Carrier AHUBuilder February 14, 2014 Page 1 Job Name Mark for Untitled UMA-01

Unit Parameters Aero Indoor Air Handler Unit Size: Size 36 Insulation: R-13 Double Wall Sealed Panel Exterior Finish: Galvanized Exterior Panels Interior Finish: Galvanized Interior Panels Level I Thermal Break 6 inch tall Base Rail Filter Mixing Box Damper: Rear Premium Parallel Top: Blank Opening 2In. Angle Filter Qty (16) 20in. x 25in. Door Left Side Bag/Cartridge Filter Shipping Split After Bag/Cartridge Filter 6 - 12 IN. Side Loading Field Supplied Bag MERV 14 Filter Qty (4) 12in. x 24in. Qty (8) 24in. x 24in. Door Left Side Direct Expansion Coil 304 Stainless Steel Drain Pan Right Side Direct Expansion 36.67 sq.ft 4 Row 8 FPI Intertwined FullCircuit Coil Connection Right Side 1/2 in. Tube Diameter AL fins Galv. Casing No Coating R-410A SUBJECT TO CHANGE WITHOUT NOTICE v6.31 09/16/13

Carrier AHUBuilder February 14, 2014 Page 2 Job Name Mark for Untitled UMA-01

Cooling Performance Ratings Type: 1/2 inch Tube Altitude, ft 7380 Face Vel., fpm 429.2 Site Airflow, CFM 15740 Std. Airflow, CFM 11971 Total Clg. Cap, MBH 467.38 Sen. Clg. Cap, MBH 375.66 0.25 Air Friction, in wg Cond. EAT, F 95.0 Suction Loss, F 2.7 SST(Upstream Coil), F 48.4 SST(Downstream Coil), F 46.0 SCT(Upstream Coil), F 122.4 SCT(Downstream Coil), F 117.7 Note: * Nozzle Factory Supplied and Installed. * Nozzle NOT sized for available unloading.

Tons/Circuit (Upstream Coil) 0.84 Tons/Circuit (Downstream Coil) 0.93 Compressor, kW 36.7 EADB, F 89.00 EAWB, F 67.00 Ent. Enthalpy, BTU/lb 36.38 LADB, F 60.30 LAWB, F 56.80 Lvg. Enthalpy, BTU/lb 27.70 Condensing Unit 38AP040(D) Nozzle Size (Upstream/Downstream) E12 Number of TXV's (Upstream/Downstream) 4 TXV Tonnage (Upstream/Downstream) 8/8

* Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410. Certified units may be found in AHRI Directory (www.ahridirectory.org).

Door Left Side Blow-Thru Supply Fan Shipping Split After Rear Inlet Integral Diffuser Fan Sled AirFoil B AFMV01241 2176 fanRPM Class II Top Horiz. Front Discharge Right Side Fan Motor Location Spring Fan Isolation Motor 25 HP Premium Efficiency ODP 208-230/460 3Ph 60Hz 1800 RPM Manufacturer - Generic Frame Size - 284T Motor Shaft Diameter (in.) - 1.875 Voltage Selected - 460/3/60 Full Load Amps - 29.6 MCA - 37.0 MOCP - 60 Efficiency - 93.6% SUBJECT TO CHANGE WITHOUT NOTICE v6.31 09/16/13

Carrier AHUBuilder February 14, 2014 Page 3 Job Name Mark for Untitled UMA-01

Belt Drive 1.2 Service Factor Fixed Pitch Drive 1 or more belts Door Right Side Door Left Side
Performance Ratings Site Airflow, CFM 15740 Altitude, ft 7380 Std. Airflow, CFM 11971 Upstream Ext. Static, in wg 1.10 DownStream Ext. Static, in wg 2.00 Clg. Coil Static, in wg 0.25 Htg. Coil Static, in wg 0.00 Acoustic Data: Freq. Disch. Inlet Casing 63 hz 104 101 97 125 hz 99 96 91 250 hz 109 103 97 500 hz 109 103 99 Other Losses, in wg 0.00 Accessories Static, in wg 1.84 Blow thru perforated plate losses, in wg 0.23 Total Static, in wg 5.42 Calculated Fan Speed, rpm 2176 Calculated Fan BHP 21.9 Static Efficiency (%) 45 1000 hz 2000 hz 4000 hz 8000 hz 97 91 89 85 91 86 84 80 85 80 78 75

HEPA Filter Hepa Filter Qty (4) 12in. x 24in. Qty (8) 24in. x 24in. Door Right Side Door Left Side Configuration Notes Discharge duct(s) must be gasketed and screwed directly to the discharge panel of the unit. Weights and Dimensions (LxWxH in ft in) 16' 9" x 9' 2" x 5' 11" ** Operating 5768 LB ** Field Installed Accessory Part Number(s) Qty 1 Filter Kit, 2'' ANG/FMB Pleated (MERV8), 39M036 Qty 1 Filter Kit, 12'' HEPA (MERV17) 99.97%, 39M036

Ordering Information

39MJ1636YHGV532BRS 39MJ23413-H-LHJN-S

Qty Qty

1 1

SUBJECT TO CHANGE WITHOUT NOTICE v6.31 09/16/13

Carrier AHUBuilder February 14, 2014 Page 4 Job Name Mark for Untitled UMA-01

39MJ3H513SK878FH8T 39MJ42BTH43JY2RQ9N 39MJ54J-2189P9DN13 39MJ6-B-NHNTTK9Y-7 31KFD39MD036522 31KFK39MH036AA2

Qty Qty Qty Qty Qty Qty

1 1 1 1 1 1

Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are provided primarily for shipping purposes, for exact dimensions, refer to submittal drawings. Shipping skids are not included. All filter media efficiency ratings are for the filter media only.

SUBJECT TO CHANGE WITHOUT NOTICE v6.31 09/16/13