Trenching: Underground Construction Manual
Trenching: Underground Construction Manual
TRENCHING
Back to MAIN INDEX Go to SECTION INDEX
DESCRIPTION Conduit ducting arrangement Conduit ducting arrangement Conduit ducting arrangement FN REGION Joint electricity, gas and Telstra Joint electricity, gas and multiple Telstra Conduit bend at pillar - sections 16mm 4 core cross road cable Conduit bend details at pillar 16mm 4 core cross road cable Conduit bend at pillar - sections 240mm 4 core cross road cable Conduit bend details at pillar 240mm 4 core cross road cable Allow bends for HV conduit road crossing Pillar base installation
DESCRIPTION MK REGION Joint electricity and Telstra Joint electricity, Telstra and gas Conduit bend at pillar - sections 16mm 4 core cross road cable Conduit bend details at pillar 16mm 4 core cross road cable
DWG
5164/1 5164/2 5164/3 5164/4 5164/5 5164/6 5164/7 5164/8 5164/9 5164/10 5164/11
Conduit bend at pillar - sections 240mm 4 core cross road cable Conduit bend details at pillar 240mm 4 core cross road cable With Gas - Conduit bends at pillar - sections 16mm 4 core cross road cable With Gas - Conduit bend details at pillar 16mm 4 core cross road cable With Gas - Conduit bends at pillar - sections 240mm 4 core cross road cable With Gas - Conduit bend details at pillar 240mm 4 core cross road cable
NQ REGION URD areas URD areas joint electricity and Telstra City and urban areas Joint electricity - Telstra URD areas general layout Conduit bend at pillar - sections 16mm 4 core cross road cable Conduit bend details at pillar 16mm 4 core cross road cable Conduit bend at pillar - sections 240mm 4 core cross road cable Conduit bend details at pillar 240mm 4 core cross road cable Pillar base installation 5163/1 5163/2 5163/3 5163/4 5163/5 5163/6 5163/7 5163/8 5163/9
A B
APPROVED
J. Brooks 11.08.10
UNDERGROUND DISTRIBUTION
TRENCHING INDEX
DATE
PASSED
c D. McKeown
T.Borg FILE: 5 54 5012 1
DRAWN
Dwg
Sh
DESCRIPTION CA REGION Conduit, trench and pillar alignment schedule Trench detail electricity and Telstra Trench detail electricity and Telstra Gladstone electricity and Telstra Conduit bends at pillar - sections 16mm 4 core cross road cable Conduit bend details at pillar 16mm 4 core cross road cable
DWG
DESCRIPTION SW REGION
DWG
Electricity and Telstra Conduit bends at pillar - sections 16mm 4 core cross road cable Conduit bend details at pillar 16mm 4 core cross road cable
Conduit bends at pillar - sections 240mm 4 core cross road cable 5167/4 Conduit bend details at pillar 240mm 4 core cross road cable 5167/5 Pillar base installation 5167/6
Conduit bends at pillar - sections 240mm 4 core cross road cable 5165/7 Conduit bend details at pillar 240mm 4 core cross road cable 5165/8 Pillar base installation 5165/9 TELECOMMUNICATION Joint electricity & Telecommunication WB REGION Electricity and Telstra Conduit bends at pillar - sections 16mm 4 core cross road cable Conduit bend details at pillar 16mm 4 core cross road cable 5166/1 5166/2 5166/3 Cable protection footpaths concrete slab detail Cable protection roadways concrete encasement detail Exclusion zone an LV pillars Pillar installation at easement or road reserve boundary Detail at pillar for future extension Underground service from overhead system service conduit bend location at pillar 5016 5017 5196/1 5196/2 5197 5187 ALL REGIONS Joing electricity - Telecommunication URD areas - General layout 5228 5249
Conduit bends at pillar - sections 240mm 4 core cross road cable 5166/4 Conduit bend details at pillar 240mm 4 core cross road cable 5166/5 Pillar base installation 5166/6
A B C D E
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING INDEX
DATE
PASSED
2.6.11
Ergon Energy Corporation Ltd
17.07.12
DRAWN
FILE: 5 54 5012 2
Dwg
Sh
DWG
DESCRIPTION Rectangular 22kV padmounted substation To suit RM6 switchgear - HV conduit location Rectangular 22kV padmounted substation 500kVA - Schneider Electric LV conduit location Rectangular 22kV padmounted substation 1000kVA - Schneider Electric LV conduit location
Front entry type conduit location & cross section 5115/1 Front entry type conduit location - ABB RMU 5115/2 Front entry type conduit location - ABB RMU 5115/3 Front entry type conduit location insect prot. cable - ABB RMU5115/4 Front entry type conduit location insect prot. cable - ABB RMU5115/5 Front entry type conduit location - FBX RMU 5115/6 Front entry type conduit location - FBX RMU 5115/7 Front entry type conduit location insect prot. cable - FBX RMU5115/8 Front entry type conduit location insect prot. cable - FBX RMU5115/9 Front entry type LV cable location - ABB RMU 5128 Front entry type HV cable location ABB SDAF3 RMU 5129 Front entry type HV cable location Magnefix RMU + T 5130 Front entry type HV cable location Magnefix RMU & SFU 5131 Front entry type HV cable location no switchgear 5160 Front entry type LV cable location - FBX RMU Front entry type HV cable location - FBX RMU 22kV PADMOUNTED SUBSTATIONS Rectangular 22kV padmounted substation conduit location and cross section Rectangular 22kV padmounted substation conduit location Rectangular 22kV padmounted substation conduit location Rectangular 22kV padmounted substation 500kVA - LV conduit location Rectangular 22kV padmounted substation 1000kVA - LV conduit location Rectangular 22kV padmounted substation 3.7m padmount length - HV conduit location Rectangular 22kV padmounted substation To suit F & G HV switchgear 5142/1 5142/2 5142/3 5142/4 5142/5 5142/6 5142/7 5268 5269
HV SWITCHGEAR ABB free standing RMU conduit location and cross section ABB free standing RMU conduit location ABB free standing RMU conduit location Insect protected 5227/1 5227/2 5227/3
HV / LV Pole termination conduit and trench detail Pole termination conduit and trench detail Pole termination conduit bend detail Pole termination conduit bend detail Distribution cabinet 6 module conduit location and cross section Distribution cabinet 6 module conduit bend details Distribution cabinet 6 module conduit location Distribution cabinet 6 module conduit location Insect protected cable Distribution cabinet 6 module LV cable location 5144/1 5144/2 5173/1 5173/2 5143/1 5143/2 5143/3 5143/4 5141
A B C D E
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING INDEX
DATE
PASSED
10.01.12
Ergon Energy Corporation Ltd
17.07.12
DRAWN
FILE: 5 54 5012 3
Dwg
Sh
NOTES: 1. Conduit and cable nearest R.P. Street Alignment only, shown. 2. Locations and depths shown to conduit ends allow minimum bending radius of cables to be achieved for connection to switchgear. Refer MATERIAL DATA drawings No. 5108 to 5111 for minimum bending radius of cables. 3. Conduit depths shown are minimum and are dimensioned from finished ground line to top of conduit. Ramp down as required. Where conduits are normally laid at a depth greater than shown, that depth should be maintained. 4. Terminate LV and HV cable conduit in line, each end of pit. 5. Provide polymeric cable protection cover (and orange caution tape) over all cable not enclosed in conduit . 6. Backfill cable pit with bedding sand. 7. LV and HV cable locations shown at Padmounted Substation are illustrative only. Refer drawings No. 5128 to 5131 & 5160. Preferred sequence of construction is to install Padmounted Substation prior to cables. R.P. Street Alignment
F
(refer sheets 2 to 9)
LV & HV cables
F
Uniculvert Foundation
Depth
Cable Pit
Base Slab
F
45
F
Conduit
UNDERGROUND DISTRIBUTION
20/11/01
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
c D. M K.
C.Lindsay
TRENCHING FRONT ENTRY 11kV PADMOUNTED SUBSTATION CONDUIT LOCATION AND CROSS SECTION
FILE: 5 54 5115 1
DRAWN
Dwg
5115
Sh
3000
Site Boundary
F
F
HV
LV
F
H.V. Conduit L.V. Conduit not shown this end of Cable Pit
11kV CABLE SIZE TRIPLEX 400mm TRIPLEX 185mm TRIPLEX 35mm DEPTH 1000 1000 Normal DIM A 400 400 0 4C 240mm SIZE
A B
PLAN VIEW
H.V. CABLE ENTERING / EXITING FROM LEFT OR LEFT & RIGHT HAND SIDE OF PADMOUNT
APPROVED
UNDERGROUND DISTRIBUTION
21/01/03
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
c D. M K.
C.Lindsay
TRENCHING - ABB RMU FRONT ENTRY 11kV PADMOUNTED SUBSTATION CONDUIT LOCATION
FILE: 5 54 5115 2
DRAWN
Dwg
F
F
300
F
L.V. Conduit H.V. Conduit not shown this end of Cable Pit
5115
Sh
3000
Site Boundary
F
F
HV
LV
F
L.V. Conduit
11kV CABLE FOOTPATH SIZE TRIPLEX 400mm TRIPLEX 185mm DEPTH 1000 1000 Normal
DEPTH Normal
PLAN VIEW H.V. CABLE ENTERING / EXITING RIGHT HAND SIDE OF PADMOUNT ONLY A B
ORIGINAL ISSUE 13.12.11 APPROVED
TRIPLEX 35mm
UNDERGROUND DISTRIBUTION
21/01/03
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
c D. M K.
C.Lindsay
TRENCHING - ABB RMU FRONT ENTRY 11kV PADMOUNTED SUBSTATION CONDUIT LOCATION
FILE: 5 54 5115 3
DRAWN
600
F
300
F
H.V. Conduit L.V. Conduit not shown this end of Cable Pit
Dwg
5115
Sh
3000
Site Boundary
F
F
HV
LV
F
H.V. Conduit L.V. Conduit not shown this end of Cable Pit
11kV INSECT PROTECTED CABLE SIZE TRIPLEX 400mm TRIPLEX 185mm TRIPLEX 35mm 1250 1250 500 0 DEPTH DIM A
A B
Cable pit End of conduit Seal around cable FOOTPATH L.V. Conduit H.V. Conduit not shown this end of Cable Pit LV INSECT PROTECTED CABLE SIZE 4C 240mm DEPTH 1100 DIM A To suit 11kV cable
PLAN VIEW H.V. CABLE ENTERING / EXITING FROM LEFT OR LEFT & RIGHT HAND SIDE OF PADMOUNT
APPROVED
UNDERGROUND DISTRIBUTION
21/01/03
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
c D. M K.
C.Lindsay
TRENCHING - ABB RMU FRONT ENTRY 11kV PADMOUNTED SUBSTATION CONDUIT LOCATION INSECT PROTECTED CABLE
FILE: 5 54 5115 4
DRAWN
Dwg
5115
F
F
Cables as required
400
F
200 Min.
Sh
3000
Site Boundary
F
F
HV
LV
F
L.V. Conduit FOOTPATH End of conduit Seal around cable 11kV INSECT PROTECTED CABLE SIZE TRIPLEX 400mm TRIPLEX 185mm TRIPLEX 35mm 1250 1250 DEPTH
H.V. Conduit L.V. Conduit not shown this end of Cable Pit
PLAN VIEW H.V. CABLE ENTERING / EXITING RIGHT HAND SIDE OF PADMOUNT ONLY
APPROVED
SIZE 4C 240mm
A B
UNDERGROUND DISTRIBUTION
21/01/03
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
c D. M K.
C.Lindsay
TRENCHING - ABB RMU FRONT ENTRY 11kV PADMOUNTED SUBSTATION CONDUIT LOCATION INSECT PROTECTED CABLE
FILE: 5 54 5115 5
DRAWN
Dwg
5115
Cable pit
Cables as required
600
200 Min.
DEPTH 1100
Sh
3000
Site Boundary
F
F
HV
LV
F
H.V. Conduit L.V. Conduit not shown this end of Cable Pit
11kV CABLE SIZE TRIPLEX 400mm TRIPLEX 185mm TRIPLEX 35mm DEPTH 1000 1000 Normal DIM A 400 400 0 4C 240mm SIZE
ORIGINAL ISSUE
PLAN VIEW
H.V. CABLE ENTERING / EXITING FROM LEFT OR LEFT & RIGHT HAND SIDE OF PADMOUNT
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING - FBX RMU FRONT ENTRY 11kV PADMOUNTED SUBSTATION CONDUIT LOCATION
FILE: 5 54 5115 6
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
F
F
300
F
L.V. Conduit H.V. Conduit not shown this end of Cable Pit
5115
Sh
3000
Site Boundary
F
F
HV
LV
F
L.V. Conduit
11kV CABLE FOOTPATH SIZE TRIPLEX 400mm TRIPLEX 185mm DEPTH 1000 1000 Normal
DEPTH Normal
PLAN VIEW H.V. CABLE ENTERING / EXITING RIGHT HAND SIDE OF PADMOUNT ONLY A
ORIGINAL ISSUE APPROVED
TRIPLEX 35mm
UNDERGROUND DISTRIBUTION
TRENCHING - FBX RMU FRONT ENTRY 11kV PADMOUNTED SUBSTATION CONDUIT LOCATION
FILE: 5 54 5115 7
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
600
F
300
F
H.V. Conduit L.V. Conduit not shown this end of Cable Pit
Dwg
5115
Sh
3000
Site Boundary
F
F
HV
F
LV 200 Min.
F
H.V. Conduit L.V. Conduit not shown this end of Cable Pit
11kV INSECT PROTECTED CABLE SIZE TRIPLEX 400mm TRIPLEX 185mm TRIPLEX 35mm 1250 1250 500 0 DEPTH DIM A
ORIGINAL ISSUE
Cable pit End of conduit Seal around cable FOOTPATH L.V. Conduit H.V. Conduit not shown this end of Cable Pit LV INSECT PROTECTED CABLE SIZE 4C 240mm DEPTH 1100 DIM A To suit 11kV cable
PLAN VIEW H.V. CABLE ENTERING / EXITING FROM LEFT OR LEFT & RIGHT HAND SIDE OF PADMOUNT
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING - FBX RMU FRONT ENTRY 11kV PADMOUNTED SUBSTATION CONDUIT LOCATION INSECT PROTECTED CABLE
FILE: 5 54 5115 8
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5115
F
F
400
F
Sh
3000
Site Boundary
F
F
HV
LV
F
L.V. Conduit FOOTPATH End of conduit Seal around cable 11kV INSECT PROTECTED CABLE SIZE TRIPLEX 400mm TRIPLEX 185mm TRIPLEX 35mm 1250 1250 DEPTH
H.V. Conduit L.V. Conduit not shown this end of Cable Pit
PLAN VIEW H.V. CABLE ENTERING / EXITING RIGHT HAND SIDE OF PADMOUNT ONLY
APPROVED
SIZE 4C 240mm
ORIGINAL ISSUE
UNDERGROUND DISTRIBUTION
TRENCHING - FBX RMU FRONT ENTRY 11kV PADMOUNTED SUBSTATION CONDUIT LOCATION INSECT PROTECTED CABLE
FILE: 5 54 5115 9
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5115
Cable pit
600
200 Min.
DEPTH 1100
Sh
FOOTPATH
3000
FOOTPATH
LV cable
F
LV cable 1st cable position 2nd cable position 3rd cable position 4th cable position Cables as reqd (Refer design)
100F
100 F
1230
1100
80
BACK of LV cable
100kVA A B
ORIGINAL ISSUE 29.12.11 APPROVED
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
c D. M K.
C.Lindsay
DRAWN
580 (ref)
560
560
TRENCHING - ABB SAFELINK RMU FRONT ENTRY 11kV PADMOUNTED SUBSTATION LV CABLE LOCATION
FILE: 5 54 5128 1
Dwg
5128
Cable position
Sh
3000
F
F
F F F
2800
2800
F
F
F F
6000
F
550
F
2nd conduit position 3rd conduit position 4th conduit position 4000 H.V. 5th conduit position 6th conduit position
320
F F
Site Boundary
R.P.Street Alignment
UNDERGROUND DISTRIBUTION
TRENCHING RECTANGULAR 22kV PADMOUNTED SUBSTATION 500kVA - LV CONDUIT LOCATION
FILE: 5 54 5142 4
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5142
FOOTPATH
Sh
F
F
F F
100 Dia 1830 Radius, 90 vertical bends to 50mm Min. above concrete level.
6000
F
550
1st conduit position 2nd conduit position 3rd conduit position 4000 H.V.
Cable Pit
320
F F
Site Boundary
R.P.Street Alignment
UNDERGROUND DISTRIBUTION
TRENCHING RECTANGULAR 22kV PADMOUNTED SUBSTATION 1000kVA - LV CONDUIT LOCATION
FILE: 5 54 5142 5
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5142
FOOTPATH
Sh
100 100
F
F
F F
100 Dia 1830 Radius, 90 vertical bends to 50mm Min. above concrete level.
6000
F
H.V.
F
L.V.
F
4 0 0 0
5 0 0
Cable Pit Cable exit direction as required. 450 max. wide cable trench where service platforms required. F
F
F
1 0 0 0 F
1 0 0 0 F
150
A B C D
UNDERGROUND DISTRIBUTION
TRENCHING RECTANGULAR 22kV PADMOUNTED SUBSTATION
F & G HV SWITCHGEAR - HV CONDUIT LOCATION
DATE
PASSED
11.07.12
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
FILE: 5 54 5142 7
Dwg
5142
F
F F
FOOTPATH
F Site Boundary
F
F
F
R.P.Street Alignment
Sh
6000
F
H.V.
F
360 365
700
4 0 0 0
L.V.
F 4 0 0
Cable Pit Cable exit direction as required. 450 max. wide cable trench where service platforms required. F
F
F
1 0 0 0 F
1 0 0 0 F
150
ORIGINAL ISSUE
UNDERGROUND DISTRIBUTION
TRENCHING RECTANGULAR 22kV PADMOUNTED SUBSTATION SUIT RM6 SWITCHGEAR - HV CONDUIT LOCATION
FILE: 5 54 5142 8
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5142
F
F F
FOOTPATH
F Site Boundary
F
F
R.P.Street Alignment
Sh
NOTES: LV CABLE 1. Locate cable on opposite side of pole to oncoming traffic where possible. 2. Excessive excavation at the pole base may disturb pole foundation. Avoid excavating in areas shown. 3. Location of conduit end and depth of excavation shown allow minimum bending radius of cable to be achieved. 4. Provide polymeric cable protection cover and orange caution tape to all conduit/cable outside Electricity Footpath Allocation. 5. Refer drawing No. 5173 for detail of allowable cables and bends at pole termination. 11kV CABLE CABLE DETAIL 35mm TRIPLEX 185mm TRIPLEX 35mm TRIPLEX Insect Protected 1.5m 185mm TRIPLEX Insect Protected 240mm Cu TRIPLEX Insect Protected 400mm Al TRIPLEX 400mm Cu TRIPLEX Insect Protected 2.0m 2.0m 2.0m 1.05m 1.2m 1.2m 1.2m DIMENSION A 1.5m 1.05m Normal trench depth DIMENSION B Normal trench depth CABLE DETAIL 240mm 4C 1.5m 16mm 4C 240mm 4C Insect Protected 50mm 4C Insect Protected 16mm 4C Insect Protected 2.5m 1.5m 1.5m 1.2m 1.05m Normal trench depth Normal trench depth DIMENSION A DIMENSION B
22kV CABLE CABLE DETAIL 185mm TRIPLEX 630mm 3 x 1C 35mm TRIPLEX Insect Protected DIMENSION A 1.5m 2.0m DIMENSION B 1.2m (CA) Normal trench depth (FN) 1.05m (CA) Normal trench depth (FN) Normal trench depth
1.5m
A B C
APPROVED
C.Noel
14/01/03
UNDERGROUND DISTRIBUTION
TRENCHING POLE TERMINATION CONDUIT AND TRENCH DETAIL
FILE: 5 54 5144 1
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
A.Bletchly
C.Lindsay
DRAWN
Dwg
5144
Sh
Kerb
Electricity Footpath Allocation for FN Region and Telstra is from 0.3 to 1.2m from property FN Region to be property side of Telstra.
F
F
A B
APPROVED
UNDERGROUND DISTRIBUTION
20/12/01
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
c D. M K.
DJB
DRAWN
Dwg
5162
Sh
NOTES: 1. Locate cable on opposite side of pole to oncoming traffic where possible. 2. Excessive excavation at the pole base may disturb pole foundation. Avoid excavating in areas shown. 3. Conduit bends shown allow minimum bending radius of cable to be achieved. 4. Provide polymeric cable protection cover and orange caution tape to all conduit/cable outside Electricity Footpath Allocation. 5. Cables not listed must be direct buried at pole. Refer drawing No. 5144. CABLE DETAIL 240mm 4C 16mm 4C 50mm 4C Insect Protected 16mm 4C Insect Protected 80 Dia. 90 1000 Radius LV CABLE BEND DETAIL 80 Dia. 90 750 Radius
11kV CABLE CABLE DETAIL 35mm TRIPLEX BEND DETAIL 125 Dia. 90 1000 Radius
22kV CABLE CABLE DETAIL 35mm TRIPLEX Insect Protected BEND DETAIL 125 Dia. 90 1000 Radius
A B
APPROVED
UNDERGROUND DISTRIBUTION
14/01/03
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
D. M K.
DRAWN
C.Lindsay
Dwg
5173
Sh
Property Allotment
Survey peg
Property Allotment
400
400
Refer applicable regional TRENCHING detail for trench details and conduit positions.
F
F
FRONT
c Pillar L
400 min
F
Exclusion Zone FOOTPATH No other service authorities pits or above ground plant to be located in this area.
A B C
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING - ALL REGIONS EXCLUSION ZONE AT LV PILLARS
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
FILE: 5 54 5196 1
Dwg
5196
Sh
NOTES: Offset base to align with centre line of survey peg clear of Road Reserve or Easement area. 1. Pillars shall be located in areas remote from vehicular access. 2. Should the edge of the pillar base, at ground level, be located less than 1000mm from the kerb or the edge of trafficable areas, then the pillar shall be protected by two bollards. Refer to CONSTRUCTIONS PRACTICES for bollard details. 3. To gain access to a consumers property, remote from pillars, the lead in conduits shall be placed and run in the electricity footpath allocation. Locate to clear possible future fence corner post.
F
F
FOOTPATH
A B
F
F
Survey peg
Property Allotment
400
Refer applicable regional TRENCHING detail for trench details and conduit positions.
F
c Pillar L
FRONT
400 min Exclusion Zone No other service authorities pits or above ground plant to be located in this area.
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING - ALL REGIONS PILLAR INSTALLATION AT EASEMENT OR ROAD RESERVE BOUNDARY
FILE: 5 54 5196 2
DATE
PASSED
DRAWN
Dwg
5196
Sh
NOTES: 1. Conduit and cable nearest R.P. Street Alignment only, shown. 2. Locations and depths shown to conduit ends allow minimum bending radius of cables to be achieved for connection to switchgear. Refer MATERIAL DATA drawings No. 5108 to 5111 for minimum bending radius of cables. 3. Conduit depths shown are minimum and are dimensioned from finished ground line to top of conduit. Ramp down as required. Where conduits are normally laid at a depth greater than shown, that depth should be maintained. 4. Terminate HV cable conduit in line, each end of pit. 5. Provide polymeric cable protection cover (and orange caution tape) over all cable not enclosed in conduit . 6. Backfill cable pit with bedding sand. 7. HV cable locations shown at RMU site illustrative only. Preferred sequence of construction is to install Padmounted RMU prior to cables. R.P. Street Alignment
F
LV & HV cables
F
RMU Foundation
Depth
Cable Pit
F
Base Slab
F
Conduit
45
F
UNDERGROUND DISTRIBUTION
TRENCHING ABB FREE STANDING RMU CONDUIT LOCATION AND CROSS SECTION
FILE: 5 54 5227 1
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5227
Sh
3000
Cable Pit
F
F
H.V. Conduit FOOTPATH 11kV CABLE SIZE TRIPLEX 35mm TRIPLEX 185mm TRIPLEX 400mm 1000 DEPTH End of conduit Seal around cable
PLAN VIEW
HV cable entering / exiting from left or left & right hand side of RMU.
APPROVED
ORIGINAL ISSUE
UNDERGROUND DISTRIBUTION
TRENCHING ABB FREE STANDING RMU CONDUIT LOCATION
FILE: 5 54 5227 2
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5227
Site boundry
H.V. Conduit
Sh
3000
A
F F
200 Min.
F
Cable Pit
F
F
H.V. Conduit 11kV INSECT PROTECTED CABLE SIZE TRIPLEX 35mm TRIPLEX 185mm TRIPLEX 240mm TRIPLEX 400mm DIM A 0 210 310 360 1250 DEPTH FOOTPATH End of conduit Seal around cable
PLAN VIEW
HV cable entering / exiting from left or left & right hand side of RMU.
ORIGINAL ISSUE
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING ABB FREE STANDING RMU CONDUIT LOCATION INSECT PROTECTED CABLE
FILE: 5 54 5227 3
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5227
F
F
Site boundry
H.V. Conduit
Sh
As per region
Re f e rn o t e2f o rAr t e r i a l Ro a d wa y s
9 0 0mi n Fo o t p a t h 1 0 5 0mi n Ro a d wa y -M i n o r
1 2 0 0mi n Ro a d wa y -Ar t e r i a l
7 5 0mi n Fo o t p a t h 9 0 0mi n Ro a d wa y -M i n o r
3 5 0
5 0 0
1 5 0ma x
7 5mi n
LV
F F
LV
F
25 min
25 min
25 min
A B
HV
HV
PL
F
F
Alignment
Trench width
F
NOTES: 1. Refer CONSTRUCTION PRACTICES drawing No. 5124 sheet 1 for locations. 2. For ARTERIAL (DMR) roads LV and HV cables may be laid at the same depth to avoid trench depth in excess of 1.5m. Telecommunication marker 3. Ergon cables are to occupy property tape to side conduits first. Telecommunication Authority requirements 4. Telecommunication conduit laid against roadside of trench to Telecommunication Authority requirements Telecommunication conduit (T) as required SEPARATION FROM TELECOMMUNICATION Polymeric cable protection cover where required Refer Note 1 Public Lighting Conduit CONDUITS CROSSING DIMENSION LV HV RADIAL 100 Min 100 Min
F
F
As per region
SEPARATION FROM TELECOMMUNICATION CONDUITS PARALLEL DIMENSION LV HV VERTICAL 100 Min 300 Min
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING - ALL REGIONS JOINT ELECTRICITY & TELECOMMUNICATION
DATE
PASSED
DRAWN
FILE: 5 54 5228 1
Dwg
5228
Sh
B
01.11.11
R. P. St r e e t Al i g n me n t F Note 1 T
Cr o s s r o a d Pi l l a r
C. Noel
23/3/11
Te l e c o mmu n i c a t i o np i t
F
Note 1
R. P. St r e e t Al i g n me n t T
LOT 2
Su p p l y Pi l l a r T Te l e c o mmu n i c a t i o n L e a d i nc o n d u i t Sh Pi l l a r Ex c l u s i o n Zo n e
UNDERGROUND DISTRIBUTION
TRENCHING - ALL REGIONS JOINT ELECTRICITY - TELECOMMUNICATION URD AREAS GENERAL LAYOUT
5249
C
Re a l Pr o p e r t y Bo u n d a r y
FILE: 5 54 5249 1
El e c t r i c i t y s e r v i c e s
Te l e c o mmu n i c a t i o n L e a d i nc o n d u i t
A. Bletchly
DATE
DRAWN PASSED
D T
Cr o s s Ro a d Te l e c o mmu n i c a t i o nc o n d u i t
APPROVED
T
F
Note 1. Refer applicable regional trenching detail for trench details and conduit positions.
LOT 4
El e c t r i c i t y s e r v i c e s
Pi l l a r Ex c l u s i o n Zo n e
Te l e c o mmu n i c a t i o np i t Ke r b
C
ORIGINAL ISSUE 09.07.12
Re a l Pr o p e r t y Bo u n d a r y
Te l e c o mmu n i c a t i o n L e a d i nc o n d u i t
F
Te l e c o mmu n i c a t i o n L e a d i nc o n d u i t
LOT 3
L. Burton
Sh a r e d Tr e n c ho n t h i s Fo o t p a t h Dwg
LOT 1
FOOTPATH
3000
FOOTPATH
LV cable 1st cable position 2nd cable position 3rd cable position 4th cable position Cables as reqd (Refer design)
2nd cable position 3rd cable position 4th cable position Cables as reqd (Refer design)
F
110
110 F
110
110 F
1100
1000
110 F
110
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
790 (ref)
Site Boundary
640
BACK of LV cable
640
790 (ref)
F
Dwg
5268
Sh
3000
F
F
F
F
F F F F
2800
2800
F
F F F
790 (ref)
F F
Site Boundary
685
Centre of lug
320
750
FOOTPATH
2800
F
FBX RMU A
ORIGINAL ISSUE APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING FRONT ENTRY 11kV PADMOUNTED SUBSTATION HV CABLE LOCATION FBX RMU
FILE: 5 54 5269 1
DATE
PASSED
DRAWN
Dwg
5269
3000
F
HV cable
F
F
F F F
Sh
6000
F
450
F
2nd conduit position 3rd conduit position 4th conduit position 4 0 0 0 H.V. 5th conduit position 6th conduit position
320
F
Site Boundary
R.P.Street Alignment
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING RECTANGULAR 22kV PADMOUNTED SUBSTATION 500kVA - SCHNEIDER ELECTRIC LV CONDUIT LOCATION
FILE: 5 54 5278 1
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5278
Sh
FOOTPATH
F
F
F
F
80 Dia 1000 Radius, 90 vertical bends to 50mm Min. above concrete level.
6000
F
450
F
1st conduit position 2nd conduit position 3rd conduit position 4 0 0 0 H.V.
Cable Pit
320
F
Site Boundary
R.P.Street Alignment
APPROVED
UNDERGROUND DISTRIBUTION
TRENCHING RECTANGULAR 22kV PADMOUNTED SUBSTATION 1000kVA - SCHNEIDER ELECTRIC LV CONDUIT LOCATION
FILE: 5 54 5278 2
DATE
PASSED
Ergon Energy Corporation Ltd ABN 50 087 646 062
DRAWN
Dwg
5278
Sh
FOOTPATH
100 100
F
F
F
F
80 Dia 1000 Radius, 90 vertical bends to 50mm Min. above concrete level.