thermal Source type (0 - 5)
SPR03 5 No.3 Thermal Source type (0 - 5)
SPR04 5 No.4 Thermal Source type (0 - 5)
SPR05 5 No.5 Thermal Source type (0 - 5)
SPR06 5 No.6 Thermal Source type (0 - 5)
SPR07 5 No.7 Thermal Source type (0 - 5)
SPR08 5 No.8 Thermal Source type (0 - 5)
SPR09 5 No.9 Thermal Source type (0 - 5)
SPR10 5 No.10 Thermal Source type (0 - 5)

GP 6 PXN
SPR11 5 No.11 Thermal Source type (0 - 5)
These parameters are not
used for control frequently.
0: Delete
1: Cooling
2: Heating
3: Cooling/Heating
4: Simultaneous
5: No display (pump etc.)
These are displayed on OI
operation sequence setting
screen.

27. Panel 20 - Sequence Control (Thermal Source) <Item001>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
68
(2/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
SPR12 5
No.12 Thermal Source type
(0 - 5)

FR01 0 No.1 Forced ON (0 - 1)
FR02 0 No.2 Forced ON (0 - 1)
FR03 0 No.3 Forced ON (0 - 1)
FR04 0 No.4 Forced ON (0 - 1)
FR05 0 No.5 Forced ON (0 - 1)
FR06 0 No.6 Forced ON (0 - 1)
FR07 0 No.7 Forced ON (0 - 1)
FR08 0 No.8 Forced ON (0 - 1)
FR09 0 No.9 Forced ON (0 - 1)
FR10 0 No.10 Forced ON (0 - 1)
FR11 0 No.11 Forced ON (0 - 1)

GP
FR12 0 No.12 Forced ON (0 - 1)
Can't be changed.

3 MHD 12
Heating/Daytime Maximum
Operating Units

4 MHN 12
Heating/Nighttime
Maximum Operating Units

5 MCD 12
Cooling/Daytime Maximum
Operating Units

6 MCN 12
Cooling/Nighttime
Maximum Operating Units
If OI is not used, set the parameter
using PC-MMI.
Set the maximum number of
thermal source operated by the
sequence control.
11 RT 0 Rotation ON method (0 - 1)
0: ON the longest OFF
equipment/OFF the longest
ON equipment.
(PMX-III method)
1: Rotation the equipment by the
totalized run time.
(ON the lowest totalized run
time equipment/OFF the
highest totalized run time
equipment)
12 CRT 1
Forced rotation ON method
(0 - 1)
0: Forced rotation by the preset
time.
(PMX-III method)
1: Forced rotation by the
specified time.

LP
6 PXN
13 NJP 1
Sequence control decrease
point calculation method (0
- 1)
0: Calculate the total rated
capacity of ON equipment.
(Stability precedence)
(PMX-III method)
1: Calculate by the rated
capacity of equipment 1 level
down (for program method,
the difference of the rated
capacity of the equipment
between 1 level down and 2
level done).
(Energy saving precedence)
The operation method of the
decrease limit and Low limit
ratio can be changed by this
parameter. High limit ratio is
always calculated by the total
of rated capacity of the ON
equipments. If "0" is selected,
the Differential and the Low
limit ratio can be set
separately. However if "1" is
selected, only the Differential
can be set, and make the Low
limit ratio = Differential.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
69
(3/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
15 DHD % 40.0
Heating daytime level
1-2 sequence control
differential (0 - 100.0)
16 DHD % 40.0
Heating daytime level
2-3 sequence control
differential (0 - 100.0)
17 DHD % 40.0
Heating daytime level
3-4 sequence control
differential (0 - 100.0)
18 DHD % 40.0
Heating daytime level
4-5 sequence control
differential (0 - 100.0)
19 DHD % 40.0
Heating daytime level
5-6 sequence control
differential (0 - 100.0)
20 DHD % 40.0
Heating daytime level
6-7 sequence control
differential (0 - 100.0)
It is an operation gap will be used at
the thermal source decrease capacity
decision.
< Recommended value>
Sequence control decease capacity
method 1: energy saving precedence
Pump 20
Heat pump chiller 40
Turbo chiller 40
Chilled/hot water
generator
40
Hear exchanger 40
In this case, the Low limit ratio =
Differential, so it is not required to
set the Low limit ratio. Only when
the operation sequence method is
program and sequence control
decrease limit method = 1, use
the parameter.
When sequential/rotation/
program method (sequence
control decrease limit method =
0), set LPX97 - 108.
21 DHD % 40.0
Heating daytime level
7-8 sequence control
differential (0 - 100.0)
22 DHD % 40.0
Heating daytime level
8-9 sequence control
differential (0 - 100.0)
23 DHD % 40.0
Heating daytime level
9-10 sequence control
differential (0 - 100.0)
24 DHD % 40.0
Heating daytime level
10-11 sequence control
differential (0 - 100.0)
25 DHD % 40.0
Heating daytime level
11-12 sequence control
differential (0 - 100.0)
It is an operation gap will be used at
the Thermal Source decision.
It can be used only when the program
method is selected and the sequence
control decrease limit operation
method = 1.
In this case, the Low limit ratio =
Differential, so it is not required to
set the Low limit ratio.
26 DHN % 40.0
Heating nighttime level
1-2 sequence control
differential (0 - 100.0)
27 DHN % 40.0
Heating nighttime level
2-3 sequence control
differential (0 - 100.0)
28 DHN % 40.0
Heating nighttime level
3-4 sequence control
differential (0 - 100.0)
29 DHN % 40.0
Heating nighttime level
4-5 sequence control
differential (0 - 100.0)
30 DHN % 40.0
Heating nighttime level
5-6 sequence control
differential (0 - 100.0)
31 DHN % 40.0
Heating nighttime level
6-7 sequence control
differential (0 - 100.0)
32 DHN % 40.0
Heating nighttime level
7-8 sequence control
differential (0 - 100.0)
33 DHN % 40.0
Heating nighttime level
8-9 sequence control
differential (0 - 100.0)
34 DHN % 40.0
Heating nighttime level
9-10 sequence control
differential (0 - 100.0)
35 DHN % 40.0
Heating nighttime level
10-11 sequence control
differential (0 - 100.0)

LP 6 PXN
36 DHN % 40.0
Heating nighttime level
11-12 sequence control
differential (0 - 100.0)
It is an operation gap will be used at
the thermal source decrease decision.
< Recommended value>
Sequence control decease capacity
method 1: energy saving precedence
Pump 20
Heat pump chiller 40
Turbo chiller 40
Chilled/hot water
generator
40
Hear exchanger 40
In this case, the Low limit ratio =
Differential, so it is not required to
set the Low limit ratio.
Only when the operation
sequence method is program and
sequence control decrease limit
method = 1, use the parameter.
When sequential/rotation/
program method (sequence
control decrease limit method =
0), set LPX97 - 108.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
70
(4/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
37 DCD % 40.0
Cooling daytime level 1-2
sequence control
differential (0 - 100.0)
38 DCD % 40.0
Cooling daytime level 2-3
sequence control
differential (0 - 100.0)
39 DCD % 40.0
Cooling daytime level 3-4
sequence control
differential (0 - 100.0)
40 DCD % 40.0
Cooling daytime level 4-5
sequence control
differential (0 - 100.0)
41 DCD % 40.0
Cooling daytime level 5-6
sequence control
differential (0 - 100.0)
42 DCD % 40.0
Cooling daytime level 6-7
sequence control
differential (0 - 100.0)
43 DCD % 40.0
Cooling daytime level 7-8
sequence control
differential (0 - 100.0)
44 DCD % 40.0
Cooling daytime level 8-9
sequence control
differential (0 - 100.0)
45 DCD % 40.0
Cooling daytime level 9-10
sequence control
differential (0 - 100.0)
46 DCD % 40.0
Cooling daytime level 10-11
sequence control
differential (0 - 100.0)
47 DCD % 40.0
Cooling daytime level 11-12
sequence control
differential (0 - 100.0)
It is an operation gap will be used at
the thermal source decrease
decision.
< Recommended value>
Sequence control decease capacity
method 1: energy saving
precedence
Pump 20
Heat pump chiller 40
Turbo chiller 40
Chilled/hot water
generator
40
Hear exchanger 40
In this case, the Low limit ratio
= Differential, so it is not
required to set the Low limit
ratio.
Only when the operation
sequence method is program
and sequence control
decrease limit method = 1, use
the parameter.
When sequential/rotation/
program method (sequence
control decrease limit method
= 0), set LPX97 - 108.
48 DCN % 40.0
Cooling nighttime level 1-2
sequence control
differential (0 - 100.0)
49 DCN % 40.0
Cooling nighttime level 2-3
sequence control
differential (0 - 100.0)
50 DCN % 40.0
Cooling nighttime level 3-4
sequence control
differential (0 - 100.0)
51 DCN % 40.0
Cooling nighttime level 4-5
sequence control
differential (0 - 100.0)
52 DCN % 40.0
Cooling nighttime level 5-6
sequence control
differential (0 - 100.0)
53 DCN % 40.0
Cooling nighttime level 6-7
sequence control
differential (0 - 100.0)
54 DCN % 40.0
Cooling nighttime level 7-8
sequence control
differential (0 - 100.0)
55 DCN % 40.0
Cooling nighttime level 8-9
sequence control
differential (0 - 100.0)
56 DCN % 40.0
Cooling nighttime level 9-10
sequence control
differential (0 - 100.0)
57 DCN % 40.0
Cooling nighttime level
10-11 sequence control
differential (0 - 100.0)

LP 6 PXN
58 DCN % 40.0
Cooling nighttime level
11-12 sequence control
differential (0 - 100.0)
It is an operation gap will be used at
the thermal source decrease
decision.
< Recommended value>
Sequence control decease capacity
method 1: energy saving
precedence
Pump 20
Heat pump chiller 40
Turbo chiller 40
Chilled/hot water
generator
40
Hear exchanger 40
In this case, the Low limit ratio
= Differential, so it is not
required to set the Low limit
ratio.
Only when the operation
sequence method is program
and sequence control
decrease limit method = 1, use
the parameter.
When sequential/rotation/
program method (sequence
control decrease limit method
= 0), set LPX97 - 108.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
71
(5/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 SHD 0
Heating daytime sequential
update step
When Sequential method with
base unit changeover is adopted,
change the value to any number
other than 0. While in the group
OFF mode, the ON sequence is
shifted for the number of
equipment specified here.
2 JHD 01 1
Heating daytime No.01
operation sequence
3 JHD 02 2
Heating daytime No.02
operation sequence
4 JHD 03 3
Heating daytime No.03
operation sequence
5 JHD 04 4
Heating daytime No.04
operation sequence
6 JHD 05 5
Heating daytime No.05
operation sequence
7 JHD 06 6
Heating daytime No.06
operation sequence
8 JHD 07 7
Heating daytime No.07
operation sequence
9 JHD 08 8
Heating daytime No.08
operation sequence
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
sequential or rotation.
14 L11 1
Heating daytime GR1 level 1
number of operating units
15 L12 2
Heating daytime GR1 level 2
number of operating units
16 L13 3
Heating daytime GR1 level 3
number of operating units
17 L14 4
Heating daytime GR1 level 4
number of operating units
18 L21 5
Heating daytime GR1 level 5
number of operating units
19 L22 6
Heating daytime GR1 level 6
number of operating units
20 L23 7
Heating daytime GR1 level 7
number of operating units
21 L24 8
Heating daytime GR1 level 8
number of operating units
22 L31 9
Heating daytime GR1 level 9
number of operating units
23 L32 10
Heating daytime GR1 level 10
number of operating units
24 L33 11
Heating daytime GR1 level 11
number of operating units
25 L34 12
Heating daytime GR1 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
program mode.
26 L11 0
Heating daytime GR2 level 1
number of operating units
27 L12 0
Heating daytime GR2 level 2
number of operating units
28 L13 0
Heating daytime GR2 level 3
number of operating units
29 L14 0
Heating daytime GR2 level 4
number of operating units
30 L21 0
Heating daytime GR2 level 5
number of operating units

31 L22 0
Heating daytime GR2 level 6
number of operating units

32 L23 0
Heating daytime GR2 level 7
number of operating units

33 L24 0
Heating daytime GR2 level 8
number of operating units

34 L31 0
Heating daytime GR2 level 9
number of operating units

35 L32 0
Heating daytime GR2 level 10
number of operating units

36 L33 0
Heating daytime GR2 level 11
number of operating units

GPX 6 PXN
37 L34 0
Heating daytime GR2 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
program mode.
Gr5 and Gr6 are set by LPX.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
72
(6/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
38 L11 0
Heating daytime GR3 level 1
number of operating units
39 L12 0
Heating daytime GR3 level 2
number of operating units
40 L13 0
Heating daytime GR3 level 3
number of operating units
41 L14 0
Heating daytime GR3 level 4
number of operating units
42 L21 0
Heating daytime GR3 level 5
number of operating units
43 L22 0
Heating daytime GR3 level 6
number of operating units
44 L23 0
Heating daytime GR3 level 7
number of operating units
45 L24 0
Heating daytime GR3 level 8
number of operating units
46 L31 0
Heating daytime GR3 level 9
number of operating units
47 L32 0
Heating daytime GR3 level 10
number of operating units
48 L33 0
Heating daytime GR3 level 11
number of operating units
49 L34 0
Heating daytime GR3 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
program mode.
Gr5 and Gr6 are set by LPX.
50 L11 0
Heating daytime GR4 level 1
number of operating units
51 L12 0
Heating daytime GR4 level 2
number of operating units
52 L13 0
Heating daytime GR4 level 3
number of operating units
53 L14 0
Heating daytime GR4 level 4
number of operating units
54 L21 0
Heating daytime GR4 level 5
number of operating units
55 L22 0
Heating daytime GR4 level 6
number of operating units
56 L23 0
Heating daytime GR4 level 7
number of operating units
57 L24 0
Heating daytime GR4 level 8
number of operating units
58 L31 0
Heating daytime GR4 level 9
number of operating units
59 L32 0
Heating daytime GR4 level 10
number of operating units
60 L33 0
Heating daytime GR4 level 11
number of operating units
61 L34 0
Heating daytime GR4 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
program mode.
Gr5 and Gr6 are set by LPX.
62 SHN 0 62
Heating nighttime sequential
update step
When Sequential method with
base unit changeover is adopted,
set value other than 0. At group
stopped timing, the number of
units set here will be slid its
operation sequence.
63 JHN 01 1 63
Heating nighttime No.01
operation sequence

64 JHN 02 2 64
Heating nighttime No.02
operation sequence

65 JHN 03 3 65
Heating nighttime No.03
operation sequence

66 JHN 04 4 66
Heating nighttime No.04
operation sequence

67 JHN 05 5 67
Heating nighttime No.05
operation sequence

68 JHN 06 6 68
Heating nighttime No.06
operation sequence

69 JHN 07 7 69
Heating nighttime No.07
operation sequence

GPX 6 PXN
70 JHN 08 8 70
Heating nighttime No.08
operation sequence
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
sequential or rotation.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
73
(7/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

75 L11 1
Heating nighttime GR1 level 1
number of operating units

76 L12 2
Heating nighttime GR1 level 2
number of operating units

77 L13 3
Heating nighttime GR1 level 3
number of operating units

78 L14 4
Heating nighttime GR1 level 4
number of operating units

79 L21 5
Heating nighttime GR1 level 5
number of operating units

80 L22 6
Heating nighttime GR1 level 6
number of operating units

81 L23 7
Heating nighttime GR1 level 7
number of operating units

82 L24 8
Heating nighttime GR1 level 8
number of operating units

83 L31 9
Heating nighttime GR1 level 9
number of operating units

84 L32 10
Heating nighttime GR1 level 10
number of operating units

85 L33 11
Heating nighttime GR1 level 11
number of operating units

86 L34 12
Heating nighttime GR1 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5 and Gr6 are set by LPX.

87 L11 0
Heating nighttime GR2 level 1
number of operating units

88 L12 0
Heating nighttime GR2 level 2
number of operating units

89 L13 0
Heating nighttime GR2 level 3
number of operating units

90 L14 0
Heating nighttime GR2 level 4
number of operating units

91 L21 0
Heating nighttime GR2 level 5
number of operating units

92 L22 0
Heating nighttime GR2 level 6
number of operating units

93 L23 0
Heating nighttime GR2 level 7
number of operating units

94 L24 0
Heating nighttime GR2 level 8
number of operating units

95 L31 0
Heating nighttime GR2 level 9
number of operating units

96 L32 0
Heating nighttime GR2 level 10
number of operating units

97 L33 0
Heating nighttime GR2 level 11
number of operating units

98 L34 0
Heating nighttime GR2 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5 and Gr6 are set by LPX.

99 L11 0
Heating nighttime GR3 level 1
number of operating units

100 L12 0
Heating nighttime GR3 level 2
number of operating units

101 L13 0
Heating nighttime GR3 level 3
number of operating units

102 L14 0
Heating nighttime GR3 level 4
number of operating units

103 L21 0
Heating nighttime GR3 level 5
number of operating units

104 L22 0
Heating nighttime GR3 level 6
number of operating units

105 L23 0
Heating nighttime GR3 level 7
number of operating units

106 L24 0
Heating nighttime GR3 level 8
number of operating units

107 L31 0
Heating nighttime GR3 level 9
number of operating units

108 L32 0
Heating nighttime GR3 level 10
number of operating units

GPX 6 PXN
109 L33 0
Heating nighttime GR3 level 11
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5 and Gr6 are set by LPX.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
74
(8/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

110 L34 0
Heating nighttime GR3 level 12
number of operating units


111 L11 0
Heating nighttime GR4 level 1
number of operating units

112 L12 0
Heating nighttime GR4 level 2
number of operating units

113 L13 0
Heating nighttime GR4 level 3
number of operating units

114 L14 0
Heating nighttime GR4 level 4
number of operating units

115 L21 0
Heating nighttime GR4 level 5
number of operating units

116 L22 0
Heating nighttime GR4 level 6
number of operating units

117 L23 0
Heating nighttime GR4 level 7
number of operating units

118 L24 0
Heating nighttime GR4 level 8
number of operating units

119 L31 0
Heating nighttime GR4 level 9
number of operating units

120 L32 0
Heating nighttime GR4 level 10
number of operating units

121 L33 0
Heating nighttime GR4 level 11
number of operating units

122 L34 0
Heating nighttime GR4 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5 and Gr6 are set by LPX.



123 SCD 0
Cooling daytime sequential
update step
When Sequential method with
base unit changeover is
adopted, change value other
than 0. At group stopped timing,
the number of units set here will
be slid its operation sequence.

124 JCD 01 1
Cooling daytime No.01
operation sequence

125 JCD 02 2
Cooling daytime No.02
operation sequence

126 JCD 03 3
Cooling daytime No.03
operation sequence

127 JCD 04 4
Cooling daytime No.04
operation sequence

128 JCD 05 5
Cooling daytime No.05
operation sequence

129 JCD 06 6
Cooling daytime No.06
operation sequence

130 JCD 07 7
Cooling daytime No.07
operation sequence

131 JCD 08 8
Cooling daytime No.08
operation sequence
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the sequential or rotation.

136 L11 1
Cooling daytime GR1 level 1
number of operating units

137 L12 2
Cooling daytime GR1 level 2
number of operating units

138 L13 3
Cooling daytime GR1 level 3
number of operating units

139 L14 4
Cooling daytime GR1 level 4
number of operating units

140 L21 5
Cooling daytime GR1 level 5
number of operating units

141 L22 6
Cooling daytime GR1 level 6
number of operating units

142 L23 7
Cooling daytime GR1 level 7
number of operating units

143 L24 8
Cooling daytime GR1 level 8
number of operating units

144 L31 9
Cooling daytime GR1 level 9
number of operating units

145 L32 10
Cooling daytime GR1 level 10
number of operating units

GPX 6 PXN
146 L33 11
Cooling daytime GR1 level 11
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5 and Gr6 are set by LPX.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
75
(9/17
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

147 L34 12
Cooling daytime GR1 level 12
number of operating units


148 L11 0
Cooling daytime GR2 level 1
number of operating units

149 L12 0
Cooling daytime GR2 level 2
number of operating units

150 L13 0
Cooling daytime GR2 level 3
number of operating units

151 L14 0
Cooling daytime GR2 level 4
number of operating units

152 L21 0
Cooling daytime GR2 level 5
number of operating units

153 L22 0
Cooling daytime GR2 level 6
number of operating units

154 L23 0
Cooling daytime GR2 level 7
number of operating units

155 L24 0
Cooling daytime GR2 level 8
number of operating units

156 L31 0
Cooling daytime GR2 level 9
number of operating units

157 L32 0
Cooling daytime GR2 level 10
number of operating units

158 L33 0
Cooling daytime GR2 level 11
number of operating units

159 L34 0
Cooling daytime GR2 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5 and Gr6 are set by LPX.

160 L11 0
Cooling daytime GR3 level 1
number of operating units

161 L12 0
Cooling daytime GR3 level 2
number of operating units

162 L13 0
Cooling daytime GR3 level 3
number of operating units

163 L14 0
Cooling daytime GR3 level 4
number of operating units

164 L21 0
Cooling daytime GR3 level 5
number of operating units

165 L22 0
Cooling daytime GR3 level 6
number of operating units

166 L23 0
Cooling daytime GR3 level 7
number of operating units

167 L24 0
Cooling daytime GR3 level 8
number of operating units

168 L31 0
Cooling daytime GR3 level 9
number of operating units

169 L32 0
Cooling daytime GR3 level 10
number of operating units

170 L33 0
Cooling daytime GR3 level 11
number of operating units

171 L34 0
Cooling daytime GR3 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the sequential or rotation.

172 L11 0
Cooling daytime GR4 level 1
number of operating units

173 L12 0
Cooling daytime GR4 level 2
number of operating units

174 L13 0
Cooling daytime GR4 level 3
number of operating units

175 L14 0
Cooling daytime GR4 level 4
number of operating units

176 L21 0
Cooling daytime GR4 level 5
number of operating units

177 L22 0
Cooling daytime GR4 level 6
number of operating units

178 L23 0
Cooling daytime GR4 level 7
number of operating units

179 L24 0
Cooling daytime GR4 level 8
number of operating units

180 L31 0
Cooling daytime GR4 level 9
number of operating units

GPX 6 PXN
181 L32 0
Cooling daytime GR4 level 10
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5 and Gr6 are set by LPX.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
76
(10/17
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

182 L33 0
Cooling daytime GR4 level 11
number of operating units

183 L34 0
Cooling daytime GR4 level 12
number of operating units




184 SCN 0
Cooling nighttime sequential
update step
When Sequential method with
base unit changeover is
adopted, set value other than 0.
At group stopped timing, the
number of units set here will be
slid its operation sequence.

185 JCN 01 1
Cooling daytime No.01
operation sequence

186 JCN 02 2
Cooling daytime No.02
operation sequence

187 JCN 03 3
Cooling daytime No.03
operation sequence

188 JCN 04 4
Cooling daytime No.04
operation sequence

189 JCN 05 5
Cooling daytime No.05
operation sequence

190 JCN 06 6
Cooling daytime No.06
operation sequence

191 JCN 07 7
Cooling daytime No.07
operation sequence

192 JCN 08 8
Cooling daytime No.08
operation sequence
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the sequential or rotation.

197 L11 1
Cooling nighttime GR1 level 1
number of operating units

198 L12 2
Cooling nighttime GR1 level 2
number of operating units

199 L13 3
Cooling nighttime GR1 level 3
number of operating units

200 L14 4
Cooling nighttime GR1 level 4
number of operating units

201 L21 5
Cooling nighttime GR1 level 5
number of operating units

202 L22 6
Cooling nighttime GR1 level 6
number of operating units

203 L23 7
Cooling nighttime GR1 level 7
number of operating units

204 L24 8
Cooling nighttime GR1 level 8
number of operating units

205 L31 9
Cooling nighttime GR1 level 9
number of operating units

206 L32 10
Cooling nighttime GR1 level 10
number of operating units

207 L33 11
Cooling nighttime GR1 level 11
number of operating units

208 L34 12
Cooling nighttime GR1 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the sequential or rotation.

209 L11 0
Cooling nighttime GR2 level 1
number of operating units

210 L12 0
Cooling nighttime GR2 level 2
number of operating units

211 L13 0
Cooling nighttime GR2 level 3
number of operating units

212 L14 0
Cooling nighttime GR2 level 4
number of operating units

213 L21 0
Cooling nighttime GR2 level 5
number of operating units

214 L22 0
Cooling nighttime GR2 level 6
number of operating units

215 L23 0
Cooling nighttime GR2 level 7
number of operating units

216 L24 0
Cooling nighttime GR2 level 8
number of operating units

217 L31 0
Cooling nighttime GR2 level 9
number of operating units

GPX 6 PXN
218 L32 0
Cooling nighttime GR2 level 10
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5 and Gr6 are set by LPX.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
77
(11/17
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

219 L33 0
Cooling nighttime GR2 level 11
number of operating units

220 L34 0
Cooling nighttime GR2 level 12
number of operating units


221 L11 0
Cooling nighttime GR3 level 1
number of operating units

222 L12 0
Cooling nighttime GR3 level 2
number of operating units

223 L13 0
Cooling nighttime GR3 level 3
number of operating units

224 L14 0
Cooling nighttime GR3 level 4
number of operating units

225 L21 0
Cooling nighttime GR3 level 5
number of operating units

226 L22 0
Cooling nighttime GR3 level 6
number of operating units

227 L23 0
Cooling nighttime GR3 level 7
number of operating units

228 L24 0
Cooling nighttime GR3 level 8
number of operating units

229 L31 0
Cooling nighttime GR3 level 9
number of operating units

230 L32 0
Cooling nighttime GR3 level 10
number of operating units

231 L33 0
Cooling nighttime GR3 level 11
number of operating units

232 L34 0
Cooling nighttime GR3 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the sequential or rotation.

233 L11 0
Cooling nighttime GR4 level 1
number of operating units

234 L12 0
Cooling nighttime GR4 level 2
number of operating units

235 L13 0
Cooling nighttime GR4 level 3
number of operating units

236 L14 0
Cooling nighttime GR4 level 4
number of operating units

237 L21 0
Cooling nighttime GR4 level 5
number of operating units

238 L22 0
Cooling nighttime GR4 level 6
number of operating units

239 L23 0
Cooling nighttime GR4 level 7
number of operating units

240 L24 0
Cooling nighttime GR4 level 8
number of operating units

241 L31 0
Cooling nighttime GR4 level 9
number of operating units

242 L32 0
Cooling nighttime GR4 level 10
number of operating units

243 L33 0
Cooling nighttime GR4 level 11
number of operating units

GPX 6 PXN
244 L34 0
Cooling nighttime GR4 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5 and Gr6 are set by LPX.


Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
78
(12/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
13 TYP01 2
No.1 Thermal Source equipment
type (0 - 4)
14 TYP02 2
No.2 Thermal Source equipment
type (0 - 4)
15 TYP03 2
No.3 Thermal Source equipment
type (0 - 4)
16 TYP04 2
No.4 Thermal Source equipment
type (0 - 4)
17 TYP05 2
No.5 Thermal Source equipment
type (0 - 4)
18 TYP06 2
No.6 Thermal Source equipment
type (0 - 4)
19 TYP07 2
No.7 Thermal Source equipment
type (0 - 4)
20 TYP08 2
No.8 Thermal Source equipment
type (0 - 4)
21 TYP09 2
No.9 Thermal Source equipment
type (0 - 4)
22 TYP10 2
No.10 Thermal Source equipment
type (0 - 4)
23 TYP11 2
No.11 Thermal Source equipment
type (0 - 4)
24 TYP12 2
No.12 Thermal Source equipment
type (0 - 4)
It is not used for the
sequence control
frequently.
0: Pump
1: Heat pump chiller
2: Absorption Chilled/Hot
Water Generator
3: Turbo Chiller
4: Heat Exchanger
25 TNN01 min 30 No.1 Restart prevent time (0 - 1440)
26 TNN02 min 30 No.2 Restart prevent time (0 - 1440)
27 TNN03 min 30 No.3 Restart prevent time (0 - 1440)
28 TNN04 min 30 No.4 Restart prevent time (0 - 1440)
29 TNN05 min 30 No.5 Restart prevent time (0 - 1440)
30 TNN06 min 30 No.6 Restart prevent time (0 - 1440)
31 TNN07 min 30 No.7 Restart prevent time (0 - 1440)
32 TNN08 min 30 No.8 Restart prevent time (0 - 1440)
33 TNN09 min 30 No.9 Restart prevent time (0 - 1440)
34 TNN10 min 30 No.10 Restart prevent time (0 - 1440)
35 TNN11 min 30 No.11 Restart prevent time (0 - 1440)
36 TNN12 min 30 No.12 Restart prevent time (0 - 1440)
Can set using OI as "MAIN
MENU" - "Thermal Source"
- "Sequential Control
Parameter".
37 TFN01 min 20 No.1 Minimum stop time (0 - 1440)
38 TFN02 min 20 No.2 Minimum stop time (0 - 1440)
39 TFN03 min 20 No.3 Minimum stop time (0 - 1440)
40 TFN04 min 20 No.4 Minimum stop time (0 - 1440)
41 TFN05 min 20 No.5 Minimum stop time (0 - 1440)
42 TFN06 min 20 No.6 Minimum stop time (0 - 1440)
43 TFN07 min 20 No.7 Minimum stop time (0 - 1440)
44 TFN08 min 20 No.8 Minimum stop time (0 - 1440)
45 TFN09 min 20 No.9 Minimum stop time (0 - 1440)
46 TFN10 min 20 No.10 Minimum stop time (0 - 1440)
47 TFN11 min 20 No.11 Minimum stop time (0 - 1440)

LPX 6 PXN
48 TFN12 min 20 No.12 Minimum stop time (0 - 1440)
Can set using OI as "MAIN
MENU" - "Thermal Source"
- "Sequential Control
Parameter".
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
79
(13/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
49 TWS01 min 30
No.1 Thermal Source Startup
time (0 - 1440)
50 TWS02 min 30
No.2 Thermal Source Startup
time (0 - 1440)
51 TWS03 min 30
No.3 Thermal Source Startup
time (0 - 1440)
52 TWS04 min 30
No.4 Thermal Source Startup
time (0 - 1440)
53 TWS05 min 30
No.5 Thermal Source Startup
time (0 - 1440)
54 TWS06 min 30
No.6 Thermal Source Startup
time (0 - 1440)
55 TWS07 min 30
No.7 Thermal Source Startup
time (0 - 1440)
56 TWS08 min 30
No.8 Thermal Source Startup
time (0 - 1440)
57 TWS09 min 30
No.9 Thermal Source Startup
time (0 - 1440)
58 TWS10 min 30
No.10 Thermal Source Startup
time (0 - 1440)
59 TWS11 min 30
No.11 Thermal Source Startup
time (0 - 1440)
60 TWS12 min 30
No.12 Thermal Source Startup
time (0 - 1440)
Can set using OI as "MAIN
MENU" - "Thermal Source" -
"Sequential Control Parameter".
61 TWR01 min 30 No.1 Remain run time (0 - 1440)
62 TWR02 min 30 No.2 Remain run time (0 - 1440)
63 TWR03 min 30 No.3 Remain run time (0 - 1440)
64 TWR04 min 30 No.4 Remain run time (0 - 1440)
65 TWR05 min 30 No.5 Remain run time (0 - 1440)
66 TWR06 min 30 No.6 Remain run time (0 - 1440)
67 TWR07 min 30 No.7 Remain run time (0 - 1440)
68 TWR08 min 30 No.8 Remain run time (0 - 1440)
69 TWR09 min 30 No.9 Remain run time (0 - 1440)
70 TWR10 min 30 No.10 Remain run time (0 - 1440)
71 TWR11 min 30 No.11 Remain run time (0 - 1440)
72 TWR12 min 30 No.12 Remain run time (0 - 1440)
Can set using OI as "MAIN
MENU" - "Thermal Source" -
"Sequential Control Parameter".

73 HIL01 % 0
No.1 Sequence control high limit
ratio

74 HIL02 % 0
No.2 Sequence control high limit
ratio

75 HIL03 % 0
No.3 Sequence control high limit
ratio

76 HIL04 % 0
No.4 Sequence control high limit
ratio

77 HIL05 % 0
No.5 Sequence control high limit
ratio

78 HIL06 % 0
No.6 Sequence control high limit
ratio

79 HIL07 % 0
No.7 Sequence control high limit
ratio

80 HIL08 % 0
No.8 Sequence control high limit
ratio

81 HIL09 % 0
No.9 Sequence control high limit
ratio

82 HIL10 % 0
No.10 Sequence control high
limit ratio

83 HIL11 % 0
No.11 Sequence control high limit
ratio

LPX 6 PXN
84 HIL12 % 0
No.12 Sequence control high
limit ratio
Chiller's capacity may change
according to the cooling water
temperature. Hi limit is set to
show how the maximum
capacity of the Thermal Source
is greater than the rated
capacity. When the Hi limit is set
to 20%, it means that the
maximum capacity of the
Thermal Source is 120% of the
rated capacity. However, it is not
required to consider the capacity
change when the sequence
control load is flow, so the Hi
limit is set to "0".
< Recommended Value >
Flow Energy
Pump 0% -
Heat pump
chiller
0% 20%
Turbo chiller 0% 20%
Chilled/Hot
water generator
0% 20%
Heat exchanger 0% 0%

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
80
(14/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
85 LOL01 % 40
No.1 Sequence control
LO limit ratio
86 LOL02 % 40
No.2 Sequence control
LO limit ratio
87 LOL03 % 40
No.3 Sequence control
LO limit ratio
88 LOL04 % 40
No.4 Sequence control
LO limit ratio
89 LOL05 % 40
No.5 Sequence control
LO limit ratio
90 LOL06 % 40
No.6 Sequence control
LO limit ratio
91 LOL07 % 40
No.7 Sequence control
LO limit ratio
92 LOL08 % 40
No.8 Sequence control
LO limit ratio
93 LOL09 % 40
No.9 Sequence control
LO limit ratio
94 LOL10 % 40
No.10 Sequence control
LO limit ratio
95 LOL10 % 40
No.11 Sequence control
LO limit ratio
96 LOL12 % 40
No.12 Sequence control
LO limit ratio
The value is to set the available capacity
of the Thermal Source is how much
lower than the rated capacity in the
worst environmental condition. When
the load is between the Hi limit and the
Lo limit, the capacity adjustment request
by temperature can be accepted.
If the sequence control decrease
point calculation method is
(LP:013(NJP))=1, the Lo limit ratio
is set equal to the Differential, it is
not required to set the Lo limit
ratio.
<< Recommended Value >>
Flow Energy
Pump 0% -
Heat pump
chiller
20% 20%
Turbo chiller 20% 20%
Chilled/Hot
water generator
20% 20%
Heat exchanger 20% 20%
97 DIF01 % 40
No.1 Sequence control
Differential
98 DIF02 % 40
No.2 Sequence control
Differential
99 DIF03 % 40
No.3 Sequence control
Differential
100 DIF04 % 40
No.4 Sequence control
Differential
101 DIF05 % 40
No.5 Sequence control
Differential
102 DIF06 % 40
No.6 Sequence control
Differential
103 DIF07 % 40
No.7 Sequence control
Differential
104 DIF08 % 40
No.8 Sequence control
Differential
105 DIF09 % 40
No.9 Sequence control
Differential
106 DIF10 % 40
No.10 Sequence control
Differential

107 DIF11 % 40
No.11 Sequence control
Differential




108 DIF12 % 40
No.12 Sequence control
Differential
It is an operation gap will be used at the
thermal source decrease decision.
<< Recommended Value >>
Sequence control
decrease capa method

1:
Energy
saving
precedence
0:
Stability
precedence

Pump 20% 10%
Heat pump
chiller
40% 20%
Turbo
chiller
40% 20%
Chilled/Hot
water
generator
40% 20%
Heat
exchanger
40% 20%

When the operating sequence
method is Sequential
method/Rotation method/Program
method (Sequence control
decrease limit operation method =
0), it is used.
If Program method (Sequence
control decrease limit operation
method = 1) selected, set at LP15
- 58.

109 GR 01 1 No.01 Heating group No.

110 GR 02 1
No.02 Heating group No.

111 GR 03 1
No.03 Heating group No.
If OI is not used. set the parameter using
PC-MMI.
Set the parameter when the operation
sequence method is the program mode.

112 GR 04 1
No.04 Heating group No.

113 GR 05 1
No.05 Heating group No.

114 GR 06 1
No.06 Heating group No.

115 GR 07 1
No.07 Heating group No.

LPX 6 PXN
116 GR 08 1
No.08 Heating group No.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
81
(15/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
121 GR 01 1 No.01 Cooling group No.
122 GR 02 1
No.02 Cooling group No.
123 GR 03 1
No.03 Cooling group No.
124 GR 04 1
No.04 Cooling group No.
125 GR 05 1
No.05 Cooling group No.
126 GR 06 1
No.06 Cooling group No.
127 GR 07 1
No.07 Cooling group No.
128 GR 08 1
No.08 Cooling group No.
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
program mode.
133 L11 0
Heating daytime GR5 level 1
number of operating units
134 L12 0
Heating daytime GR5 level 2
number of operating units
135 L13 0
Heating daytime GR5 level 3
number of operating units
136 L14 0
Heating daytime GR5 level 4
number of operating units
137 L21 0
Heating daytime GR5 level 5
number of operating units
138 L22 0
Heating daytime GR5 level 6
number of operating units
139 L23 0
Heating daytime GR5 level 7
number of operating units
140 L24 0
Heating daytime GR5 level 8
number of operating units
141 L31 0
Heating daytime GR5 level 9
number of operating units
142 L32 0
Heating daytime GR5 level 10
number of operating units

143 L33 0
Heating daytime GR5 level 11
number of operating units

144 L34 0
Heating daytime GR5 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
program mode.
Gr1Gr4 are set by GPX.



















145 L11 0
Heating daytime GR6 level 1
number of operating units

146 L12 0
Heating daytime GR6 level 2
number of operating units

147 L13 0
Heating daytime GR6 level 3
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
program mode.
Gr1Gr4 are set by GPX.

148 L14 0
Heating daytime GR6 level 4
number of operating units

149 L21 0
Heating daytime GR6 level 5
number of operating units

150 L22 0
Heating daytime GR6 level 6
number of operating units

151 L23 0
Heating daytime GR6 level 7
number of operating units

152 L24 0
Heating daytime GR6 level 8
number of operating units

153 L31 0
Heating daytime GR6 level 9
number of operating units

154 L32 0
Heating daytime GR6 level 10
number of operating units

155 L33 0
Heating daytime GR6 level 11
number of operating units


156 L34 0
Heating daytime GR6 level 12
number of operating units


157 L11 0
Heating nighttime GR5 level 1
number of operating units

158 L12 0
Heating nighttime GR5 level 2
number of operating units

159 L13 0
Heating nighttime GR5 level 3
number of operating units

LPX 6 PXN
160 L14 0
Heating nighttime GR5 level 4
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is the
program mode.
Gr1Gr4 are set by GPX.


Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
82
(16/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

161 L21 0
Heating nighttime GR5 level 5
number of operating units

162 L22 0
Heating nighttime GR5 level 6
number of operating units

163 L23 0
Heating nighttime GR5 level 7
number of operating units

164 L24 0
Heating nighttime GR5 level 8
number of operating units

165 L31 0
Heating nighttime GR5 level 9
number of operating units

166 L32 0
Heating nighttime GR5 level 10
number of operating units

167 L33 0
Heating nighttime GR5 level 11
number of operating units

168 L34 0
Heating nighttime GR5 level 12
number of operating units


169 L11 0
Heating nighttime GR6 level 1
number of operating units

170 L12 0
Heating nighttime GR6 level 2
number of operating units

171 L13 0
Heating nighttime GR6 level 3
number of operating units

172 L14 0
Heating nighttime GR6 level 4
number of operating units

173 L21 0
Heating nighttime GR6 level 5
number of operating units

174 L22 0
Heating nighttime GR6 level 6
number of operating units

175 L23 0
Heating nighttime GR6 level 7
number of operating units

176 L24 0
Heating nighttime GR6 level 8
number of operating units

177 L31 0
Heating nighttime GR6 level 9
number of operating units

178 L32 0
Heating nighttime GR6 level 10
number of operating units

179 L33 0
Heating nighttime GR6 level 11
number of operating units

180 L34 0
Heating nighttime GR6 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 are set by GPX.

181 L11 0
Cooling daytime GR5 level 1
number of operating units

182 L12 0
Cooling daytime GR5 level 2
number of operating units

183 L13 0
Cooling daytime GR5 level 3
number of operating units

184 L14 0
Cooling daytime GR5 level 4
number of operating units

185 L21 0
Cooling daytime GR5 level 5
number of operating units

186 L22 0
Cooling daytime GR5 level 6
number of operating units

187 L23 0
Cooling daytime GR5 level 7
number of operating units

188 L24 0
Cooling daytime GR5 level 8
number of operating units

189 L31 0
Cooling daytime GR5 level 9
number of operating units

190 L32 0
Cooling daytime GR5 level 10
number of operating units

191 L33 0
Cooling daytime GR5 level 11
number of operating units

192 L34 0
Cooling daytime GR5 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 are set by GPX.

193 L11 0
Cooling daytime GR6 level 1
number of operating units

194 L12 0
Cooling daytime GR6 level 2
number of operating units

LPX 6 PXN
195 L13 0
Cooling daytime GR6 level 3
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 are set by GPX
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
83
(17/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

196 L14 0
Cooling daytime GR6 level 4
number of operating units

197 L21 0
Cooling daytime GR6 level 5
number of operating units

198 L22 0
Cooling daytime GR6 level 6
number of operating units

199 L23 0
Cooling daytime GR6 level 7
number of operating units

200 L24 0
Cooling daytime GR6 level 8
number of operating units

201 L31 0
Cooling daytime GR6 level 9
number of operating units

202 L32 0
Cooling daytime GR6 level 10
number of operating units

203 L33 0
Cooling daytime GR6 level 11
number of operating units

204 L34 0
Cooling daytime GR6 level 12
number of operating units


205 L11 0
Cooling nighttime GR5 level 1
number of operating units

206 L12 0
Cooling nighttime GR5 level 2
number of operating units

207 L13 0
Cooling nighttime GR5 level 3
number of operating units

208 L14 0
Cooling nighttime GR5 level 4
number of operating units

209 L21 0
Cooling nighttime GR5 level 5
number of operating units

210 L22 0
Cooling nighttime GR5 level 6
number of operating units

211 L23 0
Cooling nighttime GR5 level 7
number of operating units

212 L24 0
Cooling nighttime GR5 level 8
number of operating units

213 L31 0
Cooling nighttime GR5 level 9
number of operating units

214 L32 0
Cooling nighttime GR5 level 10
number of operating units

215 L33 0
Cooling nighttime GR5 level 11
number of operating units

216 L34 0
Cooling nighttime GR5 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 are set by GPX.

217 L11 0
Cooling nighttime GR6 level 1
number of operating units

218 L12 0
Cooling nighttime GR6 level 2
number of operating units

219 L13 0
Cooling nighttime GR6 level 3
number of operating units

220 L14 0
Cooling nighttime GR6 level 4
number of operating units

221 L21 0
Cooling nighttime GR6 level 5
number of operating units

222 L22 0
Cooling nighttime GR6 level 6
number of operating units

223 L23 0
Cooling nighttime GR6 level 7
number of operating units

224 L24 0
Cooling nighttime GR6 level 8
number of operating units

225 L31 0
Cooling nighttime GR6 level 9
number of operating units

226 L32 0
Cooling nighttime GR6 level 10
number of operating units

227 L33 0
Cooling nighttime GR6 level 11
number of operating units

LPX 6 PXN
228 L34 0
Cooling nighttime GR6 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 are set by GPX.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
84
(1/17)
<< General >>
This panel is main part of sequence control; it defines the number of operating units according
to the load, suspends ON/OFF decision until the Thermal Source starts up.
Affected Instrumentation Code
All pump controllers

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
GP 5 SW V1 min 0
Forced rotation time (0 - 2880)
Set the timing of the forced increase capacity when
rotation with forced increase capacity is selected.
Q Forced rotation by the set time (PMX-III method)
Set the interval time (min) to activate the forced increase
capacity.
, Forced rotation by the specified time
Set the time to activate the forced increase capacity.
When the forced rotation to be executed at 23:30
Set: 1410 (23 x 60 min + 30 min = 1410)
(0: Forced rotation is disabled, at 1440:24 (0:00 AM),
1440 or more is regarded as 1440.)
Q and , can be changed by LP:12 (CRT).
MIN unit 1 Minimum number of operating units (0 - 12)
TON sec 30
Sequential start time (0 - 15300)
Interval of start command the to Thermal Sources that are
recovered from power failure simultaneously.
TOF sec 30
Sequential stop time (0 - 15300)
Interval of stop command to the Thermal Sources that are
ordered to stop simultaneously.
TWW sec 0
Water round time (0 - 15300)
Set the time in which water goes round in the pipe.
TIM min 0
Failure auto reset time (0 - 1440)
Send OFF command to the failed Thermal Source after
the preset time (Failure auto reset time) has passed and
reset the alarm automatically. This function can't be used
for the Thermal Sources that don't have the failure reset
function by OFF command. When it is set as "0", reset
manually.
When point type is changed from CAPf to CAPl and then
the thermal source (pump) is recovered form failure status,
the thermal source may start automatically. To avoid the
automatic start, set this parameter.
TIC sec 0
Increase notice time (0 - 15300)
The interval time between when the increase command is
issued and when the Thermal Source receives the startup
command actually.
ABP GJ/H 59999
ON/OFF simultaneous process (59999 - 59999)
According to the difference of ON/OFF simultaneous
process, change the value. If ON priority process is
adopted, set a positive number (can be set as default). If
OFF priority process is adopted, set to -1. The ON/OFF
simultaneous process can be changed by this setting. "0"
is regarded as a positive number.
SWJ 0
Operating sequence adjustment method (0 - 1)
Set the operating sequence adjustment method when
returning from failed condition.
0: Sequence setting priority method, 1: Operating unit priority
method
SPR01 5 No.1 Thermal Source type (0 - 5)
SPR02 5 No.2 Thermal Source type (0 - 5)
SPR03 5 No.3 Thermal Source type (0 - 5)
SPR04 5 No.4 Thermal Source type (0 - 5)
SPR05 5 No.5 Thermal Source type (0 - 5)
SPR06 5 No.6 Thermal Source type (0 - 5)
SPR07 5 No.7 Thermal Source type (0 - 5)
SPR08 5 No.8 Thermal Source type (0 - 5)
SPR09 5 No.9 Thermal Source type (0 - 5)
SPR10 5 No.1 Thermal Source type (0 - 5)
SPR11 5 No.2 Thermal Source type (0 - 5)

GP 6 PXN
SPR12 5 No.3 Thermal Source type (0 - 5)
These parameters are not
used for control
frequently.
0: Delete
1: Cooling
2: Heating
3: Cooling/Heating
4: Simultaneous
5: No display (pump
etc.)
These are displayed on
OI operation sequence
setting screen.

28. Panel 20 - Sequence Control (Pump) <Item002>
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
85
(2/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
FR01 0 No.1 Forced ON (0 - 1)
FR02 0 No.2 Forced ON (0 - 1)
FR03 0 No.3 Forced ON (0 - 1)
FR04 0 No.4 Forced ON (0 - 1)
FR05 0 No.5 Forced ON (0 - 1)
FR06 0 No.6 Forced ON (0 - 1)
FR07 0 No.7 Forced ON (0 - 1)
FR08 0 No.8 Forced ON (0 - 1)
FR09 0 No.9 Forced ON (0 - 1)
FR10 0 No.10 Forced ON (0 - 1)
FR11 0 No.11 Forced ON (0 - 1)

GP 6 PXN
FR12 0 No.12 Forced ON (0 - 1)
Can't be changed.
3 MHD 12
Heating daytime maximum
operating units
4 MHN 12
Heating nighttime maximum
operating units
5 MCD 12
Cooling daytime maximum
operating units
6 MCN 12
Cooling nighttime maximum
operating units
If OI is not used. set the
parameter using PC-MMI.
This parameter is to set the
maximum number of thermal
source that is operated by the
sequence control.
11 RT 0 Rotation ON method (0 - 1)
0: ON the longest OFF
equipment/OFF the longest
ON equipment(PMX-III
method)
1: Rotate the equipment by the
totalized run time
(ON the lowest totalized run time
equipment/OFF the highest
totalized run time
equipment)
12 CRT 1
Forced rotation ON method
(0 - 1)
0: Forced rotation by the
preset time
(PMX-III method)
1: Forced rotation by the
specified time

LP 6 PXN
13 NJP 1
Sequence control decrease
point calculation method (0 -
1)
0: Calculate the total rated
capacity of ON
equipment.(Stability
precedence )
(PMX-III method)
1: Calculate by the rated
capacity of equipment 1
level down (for program
method, the difference of
the rated capacity of the
equipment between 1 level
down and 2 level done).
(Energy saving
precedence )
The operation method of the
decrease limit and Low limit
ratio can be changed by this
parameter. High limit ratio is
always calculated by the total
of rated capacity of the ON
equipments. If "0" is
selected, the Differential and
the Low limit ratio can be set
separately. However if "1" is
selected, only the Differential
can be set, and make the
Low limit ratio = Differential.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
86
(3/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
15 DHD % 20.0
Heating daytime level 1-2
sequence control differential (0
- 100.0)
16 DHD % 20.0
Heating daytime level 2-3
sequence control differential (0
- 100.0)
17 DHD % 20.0
Heating daytime level 3-4
sequence control differential (0
- 100.0)
18 DHD % 20.0
Heating daytime level 4-5
sequence control differential (0
- 100.0)
19 DHD % 20.0
Heating daytime level 5-6
sequence control differential (0
- 100.0)
20 DHD % 20.0
Heating daytime level 6-7
sequence control differential (0
- 100.0)
21 DHD % 20.0
Heating daytime level 7-8
sequence control differential (0
- 100.0)
22 DHD % 20.0
Heating daytime level 8-9
sequence control differential (0
- 100.0)
23 DHD % 20.0
Heating daytime level 9-10
sequence control differential (0
- 100.0)
24 DHD % 20.0
Heating daytime level 10-11
sequence control differential (0
- 100.0)
25 DHD % 20.0
Heating daytime level 11-12
sequence control differential (0
- 100.0)
It is an operation gap will be
used at the thermal source
decrease decision.
<Recommended Value>
Approximately 20%.
In this case, the Low limit
ratio = Differential, so it is
not required to set the Low
limit ratio. It is used only
when the operation
sequence method is the
program method and the
sequence control
decrease limit method =
1. If the sequential/
rotation/program method
(the sequence control
decrease limit method =
0), set LPX97108).
26 DHN % 20.0
Heating nighttime level 1-2
sequence control differential (0
- 100.0)
27 DHN % 20.0
Heating nighttime level 2-3
sequence control differential (0
- 100.0)
28 DHN % 20.0
Heating nighttime level 3-4
sequence control differential (0
- 100.0)
29 DHN % 20.0
Heating nighttime level 4-5
sequence control differential (0
- 100.0)
30 DHN % 20.0
Heating nighttime level 5-6
sequence control differential (0
- 100.0)
31 DHN % 20.0
Heating nighttime level 6-7
sequence control differential (0
- 100.0)
32 DHN % 20.0
Heating nighttime level 7-8
sequence control differential (0
- 100.0)
33 DHN % 20.0
Heating nighttime level 8-9
sequence control differential (0
- 100.0)
34 DHN % 20.0
Heating nighttime level 9-10
sequence control differential (0
- 100.0)
35 DHN % 20.0
Heating nighttime level 10-11
sequence control differential (0
- 100.0)

LP 6 PXN
36 DHN % 20.0
Heating nighttime level 11-12
sequence control differential (0
- 100.0)
It is an operation gap will be
used at the thermal source
decrease decision.
<Recommended Value>
Approximately 20%.
In this case, the Low limit
ratio = Differential, so it is
not required to set the Low
limit ratio. It is used only
when the operation
sequence method is the
program method and the
sequence control
decrease limit method =
1. If the sequential/
rotation/program method
(the sequence control
decrease limit method =
0), set LPX97108).

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
87
(4/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
37 DCD % 20.0
Cooling daytime level 1-2
sequence control differential (0
- 100.0)
38 DCD % 20.0
Cooling daytime level 2-3
sequence control differential (0
- 100.0)
39 DCD % 20.0
Cooling daytime level 3-4
sequence control differential (0
- 100.0)
40 DCD % 20.0
Cooling daytime level 4-5
sequence control differential (0
- 100.0)
41 DCD % 20.0
Cooling daytime level 5-6
sequence control differential (0
- 100.0)
42 DCD % 20.0
Cooling daytime level 6-7
sequence control differential (0
- 100.0)
43 DCD % 20.0
Cooling daytime level 7-8
sequence control differential (0
- 100.0)
44 DCD % 20.0
Cooling daytime level 8-9
sequence control differential (0
- 100.0)
45 DCD % 20.0
Cooling daytime level 9-10
sequence control differential (0
- 100.0)
46 DCD % 20.0
Cooling daytime level 10-11
sequence control differential (0
- 100.0)
47 DCD % 20.0
Cooling daytime level 11-12
sequence control differential (0
- 100.0)
It is an operation gap will be
used at the thermal source
decrease decision.
<Recommended Value>
Approximately 20%.
In this case, the Low limit
ratio = Differential, so it is
not required to set the Low
limit ratio. It is used only
when the operation
sequence method is the
program method and the
sequence control
decrease limit method =
1. If the sequential/
rotation/program method
(the sequence control
decrease limit method =
0), set LPX97108).
48 DCN % 20.0
Cooling nighttime level 1-2
sequence control differential (0
- 100.0)
49 DCN % 20.0
Cooling nighttime level 2-3
sequence control differential (0
- 100.0)
50 DCN % 20.0
Cooling nighttime level 3-4
sequence control differential (0
- 100.0)
51 DCN % 20.0
Cooling nighttime level 4-5
sequence control differential (0
- 100.0)
52 DCN % 20.0
Cooling nighttime level 5-6
sequence control differential (0
- 100.0)
53 DCN % 20.0
Cooling nighttime level 6-7
sequence control differential (0
- 100.0)
54 DCN % 20.0
Cooling nighttime level 7-8
sequence control differential (0
- 100.0)
55 DCN % 20.0
Cooling nighttime level 8-9
sequence control differential (0
- 100.0)
56 DCN % 20.0
Cooling nighttime level 9-10
sequence control differential (0
- 100.0)
57 DCN % 20.0
Cooling nighttime level 10-11
sequence control differential (0
- 100.0)

LP 6 PXN
58 DCN % 20.0
Cooling nighttime level 11-12
sequence control differential (0
- 100.0)
It is an operation gap will be
used at the thermal source
decrease decision.
<Recommended Value>
Approximately 20%.
In this case, the Low limit
ratio = Differential, so it is
not required to set the Low
limit ratio. It is used only
when the operation
sequence method is the
program method and the
sequence control
decrease limit method =
1. If the sequential/
rotation/program method
(the sequence control
decrease limit method =
0), set LPX97108).

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
88
(5/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 SHD unit 0


Heating daytime sequential
update step
When Sequential method with
base unit changeover is
adopted, change the value other
than 0. While in the group OFF
mode, the ON sequence is
shifted for the number of
equipment specified here.

2 JHD 01 1
Heating daytime No.01
operation sequence

3 JHD 02 2
Heating daytime No.02
operation sequence

4 JHD 03 3
Heating daytime No.03
operation sequence

5 JHD 04 4
Heating daytime No.04
operation sequence

6 JHD 05 5
Heating daytime No.05
operation sequence

7 JHD 06 6
Heating daytime No.06
operation sequence

8 JHD 07 7
Heating daytime No.07
operation sequence

9 JHD 08 8
Heating daytime No.08
operation sequence
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the sequential or rotation.

14 L11 1
Heating daytime GR1 level 1
number of operating units

15 L12 2
Heating daytime GR1 level 2
number of operating units

16 L13 3
Heating daytime GR1 level 3
number of operating units

17 L14 4
Heating daytime GR1 level 4
number of operating units

18 L21 5
Heating daytime GR1 level 5
number of operating units

19 L22 6
Heating daytime GR1 level 6
number of operating units

20 L23 7
Heating daytime GR1 level 7
number of operating units

21 L24 8
Heating daytime GR1 level 8
number of operating units

22 L31 9
Heating daytime GR1 level 9
number of operating units

23 L32 10
Heating daytime GR1 level 10
number of operating units

24 L33 11
Heating daytime GR1 level 11
number of operating units

25 L34 12
Heating daytime GR1 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.

26 L11 0
Heating daytime GR2 level 1
number of operating units

27 L12 0
Heating daytime GR2 level 2
number of operating units

28 L13 0
Heating daytime GR2 level 3
number of operating units

29 L14 0
Heating daytime GR2 level 4
number of operating units

30 L21 0
Heating daytime GR2 level 5
number of operating units

31 L22 0
Heating daytime GR2 level 6
number of operating units

32 L23 0
Heating daytime GR2 level 7
number of operating units

33 L24 0
Heating daytime GR2 level 8
number of operating units

34 L31 0
Heating daytime GR2 level 9
number of operating units

35 L32 0
Heating daytime GR2 level 10
number of operating units

36 L33 0
Heating daytime GR2 level 11
number of operating units

GPX 6 PXN
37 L34 0
Heating daytime GR2 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
89
(6/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

38 L11 0
Heating daytime GR3 level 1
number of operating units

39 L12 0
Heating daytime GR3 level 2
number of operating units

40 L13 0
Heating daytime GR3 level 3
number of operating units

41 L14 0
Heating daytime GR3 level 4
number of operating units

42 L21 0
Heating daytime GR3 level 5
number of operating units

43 L22 0
Heating daytime GR3 level 6
number of operating units

44 L23 0
Heating daytime GR3 level 7
number of operating units

45 L24 0
Heating daytime GR3 level 8
number of operating units

46 L31 0
Heating daytime GR3 level 9
number of operating units

47 L32 0
Heating daytime GR3 level 10
number of operating units

48 L33 0
Heating daytime GR3 level 11
number of operating units

49 L34 0
Heating daytime GR3 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.

50 L11 0
Heating daytime GR4 level 1
number of operating units

51 L12 0
Heating daytime GR4 level 2
number of operating units

52 L13 0
Heating daytime GR4 level 3
number of operating units

53 L14 0
Heating daytime GR4 level 4
number of operating units

54 L21 0
Heating daytime GR4 level 5
number of operating units

55 L22 0
Heating daytime GR4 level 6
number of operating units

56 L23 0
Heating daytime GR4 level 7
number of operating units

57 L24 0
Heating daytime GR4 level 8
number of operating units

58 L31 0
Heating daytime GR4 level 9
number of operating units

59 L32 0
Heating daytime GR4 level 10
number of operating units

60 L33 0
Heating daytime GR4 level 11
number of operating units

61 L34 0
Heating daytime GR4 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.



62 SHN unit 0
Heating nighttime sequential
update step
When Sequential method with
base unit changeover is
adopted, change the value other
than 0. While in the group OFF
mode, the ON sequence is
shifted for the number of
equipment specified here.

63 JHN 01 1
Heating daytime No.01
operation sequence

64 JHN 02 2
Heating daytime No.02
operation sequence

65 JHN 03 3
Heating daytime No.03
operation sequence

66 JHN 04 4
Heating daytime No.04
operation sequence

67 JHN 05 5
Heating daytime No.05
operation sequence

68 JHN 06 6
Heating daytime No.06
operation sequence

69 JHN 07 7
Heating daytime No.07
operation sequence

GPX 6 PXN
70 JHN 08 8
Heating daytime No.08
operation sequence
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
90
(7/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

75 L11 1
Heating nighttime GR1 level 1
number of operating units

76 L12 2
Heating nighttime GR1 level 2
number of operating units

77 L13 3
Heating nighttime GR1 level 3
number of operating units

78 L14 4
Heating nighttime GR1 level 4
number of operating units

79 L21 5
Heating nighttime GR1 level 5
number of operating units

80 L22 6
Heating nighttime GR1 level 6
number of operating units

81 L23 7
Heating nighttime GR1 level 7
number of operating units

82 L24 8
Heating nighttime GR1 level 8
number of operating units

83 L31 9
Heating nighttime GR1 level 9
number of operating units

84 L32 10
Heating nighttime GR1 level 10
number of operating units

85 L33 11
Heating nighttime GR1 level 11
number of operating units

86 L34 12
Heating nighttime GR1 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.

87 L11 0
Heating nighttime GR2 level 1
number of operating units

88 L12 0
Heating nighttime GR2 level 2
number of operating units

89 L13 0
Heating nighttime GR2 level 3
number of operating units

90 L14 0
Heating nighttime GR2 level 4
number of operating units

91 L21 0
Heating nighttime GR2 level 5
number of operating units

92 L22 0
Heating nighttime GR2 level 6
number of operating units

93 L23 0
Heating nighttime GR2 level 7
number of operating units

94 L24 0
Heating nighttime GR2 level 8
number of operating units

95 L31 0
Heating nighttime GR2 level 9
number of operating units

96 L32 0
Heating nighttime GR2 level 10
number of operating units

97 L33 0
Heating nighttime GR2 level 11
number of operating units

98 L34 0
Heating nighttime GR2 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.

99 L11 0
Heating nighttime GR3 level 1
number of operating units

100 L12 0
Heating nighttime GR3 level 2
number of operating units

101 L13 0
Heating nighttime GR3 level 3
number of operating units

102 L14 0
Heating nighttime GR3 level 4
number of operating units

103 L21 0
Heating nighttime GR3 level 5
number of operating units

104 L22 0
Heating nighttime GR3 level 6
number of operating units

105 L23 0
Heating nighttime GR3 level 7
number of operating units

106 L24 0
Heating nighttime GR3 level 8
number of operating units

107 L31 0
Heating nighttime GR3 level 9
number of operating units

108 L32 0
Heating nighttime GR3 level 10
number of operating units

GPX 6 PXN
109 L33 0
Heating nighttime GR3 level 11
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
91
(8/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

110 L34 0
Heating nighttime GR3 level 12
number of operating units


111 L11 0
Heating nighttime GR4 level 1
number of operating units

112 L12 0
Heating nighttime GR4 level 2
number of operating units

113 L13 0
Heating nighttime GR4 level 3
number of operating units

114 L14 0
Heating nighttime GR4 level 4
number of operating units

115 L21 0
Heating nighttime GR4 level 5
number of operating units

116 L22 0
Heating nighttime GR4 level 6
number of operating units

117 L23 0
Heating nighttime GR4 level 7
number of operating units

118 L24 0
Heating nighttime GR4 level 8
number of operating units

119 L31 0
Heating nighttime GR4 level 9
number of operating units

120 L32 0
Heating nighttime GR4 level 10
number of operating units

121 L33 0
Heating nighttime GR4 level 11
number of operating units

122 L34 0
Heating nighttime GR4 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.



123 SCD unit 0
Cooling daytime sequential
update step
When Sequential method with
base unit changeover is
adopted, change the value other
than 0. While in the group OFF
mode, the ON sequence is
shifted for the number of
equipment specified here.

124 JCD 01 1
Cooling daytime No.01
operation sequence

125 JCD 02 2
Cooling daytime No.02
operation sequence

126 JCD 03 3
Cooling daytime No.03
operation sequence

127 JCD 04 4
Cooling daytime No.04
operation sequence

128 JCD 05 5
Cooling daytime No.05
operation sequence

129 JCD 06 6
Cooling daytime No.06
operation sequence

130 JCD 07 7
Cooling daytime No.07
operation sequence

131 JCD 08 8
Cooling daytime No.08
operation sequence
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
sequential or rotation.

136 L11 1
Cooling daytime GR1 level 1
number of operating units

137 L12 2
Cooling daytime GR1 level 2
number of operating units

138 L13 3
Cooling daytime GR1 level 3
number of operating units

139 L14 4
Cooling daytime GR1 level 4
number of operating units

140 L21 5
Cooling daytime GR1 level 5
number of operating units

141 L22 6
Cooling daytime GR1 level 6
number of operating units

142 L23 7
Cooling daytime GR1 level 7
number of operating units

143 L24 8
Cooling daytime GR1 level 8
number of operating units

144 L31 9
Cooling daytime GR1 level 9
number of operating units

145 L32 10
Cooling daytime GR1 level 10
number of operating units

GPX 6 PXN
146 L33 11
Cooling daytime GR1 level 11
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
92
(9/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

147 L34 12
Cooling daytime GR1 level 12
number of operating units


148 L11 0
Cooling daytime GR2 level 1
number of operating units

149 L12 0
Cooling daytime GR2 level 2
number of operating units

150 L13 0
Cooling daytime GR2 level 3
number of operating units

151 L14 0
Cooling daytime GR2 level 4
number of operating units

152 L21 0
Cooling daytime GR2 level 5
number of operating units

153 L22 0
Cooling daytime GR2 level 6
number of operating units

154 L23 0
Cooling daytime GR2 level 7
number of operating units

155 L24 0
Cooling daytime GR2 level 8
number of operating units

156 L31 0
Cooling daytime GR2 level 9
number of operating units

157 L32 0
Cooling daytime GR2 level 10
number of operating units

158 L33 0
Cooling daytime GR2 level 11
number of operating units

159 L34 0
Cooling daytime GR2 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.

160 L11 0
Cooling daytime GR3 level 1
number of operating units

161 L12 0
Cooling daytime GR3 level 2
number of operating units

162 L13 0
Cooling daytime GR3 level 3
number of operating units

163 L14 0
Cooling daytime GR3 level 4
number of operating units

164 L21 0
Cooling daytime GR3 level 5
number of operating units

165 L22 0
Cooling daytime GR3 level 6
number of operating units

166 L23 0
Cooling daytime GR3 level 7
number of operating units

167 L24 0
Cooling daytime GR3 level 8
number of operating units

168 L31 0
Cooling daytime GR3 level 9
number of operating units

169 L32 0
Cooling daytime GR3 level 10
number of operating units

170 L33 0
Cooling daytime GR3 level 11
number of operating units

171 L34 0
Cooling daytime GR3 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
sequential or rotation.

172 L11 0
Cooling daytime GR4 level 1
number of operating units

173 L12 0
Cooling daytime GR4 level 2
number of operating units

174 L13 0
Cooling daytime GR4 level 3
number of operating units

175 L14 0
Cooling daytime GR4 level 4
number of operating units

176 L21 0
Cooling daytime GR4 level 5
number of operating units

177 L22 0
Cooling daytime GR4 level 6
number of operating units

178 L23 0
Cooling daytime GR4 level 7
number of operating units

179 L24 0
Cooling daytime GR4 level 8
number of operating units

180 L31 0
Cooling daytime GR4 level 9
number of operating units

GPX 6 PXN
181 L32 0
Cooling daytime GR4 level 10
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr5, Gr6 is set by LPX.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
93
(10/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

182 L33 0
Cooling daytime GR4 level 11
number of operating units

183 L34 0
Cooling daytime GR4 level 12
number of operating units




184 SCN unit 0
Cooling nighttime sequential
update step
When Sequential method with
base unit changeover is
adopted, change the value other
than 0. While in the group OFF
mode, the ON sequence is
shifted for the number of
equipment specified here.

185 JCN 01 1
Cooling nighttime No.01
operation sequence

186 JCN 02 2
Cooling nighttime No.02
operation sequence

187 JCN 03 3
Cooling nighttime No.03
operation sequence

188 JCN 04 4
Cooling nighttime No.04
operation sequence

189 JCN 05 5
Cooling nighttime No.05
operation sequence

190 JCN 06 6
Cooling nighttime No.06
operation sequence

191 JCN 07 7
Cooling nighttime No.07
operation sequence

192 JCN 08 8
Cooling nighttime No.08
operation sequence
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
sequential or rotation.

197 L11 1
Cooling nighttime GR1 level 1
number of operating units

198 L12 2
Cooling nighttime GR1 level 2
number of operating units

199 L13 3
Cooling nighttime GR1 level 3
number of operating units

200 L14 4
Cooling nighttime GR1 level 4
number of operating units

201 L21 5
Cooling nighttime GR1 level 5
number of operating units

202 L22 6
Cooling nighttime GR1 level 6
number of operating units

203 L23 7
Cooling nighttime GR1 level 7
number of operating units

204 L24 8
Cooling nighttime GR1 level 8
number of operating units

205 L31 9
Cooling nighttime GR1 level 9
number of operating units

206 L32 10
Cooling nighttime GR1 level 10
number of operating units

207 L33 11
Cooling nighttime GR1 level 11
number of operating units

208 L34 12
Cooling nighttime GR1 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
sequential or rotation.

209 L11 0
Cooling nighttime GR2 level 1
number of operating units

210 L12 0
Cooling nighttime GR2 level 2
number of operating units

211 L13 0
Cooling nighttime GR2 level 3
number of operating units

212 L14 0
Cooling nighttime GR2 level 4
number of operating units

213 L21 0
Cooling nighttime GR2 level 5
number of operating units

214 L22 0
Cooling nighttime GR2 level 6
number of operating units

215 L23 0
Cooling nighttime GR2 level 7
number of operating units

216 L24 0
Cooling nighttime GR2 level 8
number of operating units

217 L31 0
Cooling nighttime GR2 level 9
number of operating units

GPX 6 PXN
218 L32 0
Cooling nighttime GR2 level 10
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
sequential or rotation.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
94
(11/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

219 L33 0
Cooling nighttime GR2 level 11
number of operating units

220 L34 0
Cooling nighttime GR2 level 12
number of operating units


221 L11 0
Cooling nighttime GR3 level 1
number of operating units

222 L12 0
Cooling nighttime GR3 level 2
number of operating units

223 L13 0
Cooling nighttime GR3 level 3
number of operating units

224 L14 0
Cooling nighttime GR3 level 4
number of operating units

225 L21 0
Cooling nighttime GR3 level 5
number of operating units

226 L22 0
Cooling nighttime GR3 level 6
number of operating units

227 L23 0
Cooling nighttime GR3 level 7
number of operating units

228 L24 0
Cooling nighttime GR3 level 8
number of operating units

229 L31 0
Cooling nighttime GR3 level 9
number of operating units

230 L32 0
Cooling nighttime GR3 level 10
number of operating units

231 L33 0
Cooling nighttime GR3 level 11
number of operating units

232 L34 0
Cooling nighttime GR3 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
sequential or rotation

233 L11 0
Cooling nighttime GR4 level 1
number of operating units

234 L12 0
Cooling nighttime GR4 level 2
number of operating units

235 L13 0
Cooling nighttime GR4 level 3
number of operating units

236 L14 0
Cooling nighttime GR4 level 4
number of operating units

237 L21 0
Cooling nighttime GR4 level 5
number of operating units

238 L22 0
Cooling nighttime GR4 level 6
number of operating units

239 L23 0
Cooling nighttime GR4 level 7
number of operating units

240 L24 0
Cooling nighttime GR4 level 8
number of operating units

241 L31 0
Cooling nighttime GR4 level 9
number of operating units

242 L32 0
Cooling nighttime GR4 level 10
number of operating units

243 L33 0
Cooling nighttime GR4 level 11
number of operating units

GPX 6 PXN
244 L34 0
Cooling nighttime GR4 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
sequential or rotation.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
95
(12/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
13 TYP01 0
No.1 Thermal Source equipment
type (0 - 4)
14 TYP02 0
No.2 Thermal Source equipment
type (0 - 4)
15 TYP03 0
No.3 Thermal Source equipment
type (0 - 4)
16 TYP04 0
No.4 Thermal Source equipment
type (0 - 4)
17 TYP05 0
No.5 Thermal Source equipment
type (0 - 4)
18 TYP06 0
No.6 Thermal Source equipment
type (0 - 4)
19 TYP07 0
No.7 Thermal Source equipment
type (0 - 4)
20 TYP08 0
No.8 Thermal Source equipment
type (0 - 4)
21 TYP09 0
No.9 Thermal Source equipment
type (0 - 4)
22 TYP10 0
No.10 Thermal Source equipment
type (0 - 4)
23 TYP11 0
No.11 Thermal Source equipment
type (0 - 4)
24 TYP12 0
No.12 Thermal Source equipment
type (0 - 4)
It is not used for the
sequence control
frequently.
0: Pump
1: Heat pump chiller
2: Absorption
Chilled/Hot Water
Generator
3: Turbo chiller
4: Heat exchanger
25 TNN01 min 0 No.1 Restart prevent time (0 - 1440)
26 TNN02 min 0 No.2 Restart prevent time (0 - 1440)
27 TNN03 min 0 No.3 Restart prevent time (0 - 1440)
28 TNN04 min 0 No.4 Restart prevent time (0 - 1440)
29 TNN05 min 0 No.5 Restart prevent time (0 - 1440)
30 TNN06 min 0 No.6 Restart prevent time (0 - 1440)
31 TNN07 min 0 No.7 Restart prevent time (0 - 1440)
32 TNN08 min 0 No.8 Restart prevent time (0 - 1440)
33 TNN09 min 0 No.9 Restart prevent time (0 - 1440)
34 TNN10 min 0 No.10 Restart prevent time (0 - 1440)
35 TNN11 min 0 No.11 Restart prevent time (0 - 1440)
36 TNN12 min 0 No.12 Restart prevent time (0 - 1440)
Can set using OI as "MAIN
MENU" - "Thermal Source"
- "Sequential Control
Parameter"..
37 TFN01 min 0 No.1 Minimum stop time (0 - 1440)
38 TFN02 min 0 No.2 Minimum stop time (0 - 1440)
39 TFN03 min 0 No.3 Minimum stop time (0 - 1440)
40 TFN04 min 0 No.4 Minimum stop time (0 - 1440)
41 TFN05 min 0 No.5 Minimum stop time (0 - 1440)
42 TFN06 min 0 No.6 Minimum stop time (0 - 1440)
43 TFN07 min 0 No.7 Minimum stop time (0 - 1440)
44 TFN08 min 0 No.8 Minimum stop time (0 - 1440)
45 TFN09 min 0 No.9 Minimum stop time (0 - 1440)
46 TFN10 min 0 No.10 Minimum stop time (0 - 1440)
47 TFN11 min 0 No.11 Minimum stop time (0 - 1440)
48 TFN12 min 0 No.12 Minimum stop time (0 - 1440)
Can set using OI as "MAIN
MENU" - "Thermal Source"
- "Sequential Control
Parameter".
49 TWS01 min 5
No.1 Thermal Source Startup time
(0 - 1440)
50 TWS02 min 5
No.2 Thermal Source Startup time
(0 - 1440)
51 TWS03 min 5
No.3 Thermal Source Startup time
(0 - 1440)
52 TWS04 min 5
No.4 Thermal Source Startup time
(0 - 1440)
53 TWS05 min 5
No.5 Thermal Source Startup time
(0 - 1440)

LPX 6 PXN
54 TWS06 min 5
No.6 Thermal Source Startup time
(0 - 1440)
Can set using OI as "MAIN
MENU" - "Thermal Source"
- "Sequential Control
Parameter".
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
96
(13/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
55 TWS07 min 5
No.7 Thermal Source Startup time
(0 - 1440)
56 TWS08 min 5
No.8 Thermal Source Startup time
(0 - 1440)
57 TWS09 min 5
No.9 Thermal Source Startup time
(0 - 1440)
58 TWS10 min 5
No.10 Thermal Source Startup time
(0 - 1440)
59 TWS11 min 5
No.11 Thermal Source Startup time
(0 - 1440)
60 TWS12 min 5
No.12 Thermal Source Startup time
(0 - 1440)

61 TWR01 min 0 No.1 Remain run time (0 - 1440)
62 TWR02 min 0 No.2 Remain run time (0 - 1440)
63 TWR03 min 0 No.3 Remain run time (0 - 1440)
64 TWR04 min 0 No.4 Remain run time (0 - 1440)
65 TWR05 min 0 No.5 Remain run time (0 - 1440)
66 TWR06 min 0 No.6 Remain run time (0 - 1440)
67 TWR07 min 0 No.7 Remain run time (0 - 1440)
68 TWR08 min 0 No.8 Remain run time (0 - 1440)
69 TWR09 min 0 No.9 Remain run time (0 - 1440)
70 TWR10 min 0 No.10 Remain run time (0 - 1440)
71 TWR11 min 0 No.11 Remain run time (0 - 1440)
72 TWR12 min 0 No.12 Remain run time (0 - 1440)
Can set using OI as "MAIN
MENU" - "Thermal Source"
- "Sequential Control
Parameter".
73 HIL01 % 0
No.1 Sequence control high limit
ratio
74 HIL02 % 0
No.2 Sequence control high limit
ratio
75 HIL03 % 0
No.3 Sequence control high limit
ratio
76 HIL04 % 0
No.4 Sequence control high limit
ratio
77 HIL05 % 0
No.5 Sequence control high limit
ratio
78 HIL06 % 0
No.6 Sequence control high limit
ratio

79 HIL07 % 0
No.7 Sequence control high limit
ratio

80 HIL08 % 0
No.8 Sequence control high limit
ratio

81 HIL09 % 0
No.9 Sequence control high limit
ratio

82 HIL10 % 0
No.10 Sequence control high limit
ratio

83 HIL11 % 0
No.11 Sequence control high limit
ratio

84 HIL12 % 0
No.12 Sequence control high limit
ratio
Since capacity of pump
does not depend on the
outdoor temperature and it
hardly require the units
adjustment, the Hi limit is
set to 0.



85 LOL01 % 0
No.1 Sequence control LO limit
ratio

86 LOL02 % 0
No.2 Sequence control LO limit
ratio

87 LOL03 % 0
No.3 Sequence control LO limit
ratio

88 LOL04 % 0
No.4 Sequence control LO limit
ratio

89 LOL05 % 0
No.5 Sequence control LO limit
ratio



LPX 6 PXN
90 LOL06 % 0
No.6 Sequence control LO limit
ratio
Since capacity of pump
does not depend on the
outdoor temperature and it
hardly require the units
adjustment, the Hi limit is
set to 0.
If the sequence
control decrease
point calculation
method is
(LP:013(NJP))=1, the
Lo limit ratio is set
equal to the
Differential, it is not
required to set the Lo
limit ratio.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
97
(14/7)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
91 LOL07 % 0
No.7 Sequence control LO limit
ratio
92 LOL08 % 0
No.8 Sequence control LO limit
ratio
93 LOL09 % 0
No.9 Sequence control LO limit
ratio
94 LOL10 % 0
No.10 Sequence control LO
limit ratio
95 LOL10 % 0
No.11 Sequence control LO
limit ratio
96 LOL12 % 0
No.12 Sequence control LO
limit ratio

97 DIF01 % 20
No.1 Sequence control
Differential
98 DIF02 % 20
No.2 Sequence control
Differential
99 DIF03 % 20
No.3 Sequence control
Differential
100 DIF04 % 20
No.4 Sequence control
Differential
101 DIF05 % 20
No.5 Sequence control
Differential
102 DIF06 % 20
No.6 Sequence control
Differential
103 DIF07 % 20
No.7 Sequence control
Differential
104 DIF08 % 20
No.8 Sequence control
Differential
105 DIF09 % 20
No.9 Sequence control
Differential
106 DIF10 % 20
No.10 Sequence control
Differential
107 DIF11 % 20
No.11 Sequence control
Differential
108 DIF12 % 20
No.12 Sequence control
Differential
It is an operation gap will be
used at the Thermal Source
decrease capacity decision. If
the sequence control decrease
method is "1" (energy saving
precedence), the recommended
value is 20 % or so.
If the sequence control
decrease method is "0" (stability
precedence), the recommended
value is 5 - 10 % or so.
When the operating
sequence method is
Sequential
method/Rotation
method/Program method
(Sequence control
decrease limit operation
method = 0), it is used.
If Program method
(Sequence control
decrease limit operation
method = 1) selected, set
at LP15 - 58.


109 GR 01 1 No.01 Heating group No.

110 GR 02 1
No.02 Heating group No.

111 GR 03 1
No.03 Heating group No.

112 GR 04 1
No.04 Heating group No.

113 GR 05 1
No.05 Heating group No.

114 GR 06 1
No.06 Heating group No.

115 GR 07 1
No.07 Heating group No.

116 GR 08 1
No.08 Heating group No.
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.









121 GR 01 1 No.01 Cooling group No.

122 GR 02 1
No.02 Cooling group No.

123 GR 03 1
No.03 Cooling group No.

124 GR 04 1
No.04 Cooling group No.

125 GR 05 1
No.05 Cooling group No.

126 GR 06 1
No.06 Cooling group No.

127 GR 07 1
No.07 Cooling group No.

LPX 6 PXN
128 GR 08 1
No.08 Cooling group No.
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.








Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
98
(15/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

133 L11 0
Heating daytime GR5 level 1
number of operating units

134 L12 0
Heating daytime GR5 level 2
number of operating units

135 L13 0
Heating daytime GR5 level 3
number of operating units

136 L14 0
Heating daytime GR5 level 4
number of operating units

137 L21 0
Heating daytime GR5 level 5
number of operating units

138 L22 0
Heating daytime GR5 level 6
number of operating units

139 L23 0
Heating daytime GR5 level 7
number of operating units

140 L24 0
Heating daytime GR5 level 8
number of operating units

141 L31 0
Heating daytime GR5 level 9
number of operating units

142 L32 0
Heating daytime GR5 level 10
number of operating units

143 L33 0
Heating daytime GR5 level 11
number of operating units

144 L34 0
Heating daytime GR5 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 is set by LPX.

145 L11 0
Heating daytime GR6 level 1
number of operating units

146 L12 0
Heating daytime GR6 level 2
number of operating units

147 L13 0
Heating daytime GR6 level 3
number of operating units

148 L14 0
Heating daytime GR6 level 4
number of operating units

149 L21 0
Heating daytime GR6 level 5
number of operating units

150 L22 0
Heating daytime GR6 level 6
number of operating units

151 L23 0
Heating daytime GR6 level 7
number of operating units

152 L24 0
Heating daytime GR6 level 8
number of operating units

153 L31 0
Heating daytime GR6 level 9
number of operating units

154 L32 0
Heating daytime GR6 level 10
number of operating units

155 L33 0
Heating daytime GR6 level 11
number of operating units

156 L34 0
Heating daytime GR6 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 is set by LPX.

157 L11 0
Heating nighttime GR5 level 1
number of operating units

158 L12 0
Heating nighttime GR5 level 2
number of operating units

159 L13 0
Heating nighttime GR5 level 3
number of operating units

160 L14 0
Heating nighttime GR5 level 4
number of operating units

161 L21 0
Heating nighttime GR5 level 5
number of operating units

162 L22 0
Heating nighttime GR5 level 6
number of operating units

163 L23 0
Heating nighttime GR5 level 7
number of operating units

164 L24 0
Heating nighttime GR5 level 8
number of operating units

165 L31 0
Heating nighttime GR5 level 9
number of operating units

166 L32 0
Heating nighttime GR5 level 10
number of operating units

LPX 6 PXN
167 L33 0
Heating nighttime GR5 level 11
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 is set by LPX.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
99
(16/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

168 L34 0
Heating nighttime GR5 level 12
number of operating units


169 L11 0
Heating nighttime GR6 level 1
number of operating units

170 L12 0
Heating nighttime GR6 level 2
number of operating units

171 L13 0
Heating nighttime GR6 level 3
number of operating units

172 L14 0
Heating nighttime GR6 level 4
number of operating units

173 L21 0
Heating nighttime GR6 level 5
number of operating units

174 L22 0
Heating nighttime GR6 level 6
number of operating units

175 L23 0
Heating nighttime GR6 level 7
number of operating units

176 L24 0
Heating nighttime GR6 level 8
number of operating units

177 L31 0
Heating nighttime GR6 level 9
number of operating units

178 L32 0
Heating nighttime GR6 level 10
number of operating units

179 L33 0
Heating nighttime GR6 level 11
number of operating units

180 L34 0
Heating nighttime GR6 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 is set by LPX.

181 L11 0
Cooling daytime GR5 level 1
number of operating units

182 L12 0
Cooling daytime GR5 level 2
number of operating units

183 L13 0
Cooling daytime GR5 level 3
number of operating units

184 L14 0
Cooling daytime GR5 level 4
number of operating units

185 L21 0
Cooling daytime GR5 level 5
number of operating units

186 L22 0
Cooling daytime GR5 level 6
number of operating units

187 L23 0
Cooling daytime GR5 level 7
number of operating units

188 L24 0
Cooling daytime GR5 level 8
number of operating units

189 L31 0
Cooling daytime GR5 level 9
number of operating units

190 L32 0
Cooling daytime GR5 level 10
number of operating units

191 L33 0
Cooling daytime GR5 level 11
number of operating units

192 L34 0
Cooling daytime GR5 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 is set by LPX.

193 L11 0
Cooling daytime GR6 level 1
number of operating units

194 L12 0
Cooling daytime GR6 level 2
number of operating units

195 L13 0
Cooling daytime GR6 level 3
number of operating units

196 L14 0
Cooling daytime GR6 level 4
number of operating units

197 L21 0
Cooling daytime GR6 level 5
number of operating units

198 L22 0
Cooling daytime GR6 level 6
number of operating units

199 L23 0
Cooling daytime GR6 level 7
number of operating units

200 L24 0
Cooling daytime GR6 level 8
number of operating units

201 L31 0
Cooling daytime GR6 level 9
number of operating units

LPX 6 PXN
202 L32 0
Cooling daytime GR6 level 10
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 is set by LPX.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
100
(17/17)
Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

203 L33 0
Cooling daytime GR6 level 11
number of operating units

204 L34 0
Cooling daytime GR6 level 12
number of operating units


205 L11 0
Cooling nighttime GR5 level 1
number of operating units

206 L12 0
Cooling nighttime GR5 level 2
number of operating units

207 L13 0
Cooling nighttime GR5 level 3
number of operating units

208 L14 0
Cooling nighttime GR5 level 4
number of operating units

209 L21 0
Cooling nighttime GR5 level 5
number of operating units

210 L22 0
Cooling nighttime GR5 level 6
number of operating units

211 L23 0
Cooling nighttime GR5 level 7
number of operating units

212 L24 0
Cooling nighttime GR5 level 8
number of operating units

213 L31 0
Cooling nighttime GR5 level 9
number of operating units

214 L32 0
Cooling nighttime GR5 level 10
number of operating units

215 L33 0
Cooling nighttime GR5 level 11
number of operating units

216 L34 0
Cooling nighttime GR5 level 12
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 is set by LPX.

217 L11 0
Cooling nighttime GR6 level 1
number of operating units

218 L12 0
Cooling nighttime GR6 level 2
number of operating units

219 L13 0
Cooling nighttime GR6 level 3
number of operating units

220 L14 0
Cooling nighttime GR6 level 4
number of operating units

221 L21 0
Cooling nighttime GR6 level 5
number of operating units

222 L22 0
Cooling nighttime GR6 level 6
number of operating units

223 L23 0
Cooling nighttime GR6 level 7
number of operating units

224 L24 0
Cooling nighttime GR6 level 8
number of operating units

225 L31 0
Cooling nighttime GR6 level 9
number of operating units

226 L32 0
Cooling nighttime GR6 level 10
number of operating units

227 L33 0
Cooling nighttime GR6 level 11
number of operating units

228 L34 0
Cooling nighttime GR6 level 12
number of operating units

LPX 6 PXN
202 L32 0
Cooling daytime GR6 level 10
number of operating units
If OI is not used. set the
parameter using PC-MMI.
Set the parameter when the
operation sequence method is
the program mode.
Gr1Gr4 is set by LPX.

Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
101

<< General >>
This panel is to change the output commander of the Thermal Source to DD2 when either of
following condition is met: Group command is ON, Auto/manual changeover is manual, or
Forced OFF DI is ON.
Affected Instrumentation Code
All machine types

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
































29. Panel 22 - Commander Changeover (No.1 - 8)
No parameter to be updated.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
102

<< General >>
This panel is to output OFF command to the failed thermal equipment by the Failure auto
reset function.
Affected Instrumentation Code
All machine types

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions






























30. Panel 23 - Failure Auto Reset Output
No parameter to be updated.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
103

<< General >>
This panel is to output commands to the equipments considering the output of the sequence
control panel and the Forced OFF DI.
Affected Instrumentation Code
All machine types

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions






























31. Panel 24 - ON/OFF Equipment (No.1 - 8)
No parameter to be updated.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
104

<< General >>
This panel is to output the recovery command to the thermal equipment when PMX-4 is
recovered from power failure to power on by the commercial power.
Affected Instrumentation Code
All machine types

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions































32. Panel 28 - Power Restoration Process (No.1 - 8)
No parameter to be updated.
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
105

<< General >>
When Forced OFF DI is activated, Thermal Source equipments are stopped forcibly. Then the
substitute equipments are ON after the waiting effect time has passed. Also while in waiting
effect status after the Forced OFF DI was disabled, then the waiting effect time has passed,
sequence control will be performed. Therefore this panel enables to follow the load variance
while in the waiting effect by doing ON/OFF decision when the Forced OFF DI status is
changed.
Affected Instrumentation Code
All machine types



Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions
1 AND V2 0
No.1 ON/OFF decision while Forced off is enabled
Set "1" to enable the ON/OFF decision.
3 AND V2 0
No.1 ON/OFF decision while Forced off is disabled
Set "1" to enable the ON/OFF decision.
6 AND V2 0
No.2 ON/OFF decision while Forced off is enabled
Set "1" to enable the ON/OFF decision.
8 AND V2 0
No.2 ON/OFF decision while Forced off is disabled
Set "1" to enable the ON/OFF decision.
11 AND V2 0
No.3 ON/OFF decision while Forced off is enabled
Set "1" to enable the ON/OFF decision.
13 AND V2 0
No.3 ON/OFF decision while Forced off is disabled
Set "1" to enable the ON/OFF decision.
16 AND V2 0
No.4 ON/OFF decision while Forced off is enabled
Set "1" to enable the ON/OFF decision.
18 AND V2 0
No.4 ON/OFF decision while Forced off is disabled
Set "1" to enable the ON/OFF decision.
21 AND V2 0
No.5 ON/OFF decision while Forced off is enabled
Set "1" to enable the ON/OFF decision.
23 AND V2 0
No.5 ON/OFF decision while Forced off is disabled
Set "1" to enable the ON/OFF decision.
26 AND V2 0
No.6 ON/OFF decision while Forced off is enabled
Set "1" to enable the ON/OFF decision.
28 AND V2 0
No.6 ON/OFF decision while Forced off is disabled
Set "1" to enable the ON/OFF decision.
31 AND V2 0
No.7 ON/OFF decision while Forced off is enabled
Set "1" to enable the ON/OFF decision.
33 AND V2 0
No.7 ON/OFF decision while Forced off is disabled
Set "1" to enable the ON/OFF decision.
36 AND V2 0
No.8 ON/OFF decision while Forced off is enabled
Set "1" to enable the ON/OFF decision.
38 AND V2 0
No.8 ON/OFF decision while Forced off is disabled
Set "1" to enable the ON/OFF decision.
OND 0
Delay time (On-delay time)
Can't be set.

42 TMR
OFD 10
Delay time (Off-delay time)
Set the delay time according to the number units that are operated
by the Forced OFF DI simultaneously. Calculate the minimum
required delay time by the following arithmetic expression.

Delay time (sec) Panel execution cycle (10 sec)
+ Maximum value of sequential startup and stop
x (Maximum number of equipments that are Forced OFF DI
operated - 1)
Set 40 sec or more to the following value: Sequential startup
(default: 30 sec), sequential stop (default: 30 sec), and
Delay time of the Forced OFF DI when maximum number of
units is 2 that can be input simultaneously.

GP
43 TMR OFD 0
Delay time (Off-delay time)
Can't be set.
33. Panel 29 - ON/OFF Decision
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
106

<< General >>
This panel is to output the insufficient capacity or the capacity depletion of the Thermal Source
detected while sequence control to the corresponding point (insufficient capacity, capacity
depletion).
Affected Instrumentation Code
All machine types

Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions






























34. Panel 30 - Caution Output
No parameter to be updated
Chapter 3 Parameter Description
AB-7118_Rev.0.0 PARAMATRIX4 Pump/Chiller Controller Parameter Description
107

<< General >>
The software, which does not affect the existing panels (e.g., control outlet temperature of
heat exchanger, attach flow meter to each thermal source equipment, calculate energy each
thermal source), can be added on Panel 3133.
Affected Instrumentation Code
All machine types



Severity Type
Execution
Order
Module No.
Input
Symbol
Unit
Default
Value
Changed
Value
Parameter Name and Descriptions

































35. Panel 31 to 33 - Free Panel


Specifications are subject to change without notice.


Building Systems Company

http://www.azbil.com/

Rev. 0.0 Jun. 2012 AB-7118
(J: AI-7118 Rev. 0.0) Printed in Japan.