INSTALLATION AND COMMISSIONING INSTRUCTIONS CONTENTS
Safety Information ............................................................. 3 General Safety Information ............................................ 3 Safety Information as per EN60730-1........................... 3 System Overview............................................................... 4 System Architecture....................................................... 4 I/O Modules ................................................................... 5 Interfaces and Bus Connections .................................... 9 Technical Data............................................................... 9 Planning ........................................................................... 10 Overview...................................................................... 10 Transformer Selection ................................................. 10 Fusing Specifications ................................................... 11 System Protective Earth Grounding............................. 11 Lightning Protection ..................................................... 11 Panel Bus Topologies .................................................. 11 LONWORKS Bus Topologies.......................................... 12 C-Bus Topologies ........................................................ 12 Accessories ................................................................. 12 Cable Specifications .................................................... 13 Dimensions .................................................................. 16 Mounting/Dismounting Modules .................................... 18 Mounting/Dismounting Controller/Sockets ................... 18 Mounting/Dismounting Electronic Modules .................. 20 Mounting/Dismounting Manual Disconnect Modules ... 21 Mounting/Dismounting Auxiliary Terminal Packages ... 22 Mounting/Dismounting Cross Connectors.................... 23 Mounting/Dismounting Swivel Label Holders............... 23 Wiring and Setting Up the System ................................. 24 General Safety Considerations .................................... 24 Wiring Push-in Terminals............................................. 24 Connecting Power Supply............................................ 25 Connecting Single Bus Controller Systems ................. 26 Connecting Panel Bus and LONWORKS Bus Mixed Controller Systems ...................................................... 27 Setting Address of Panel Bus I/O Modules .................. 29 Setting I/O Bus Switch ................................................. 29 Connecting Field Devices ............................................ 30 Commissioning I/O Modules ........................................ 31 Updating Software ....................................................... 31 Connecting to External Systems or Interfaces ............. 32 Connecting via LONWORKS Bus.................................... 32 Connecting via C-Bus .................................................. 33 Connecting HMIs or Laptops ....................................... 33 Connecting Modems .................................................... 33 Description of the CLLIONLC01 ..................................... 34 Overview...................................................................... 34 Features....................................................................... 35 Description of the I/O Modules....................................... 40 Common Features ....................................................... 40 Analog Input Modules .................................................. 40 Analog Output Modules ............................................... 45 Binary Input Modules ................................................... 50 Relay Output Modules ................................................. 53 Floating Output Module................................................ 58 Mixed Panel Bus I/O Module CLIOP830A ................... 62 Description of Extra Parts............................................... 65 Manual Disconnect Modules ........................................ 65 XS814 Auxiliary Terminal Package.............................. 66 XS830 Auxiliary Terminal Package.............................. 66 XS831 Auxiliary Terminal Package.............................. 66 Cross Connectors ........................................................ 67 XAL10 Swivel Label Holders........................................ 67 XAL11 Swivel Label Holders........................................ 67 XS816 Bridge Connectors ........................................... 67 LON Software Interface Description .............................. 68 Overview...................................................................... 68 CLIOL821A Analog Input Module ................................ 68 CLIOL(R)822A Analog Output Module......................... 70 CLIOL823A Binary Input Module ................................. 72 CLIOL(R)824A Relay Output Module........................... 73
EN1Z-0921GE51 R0709
LION System
Troubleshooting...............................................................74 Testing Wiring Connections..........................................74 Troubleshooting on the CLLIONLC01 Controller ..........74 I/O Modules Troubleshooting........................................78 Appendix 1: System Protective Earth Grounding .........82 LION Systems and SELV .............................................82 LION Systems and Standard EN60204-1.....................82 Earth Grounding of EN60204-1 Applicable Systems ....82 Appendix 2: Remote Communications...........................84 Approved Modems .......................................................84 Modem or ISDN Terminal Adapter Connection ............84 Modem Requirements ..................................................84 Troubleshooting............................................................84 Appendix 3: Sensor Characteristics...............................85 BALCO 500 ..................................................................85 NTC 20 k....................................................................86 PT 1000 ........................................................................87 NI1000TK5000 .............................................................89 NTC 10 k....................................................................90 PT 3000 ........................................................................91
Trademark Information Echelon, LON, LONMARK, LONTALK, LONWORKS, Neuron, are trademarks of Echelon Corporation registered in the United States and other countries.
EN1Z-0921GE51 R0709
LION System
Safety Information
General Safety Information
When performing any work (installation, mounting, start-
up), all instructions given by the manufacturer and in particular the safety instructions provided in these Installation and Commissioning Instructions are to be observed.
The LION System (including the CLLIONLC01, I/O
modules, manual disconnect modules, and the auxiliary terminal packages) may be installed and mounted only by authorized and trained personnel.
Rules regarding electrostatic discharge should be
followed.
If the LION System is modified in any way, except by the
observed at all times. Examples of such regulations are VDE 0800 and VDE 0100 or EN 60204-1 for earth grounding.
Use only accessory equipment which comes from or has
Overvoltage category
temperature for at least 24 hours before applying power. This is to allow any condensation resulting from low shipping/storage temperatures to evaporate.
The LION System must be installed in such a manner
(e.g., in a lockable cabinet) as to ensure that uncertified persons have no access to the terminals.
System transformer Europe: safety isolating transformers according to IEC61558-2-6 U.S.A. and Canada: NEC Class-2 transformers Table 1 System data as per EN60730-1
EN1Z-0921GE51 R0709
System Overview
LION System
System Overview
System Architecture
An LION System consists of the CLLIONLC01 Controller and various I/O modules. The CLLIONLC01 Controller provides interface connections, which allow connection to external systems. Auxiliary parts enable special features.
Panel I/O (CLIOPxx) Panel Bus (<40 m) existing XL500 controllers C-Bus
CLLIONLC01 + CLIOxx
XFCxxx
Fig. 1 LION System architecture
XFCLxxx
SERVAL
Controller
I/O Modules
Fig. 2
EN1Z-0921GE51 R0709
LION System
System Overview
I/O Modules
Variants of Pluggable I/O Modules There are 2 variants of pluggable I/O modules: Panel Bus I/O modules with communication via Panel Bus (light gray housings) Modules are automatically commissioned (with firmware download) by the CLLIONLC01 Controller LONWORKS Bus I/O modules (dark gray housings) with communication via LONWORKS (FTT10-A, link power rd compatible) for easy integration and use with 3 -party controllers Mixed I/O Modules Besides the pluggable Panel Bus I/O modules (consisting of a terminal socket and a removable electronic module), there are also mixed Panel Bus I/O modules. Specifically: the CLIOP830A is a mixed Panel Bus I/O modules, featuring an integrated terminal socket and a variety of inputs and outputs. Mixed Panel Bus I/O modules have a light-gray housing and are likewise automatically commissioned (with firmware download) by the CLLIONLC01 Controller.
Terminal Sockets Pluggable I/O modules are mounted on the appropriate terminal sockets. Pluggable Panel Bus I/O modules and pluggable LONWORKS Bus I/O modules use the same terminal sockets. The terminal sockets are available with push-in terminals (XS82) or with screw-type terminals (XSU82). Mixed I/O modules feature an integrated terminal socket. Color Coding To distinguish modules and components, the following color coding is used: Color Red Part All of the user-accessible adjustable mechanical parts (i.e., bridge connectors and locking mechanism) and operating controls (manual overrides, etc.) Panel Bus I/O modules LONWORKS Bus I/O modules
MIXED I/Os
CLIOLR822A
CLIOLR824A
CLIOL822A
CLIOL823A
CLIOL824A
CLIOPR822A
CLIOPR824A
CLIOPR825A
CLIOP822A
CLIOP823A
CLIOP824A
CLLIONLC01
XS821-22 XSU821-22
XS823 XSU823
XS824-25 XSU824-25
EN1Z-0921GE51 R0709
System Overview
LION System
I/O Module Overview Panel Bus module CLIOP821A CLIOP822A CLIOPR822A CLIOP823A CLIOP824A CLIOPR824A CLIOPR825A CLIOP830A
1) 2)
Description Analog input module Analog output module Analog output module Binary input module Relay output module Relay output module Floating output module Mixed I/O module
Inputs Outputs 8 12 20 8 8 6 2) 6
2)
Manual controls
6 Manual overrides 6 status LEDs 3 Manual overrides 3 pairs of status LEDs -18 status LEDs
3 14
In addition to the power LED and service LED Changeover outputs Overview of I/O modules Note In the following e.g., 822 is used to summarize all analog output modules (Panel Bus/LONWORKS Bus, with/without manual overrides)
Table 3
Corresponding Terminal Sockets I/O module Socket CLIOP/CLIOL 821 822 823 824 825 Table 4 XS821-22 XSU821-22 XS823 XSU823 XS824-25 XSU824-25 Scope of delivery 1 terminal socket, 1 bridge connector 1 swivel label holder 1 terminal socket, 1 bridge connector 1 swivel label holder 1 terminal socket, 1 bridge connector 1 swivel label holder 1 long cross connector
EN1Z-0921GE51 R0709
LION System
System Overview
Auxiliary Parts Module Type Figure Corresponding I/O modules CLIOP/CLIOL 821 XS812 Manual disconnect modules XS812RO 822 823 824 825 Information
Module allows disconnection of individual I/O signals Module allows disconnection of individual I/O signals For 24 V applications only Two groups of 7 terminals connected to each other for redistributing voltage (see also Fig. 94) Two groups of nine internallyconnected push-in terminals, for distributing signals/power (see also Fig. 96).
XS814
XS830
A1 A2 A3 A4 A5 A6 A7 A8 A9
B1 B2 B3 B4 B5 B6 B7 B8 B9
Two groups of four pairs of push-in terminals, for converting 020 mA signals into 010 Vdc signals, and one push-in ground terminal per group. (see also Fig. 98) Connects 3 relay commons, required in case of line voltage and low voltage in the same I/O module
XS817
824 825
Spare Parts
EN1Z-0921GE51 R0709
System Overview
LION System
Module
Type
Figure
Corresponding I/O modules CLIOP/CLIOL 824 825 All LION I/O modules
Information
Connector bridge
XS816
Connects CLLIONLC01 and I/O modules Can be plugged into socket, for attaching label generated by the engineering tool Can be plugged into module, for attaching label generated by the engineering tool.
XAL10
XAL11
CLIOP830A, only
Table 6
Spare parts
EN1Z-0921GE51 R0709
LION System
System Overview
Standards
Protection class IP20
Product standard EMC EN 60730-2-9 Testing electrical components Certification System transformer IEC68 CE The system transformer(s) must be safety isolating transformers according to IEC 61558-2-6. In the U.S.A. and Canada, NEC Class 2 transformers must be used. EN 60730-1 EN 60730-2-9
Operational Environment
Ambient operating temperature Ambient operating humidity Ambient storage temperature Ambient storage humidity Vibration under operation Dust, vibration RFI, EMI 0 50 C (32 122 F) 5 93 % rel. humidity (non condensing) 20 70 C (4 +158 F) 5 95 % rel. humidity (non condensing) 0.024 double amplitude (2 30 Hz), 0.6 g (30 300 Hz) According to EN60730-1 Home environment
Technical Data
System Data
Operating voltage Max. number of C-Bus participants Power consumption 24 VAC, 20 %, 21 30 VDC 30 Max. 3.57 A (1 CLLIONLC01 Controller + 16 I/O modules) 1.5 mm2 1.5 mm2
Overvoltage protection All inputs and outputs are protected against 24 VAC and 40 VDC overvoltage as well as against short-circuiting. Calculated lifetime of MTBF 13.7 years weakest component under typical operating conditions Table 7 System data
EN1Z-0921GE51 R0709
Planning
LION System
Planning
Overview
Engineering with CARE During CARE engineering, the type of I/O modules, terminal assignment and module configuration are defined depending on the application. The same applies to engineering with COACH (which is possible starting with COACH version 2.02). Planning In this step, the following has to be defined, if applicable: Power supply Fusing Earth grounding Lightning protection Panel Bus wiring Design of a LONWORKS network Design of a C-Bus network Useful accessories Cable selection Devices powered CLLIONLC01 with CLMMI00N22 (backlight ON) and with watchdog load (max. 500 mA) CLLIONLC01 with CLMMI00N22 (backlight ON) but without watchdog load 821 822 823 824 825 CLIOP830A Power consumption 24 VAC 24 VDC Note In Europe the system transformer(s) must be safety isolating transformers according to IEC61558-2-6. In the U.S.A. and Canada, NEC Class-2 transformers must be used.
Transformer Selection
Power Consumption
When selecting the appropriate transformer, take into account the number of individual modules, accessories, and field devices in determining the total power consumption.
690 mA
640 mA
EN1Z-0921GE51 R0709
10
LION System
Planning
CentraLine 1450 Series (North America) 50/60 Hz Insulated accessory outputs Built-in fuses Line transient /surge protection AC convenience outlet NEC Class-2 Part number Primary side 1450 7287 -001 -002 120 VAC 120 VAC
Secondary side 24 VAC, 50 VA 2 x 24 VAC, 40 VA, and 100 VA from separate transformer 24 VAC, 100 VA, and 24 VDC; 600 mA 24 VAC, 50 VA 2 x 24 VAC, 40 VA, and 100 VA from separate transformer 24 VAC, 100 VA, and 24 VDC, 600 mA
Fusing Specifications
For connection examples see description of the I/O modules on page 40 and following. F1 (Fusing for CLLIONLC01 and I/O Modules)) Rating: For example: Manufacturer: Type: Littlefuse 218004 4 A, time-lag fuse (slo-blo)
-006
240/220 VAC
Standard Transformers (Europe, North America) Standard commercially available transformers used to supply power to LION Systems must fulfill the following specifications: Output voltage 24.5 VAC to 25.5 VAC 24.5 VAC to 25.5 VAC 24.5 VAC to 25.5 VAC Impedance 1.15 0.40 0.17 AC current max. 2 A max. 6 A max. 12 A
Lightning Protection
Please contact your local CentraLine representative for information on lightning protection.
RIN-APU24 Uninterruptable Power Supply The RIN-APU24 Uninterruptable Power Supply can be wired to power LION Systems. See also RIN-APU24 Uninterruptable Power Supply Mounting Instructions (MU1B-0258GE51) for detailed wiring diagrams.
11
EN1Z-0921GE51 R0709
Planning
LION System
Accessories
Besides the auxiliary parts of Table 5 on page 7, the following accessories are available.
C-Bus Topologies
Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.) can communicate with one another and a PC central. The C-Bus must be connected via the individual controllers (open ring). Note Star connection is not allowed because uncontrollable line reflections may occur. Instead of LION Controllers, other C-Bus controllers (e.g., the Excel 500, Excel 100, PANTHER) can also be connected.
XW586
8 7 6 5 4 3 2 1
LOOSE ENDS
GRAY (not used) YELLOW TxD BROWN +5VE GREEN RxD WHITE GND
+5V
XW882
Fig. 5
LION Excel 100 Excel 500 PANTHER
Fig. 4
8 7 6 5 4 3 2 1
6 2 7 3 8 4 9 5
+5V
XW884
Fig. 6 CLLIONLC01/Excel 500/600 cable details
EN1Z-0921GE51 R0709
12
LION System
Planning
8 7 6 5 4 3 2 1
Description LONWORKS Bus termination module LONWORKS connection and termination module, which can be mounted on DIN rails and in fuse boxes
+5V
XW885
Fig. 7 CLLIONLC01/laptop cable details
5 4 3 2 1
Cable Specifications
SHIELD LOOSE ENDS
CLMMI00N22 WIRING TERMINALS
1 2 3 4
to XC5010C
5 4 3 2 1 9 8 7 6
XW582
Fig. 8 XW582 cable details Cross section
SHIELD
+5V
5 4 3 2 1
Cable type
XW585
Fig. 9 XW585 cable details
8 7 6 5 4 3 2 1
+5V
XW586
Fig. 10 XW586 cable details
9 8 7 6
13
EN1Z-0921GE51 R0709
Planning
LION System
Note In the event that the limit on the total wire length is exceeded, the FTT physical layer repeaters (FTT 10A) can be added to interconnect segments. This increases the overall length by an amount equal to the original specification for that cable type and bus type for each repeater used. For example, adding repeaters for a doubly-terminated bus using JY (St) Y 2 x 2 x 0.8 cable increases the maximum length 900 m (3000 ft) for each repeater.
Table 18 Doubly-terminated bus specifications Notes The cable types listed above are as recommended by Echelon in their FTT-10A User Guide. The cable recommended by CentraLine is the level IV, 22 AWG, solid core, non-shielded cable. Belden part numbers are 9H2201504 (plenum) and 9D220150 (non-plenum).
24 VAC power FTT Specification The FTT specification includes two components that must be met for proper system operation: The distance from each transceiver to all other transceivers and to the termination must not exceed the max. node-to-node distance. If multiple paths exist, the maximum total wire length is the total amount of wire used. Max. node-tonode distance 500 m (1650 ft) 400 m (1300 ft) 400 m (1300 ft) 320 m (1050 ft) Max. total wire length 500 m (1650 ft) 500 m (1650 ft) 500 m (1650 ft) 500 m (1650 ft) 450 m (1500 ft) 010 V signals
Table 20 Cable sizing for connection of field devices For wiring field devices see page 30.
Cable type Belden 85102 Belden 8471 Level IV, 22AWG JY (St) Y 2 x 2 x 0.8
NOTICE
Unpredictable reflections on the bus due to step change in line impedance characteristics!
Do not use different wire types or gauges on the same
EN1Z-0921GE51 R0709
14
LION System
Planning
C-Bus Cables
Note Observe national regulations for C-Bus cables! For Europe only shielded cable is permitted. For the U.S. shielded or unshielded cable can be used. Cable type J-Y-(ST)Y 2 x 2 x 0.8 A-Y-(ST)Y 2 x 2 x 0.8 AK 3702 AK 3740A Belden 9842 Belden 9841 AK 3702 AK 3740A Description shielded, twisted pair shielded, twisted pair unshielded, twisted pair shielded twisted pair shielded unshielded, twisted pair shielded Recommended for Europe, inside cabinet Europe, outside cabinet US not approved for Europe US (low-cost) not approved for Europe Europe, US also possible US US not approved for Europe US (low-cost) not approved for Europe
Maximum Cable Length The maximum C-Bus cable length is 1200 m (4000 ft). See section "C-Bus Topologies" on page 12.
15
EN1Z-0921GE51 R0709
Planning
LION System
Dimensions
Controller Module
144
92.75
110
28 32
Fig. 11 Controller module, outside dimensions (in mm)
89.5
LOCK
94.1
110
67.5
30.6 28
83
SCREW-TYPE TERMINALS
14
XS814 Aux. Terminal Package (optional)
SWIVEL LABEL HOLDER
38
51.5
Fig. 12
Pluggable I/O modules (shown with manual overrides), including XS814 Aux. Terminal Package, dimensions (in mm)
EN1Z-0921GE51 R0709
16
45
45
LION System
Planning
92.5
24V for relay 1...5
J1 J2 J3 J4 J5
Binary Inputs
Analog Inputs
110
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 7 8 9 10 11 12 17 18 19 20 1 2 3 4 5 6 13 14 15 16 B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4
Install. Instr. EN1B-0375GE51
G1 G2 41 42
DI
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6
DO
100 CLEARANCE
7 8 9 10 11 12 17 18 19 20
25 26 27 28 35 36 37 38 39 40
69
CLIOP830A
1 2 3 4 5 6 13 14 15 16
41 42
21 22 23 24 29 30 31 32 33 34
28 15
SWIVEL LABEL HOLDER
A1 A2 A3 A4 A5 A6 A7 A8 A9
A C
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 A2 A3 A4 A5 A6 A7 A8 A9
B D
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 A2 A3 A4 A5 A6 A7 A8 A9
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 B1 A2 B2 A3 B3 A4 B4 G1
A5 B5 A6 B6 A7 B7 A8 B8 G2
51.5
Fig. 13
Mixed I/O Module CLIOP830A (shown with four auxiliary terminal packages), dimensions (in mm)
17
EN1Z-0921GE51 R0709
45
BCD
EF
S2
75 76 77 78
012
67
8 9A
GND
Analog Outputs
AO5 25 21 AO1 AO6 26 22 AO2 AO7 27 23 AO3 AO8 IN1 28 35 24 29 AO4 NO1
24V Relays
IN2 36 30 NO2 IN3 37 31 NO3 IN4 38 32 NO4 IN5 39 33 NO5 IN6 40 34 NO6
Mounting/Dismounting Modules
LION System
Mounting/Dismounting Modules
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet. Disconnect the power supply before you start to install
Mounting/Dismounting Controller/Sockets
Mounting Sockets
Notes When using both Panel Bus and LONWORKS Bus I/O modules in a LION System, group both Panel Bus modules (light gray) and LONWORKS Bus I/O modules (dark gray), e.g., on different rails. Up to 10 Panel Bus I/O modules can be mounted to one side of the controller. In total, up to 16 Panel Bus I/O modules can be mounted to one controller. The CLLIONLC01 and the mixed Panel Bus I/O module are mounted on the DIN rail in the same way as a terminal socket.
the LION System. More than one disconnect switch may be required to deenergize the system.
Do not reconnect the power supply until you have
Note The terminal socket of each pluggable I/O module can be mounted and wired before inserting and locking the corresponding electronic module.
1
PRESS
71 COM a 72 COM b 73 24V~ 74 24V~0 COM a COM b 24V~ 24V~0
2
1:ABCDFERTAQWESDERT1 2:ABCDFERTAQWESDERT2 3:ABCDFERTAQWESDERT3 4:ABCDFERTAQWESDERT4 5:ABCDFERTAQWESDERT5 6:ABCDFERTAQWESDERT6 7:ABCDFERTAQWESDERT7 8:ABCDFERTAQWESDERT8 1:ABCDFERTAQWESDERT1 2:ABCDFERTAQWESDERT2 3:ABCDFERTAQWESDERT3 4:ABCDFERTAQWESDERT4 5:ABCDFERTAQWESDERT5 6:ABCDFERTAQWESDERT6 7:ABCDFERTAQWESDERT7 8:ABCDFERTAQWESDERT8
CLLIONLC01 max. 16
PRESS
LON
C-BUS
RESET
PC/HMI
1
87 654 32 1 8 765 43 21 !
1 2 3 4 5 6 7 8 9 10 11 12
max. 10
!
max. 10
S1
S2
Panel LON
Modem
87 65 432 1
1 2 3 4 21 22 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12
VAUX
AI/AO GND
9 10 11 12 13 14 15 16 17 18 25 26
BI GND
13 14 15 16 17 18 19 20 21 22 23 24 25 26
Rx Tx
LON
C-Bus in
C-Bus out
Power/ Alarm
GND
Fig. 15
4
PRESS
71 COM a 72 COM b 73 24V~ 74 24V~0
5
01 01 01
23
45
67
23
45
67
PRESS
S1
S2
8 9A
S1
S2
8 9A
S1
23
45
67
S2
8 9A
PRESS
PRESS
EF
EF
100
100
AUTO
AUTO
11 12 13
21 22 23
31 32 33
41 42 43
51 52 53
61 62 63
21
22
11
21 22 23
31 32 33
VAUX GND
9 10 11 12 13 14 15 16 17 18
AI/AO GND
25 26
12 13
14
24
34
44
54
64
25
14
24
34
6
Fig. 14 Legend 1 2 3 4 5 6 CLLIONLC01 Swivel label holder Cable connection Stopper (from 3rd-party supplier) Bridge connectors Auxiliary terminal package CLLIONLC01 and I/O modules mounted on multiple DIN rails
EN1Z-0921GE51 R0709
BCD
EF
BCD
BCD
6
--1 --0 --AUTO
CLLIONLC01 max. 20
41 42 43
51 52 53
max. 10
max. 10
44
54
64
25
Fig. 16
Max. number of LONWORKS Bus I/O modules with power supply via CLLIONLC01
18
LION System
Mounting/Dismounting Modules
Connecting Sockets
Controller, terminal sockets, and mixed I/O modules on the same DIN rail can be connected mechanically and electrically with bridge connectors. Controller and terminal sockets on different DIN rails must be connected using cables, see Fig. 14 and page 25.
prevent sliding.
NOTICE
Risk of malfunction!
Wire Panel Bus I/O modules and LONWORKS Bus
I/O modules in a LION System, LONWORKS Bus I/O modules must be connected to the controller via LON terminals 11 14.
Position the bridge connector on terminals 71 74 of the right hand terminal socket or mixed I/O module or controller and on terminals 75 78 of the left hand terminal socket or mixed I/O module or controller. Then press the bridge connector down.
Fig. 17 Note
Take care to not bend the Omega clamp, which serves to establish the electrical contact with the DIN rail and which located on the back of the terminal socket.
Fig. 18 Notes
Bridge connectors transmit both communication signals and power supply between modules. Removing bridge connectors will interrupt the transmission of both communication signals and power supply between the modules.
19
EN1Z-0921GE51 R0709
Mounting/Dismounting Modules
LION System
Dismounting Sockets
Disconnecting Sockets Release all bridge connectors before removing the controller module and/or the terminal sockets and/or mixed I/O modules from the DIN rail.
Press down at the same time both the gray side wings
next to the red button and then pull the bridge connector out of the module.
Fig. 19
module and lever the red latch 23 mm downwards. The module can then be swung away from the rail. Fig. 21 Inserting the electronic module
Fig. 22
Note The red locking mechanism will not close if the electronic module is not properly mounted.
EN1Z-0921GE51 R0709
20
LION System
Mounting/Dismounting Modules
and then gently pull the electronic module out of the terminal socket.
WARNING
Risk of electric shock or equipment damage! The XS812RO Manual Disconnect Module is designed for 24 V applications only!
Never use the XS812RO Manual Disconnect Module with
line voltage.
Fig. 23
Fig. 24
21
EN1Z-0921GE51 R0709
Mounting/Dismounting Modules
LION System
Fig. 25
then gently pull the electronic module out of the terminal socket.
Fig. 26
Mounting the auxiliary terminal package onto the terminal socket / mixed I/O module
and pull it out of the grooves of the terminal socket / the mixed I/O module.
Fig. 27
Dismounting the auxiliary terminal package from the terminal socket / the mixed I/O module
EN1Z-0921GE51 R0709
22
LION System
Mounting/Dismounting Modules
connecter and swivel it to the right and to left until the cross connector is released.
If desired, insert another cross connector.
Fig. 28
Dismounting the cross connectors (long cross connector shown here) Fig. 30 Mounting the swivel label holder
holder.
Fig. 29
23
EN1Z-0921GE51 R0709
LION System
0.14 1.50 mm 0.25 1.50 mm 0.25 1.50 mm 0.25 ... 1.50 mm 8.0 +1.0 mm
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet. Disconnect the power supply before making connections
0.14 1.50 mm 0.25 1.50 mm 0.25 1.50 mm 0.25 ... 1.50 mm 11.0 +1.0 mm
devices.
Stranded conductor with wire end ferrules (without plastic collar) Stripping length
EN1Z-0921GE51 R0709
24
LION System
Additional Transformer
Connect the additional transformer in a second room or
TRANSFORMER 2
71 72 73 74
I/O
MAX. 3 m
I/O
CLLIONLC01 Controller.
I/O
B
I/O
CPU
1 2
I/O
C A
Fig. 32
NOTICE
Equipment damage!
Do not use bridge connectors to connect modules
transformers using cables, be sure to not connect terminals 73 and 77. Fig. 31 Wiring power supply from the (first) transformer to the controller module
25
EN1Z-0921GE51 R0709
LION System
room 2: Reference voltage via power supply terminals 74 or 78 terminals 73 and 77 must not be connected Communication via communication terminals 71, 72 or 75, 76
connectors. This provides power supply and communication connection. No further wiring is necessary.
CPU
1 2
PANEL I/O
75 76 77 78
MAX. 40 m
Power supply via power supply terminals 73, 74 or 77, 78 Communication via communication terminals 71, 72 or 75, 76
71 72 73 74
71 72 73 74
PANEL I/O
PANEL I/O
75 76 77 78 24 V0
I/O
I/O
Fig. 34
71 72 73 74
I/O
I/O
I/O
75 76 77 78
Maximum Cable Length The maximum cable length for connecting room 1 and room 2 is 40 m.
71 72 73 74
I/O
CPU
1 2
I/O
75 76 77 78
71 72 73 74
I/O
I/O
Fig. 33
Wiring the power supply and the communication lines to the I/O modules
Maximum Power Cable Length The maximum length for power supply cable per side is 3 m. This also includes the connection cables between the rails, the lengths of the modules, and the cable from the transformer.
EN1Z-0921GE51 R0709
26
LION System
CPU
1 2
75 LonWorks 76 I/O 77 78
Panel Bus I/O modules to communication terminals 71 74 or 75 78 of the controller module using either Bridge connectors for flush mounting on a single DIN rail or
71 72 LonWorks I/O 73 74
75 LonWorks 76 I/O 77 78
Cables for separate mounting, e.g., on multiple rails, separate cabinets, etc. LONWORKS Bus I/O Modules
Connect communication terminals 71 74 or 75 78 of
Fig. 35
LONWORKS Bus I/O modules to LONWORKS terminals 11 14 of the controller module using cables.
Maximum Cable Length For maximum cable lengths and cable specifications of the communication lines, see Table 18 and Table 19 on page 14.
27
EN1Z-0921GE51 R0709
LION System
XF...
11 12 13 14
CLLIONLC01
1 2 3 4
Fig. 36
11 12 13 14
1 2 3 4
Fig. 37
EN1Z-0921GE51 R0709
28
LION System
LON
Panel
Use the rotary HEX switch to set the address to the one
S2
4 4
Panel LON
LOCK
I/O Bus
Fig. 39
Fig. 38
Notes If the HEX switch is changed, the Panel Bus I/O module will revert to its default configuration. With LONWORKS Bus I/O modules, the HEX switch is without function.
29
EN1Z-0921GE51 R0709
LION System
Route low-voltage signal and output cables separately from mains cables.
Cable Minimum distance
Shielded Unshielded
F2 F1 230 V~ 24 V~ 24 V0
CLLIONLC01
All low-voltage signal and output cables should be regarded as communication circuits in accordance with VDE 0100 and VDE 0800 (or NEC or other equivalent).
822 Y (0...10 Vdc) 24V~ Y GND
1 2 9
Cable Shielding If the general guidelines for cable routing are observed, it is not necessary to shield field device signal and power supply cables. If, for whatever reason, the routing guidelines cannot be observed, the field device signal and power supply cables must be shielded.
1...8 11...18
max. 100 m
Fig. 40
Example 2: Power Supply via Separate Transformer 24 V actuator connected to an analog output module 100 400 m away from the controller
Shielding of cables leading to field devices must be grounded only at the cabinet end. The shield must not be terminated at the CLLIONLC01.
24 V0 24 V~ F2 F1 230 V~ 24 V~ 24 V0
CLLIONLC01
230 V~
1 2
1...8 11...18
max. 400 m
Fig. 41
EN1Z-0921GE51 R0709
30
LION System
The CLLIONLC01 Controller automatically commissions all Panel Bus I/O modules.
Updating Software
CARE is used to update the CLLIONLC01 Controller.
31
EN1Z-0921GE51 R0709
LION System
Termination Examples
completed installation.
Observe the rules regarding electrostatic discharge.
Fig. 42
Fig. 43
Fig. 44
EN1Z-0921GE51 R0709
32
LION System
Input to C-Bus terminals 8 and 9 Output to C-Bus terminals 5 and 6 Do not connect the C-Bus to the cabinet earth or any other earth ground points
interface of the CLLIONLC01 by means of the XW882 cable or the XW582 cable connected with an XW586 cable. For mounting details refer to the CLMMI00N22 Installation Instructions (Product Literature no.: EN2B-0126GE51). For cable details refer to section "Preconfigured Connection Cables" on page 12.
S1
the XW882 cable or the XW586 cable connected with an XW585 cable. For cable details refer to section "Preconfigured Connection Cables" on page 12.
C-Bus
Fig. 45
Switch setting S1
been installed) to the HMI interface of the CLLIONLC01 by means of the XW885 cable or the XW585 cable connected with an XW586 Cable. For cable details refer to section "Preconfigured Connection Cables" on page 12.
Up to 76800 baud without bus termination Up to 76800 baud with bus termination
Connecting Modems
How to Shield
In principle, data transmitting cables should be shielded in case of RFI.
On the controller side, connect the shield to terminals 7
An LION System can be connected to a modem or an ISDN terminal adapter via the Modem Interface of the CLLIONLC01 by means of the XW586 Cable.
Connect the RJ45 female connector of the XW586 cable
and 10.
On the side of the device, connect the shield to the
respective terminals. Do not connect it to the cabinet ground or any other ground points.
For cable details refer to section "Preconfigured Connection Cables" on page 12. Refer to Appendix 2 for details regarding remote communication.
33
EN1Z-0921GE51 R0709
LION System
CLLIONLC01 + CLIOxx
XFCxxx
Fig. 46 Connections to the CLLIONLC01 Controller
XFCLxxx
SERVAL
3 2 1
71 COM a 72 COM b 73 24V ~ 74 24V0 ~
4 5
67
9
COM a 75 COM b 76 24V ~ 77 24V ~0 78
2 1
LON
C-BUS
PC/HMI
10
87654321 8 765 43 21 !
11 12 13
S1
S2
Panel LON
Modem
8 765 43 21
1 2 3 4
Tx Rx
LON
C-Bus in
C-Bus out
Power/ Alarm
18
17
16
15
14
Fig. 47
Legend 1 Power supply for I/O modules 2 I/O Bus communication terminals 3 LONWORKS interface 4 LONWORKS service button 5 LONWORKS service LED 6 C-Bus Tx LED 7 C-Bus Rx LED 8 Reset button 9 HMI interface and LEDs 10 Alarm LED 11 Power LED 12 Power supply terminals 13 Alarm/watchdog outputs 14 Modem interface and LEDs 15 S2 I/O Bus switch 16 S1 C-Bus termination switch 17 C-Bus terminals 18 LONWORKS terminals
EN1Z-0921GE51 R0709
34
LION System
CLLIONLC01 Terminals
71 COM A 72 COM B 73 74
24 V~ 24 V~0 COM A COM B 24 V~ 24 V~0
Features
75 76 77 78
87 65 4 321
11 LON 1 12 13 14
LON 2 LON 1 LON 2
1 8 C+ 9 C10
SHIELD
5 C+ 6 C7
SHIELD
2 3
*Watch Dog Relay
24 V~ 24 V~0 24 V~0 NC
Fig. 48
87654 321
Terminal
11 12 13 14
Signal Comment
LON
COM a COM b 24 V~
2-wire communication bus (LON/Panel Bus) 2-wire communication bus (LON/Panel Bus) Power supply for I/O modules
Fig. 49
24 V~0 Power supply for I/O modules 24 V~ Power supply from transformer
1 2 38
24 V~0 Power supply from transformer 24 V~0 Alarm/watchdog output NC C+ CShield LON LON Alarm/watchdog output C-Bus C-Bus C-Bus shield LONWORKS IN LONWORKS OUT
Fig. 50
35
EN1Z-0921GE51 R0709
LION System
HMI Interface
The controller module is equipped with an HMI Interface for the connection of HMIs (e.g., the CLMMI00N22 or the CLMMI00N31) or a laptop (with XL-Online/CARE).
1 2
Tx
Rx
12 8 73 6 45 5 4 3 78 21
Fig. 51
C-Bus Tx LED (1) and Rx LED (2) Fig. 53 HMI interface, Tx LED (1) and Rx LED (2)
The controller is sending data onto the C-Bus The controller is receiving data from the C-Bus
The controller is transmitting data to the HMI The controller is receiving data from the HMI
Reset Button
The CLLIONLC01 is equipped with a reset button.
1 2 3 4 5 6 7
Fig. 52 Reset button (1)
Pushing the reset button (1), e.g. using a paperclip, will cause the CLLIONLC01 to reset.
Note In the event of a reset, all non-volatile memory contents are permanently deleted, though the clock will not be set to zero. In order to avoid problems, we therefore recommend that you always save your application changes (e.g., time program changes) to FLASH memory.
NOTICE
Equipment damage!
Make sure that the controller is not connected to earth
ground.
If nonetheless earth grounding is required, make sure
that only terminal 2 is connected to earth ground. Terminal 1 must not be connected to earth ground. See also Appendix 1.
EN1Z-0921GE51 R0709
36
LION System
Normal operation One or more of the internal voltage supplies are outside of the permissible ranges. The controller stops operation.
Check wiring or see section "Trouble-
Fig. 54
Watchdog
Watchdog status Status Signal on terminal 4
24 V 0V
Permissible Load of Normally Closed Contact (Terminal 4) Max. load Per normally closed contact (terminal 4) 1929 VAC current at cos 0.95: 0.5 A, current at cos 0.6: 0.5 A 1929 VDC 0.5 A resistive or inductive Min. current
10 mA
Flashing
The watchdog alarm output has not yet been powered, although the controller has encountered a problem. The controller performs a warm start. If the problem persists, the LED will become lit constantly, see above. See section "Troubleshooting" on page 74.
37
EN1Z-0921GE51 R0709
LION System
Modem Interface
The controller module is equipped with a modem interface for the connection of a modem or an ISDN terminal adapter.
12 3 45 6 78
Tx
Rx
1 2
S2
Panel LON
Fig. 55
I/O Bus
Modem LEDs on RJ45 socket Tx (1) flickering The controller is transmitting data to the HMI, e.g., CLMMI00N22 or CLMMI00N31 Rx (2) flickering Fig. 56 I/O Bus switch S2
Communication
S2 setting
LONWORKS Bus only Panel Bus and LONWORKS Bus LONWORKS BUS modules connected to terminals 11 . 14 of the controller Panel Bus connected to terminals 71, 72 or 75, 76 of the controller
Table 39 I/O Bus switch settings
LON Panel
Panel
1 2 3 4 5 6 7 8
Carrier detect Receive Transmit Data terminal ready Signal ground 5V Clear to send
Communication Speed
Default setting: 9600 baud The communication speed can be set to as high as 38.4 Kbaud, e.g., using the CLMMI00N22 or CLMMI00N31 or a laptop with XL-Online, see Appendix 2.
EN1Z-0921GE51 R0709
38
LION System
S1
C-Bus
Fig. 57
Switch setting S1
Up to 76800 baud without bus termination Up to 76800 baud with bus termination controller at the end of the C-Bus
Memory
Memory Size Usage
SRAM
512 KB
For controller application, modem trend and firmware RACL application: 128 KB Total application: 192 KB
Flash EPROM
2 MB 128 KB
Note The CLLIONLC01 does not contain a battery. RAM (data and realtime clocktime) is buffered for 3 days by a super capacitor.
39
EN1Z-0921GE51 R0709
LION System
Service LED test, see section "Troubleshooting" button S1 on page 74 (pluggable I/O LONWORKS service button functionality modules, for LONWORKS Bus I/O modules only) Hex switch S2
Module addressing for Panel Bus I/O modules
Panel Bus analog input module LONWORKS Bus analog input module Terminal socket
LEDs located on the I/O Module Feature Function Service information, see section "Troubleshooting" on page 74 Information on power supply, see section "Troubleshooting" on page 74
Features
8 analog inputs Sensor-break and short-circuit detection, see section "Troubleshooting" on page 74.
For the location of these elements, see figures of the relative modules.
1 2
3 4
Fig. 58 Legend
1 2 3 4
Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following.
EN1Z-0921GE51 R0709
40
LION System
Terminals
72 COM B 73 74
24 V~ 24 V~0
Technical Data
COM A COM B 24 V~ 24 V~0
71 COM A
75 76 77 78
Input
0(2) ... 10 VDC 0(4) ... 20 mA (via external 499 /0.25 % resistor NTC20k (-50+150 C; default) PT1000-1 (-50+150 C) PT1000-2 (0+400 C) PT3000 (-50+150 C) BALCO500 (-30+120 C) Slow binary input
VAUX VAUX
21 22
GND GND
Protection
25 26
9 10
11 12 13 14 15 16 17 18
Protected against failure voltage (24 VAC, 40 VDC) 16-bit resolution 75 mV (0 ... 10 V), without sensor
Resolution Fig. 59 Terminal assignment and internal connections of analog input modules Accuracy
2-wire communication bus (LON/Panel Bus) Power supply Power supply Ground. All grounds are connected internally to each other
1.2 K 0.7 K
1.2 K 1.2 K 5.0 K 5.0 K 1.2 K 0.7 K 0.7 K 1.0 K 1.0 K 0.7 K
Auxiliary voltage signal (used e.g. for 10 VDC/ 5 mA, 2 % supplying setpoint potentiometers) Shield connection (functional earth), internally connected to the DIN rail
0.5 K 0.5 K 0.5 K 0.5 K 0.3 K 0.5 K 0.5 K 0.7 K 0.7 K 0.7 K 0.7 K 0.5 K 0.5 K 0.7 K
Table 43 Description of analog input module terminals Notes Shield connection to be used for shielded I/O cables only. It is not allowed to connect a LONWORKS shield, since LONWORKS requires a resistor and a capacitor. If additional shield terminals are needed, the XS814 Auxiliary Terminal Package can be installed.
70...100 C 1.2 K 1.2 K 1.2 K 1.2 K 1.0 K 1.0 K 1.2 K (158...212 F) 100...130 C 1.2 K 1.2 K 1.2 K 1.2 K 3.0 K (212...266 F) 130...150 C 1.2 K 1.2 K (266...302 F) 150400 C (302752 F)
(1 (2 (3
PT3000
Range
NTC10k(2
Balco500(1
NTC20k (default)
71, 75
COM a
PT1000-1
PT1000-2
1.2 K
1.2 K 5.5 K
1.2 K
Balco specified for -30 C +120 C, only NTC10k specified for -30 C +100 C, only NI1000TK5000 specified for -30 C +130 C, only
Note The accuracy of the sensor itself is not included in this table.
41
EN1Z-0921GE51 R0709
NI1000TK5000(3
Terminal
SIGNAL
Comment
LION System
Fig. 60
Analog input low impedance (input circuit for PT1000, Balco500, PT3000, NI1000TK5000, slow binary input)
Fig. 61
Analog input high impedance (input circuit for voltage input for active sensors)
Fig. 62
Analog input impedance setpoint (input circuit for NTC10k, NTC20k, wall module setpoint)
EN1Z-0921GE51 R0709
42
LION System
Connection Examples
Active Sensor and Potentiometer
72 COM B 73 74
24 V~ 24 V~0
71 COM A
COM A COM B 24 V~ 24 V~ 0
75 76 77 78
72 COM B 73 74
24 V~ 24 V~0
71 COM A
VAUX VAUX
21 22
CLIOP821A
Shield internally connected to DIN rail
GND GND
GND GND
9 10
11 12 13 14 15 16 17 18
25 26
10
A1 A2 A3 A4 A5 A6 A7
1 2 3 4
5 6
F1
F2
Active Sensor 1: 24V~ power supply 2: 0...10 VDC signal 3: GND
1 2
1 2 3
0...10V
Fig. 63
43
EN1Z-0921GE51 R0709
LION System
COM A COM B 24 V~ 24 V~ 0
75 76 77 78
COM A COM B 24 V~ 24 V~ 0
75 76 77 78
72 COM B 73 74
24 V~ 24 V~0
71 COM A
VAUX VAUX
CLIOP821A
21 22
CLIOP821A
GND GND
GND GND
9 10
11 12 13 14 15 16 17 18
25 26
10
1 2
1 2 0(4)...20mA
Fig. 64
EN1Z-0921GE51 R0709
44
LION System
Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following. In the event of communication problems, the analog outputs will move to the safety positions you have configured using the engineering tool, see analog output point description in the CARE User Guide, 74-5587/EN2B-0182GE51.
CLIOP822
CLIOPR822 Panel Bus analog output module with manual overrides CLIOL822 CLIOLR822 LONWORKS Bus analog output module LONWORKS Bus analog output module with manual overrides Terminal socket
Terminals
XS821-22 XSU821-22
Light gray
Features
8 analog outputs; can also be configured per output as binary outputs (0 10 V, 2 10 V, ON/OFF, or floating) Corresponding output status LEDs (red) R822: 8 manual overrides, see figure below Fig. 66 Terminal assignment and internal connections of the analog output modules
Terminal
Signal
COMMENT
1 2
2-wire communication bus (LON/Panel Bus) 2-wire communication bus (LON/Panel Bus) Power supply Power supply Ground. All grounds are connected internally to each other Do not use! Shield connection (functional earth), internally connected to the DIN rail
21, 22 25, 26
5 6
Notes Fig. 65 CLIOP822A Analog Output Module with terminal socket Shield connection to be used for shielded I/O cables only. It is not allowed to connect a LONWORKS shield, since LONWORKS requires a resistor and a capacitor. If additional shield terminals are needed, the XS814 Auxiliary Terminal Package can be installed.
Legend 1 Service button S1 2 Hex switch S2 3 Manual overrides 4 Output LEDs 5 Service LED 6 Power LED
45
EN1Z-0921GE51 R0709
LION System
Technical Data
Voltage rating Current rating Resolution Accuracy Zero output voltage Protection
0(2)11 V (default) max. 1 mA 8 bit 150 mV < 200 mV Short-circuit protected; protected against failure voltage (24 VAC, 40 VDC) Auto/manual mode and output value
When a manual override of the CLIOPR822A/CLIOLR822A is set to AUTO, and the corresponding analog output has been configured, the following applies:
If the LONWORKS network is functioning properly, the output voltage of the analog output will be as commanded. If the LONWORKS network is not functioning properly, the output voltage of the analog output will be the safety position value. The brightness of the status LED (red) of the analog output will be proportional to the commanded output signal.
Feedback signal
When a manual override of the CLIOPR822A/CLIOLR822A is set to AUTO, and the corresponding analog output has not been configured, the following applies:
Regardless as to whether the LONWORKS network is functioning properly or not, the output voltage of the analog output will be 0 V (values from the LONWORKS Bus will be ignored, and there will be no heartbeat or safety position). The feedback signal on the LONWORKS network nvoAoActPosnFb[ ] will have a value of 0% and a state of 0. The analog output status LED will be dark.
When a manual override of the CLIOPR822A/CLIOLR822A is set to 0100%, and the corresponding analog output has been configured, the following applies:
0
AUTO
100
The output voltage of the analog output will be 010 V (direct) or 100 V (reverse). The feedback signal on the LONWORKS network nvoAoActPosnFb[ ] will have a value of 0100% and a state of -1. The status LED (red) of the analog output will flash to indicate manual override.
Fig. 67.
The CLIOPR822A/CLIOLR822A Analog Output Modules are equipped with manual overrides: one for each analog output. These rotary knobs can be manually set to either "AUTO" or "0100%" (infinitely adjustable).
When a manual override of the CLIOPR822A/CLIOLR822A is set to 0100%, and the corresponding analog output has not been configured, the following applies:
The output voltage of the analog output will be 010 V. The feedback signal on the LONWORKS network nvoAoActPosnFb[ ] will have a value of 0100% and a state of -1. The status LED (red) of the analog output will flash to indicate manual override.
NOTICE
Damage to the electronic module!
Do not use a tool to adjust the rotary knobs. Do not use excessive force. Adjust only by hand.
EN1Z-0921GE51 R0709
46
LION System
Connection Example
71 COM A 72 73 74
COM B 24 V~ 24 V~0
COM A COM B 24 V~ 24 V~ 0
75 76 77 78
72 COM B 73 74
24 V~ 24 V~0
71 COM A
NC NC
21 22
CLIOP822A
Shield internally connected to DIN rail
GND GND
GND GND
9 10
11 12 13 14 15 16 17 18
25 26
10
XS814
A1 A2 A3 A4 A5 A6 A7
A1 A2
1 2 3 4
5 6
1 2
F1
F2
24V~ drive with 0...10V signal 1: 24V~ power supply 2: GND 3: Signal
1 2 3
M
0...10V
Fig. 68
47
EN1Z-0921GE51 R0709
LION System
This updating (synchronization) is performed: If the calculated position of the actuator < lower synchronization threshold (2 %) = synchronization towards 0 % If the calculated position of the actuator > upper synchronization threshold (98 %) = synchronization towards 100 % Following any power-up or any reset
2 M
2 M
Fig. 69
The relay module facilitates the control of peripheral devices with high load via the analog outputs. Input terminal 17 controls of MCD3 controls changeover contact K3. Relay terminal 18 of MCD3 controls the N.O. contacts (floating outputs) K1, K2. For fusing specifications, see section "Fusing Specifications" on page 11.
EN1Z-0921GE51 R0709
48
LION System
72 COM B 73
74
24 V~ 24 V~0
71 COM A
75
76 77 78
72 COM B 73
74
24 V~ 24 V~0
71 COM A
NC NC
External group required to power external devices.
CLIOP822A
21 22
1 2
GND GND
GND GND
9 10
11 12 13 14 15 16 17 18
25 26
9 10
XS814
A1 A2 A3 A4 A5 A6 A7
A1 A2
1 2
1 2
F1
11 12 13 14 15 16 17 18
F2
24V~ Drive with 0...10V Signal 1: 24V~ power supply 2: GND 3: signal
MCE 3
1 2 3
max. 240 V 0.2 A 2A K1 K2 K3
K1
1 2 3 4
K2
5 6
K3
7 8
M 0...10V
The relay module facilitates the control of peripheral devices with high load via the analog outputs.
Input terminal 16 of MCE3 controls the N.O. contact K3. Input terminal 17 of MCE3 controls the changeover contact K2. Input terminal 18 of MCE3 controls the changeover contact K1.
49
EN1Z-0921GE51 R0709
LION System
Terminals
71 COM A
24 V~ 24 V~0 COM A COM B 24 V~ 24 V~0
75 76 77 78
72 COM B 73 74
CLIOP823 Panel Bus binary input module CLIOL823 LONWORKS Bus binary input module XS823 XSU823 Terminal socket
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12
Light gray
10 11 12
GND GND GND GND GND GND GND GND GND GND GND GND
13 14 15 16 17 18 19 20 21 22 23 24
25 26
Features
12 binary inputs 12 configurable status LEDs (green/red, yellow/OFF) Binary inputs can be used as
Fig. 72
Terminal
Signal
COMMENT
71, 75 72, 76
2-wire communication bus (LON/Panel Bus) 2-wire communication bus (LON/Panel Bus) Power supply Power supply Ground. All grounds are connected internally to each other. Shield connection (functional earth), internally connected to the DIN rail.
1 2
Notes
4 5
Shield connection to be used for shielded I/O cables only. It is not allowed to connect a LONWORKS shield, since LONWORKS requires a resistor and capacitor. If additional shield terminals are needed, the XS814 Auxiliary Terminal Package can be installed.
Fig. 71 Legend
1 2 3 4 5
Service button S1 Hex switch S2 Input LEDs Service LED Power LED
Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following.
EN1Z-0921GE51 R0709
50
LION System
Technical Data
Input type Current rating (closed input) Open contact voltage Protection
Using the engineering tool, the binary inputs can be configured as fast totalizers for operation in conjunction with devices equipped with an open collector output. max. 20 Hz min. 25 ms min. 25 ms max. 5 ms
Fig. 73
51
EN1Z-0921GE51 R0709
LION System
Connection Example
71 72 73 74
A B 24 V~ 24 V~0
A B 24 V~ 24 V~0
75 76 77 78
71 72 73 74
A B 24 V~ 24 V~0
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12
CLIOP823A
1 2
9 10 11 12
Shield internally connected to DIN rail
13 14 15 16 17 18 19 20 21 22 23 24
25 26
F1
Dry contact 1: signal 2: GND
1 2
Dry contact
1 2
min. 25 ms
Totalizer
Fig. 74
EN1Z-0921GE51 R0709
52
LION System
Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following. In the event of communication problems, the relay outputs will move to the safety positions you have configured using the engineering tool, see relay output point description in the CARE User Guide, 74-5587/EN2B-0182GE51.
CLIOP824
CLIOPR824 Panel Bus relay output module Light gray with manual overrides CLIOL824 LONWORKS Bus relay output module Dark gray Dark gray
WARNING
Risk of electric shock or equipment damage! Low voltage and line voltage must not be wired within the same relay block.
Wire low voltage e.g., to relay block 1 and line voltage to
XS824-25 Terminal socket; can be fitted Light gray XSU824-25 with long (red) cross connector (incl. in scope of the delivery)
Table 53 LION Relay Output Modules
relay block 2 or vice versa. In this case the short cross connectors must be used, see Table 5 on page 7.
NOTICE Features
6 relays (changeover contacts), arranged in two blocks R824: 6 manual overrides Low and line voltage allowed, see WARNING. Risk of malfunction! Cross connectors may only be used if the same voltage is used on all relays they connect.
Do not use a cross connector if different voltages are
1 2
used on the relays. E.g., use a short cross connector for relay block 1 with line voltage and no cross connector for relay block 2 with 12 V low voltage for relay 4 and 24 V low voltage for relays 5 and 6.
5 6
Fig. 75 Legend
1 2 3 4 5 6
Service button S1 Hex switch S2 Manual overrides Status LEDs Service LED Power LED
53
EN1Z-0921GE51 R0709
LION System
Terminals
72 COM B 73 74
24 V~ 24 V~0
Permissible Loads
COM A COM B 24 V~ 24 V~0
71 COM A
75 76 77 78
Max. load Per relay 19250 VAC output current at cos 0.6: 12 A module (total) 129 VDC 12 A resistive, 3 A inductive Per normally open contact 19250 VAC current at cos 0.6: 4 A 129 VDC 4 A resistive, 1 A inductive 19250 VAC current at cos 0.95: 2 A, current at cos 0.6: 1 A 129 VDC 4 A resistive, 1 A inductive
Min. load
Relay block 1
NO NC COM CON
Relay block 2
50 mW
11 12 13 14
NO 21 NC 22 COM 23 CON 24
NO NC COM CON
31 32 33 34
NO NC COM CON
41 42 43 44
NO NC COM CON
51 52 53 54
NO NC COM CON
61 62 63 64 25
50 mW
Fig. 76
Table 55 Permissible loads of relay output modules Notes In the case of voltages above 30 VAC/DC and if inductive components are to be connected to relays switching more often than once every 2 minutes, these components must be prevented from causing harmful interference to radio or television reception (conformance with EN 55014). Max. voltage for UL 864-compliant applications is 24 V.
Terminal Signal
2-wire communication bus COM a 71, 75 (LON/Panel Bus) 2-wire communication bus COM b 72, 76 (LON/Panel Bus) 24 V~ 73, 77 Power supply 24 V~0 74, 78 Power supply REL1 N.O. Relay 1 N.O. contact 11 REL1 N.C. Relay 1 N.C. contact 12 R1 COM 13 relay 1 common contact For connection of relay 1 common via R1 COM 14 cross connector* REL2 N.O. Relay 2 N.O. contact 21 REL2 N.C. Relay 2 N.C. contact 22 R2 COM 23 Relay 2 common contact For connection of relay 2 common via R2 COM 24 cross connector* REL3 N.O. Relay 3 N.O. contact 31 REL3 N.C. Relay 3 N.C. contact 32 R3 COM 33 Relay 3 common contact For connection of relay 3 common via R3 COM 34 cross connector* REL4 N.O. Relay 4 N.O. contact 41 REL4 N.C. Relay 4 N.C. contact 42 R4 COM 43 Relay 4 common contact For connection of relay 4 common via R4 COM 44 cross connector* REL5 N.O. Relay 5 N.O. contact 51 REL5 N.C. Relay 5 N.C. contact 52 R5 COM 53 Relay 5 common contact For connection of relay 5 common via R5 COM 54 cross connector* REL6 N.O. Relay 6 N.O. contact 61 REL6 N.C. Relay 6 N.C. contact 62 R6 COM 63 Relay 6 common contact For connection of relay 6 common via R6 COM 64 cross connector* Shield connection (functional earth), 25 internally connected to the DIN rail * Do not connect by wire!
RELAY BLOCK 1
Automatic mode, logical state ON Automatic mode, logical state OFF Override mode (setting 0) Override mode (setting 1)
ON OFF OFF ON
OFF ON ON OFF
RELAY BLOCK 2
Fig. 77
The R824A Relay Output Modules are equipped with manual overrides: one for each relay output. These sliding switches can manually be set to either "auto" or "0" or "1".
EN1Z-0921GE51 R0709
54
LION System
When a manual override of the R824 Relay Output Module is set to the AUTO position, and the corresponding relay output has been configured, the following applies:
When a manual override of the R824 Relay Output Module is set to the ON position, the following applies:
If the LONWORKS network is functioning properly, the logical status of the relay output will be AUTO. If the LONWORKS network is not functioning properly, the feedback signal will be switched to the safety position value. The feedback signal on the LONWORKS network: nvoDoActPosnFb[ ] will have a value of either 0% or 100%, and a state of -1. The status LED (yellow) will indicate the actual logical state of the relay output as commanded (by nviDoSwitch[ ]).
If the relay output has been configured, its logical state will depend upon the actual output configuration. If the relay output is unconfigured, it will be switched ON. Regardless of configuration, the feedback signal on the LONWORKS network: nvoDoActPosnFb[ ] will have a value of 10000% and a state of -1. Regardless of configuration, the status LED (yellow) will flash to indicate manual override.
When a manual override of the R824 Relay Output Module is set to the AUTO position, and the corresponding relay output has not been configured, the following applies:
When a manual override of the R824 Relay Output Module is set to the OFF position, the following applies:
If the relay output has been configured, its logical state will depend upon the actual output configuration. If the relay output is unconfigured, it will be switched OFF. Regardless of configuration, the feedback signal on the LONWORKS network: nvoDoActPosnFb[ ] will have a value of 0% (direct) or 100% (reverse) and a state of -1. Regardless of configuration, the status LED (yellow) will flash to indicate manual override.
Regardless as to whether the LONWORKS network is functioning properly or not, values from the LONWORKS Bus will be ignored, and there will be no heartbeat or safety position. The feedback signal on the LONWORKS network: nvoDoActPosnFb[ ] will have a value of 0% and a state of 0. The status LED will be dark.
55
EN1Z-0921GE51 R0709
LION System
Connection Example
72 COM B 73 74
24 V~ 24 V~0
71 COM A
75 76 77 78
72 COM B 73 74
24 V~ 24 V~ 0
71 COM A
NO NC COM CON
11 12 13 14
NO 21 NC 22 COM 23 CON 24
NO NC COM CON
31 32 33 34
NO NC COM CON
41 42 43 44
NO NC COM CON
51 52 53 54
NO NC COM CON
61 62 63 64
25
A1 A2 A3 A4 A5 A6 A7
1 2
230 V
F1
1 M
2 M
LN
Power Supply 230 V~
230V
230V
Fig. 78
EN1Z-0921GE51 R0709
56
LION System
Fig. 79
CLIOP824A connection example (relay blocks with low and line voltage)
57
EN1Z-0921GE51 R0709
LION System
WARNING
Risk of electric shock or equipment damage! Low voltage and line voltage must not be wired within the same relay block.
Wire low voltage e.g., to relay block 1 and line voltage to
relay block 2 or vice versa. In this case the short cross connectors must be used, see Table 5 on page 7.
In the event of communication problems, the 3 floating outputs will move to the safety positions you have configured using the engineering tool, see floating output point description in the CARE User Guide, 74-5587/EN2B0182GE51.
NOTICE
Risk of malfunction! Cross connectors may only be used if the same voltage is used on all relays they connected.
Do not use a cross connector if different voltages are
1 2
used on the relays. E.g., use a short cross connector for relay block 1 with line voltage and no cross connector for relay block 2 with 12 V low voltage for relay 4 and 24 V low voltage for relays 5 and 6.
Permissible loads
3
Max. load Per relay 19250 VAC output current at cos 0.6: 12 A module (total) 129 VDC 12 A resistive, 3 A inductive Per normally open contact Fig. 80 Legend CLIOPR825A Floating Output Module with terminal socket Per normally closed contact 19250 VAC current at cos 0.6: 4 A) 129 VDC 4 A resistive, 1 A inductive 19250 VAC current at cos 0.95: 2 A, current at cos 0.6: 1 A 129 VDC 4 A resistive, 1 A inductive Table 57 Permissible loads of floating output modules Min. load
5 6
50 mW
50 mW
1 2 3 4 4 5
Service button S1 Hex switch S2 Manual overrides Status LEDs Service LED Power LED
Notes
Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following.
In the case of voltages above 30 VAC/DC and if inductive components are to be connected to relays switching more often than once every 2 minutes, these components must be prevented from causing harmful interference to radio or television reception (conformance with EN 55014). Max. voltage for UL 864-compliant applications is 24 V.
EN1Z-0921GE51 R0709
58
LION System
Terminals
71 COM A 72 73 74
COM B 24 V~ 24 V~0 COM A COM B 24 V~ 24 V~0
Actuator 1
NO NC COM CON
Actuator 2
NO NC COM CON
Actuator 3
NO NC COM CON
11 12 13 14
NO 21 NC 22 COM 23 CON 24
31 32 33 34
NO NC COM CON
41 42 43 44
51 52 53 54
NO NC COM CON
61 62 63 64 25
Auto
Override
Fig. 81
Signal
COM a COM b 24 V~ 24 V~0 REL1 N.O. REL1 N.C. R1 COM R1 COM REL2 N.O. REL2 N.C. R2 COM R2 COM REL3 N.O. REL3 N.C. R3 COM R3 COM REL4 N.O. REL4 N.C. R4 COM R4 COM REL5 N.O. REL5 N.C. R5 COM R5 COM REL6 N.O. REL6 N.C. R6 COM R6 COM
Comment 2-wire communication bus (LON/Panel Bus) 2-wire communication bus (LON/Panel Bus) Power supply Power supply Floating relay 1 N.O. contact Floating relay 1 N.C. contact Floating relay 1 common contact For connection of floating relay 1 common via cross connector* Floating relay 2 N.O. contact Floating relay 2 N.C. contact Floating relay 2 common contact For connection of floating relay 2 common via cross connector* Floating relay 3 N.O. contact Floating relay 3 N.C. contact Floating relay 3 common contact For connection of floating relay 3 common via cross connector* Floating relay 4 N.O. contact Floating relay 4 N.C. contact Floating relay 4 common contact For connection of floating relay 4 common via cross connector* Floating relay 5 N.O. contact Floating relay 5 N.C. contact Floating relay 5 common contact For connection of floating relay 5 common via cross connector* Floating relay 6 N.O. contact Floating relay 6 N.C. contact Floating relay 6 common contact For connection of floating relay 6 common via cross connector* Shield connection (functional earth), internally connected to the DIN rail
0
AUTO
100
ACTUATOR 1
Fig. 82
The floating output module is equipped with manual overrides: one for each floating output. These rotary knobs can be manually set to either "AUTO" or "0 100%" (infinitely adjustable).
NOTICE
Damage to the electronic module!
Do not use a tool to adjust the rotary knobs. Do not use excessive force. Adjust only by hand.
ACTUATOR 2
When a manual override of the CLIOPR825A is set to AUTO, the following applies:
ACTUATOR 3
The output signal of the respective floating output (R1 + R2 or R3 + R4 or R5 + R6) will be as commanded. The respective pair of status LEDs will be ON/OFF as commanded.
When a manual override of the CLIOPR825A is set to 0100%, the respective floating output will drive to the set position. The runtime depends upon the actuator runtime configured using the engineering tool and on the actual position.
59
EN1Z-0921GE51 R0709
LION System
If a floating relay output has been configured, the following applies: The corresponding manual override can be used to adjust the respective floating actuator so that it drives to any desired position between fully closed (0%) and fully open (100%). The "open" relay or "closed" relay as the case may be is then switched ON for the time the actuator requires to drive to the desired position, whereupon it will stop. This required time depends upon the configured motor runtime (time to open / time to close), while the direction of movement is dependent upon the configured direct/reverse setting.
Unconfigured Floating Relay Output
50 0
AUTO
50 100 0
AUTO
100
0
AUTO
100
RELAY N CLOSED RELAY N OPEN RELAY N+1 OPEN RELAY N+1 CLOSED ACTUATOR CLOSES ACTUATOR OPENS
Fig. 83.
If a floating relay output has not been configured (see Fig. 83), the following applies: Although the motor runtime is unknown to the CLIOPR825A, the corresponding manual override can be used during the commissioning phase to adjust the respective floating actuator so that it drives to any desired position between fully closed (0%) and fully open (100%). The "open" relay (relay "n," i.e. 1, 3, or 5) and the "closed" relay (relay "n+1," i.e. 2, 4, or 6) are then switched ON and/or OFF, respectively, when the corresponding manual override is set to "0100%." Specifically, the actuator will drive towards its closed position as long as the manual override is set to "050%," and it will drive towards its open position as long as it is set to "50100%." Setting the manual override to "AUTO" stops the actuator.
EN1Z-0921GE51 R0709
60
LION System
Connection Example
72 COM B 73 74
24 V~ 24 V~0
71 COM A
75 76 77 78
72 COM B 73 74
24 V~ 24 V~0
71 COM A
NO NC COM CON
11 12 13 14
NO 21 NC 22 COM 23 CON 24
NO NC COM CON
31 32 33 34
NO NC COM CON
41 42 43 44
NO NC COM CON
51 52 53 54
NO NC COM CON
61 62 63 64
25
A1 A2 A3 A4 A5 A6 A7
1 2 3 4
5 6
F1
3 2
1 M
L N
Fig. 84
61
EN1Z-0921GE51 R0709
LION System
WARNING
Risk of electric shock or equipment damage! It is not permitted to wire the relays of the mixed Panel Bus I/O modules for anything other than low voltage.
In the event of communication problems, the relay outputs will move to the safety positions you have configured using the engineering tool, see relay output point description in the CARE User Guide, EN2B-0182GE51 / 74-5587.
71 72 73 74 COM a COM b 24V~ 24V~0
40
External 24V
Permissible Loads
load per mixed Panel Bus I/O module (total for all relay contacts) per normally open contact 24 VDC/VAC max. 3 A resistive or inductive, cos 0.6, no capacitive load 24 VDC/VAC min. 0.05 A resistive or inductive, cos 0.6, max. 0.5 A resistive or inductive, cos 0.6, no capacitive load min. load
012
3 45
Binary Inputs
Analog Inputs
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 7 8 9 10 11 12 17 18 19 20 1 2 3 4 5 6 13 14 15 16 B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4
Install. Instr. EN1B-0375GE51
DI
1 2 3 4 5 6 7 8 9 10 11 12
CLIOP830A
12 BI / 8 AI / 8 AO / 6 RO 24V, 15VA, T50 0706AX0001-XFU830A 8
Made in Germany 0532
7 8 9 10 11 12 17 18 19 20
1 2 3 4 5 6 13 14 15 16
A1 A2 A3 A4 A5 A6 A7 A8 A9
A C
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 A2 A3 A4 A5 A6 A7 A8 A9
A1 A2 A3 A4 A5 A6 A7 A8 A9
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 B1 A2 B2 A3 B3 A4 B4 G1
Fig. 85
Binary Inputs
Analog Inputs
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 7 8 9 10 11 12 17 18 19 20 1 2 3 4 5 6 13 14 15 16 B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4
Install. Instr. EN1B-0375GE51
DI
1 2 3 4 5 6 7 8 9 10 11 12
CLIOP830A
12 BI / 8 AI / 8 AO / 6 RO 24V, 15VA, T50 0706AX0001-XFU830A 8
Made in Germany 0532
7 8 9 10 11 12 17 18 19 20
1 2 3 4 5 6 13 14 15 16
2
Fig. 86 Legend CLIOP830A Mixed I/O Module - features
1 2 3 4
Functionality of service LED and power LED: see Table 77 to Table 79 on page 78.
EN1Z-0921GE51 R0709
BCD
EF
71 72 73 74
01 2
S2
BCD
EF
S2
75 76 77 78
1
40
External 24V
3 45
67
8 9A
GND
Analog Outputs
AO5 AO6 25 26 21 22 AO1 AO2 AO7 27 23 AO3
24V Relays
IN5 39 33 NO5 IN6 40 34 NO6
!
G1 G2 41 42
AO8 IN1 IN2 IN3 IN4 28 35 36 37 38 24 29 30 31 32 AO4 NO1 NO2 NO3 NO4
1 2 3 4 5 6
DO
25 26 27 28 35 36 37 38 39 40
>50 mW
41 42
21 22 23 24 29 30 31 32 33 34
B D
B1 B2 B3 B4 B5 B6 B7 B8 B9
A5 B5 A6 B6 A7 B7 A8 B8 G2
75 76 77 78
67
8 9A
GND
Analog Outputs
AO5 AO6 25 26 21 22 AO1 AO2 AO7 27 23 AO3
24V Relays
IN5 39 33 NO5 IN6 40 34 NO6
!
G1 G2 41 42
AO8 IN1 IN2 IN3 IN4 28 35 36 37 38 24 29 30 31 32 AO4 NO1 NO2 NO3 NO4
1 2 3 4 5 6
DO
25 26 27 28 35 36 37 38 39 40
41 42
21 22 23 24 29 30 31 32 33 34
62
LION System
Terminals
72 COM B 73 74
24 V~ 24 V~0
71 COM A
75 76 77 78
BINARY INPUTS
ANALOG INPUTS
GND
ANALOG OUTPUTS
JUMPER
24 V RELAYS
J1
JUMPER
J2
JUMPER
J3
JUMPER
J4
JUMPER
IN1 35 29 NO1 R1
IN2 36 30 NO2 R2
IN3 37 31 NO3 R3
IN4 38 32 NO4 R4
25 26 27 28
AO1 AO2 AO3 AO4
39 33 NO5
21 22 23 24
Fig. 87
Terminal assignment and internal connections of mixed Panel Bus I/O module terminals
Terminal 71, 75 72, 76 73, 77 74, 78 17 812 1320 41, 42 2128 2934
Comment 2-wire communication bus (Panel Bus) 2-wire communication bus (Panel Bus) Power supply Power supply Binary inputs 17 Binary inputs 812 Analog inputs 18 Ground. Both grounds are internally connected to each other and to 24 VAC0. Analog outputs 18 Relays 16, normally-open contacts Common contacts of relays 15. May be set to common supply voltage via terminal 40 by inserting jumpers J1J5 into their lower positions. When, in contrast, a jumper is in the upper position (the so-called parking position = default setting), the corresponding relay receives no supply voltage from terminal 40. Common contact of relay 6, internally connected to the middle contact of jumpers J1J5. May be used to connect common supply voltage.
AO1AO8 NO16
3539
IN15
--
40
IN6
--
63
EN1Z-0921GE51 R0709
LION System
Connection Example
F1
72 COM B 73 74
24 V~ 24 V~ 0
71 COM A
75 76 77 78
B1 B2 B3 B4 B5 B6 1 2 3 4 5 6
G1 G2 41 42
A1 A2 A3 A4 A5 A6 A7 A8 A9 1 2 3 4 5 6 7 8 9
B1 B2 B3 B4 B5 B6 B7 B8 B9 1 2 3 4 5 6 7 8 9
A1 A2 A3 A4 A5 A6 A7 A8 A9 1 2 3 4 5 6 7 8 9
B1 B2 B3 B4 B5 B6 B7 B8 B9 1 2 3 4 5 6 7 8 9
Fig. 88
For fusing specifications see section "Fusing Specifications" on page 11. For internal connections of auxiliary terminal modules, see section XS830 Auxiliary Terminal Package and section XS831 Auxiliary Terminal Package on page 66.
F1
72 COM B 73 74
24 V~ 24 V~ 0
71 COM A
COM A COM B 24 V~ 24 V~ 0
75 76 77 78
B1 B2 B3 B4 B5 B6 1 2 3 4 5 6
G1 G2 41 42
NO1NO2NO3NO4NO5NO6 29 30 31 32 33 34
A1 A2 A3 A4 A5 A6 A7 A8 A9 1 2 3 4 5 6 7 8 9
B1 B2 B3 B4 B5 B6 B7 B8 B9 1 2 3 4 5 6 7 8 9
A1 A2 A3 A4 A5 A6 A7 A8 A9 1 2 3 4 5 6 7 8 9
B1 B2 B3 B4 B5 B6 B7 B8 B9 1 2 3 4 5 6 7 8 9
A1 B1 A2 B2 A3 B3 A4 B4 G1 1 2 3 4 5 6 7 8 9
A5 B5 A6 B6 A7 B7 A8 B8 G2 1 2 3 4 5 6 7 8 9
Fig. 89
EN1Z-0921GE51 R0709
64
LION System
XS812RO
824 825
For mounting the manual disconnect modules, see Fig. 24 on page 21.
Fig. 91
WARNING
Risk of electric shock or equipment damage due to improper use of XS812RO manual disconnect module!
Do not connect line voltage to the XS812RO.
1 2 3 4
XS812RO
5 6 7 8 9 10 11 12
Features Disconnector switches are used to manually disconnect individual terminals of the corresponding electronic module of pluggable I/O modules. Useful for troubleshooting and installation. Diagrams
NO NC NO NC NO NC NO NC NO NC NO NC 1 1 2 2 3 3 4 4 5 5 6 6
Fig. 92
Fig. 90
65
EN1Z-0921GE51 R0709
LION System
Terminal Assignment
A1 A2 A3 A4 A5 A6 A7 A8 A9 1 2 3 4 5 6 7 8 9 B1 B2 B3 B4 B5 B6 B7 B8 B9 1 2 3 4 5 6 7 8 9
Fig. 96
Terminal Assignment
1 2 3 4
1 2 3 4
5 6
The ground side of each of the eight incoming 020 mA signals (A1B1, A2B2, A8B8) must be connected to a ground terminal.
Fig. 94
A1 B1 A2 B2 A3 B3 A4 B4 G1
A5 B5 A6 B6 A7 B7 A8 B8 G2
Fig. 97
Terminal Assignment
A1 B1 A2 B2 A3 B3 A4 B4 G1 1 2 3 4 5 6 7 8 9 A5 B5 A6 B6 A7 B7 A8 B8 G2 1 2 3 4 5 6 7 8 9
Fig. 98
A1 A2 A3 A4 A5 A6 A7 A8 A9
B1 B2 B3 B4 B5 B6 B7 B8 B9
Fig. 95
EN1Z-0921GE51 R0709
66
LION System
Cross Connectors
XS815 Cross Connector Features For connecting the common terminals of all 6 relays of the CLIOL824 and CLIOLR824 Relay Output Modules and the CLIOLR825 Floating Output Module. This is permitted when all terminal blocks carry the same voltage Long, red Supplied with the terminal socket
XS817 Cross Connector Features For connecting the common terminals of only relays 13 or of relays 46 of the CLIOL824 and CLIOLR824 Relay Output Modules and the CLIOLR825 Floating Output Module. Short, yellow Must be ordered separately
Fig. 100
67
EN1Z-0921GE51 R0709
LION System
LION LONWORKS Bus I/O Modules are addressed, bound, and commissioned using CARE or any other standard LONWORKS commissioning tool based on LNS 2.0 and higher, e.g., LonMaker for Windows.
Configuration
LION LONWORKS Bus I/O Modules are configured using CARE or COACH.
Fig. 101
NTC10k NTC20k PT1000-1 NI1000TK5000 PT3000 BALCO500 PT1000-2 0(2)10V Slow binary input Other Sensors Sensor break/short circuit
nvoAiTempP
Transmission/Updates
These variables are transmitted immediately when their value has been changed by a higher rate than the configured "send on delta" (default: 0.3 K). These variables are also transmitted as heartbeat output (default: 60 sec) on a regular basis as dictated by the maximum send time (nciSndHrtBt) configuration variable. EN1Z-0921GE51 R0709
68
LION System
The default value is set after power-up or reset and remains until the module has measured a valid value. nvoAiTempP = INVALID = 0x7FFF (= 327.67 C)
<0V 0 V 10 V > 10 V
0% 0 100 % 100 %
100 % 0% 0%
1 0 -1
Default Value
The default value is set after power-up or reset and remains until the module has measured a valid value. nvoAiValuePct = INVALID = 0x7FFF (=163.835 %) The sensor failure behavior can be configured for 2 10 V.
The default value is set after power-up or reset and remains until the module has measured a valid value. nvoAiTemp = INVALID = 0xFFFF (= 6279.5 C)
69
EN1Z-0921GE51 R0709
LION System
Receive Heartbeat
The default configuration for Receive Heartbeat is 300 sec. If no nvi update is received during this time, the actuators will go to their configured safety positions.
Start-up Behavior Fig. 104 Analog output control levels reverse actuator
At start-up, i.e., power-up or reset, all nvi's will be initialized with INVALID, and after 1 minute, the actuators will go to their configured safety positions.
Default Value
nvoAoValuePct = INVALID = 0x7FFF (=163.835 %) This will cause the actuator to adopt a predefined position defined for failure behavior.
EN1Z-0921GE51 R0709
70
LION System
1 0 -1
Analog output position due to normal control by nviAoSwitch or nviAoValuePct Manual override position via the manual override panel Current position unknown or synchronization active, analog output not configured
Value = 0 State = 1
0xFF
-1
Transmission
This variable is transmitted immediately when the corresponding network input variable has changed more than 1 % or immediately as an answer to an nviAoValuePct[ ] or nviAoSwitch[ ] update.
Default Service Type
71
EN1Z-0921GE51 R0709
LION System
ON OFF
100 % 0% 0%
1 0 -1
Open Loop Sensor Object (LonMark Object Type 1) nvoDiSwitch[x] SNVT_switch nvoDiCount[x] SNVT_count nciDiConfig[x] UCPT_DIConfig nciSndHrtBt SCPTmaxSendTime
Configuration Parameter Value File
Not configured
|1
#1
Default Value
The default value is set after power-up or reset and remains until the module has measured a valid value. Value = 0 State = -1
Transmission
This network variable output indicates the total number of transitions from 0 to 1 since the last reset due to power-up or network reset.
Valid Range
These variables are transmitted immediately when its value has been changed by a higher rate than the configured "send on delta" (in the case of the totalizer, send on delta has a default value of 5 counts). These variables are also transmitted as a heartbeat output on a regular basis as dictated by the maximum send time (nciSndHrtBt) (default = 0 = disabled) configuration variable.
Default Service Type
Fig. 106
Totalizer
State
Value
0 65534 65535
Power-up/Reset
After power-up and reset, the value 0xFFFF = 65535 will be sent to the network to indicate that previous count values have been lost due to a reset.
EN1Z-0921GE51 R0709
72
LION System
N/a
Open Loop Actuator Object (LonMark Object Type 3) nviDoSwitch[x] SNVT_switch |1
0 1 1
OFF OFF Outputs are switched according to actual output type configuration INVALID: as defined for failure behavior
0 0.5 100 %
N/a
-1
Default Value
Value = 0
Fig. 107 LONMARK output object
State = -1
Start-up Behavior
At start-up, i.e., power-up or reset, all nvi's will be initialized with INVALID, leading the actuator to drive to the configured safety position after 1 minute.
Receive Heartbeat
The default configuration for Receive Heartbeat is 300 sec. If no nvi update is received during this time, the field devices will go to their configured safety positions.
73
EN1Z-0921GE51 R0709
Troubleshooting
LION System
Troubleshooting
Testing Wiring Connections
Push-in terminals feature small holes (1 mm in diameter) which can be used to measure the signals.
Insert a probe (1) as shown on the right.
Fig. 108
Normal operation One or more of the internal voltage supplies are outside of the permissible ranges. The controller stops operation.
No action necessary
Check power Check wiring If the problem persists, replace
hardware
3 Goes out briefly The operator has activated the reset button The controller is performing a warm start Table 71 CLLIONLC01 power LED
No action necessary
EN1Z-0921GE51 R0709
74
LION System
Troubleshooting
Normal operation Watchdog alarm output is powered The controller has encountered a hardware problem - or The application has a fault - or The controller has been powered up without an application or the operator has manually stopped the application, e.g., using XL-Online. In this case, the LED will light up 13 minutes after power-up without application
No action necessary
Try powering down and then
hardware
Flashing
Although the controller has encountered a problem, the watchdog alarm output has not yet been powered.
If, however, it happens multiple times, If the problem persists, the LED will become lit then there is an application or hardware constantly, see case #2. problem (see case #2) The controller performs a warm start.
Table 72 CLLIONLC01 alarm LED
75
EN1Z-0921GE51 R0709
Troubleshooting
LION System
Fig. 109
The LONWORKS service LED of the controller module displays the following flashing patterns indicating possible failure modes:
case 1 2 3 4 When can it occur? Meaning Remedy
Node is configured and running normally Bad node hardware Bad node hardware
No action necessary
Replace hardware Replace hardware
Node lacks application. Using EXCELON, set module to May be caused by neuron chip firmware when configured online a mismatch occurs on application checksum If the problem persists, the MIP software on LW interface has been erased due to wrong setting performed using ECHELON tool: Replace hardware Watchdog timer resets occurring. Possible corrupt EEPROM and bootstrap mode Node is unconfigured but has an application
Download firmware
Anytime
Anytime
EN1Z-0921GE51 R0709
76
LION System
Troubleshooting
If the C-bus is functioning properly, then the No action necessary CLLIONLC01 Controller is functioning properly If the C-bus is not functioning properly, then the termination can be wrong
Check C-bus termination switch S1
2 3
If the HMI Interface is functioning properly, No action necessary then the CLLIONLC01 Controller is functioning properly No HMI Interface communication
Check HMI Interface connection and
If the Modem Interface is functioning properly, No action necessary then the CLLIONLC01 Controller is functioning properly No Modem Interface communication
Check Modem Interface connection
77
EN1Z-0921GE51 R0709
Troubleshooting
LION System
If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring. If the problem is solved, this is an indication that the I/O module was defective. For troubleshooting purposes, the following features can be used: Power LED (all LION I/O modules) Service LED (all LION 800 I/O modules) Service button (pluggable LION I/O modules, only) In addition, a module-specific troubleshooting may be necessary.
I/O module is powered No power If the I/O modules service LED is likewise flashing, the I/O module is in the boot mode
No action necessary
Check power supply Wait until rebooting (firmware
EN1Z-0921GE51 R0709
78
LION System
Troubleshooting
Service LED
LED remains OFF after power-up
Meaning
If the power LED is also OFF, then Defective device hardware Possible power supply problems, clock problems, or defective processor LONWORKS Bus I/O modules: Defective hardware Panel Bus I/O modules: I/O module has not yet been configured by XCL8010 Boot loader is active Failure during last firmware download Checksum error
Remedy
Replace hardware
LONWORKS Bus I/O modules: Replace hardware Panel Bus I/O modules: Set the hex address to the position configured with CARE Ensure that I/O Bus switch S2 of XCL8010 Controller is set to position "Panel" Check the Panel Bus wiring: - Check for cable breaks - Check for cable short-circuits - If using separate transformers: Check ground connection Eliminate any mixture of Panel Bus I/Os and LonWorks I/Os on same wire Allow XCL8010 to configure I/O module Unplug and replug the module If problem persists, replace hardware Panel Bus I/O modules, only: Wait until rebooting (firmware download) has been completed Download application
Alternating flash between service LED and power LED LED flashes at power up, goes OFF, and then is lit continuously LED repeatedly blinks ON for 1 sec and OFF for 1 sec LED remains OFF after a short ON duration LED flashes continuously in following pattern: 4 x ON/OFF followed by pause LED flashes continuously in following pattern: 5 x ON/OFF followed by pause LED flashes continuously in following pattern: 6 x ON/OFF followed by pause LED flashes continuously in following pattern: 7 x ON/OFF followed by pause
Panel Bus I/O modules, only: Download error or application checksum error. Boot loader is running LONWORKS Bus I/O modules, only: The LONWORKS Bus I/O module lacks application LONWORKS Bus I/O modules, only: The LONWORKS Bus I/O module is unconfigured, but has an application I/O module is configured and running normally Sensor failure of analog input module (in the case of LONWORKS Bus I/O modules, this behavior can occur only if the appropriate NV has been bound) LONWORKS Bus I/O modules, only: LONWORKS I/O Bus module has received the wink command from network, physical outputs are unaffected Boot loader problem or hardware defect
6 7
No action necessary
Replace hardware
10
Communications failure
Check bus wiring Check I/O Bus switch S2 of CLLIONLC01 Controller Ensure that LONWORKS Bus I/O modules and Panel Bus I/O modules are not sharing the same bus In case of Panel Bus I/O modules, only: Check for incorrect HEX addresses (2 Panel Bus I/O modules using the same HEX address) In case of LONWORKS Bus I/O modules, only: Check heartbeat
79
EN1Z-0921GE51 R0709
Troubleshooting
LION System
The service LED and all other LEDs of that Panel Bus I/O module light up for as long as the service button is pressed.
LED Correct behavior
Power LED Service LED Analog output module status LEDs Relay output module status LEDs Digital input module status LEDs
ON continuously (if it flashes, check the 24 VAC power supply) ON continuously ON continuously ON continuously Red -> green -> yellow -> red -> green -> yellow, cyclically every 0.5 sec
Table 79 Effects of pressing and holding down service button of pluggable I/O modules
Wrong sensor configuration Incorrect wiring Sensor failure Negative voltage on at least one channel
inputs.
2
Unstable sensor measurements a voltage of about 8.88 V(*) is measured (with an external voltmeter) at an open analog input configured for: NTC20k or Pt1000-1/-2 or Pt3000 or Balco 500 or NTC10k or NI1000TK5000.
(see Fig. 63 and Fig. 64 on page 43 and following) Sensor is not connected
Connect the configured sensor
a voltage of about 8.88 V(*) is measured (with an external voltmeter) at an open analog input configured for: 010V with pull-up or slow Digital Input
No action necessary
(*): voltage may differ slightly depending on the input impedance of the used voltmeter
Table 80 Failure modes of analog input modules
EN1Z-0921GE51 R0709
80
LION System
Troubleshooting
Improper manual override settings Outputs are in safety position Software problem
Improper manual override settings Outputs are in safety position Software problem
check outputs
Check communication Power down and then power up If the problem persists, replace
81
EN1Z-0921GE51 R0709
LION System
Example 1
Connecting a single transformer with multiple CLLIONLC01 Controllers earth-grounded as per EN60204-1
Connect earth ground to terminal 2 of the CLLIONLC01
Controllers
CLIOP/ CLIOL
CLIOP/ CLIOL
CLLIONLC01
24 24 V~ V~0 1 2
CLIOP/ CLIOL
CLIOP/ CLIOL
CLLIONLC01
24 24 V~ V~0 1 2
CLIOP/ CLIOL
CLIOP/ CLIOL
24 V~
LINE
24 V0
Fig. 110
If the application/plant does not contain machines that can be harmful to the operator due to an unexpected start-up, the standard EN60204-1 is not applicable. If such machines are encountered, then EN60204-1 must be followed. Grounding is required.
EN1Z-0921GE51 R0709
82
LION System
Example 2
Example 3
Connecting a LION System together with other controllers earth-grounded as per EN60204-1
Notes Use a noise-free earth ground inside the cabinet. Use one star-point to split power for controllers and field devices. If the transformer is used for several controllers, each controller ground has to be wired separately to the starpoint. If a field device that prohibits earth grounding is connected to the system ground, an isolation monitoring device must be used instead of earth grounding. If the field device transformer is physically far away from the controller, earth grounding must still be performed for the controller.
Connect earth ground to the respective terminal of the
XCL5010C
C+ 15 16 C17 18
XCL5010
C+ 5 C6
XL50
C+ 5 C6
CLLIONLC01
C+ 8 C9
SHIELD
10
XCL5010
24 24 V~ V~0 2 1
XSL511
24 24 V~ V~0 2 1
XL50
24 24 V~ V~0 2 1
XL100C
24 24 V~ V~0 71 72
CLLIONLC01
24 24 V~ V~0 1 2
FIELD DEVICE
Fig. 112
Fig. 111
If a system ground of the controller is connected to the earth ground, the available terminals for shielding the C-Bus must not be used. Instead, the C-Bus shield must be connected to the earth ground, but only once per bus connection.
NOTICE
Equipment damage!
Terminals 1 and 2 are assigned differently on the XCL5010 and CLLIONLC01 Controllers. Make sure that earth ground is connected to the correct terminal according to Fig. 111 and the respective connection diagrams.
The XL40, XL50, XL100C, Distributed IO, Smart IO, and the LION System can share one transformer. The XC5010C Controller always requires its own transformer. If EN60204-1 is applicable for the given type of controller, the system ground has the same potential as one terminal of the power supply.
83
EN1Z-0921GE51 R0709
LION System
Approved Modems
For information on modems approved for use with the LION System, please refer to the Frequently Asked Questions and Troubleshooting document available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the Intranet under: http://web.ge51.honeywell.de/tac
Go there, and enter the catchword "modemfaq" in the
Fig. 113
Modem interface
search field.
Modem Requirements
A Frequently Asked Questions and Troubleshooting document is available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the Intranet under: http://web.ge51.honeywell.de/tac
Go there, and enter the catchword "modemfaq" in the
search field.
Troubleshooting
In case of any problems, the handbook of the modem or ISDN terminal adapter must be consulted. A Frequently Asked Questions and Troubleshooting document is available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the Intranet under: http://web.ge51.honeywell.de/tac
Go there, and enter the catchword "modemfaq" in the
search field.
EN1Z-0921GE51 R0709
84
LION System
BALCO 500
Temp. [C] Resistance [] Terminal voltage [V] Temp. [C] Resistance [] Terminal voltage [V] Temp. [C] Resistance [] Terminal voltage [V] Temp. [C] Resistance [] Terminal voltage [V]
-30.0 -29.0 -28.0 -27.0 -26.0 -25.0 -24.0 -23.0 -22.0 -21.0 -20.0 -19.0 -18.0 -17.0 -16.0 -15.0 -14.0 -13.0 -12.0 -11.0 -10.0 -9.0 -8.0 -7.0 -6.0 -5.0 -4.0 -3.0 -2.0 -1.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
397 399 401 403 404 406 408 410 412 413 415 417 419 421 423 425 426 428 430 432 434 436 438 440 442 444 445 447 449 451 453 455 457 459 461 463 465 467 469 471
0.157 0.158 0.158 0.159 0.160 0.160 0.161 0.162 0.163 0.163 0.164 0.165 0.165 0.166 0.167 0.168 0.168 0.169 0.170 0.171 0.171 0.172 0.173 0.174 0.174 0.175 0.176 0.176 0.177 0.178 0.179 0.179 0.180 0.181 0.182 0.183 0.183 0.184 0.185 0.186
10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0 21.0 22.0 23.0 24.0 25.0 26.0 27.0 28.0 29.0 30.0 31.0 32.0 33.0 34.0 35.0 36.0 37.0 38.0 39.0 40.0 41.0 42.0 43.0 44.0 45.0 46.0 47.0 48.0 49.0
473 475 477 479 481 483 485 487 489 491 493 495 497 499 501 503 506 508 510 512 514 516 518 520 522 524 527 529 531 533 535 537 539 542 544 546 548 550 553 555
0.186 0.187 0.188 0.189 0.190 0.190 0.191 0.192 0.193 0.193 0.194 0.195 0.196 0.196 0.197 0.198 0.199 0.200 0.201 0.201 0.202 0.203 0.204 0.205 0.205 0.206 0.207 0.208 0.209 0.210 0.210 0.211 0.212 0.213 0.214 0.215 0.215 0.216 0.217 0.218
50.0 51.0 52.0 53.0 54.0 55.0 56.0 57.0 58.0 59.0 60.0 61.0 62.0 63.0 64.0 65.0 66.0 67.0 68.0 69.0 70.0 71.0 72.0 73.0 74.0 75.0 76.0 77.0 78.0 79.0 80.0 81.0 82.0 83.0 84.0 85.0 86.0 87.0 88.0 89.0
557 559 561 564 566 568 570 572 575 577 579 581 584 586 588 590 593 595 597 600 602 604 607 609 611 614 616 618 621 623 625 628 630 632 635 637 639 642 644 647
0.219 0.220 0.220 0.221 0.222 0.223 0.224 0.225 0.226 0.226 0.227 0.228 0.229 0.230 0.231 0.231 0.233 0.233 0.234 0.235 0.236 0.237 0.238 0.239 0.240 0.241 0.241 0.242 0.243 0.244 0.245 0.246 0.247 0.248 0.249 0.249 0.250 0.251 0.252 0.253
90.0 91.0 92.0 93.0 94.0 95.0 96.0 97.0 98.0 99.0 100.0 101.0 102.0 103.0 104.0 105.0 106.0 107.0 108.0 109.0 110.0 111.0 112.0 113.0 114.0 115.0 116.0 117.0 118.0 119.0 120.0
649 651 654 656 659 661 664 666 668 671 673 676 678 681 683 686 688 691 693 696 698 701 703 706 708 711 713 716 718 721 724
0.254 0.255 0.256 0.257 0.258 0.259 0.260 0.261 0.261 0.262 0.263 0.264 0.265 0.266 0.267 0.268 0.269 0.270 0.271 0.272 0.273 0.274 0.275 0.276 0.276 0.278 0.278 0.280 0.280 0.281 0.283
85
EN1Z-0921GE51 R0709
LION System
NTC 20 k
Temp. [C] Resistance [k] Terminal voltage [V] Temp. [C] Resistance [k] Terminal voltage [V] Temp. [C] Resistance [k] Terminal voltage [V] Temp. [C] Resistance [k] Terminal voltage [V]
-50.0 -49.0 -48.0 -47.0 -46.0 -45.0 -44.0 -43.0 -42.0 -41.0 -40.0 -39.0 -38.0 -37.0 -36.0 -35.0 -34.0 -33.0 -32.0 -31.0 -30.0 -29.0 -28.0 -27.0 -26.0 -25.0 -24.0 -23.0 -22.0 -21.0 -20.0 -19.0 -18.0 -17.0 -16.0 -15.0 -14.0 -13.0 -12.0 -11.0 -10.0 -9.0 -8.0 -7.0 -6.0 -5.0 -4.0 -3.0 -2.0 -1.0 0.0 1.0 2.0 3.0 4.0
1659 1541 1432 1331 1239 1153 1073 1000 932 869 811 757 706 660 617 577 539 505 473 443 415 389 364 342 321 301 283 266 250 235 221 208 196 184 174 164 154 146 137 130 122 116 109 103 97.6 92.3 87.3 82.6 78.2 74.1 70.2 66.5 63.0 59.8 56.7
8.78 8.77 8.76 8.75 8.74 8.72 8.71 8.70 8.69 8.67 8.66 8.64 8.62 8.60 8.58 8.56 8.54 8.52 8.49 8.47 8.44 8.41 8.38 8.35 8.32 8.28 8.25 8.21 8.17 8.13 8.08 8.04 7.99 7.94 7.89 7.83 7.78 7.72 7.66 7.60 7.53 7.46 7.39 7.32 7.25 7.17 7.09 7.01 6.93 6.85 6.76 6.67 6.58 6.49 6.40
5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0 21.0 22.0 23.0 24.0 25.0 26.0 27.0 28.0 29.0 30.0 31.0 32.0 33.0 34.0 35.0 36.0 37.0 38.0 39.0 40.0 41.0 42.0 43.0 44.0 45.0 46.0 47.0 48.0 49.0 50.0 51.0 52.0 53.0 54.0 55.0 56.0 57.0 58.0 59.0
53.8 51.1 48.5 46.0 43.7 41.6 39.5 37.6 35.7 34.0 32.3 30.8 29.3 27.9 26.6 25.3 24.2 23.0 22.0 21.0 20.0 19.1 18.2 17.4 16.6 15.9 15.2 14.5 13.9 13.3 12.7 12.1 11.6 11.1 10.7 10.2 9.78 9.37 8.98 8.61 8.26 7.92 7.60 7.29 7.00 6.72 6.45 6.19 5.95 5.72 5.49 5.28 5.08 4.88 4.69
6.30 6.20 6.10 6.00 5.90 5.80 5.70 5.59 5.49 5.38 5.28 5.17 5.07 4.96 4.85 4.75 4.64 4.53 4.43 4.32 4.22 4.12 4.01 3.91 3.81 3.71 3.62 3.52 3.43 3.33 3.24 3.15 3.06 2.97 2.89 2.81 2.72 2.64 2.57 2.49 2.42 2.34 2.27 2.20 2.14 2.07 2.01 1.94 1.88 1.82 1.77 1.71 1.66 1.61 1.56
60.0 61.0 62.0 63.0 64.0 65.0 66.0 67.0 68.0 69.0 70.0 71.0 72.0 73.0 74.0 75.0 76.0 77.0 78.0 79.0 80.0 81.0 82.0 83.0 84.0 85.0 86.0 87.0 88.0 89.0 90.0 91.0 92.0 93.0 94.0 95.0 96.0 97.0 98.0 99.0 100.0 101.0 102.0 103.0 104.0 105.0 106.0 107.0 108.0 109.0 110.0 111.0 112.0 113.0 114.0
4.52 4.35 4.18 4.03 3.88 3.73 3.59 3.46 3.34 3.21 3.10 2.99 2.88 2.78 2.68 2.58 2.49 2.41 2.32 2.24 2.17 2.09 2.02 1.95 1.89 1.82 1.76 1.70 1.65 1.59 1.54 1.49 1.44 1.40 1.35 1.31 1.27 1.23 1.19 1.15 1.11 1.08 1.05 1.01 0.98 0.95 0.92 0.90 0.87 0.84 0.82 0.79 0.77 0.75 0.73
1.51 1.46 1.41 1.37 1.32 1.28 1.24 1.20 1.16 1.13 1.09 1.06 1.02 0.991 0.960 0.929 0.900 0.872 0.844 0.818 0.792 0.767 0.744 0.720 0.698 0.676 0.655 0.635 0.616 0.597 0.578 0.561 0.544 0.527 0.511 0.496 0.481 0.466 0.452 0.439 0.425 0.413 0.401 0.389 0.378 0.367 0.356 0.346 0.336 0.326 0.317 0.308 0.299 0.290 0.282
115.0 116.0 117.0 118.0 119.0 120.0 121.0 122.0 123.0 124.0 125.0 126.0 127.0 128.0 129.0 130.0 131.0 132.0 133.0 134.0 135.0 136.0 137.0 138.0 139.0 140.0 141.0 142.0 143.0 144.0 145.0 146.0 147.0 148.0 149.0 150.0
0.70 0.68 0.66 0.64 0.63 0.61 0.59 0.57 0.56 0.54 0.53 0.51 0.50 0.49 0.47 0.46 0.45 0.43 0.42 0.41 0.40 0.39 0.38 0.37 0.36 0.35 0.34 0.33 0.32 0.32 0.31 0.30 0.29 0.29 0.28 0.27
0.274 0.266 0.259 0.252 0.245 0.238 0.231 0.225 0.219 0.213 0.207 0.201 0.196 0.191 0.186 0.181 0.176 0.171 0.167 0.162 0.158 0.154 0.150 0.146 0.142 0.139 0.135 0.132 0.128 0.125 0.122 0.119 0.116 0.113 0.110 0.107
EN1Z-0921GE51 R0709
86
LION System
PT 1000
Temp. [C] Resistance [] Terminal voltage [V] Temp. [C] Resistance [] Terminal voltage [V] Temp. [C] Resistance [] Terminal voltage [V] Temp. [C] Resistance [] Terminal voltage [V]
-50.0 -49.0 -48.0 -47.0 -46.0 -45.0 -44.0 -43.0 -42.0 -41.0 -40.0 -39.0 -38.0 -37.0 -36.0 -35.0 -34.0 -33.0 -32.0 -31.0 -30.0 -29.0 -28.0 -27.0 -26.0 -25.0 -24.0 -23.0 -22.0 -21.0 -20.0 -19.0 -18.0 -17.0 -16.0 -15.0 -14.0 -13.0 -12.0 -11.0 -10.0 -9.0 -8.0 -7.0 -6.0 -5.0 -4.0 -3.0 -2.0 -1.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
803 807 811 815 819 823 827 831 835 839 843 847 851 855 859 862 866 870 874 878 882 886 890 894 898 902 906 910 914 918 922 926 929 933 937 941 945 949 953 957 961 965 969 973 977 980 984 988 992 996 1000 1004 1008 1012 1016 1020 1023 1027 1031 1035
0.312 0.314 0.315 0.317 0.318 0.320 0.321 0.323 0.324 0.326 0.327 0.329 0.330 0.332 0.333 0.335 0.336 0.338 0.339 0.341 0.342 0.344 0.345 0.347 0.348 0.350 0.351 0.353 0.354 0.356 0.357 0.359 0.360 0.361 0.363 0.364 0.366 0.367 0.369 0.370 0.372 0.373 0.375 0.376 0.378 0.379 0.380 0.382 0.383 0.385 0.386 0.388 0.389 0.391 0.392 0.394 0.395 0.396 0.398 0.399
10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0 20.0 21.0 22.0 23.0 24.0 25.0 26.0 27.0 28.0 29.0 30.0 31.0 32.0 33.0 34.0 35.0 36.0 37.0 38.0 39.0 40.0 41.0 42.0 43.0 44.0 45.0 46.0 47.0 48.0 49.0 50.0 51.0 52.0 53.0 54.0 55.0 56.0 57.0 58.0 59.0 60.0 61.0 62.0 63.0 64.0 65.0 66.0 67.0 68.0 69.0
1039 1043 1047 1051 1055 1058 1062 1066 1070 1074 1078 1082 1086 1090 1093 1097 1101 1105 1109 1113 1117 1121 1124 1128 1132 1136 1140 1144 1148 1152 1155 1159 1163 1167 1171 1175 1179 1182 1186 1190 1194 1198 1202 1205 1209 1213 1217 1221 1225 1229 1232 1236 1240 1244 1248 1252 1255 1259 1263 1267
0.401 0.402 0.404 0.405 0.406 0.408 0.409 0.411 0.412 0.413 0.415 0.416 0.418 0.419 0.420 0.422 0.423 0.425 0.426 0.428 0.429 0.431 0.432 0.433 0.435 0.436 0.438 0.439 0.441 0.442 0.443 0.445 0.446 0.448 0.449 0.451 0.452 0.453 0.455 0.456 0.458 0.459 0.461 0.462 0.463 0.465 0.466 0.467 0.469 0.470 0.471 0.473 0.474 0.476 0.477 0.479 0.480 0.481 0.483 0.484
70.0 71.0 72.0 73.0 74.0 75.0 76.0 77.0 78.0 79.0 80.0 81.0 82.0 83.0 84.0 85.0 86.0 87.0 88.0 89.0 90.0 91.0 92.0 93.0 94.0 95.0 96.0 97.0 98.0 99.0 100.0 101.0 102.0 103.0 104.0 105.0 106.0 107.0 108.0 109.0 110.0 111.0 112.0 113.0 114.0 115.0 116.0 117.0 118.0 119.0 120.0 121.0 122.0 123.0 124.0 125.0 126.0 127.0 128.0 129.0
1271 1275 1278 1282 1286 1290 1294 1297 1301 1305 1309 1313 1317 1320 1324 1328 1332 1336 1339 1343 1347 1351 1355 1358 1362 1366 1370 1374 1377 1381 1385 1389 1393 1396 1400 1404 1408 1412 1415 1419 1423 1427 1430 1434 1438 1442 1446 1449 1453 1457 1461 1464 1468 1472 1476 1479 1483 1487 1491 1494
0.486 0.487 0.488 0.490 0.491 0.493 0.494 0.495 0.497 0.498 0.499 0.501 0.502 0.503 0.505 0.506 0.508 0.509 0.510 0.512 0.513 0.515 0.516 0.517 0.519 0.520 0.522 0.523 0.524 0.525 0.527 0.528 0.530 0.531 0.532 0.534 0.535 0.537 0.538 0.539 0.541 0.542 0.543 0.545 0.546 0.547 0.549 0.550 0.551 0.553 0.554 0.555 0.557 0.558 0.560 0.561 0.562 0.564 0.565 0.566
130.0 131.0 132.0 133.0 134.0 135.0 136.0 137.0 138.0 139.0 140.0 141.0 142.0 143.0 144.0 145.0 146.0 147.0 148.0 149.0 150.0 151.0 152.0 153.0 154.0 155.0 156.0 157.0 158.0 159.0 160.0 161.0 162.0 163.0 164.0 165.0 166.0 167.0 168.0 169.0 170.0 171.0 172.0 173.0 174.0 175.0 176.0 177.0 178.0 179.0 180.0 181.0 182.0 183.0 184.0 185.0 186.0 187.0 188.0 189.0
1498 1502 1506 1510 1513 1517 1521 1525 1528 1532 1536 1539 1543 1547 1551 1554 1558 1562 1566 1569 1573 1577 1581 1584 1588 1592 1596 1599 1603 1607 1610 1614 1618 1622 1625 1629 1633 1636 1640 1644 1648 1651 1655 1659 1662 1666 1670 1674 1677 1681 1685 1688 1692 1696 1699 1703 1707 1711 1714 1718
0.567 0.569 0.570 0.572 0.573 0.574 0.576 0.577 0.578 0.580 0.581 0.582 0.584 0.585 0.586 0.587 0.589 0.590 0.592 0.593 0.594 0.596 0.597 0.598 0.600 0.601 0.602 0.603 0.605 0.606 0.607 0.609 0.610 0.612 0.613 0.614 0.615 0.617 0.618 0.619 0.621 0.622 0.623 0.625 0.626 0.627 0.629 0.630 0.631 0.632 0.634 0.635 0.636 0.638 0.639 0.640 0.642 0.643 0.644 0.645
87
EN1Z-0921GE51 R0709
LION System
Temp. [C]
Resistance []
Temp. [C]
Resistance []
Temp. [C]
Resistance []
Temp. [C]
Resistance []
190.0 191.0 192.0 193.0 194.0 195.0 196.0 197.0 198.0 199.0 200.0 201.0 202.0 203.0 204.0 205.0 206.0 207.0 208.0 209.0 210.0 211.0 212.0 213.0 214.0 215.0 216.0 217.0 218.0 219.0 220.0 221.0 222.0 223.0 224.0 225.0 226.0 227.0 228.0 229.0 230.0 231.0 232.0 233.0 234.0 235.0 236.0 237.0 238.0 239.0 240.0 241.0 242.0 243.0 244.0 245.0 246.0 247.0 248.0 249.0
1722 1725 1729 1733 1736 1740 1744 1747 1751 1755 1758 1762 1766 1769 1773 1777 1780 1784 1788 1791 1795 1799 1802 1806 1810 1813 1817 1821 1824 1828 1832 1835 1839 1843 1846 1850 1854 1857 1861 1865 1868 1872 1875 1879 1883 1886 1890 1894 1897 1901 1905 1908 1912 1915 1919 1923 1926 1930 1934 1937
0.647 0.648 0.649 0.651 0.652 0.653 0.655 0.656 0.657 0.658 0.659 0.661 0.662 0.663 0.665 0.666 0.667 0.669 0.670 0.671 0.672 0.674 0.675 0.676 0.678 0.679 0.680 0.681 0.683 0.684 0.685 0.686 0.688 0.689 0.690 0.692 0.693 0.694 0.695 0.697 0.698 0.699 0.700 0.702 0.703 0.704 0.705 0.707 0.708 0.709 0.711 0.712 0.713 0.714 0.716 0.717 0.718 0.719 0.721 0.722
250.0 251.0 252.0 253.0 254.0 255.0 256.0 257.0 258.0 259.0 260.0 261.0 262.0 263.0 264.0 265.0 266.0 267.0 268.0 269.0 270.0 271.0 272.0 273.0 274.0 275.0 276.0 277.0 278.0 279.0 280.0 281.0 282.0 283.0 284.0 285.0 286.0 287.0 288.0 289.0 290.0 291.0 292.0 293.0 294.0 295.0 296.0 297.0 298.0 299.0 300.0 301.0 302.0 303.0 304.0 305.0 306.0 307.0 308.0 309.0
1941 1944 1948 1952 1955 1959 1962 1966 1970 1973 1977 1980 1984 1988 1991 1995 1998 2002 2006 2009 2013 2016 2020 2024 2027 2031 2034 2038 2042 2045 2049 2052 2056 2060 2063 2067 2070 2074 2077 2081 2085 2088 2092 2095 2099 2102 2106 2110 2113 2117 2120 2124 2127 2131 2134 2138 2142 2145 2149 2152
0.723 0.724 0.726 0.727 0.728 0.729 0.730 0.732 0.733 0.734 0.736 0.737 0.738 0.739 0.740 0.742 0.743 0.744 0.746 0.747 0.748 0.749 0.750 0.752 0.753 0.754 0.755 0.757 0.758 0.759 0.760 0.761 0.763 0.764 0.765 0.766 0.768 0.769 0.770 0.771 0.773 0.774 0.775 0.776 0.777 0.778 0.780 0.781 0.782 0.784 0.785 0.786 0.787 0.788 0.789 0.791 0.792 0.793 0.794 0.796
310.0 311.0 312.0 313.0 314.0 315.0 316.0 317.0 318.0 319.0 320.0 321.0 322.0 323.0 324.0 325.0 326.0 327.0 328.0 329.0 330.0 331.0 332.0 333.0 334.0 335.0 336.0 337.0 338.0 339.0 340.0 341.0 342.0 343.0 344.0 345.0 346.0 347.0 348.0 349.0 350.0 351.0 352.0 353.0 354.0 355.0 356.0 357.0 358.0 359.0 360.0 361.0 362.0 363.0 364.0 365.0 366.0 367.0 368.0 369.0
2156 2159 2163 2166 2170 2173 2177 2181 2184 2188 2191 2195 2198 2202 2205 2209 2212 2216 2219 2223 2226 2230 2234 2237 2241 2244 2248 2251 2255 2258 2262 2265 2269 2272 2276 2279 2283 2286 2290 2293 2297 2300 2304 2307 2311 2314 2318 2321 2325 2328 2332 2335 2339 2342 2346 2349 2353 2356 2360 2363
0.797 0.798 0.799 0.800 0.802 0.803 0.804 0.805 0.806 0.808 0.809 0.810 0.811 0.812 0.814 0.815 0.816 0.817 0.818 0.820 0.821 0.822 0.823 0.824 0.826 0.827 0.828 0.829 0.830 0.831 0.833 0.834 0.835 0.836 0.838 0.839 0.840 0.841 0.842 0.843 0.845 0.846 0.847 0.848 0.849 0.850 0.852 0.853 0.854 0.855 0.856 0.857 0.859 0.860 0.861 0.862 0.863 0.864 0.866 0.867
370.0 371.0 372.0 373.0 374.0 375.0 376.0 377.0 378.0 379.0 380.0 381.0 382.0 383.0 384.0 385.0 386.0 387.0 388.0 389.0 390.0 391.0 392.0 393.0 394.0 395.0 396.0 397.0 398.0 399.0 400.0
2367 2370 2373 2377 2380 2384 2387 2391 2394 2398 2401 2405 2408 2412 2415 2419 2422 2426 2429 2432 2436 2439 2443 2446 2450 2453 2457 2460 2463 2467 2470
0.868 0.869 0.870 0.871 0.872 0.874 0.875 0.876 0.877 0.878 0.879 0.881 0.882 0.883 0.884 0.885 0.886 0.888 0.889 0.890 0.891 0.892 0.893 0.894 0.896 0.897 0.898 0.899 0.900 0.901 0.902
EN1Z-0921GE51 R0709
88
LION System
NI1000TK5000
Temp. [C] Resistance [] Terminal voltage [V] Temp. [C] Resistance [] Terminal voltage [V] Temp. [C] Resistance [] Terminal voltage [V] Temp. [C] Resistance [] Terminal voltage [V]
-30 -29 -28 -27 -26 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
871.7 875.8 880 884.1 888.3 892.5 896.7 900.8 905.1 909.3 913.5 917.7 922 926.2 930.5 934.7 939 943.3 947.6 951.9 956.2 960.6 964.9 969.3 973.6 978 982.4 986.7 991.2 995.6 1000 1004.4 1008.9 1013.3 1017.8 1022.3 1026.7 1031.2 1035.8 1040.3 1044.8 1049.3 1053.9 1058.4 1063 1067.6 1072.2 1076.8
0.338 0.340 0.341 0.343 0.344 0.346 0.348 0.349 0.351 0.352 0.354 0.355 0.357 0.359 0.360 0.362 0.363 0.365 0.367 0.368 0.370 0.371 0.373 0.375 0.376 0.378 0.380 0.381 0.383 0.384 0.386 0.388 0.389 0.391 0.393 0.394 0.396 0.398 0.399 0.401 0.403 0.404 0.406 0.408 0.409 0.411 0.413 0.415
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65
1081.4 1086 1090.7 1095.3 1100 1104.6 1109.3 1114 1118.7 1123.4 1128.1 1132.9 1137.6 1142.4 1147.1 1151.9 1156.7 1161.5 1166.3 1171.2 1176 1180.9 1185.7 1190.6 1195.5 1200.4 1205.3 1210.2 1215.1 1220.1 1225 1230 1235 1240 1245 1250 1255 1260.1 1265.1 1270.2 1275.3 1280.3 1285.4 1290.6 1295.7 1300.8 1306 1311.1
0.416 0.418 0.420 0.421 0.423 0.425 0.427 0.428 0.430 0.432 0.433 0.435 0.437 0.439 0.440 0.442 0.444 0.446 0.447 0.449 0.451 0.453 0.455 0.456 0.458 0.460 0.462 0.463 0.465 0.467 0.469 0.471 0.473 0.474 0.476 0.478 0.480 0.482 0.484 0.485 0.487 0.489 0.491 0.493 0.495 0.496 0.498 0.500
66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113
1316.3 1321.5 1326.7 1331.9 1337.1 1342.4 1347.6 1352.9 1358.2 1363.5 1368.8 1374.1 1379.4 1384.8 1390.1 1395.5 1400.9 1406.3 1411.7 1417.1 1422.5 1428 1433.4 1438.9 1444.4 1449.9 1455.4 1460.9 1466.5 1472 1477.6 1483.2 1488.8 1494.4 1500 1505.6 1511.3 1517 1522.6 1528.3 1534 1539.7 1545.5 1551.2 1557 1562.8 1568.5 1574.4
0.502 0.504 0.506 0.508 0.510 0.512 0.513 0.515 0.517 0.519 0.521 0.523 0.525 0.527 0.529 0.531 0.533 0.535 0.537 0.538 0.540 0.542 0.544 0.546 0.548 0.550 0.552 0.554 0.556 0.558 0.560 0.562 0.564 0.566 0.568 0.570 0.572 0.574 0.576 0.578 0.580 0.582 0.584 0.586 0.589 0.591 0.593 0.595
114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130
1580.2 1586 1591.8 1597.7 1603.6 1609.5 1615.4 1621.3 1627.2 1633.2 1639.1 1645.1 1651.1 1657.1 1663.1 1669.1 1675.2
0.597 0.599 0.601 0.603 0.605 0.607 0.609 0.611 0.613 0.616 0.618 0.620 0.622 0.624 0.626 0.628 0.630
89
EN1Z-0921GE51 R0709
LION System
NTC 10 k
Temp. [C] Resistance [k] Terminal voltage [V] Temp. [C] Resistance [k] Terminal voltage [V] Temp. [C] Resistance [k] Terminal voltage [V] Temp. [C] Resistance [k] Terminal voltage [V]
-30 -29 -28 -27 -26 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11
177 166.35 156.413 147.136 138.47 130.372 122.8 115.718 109.089 102.883 97.073 91.597 86.471 81.667 77.161 72.932 68.962 65.231 61.723 58.424 55.321 52.399 49.648 47.058 44.617 42.317 40.15 38.106 36.18 34.363 32.65 31.027 29.494 28.047 26.68 25.388 24.166 23.01 21.916 20.88 19.898 18.968
7.904 7.848 7.790 7.730 7.666 7.601 7.534 7.464 7.392 7.318 7.241 7.161 7.080 6.996 6.910 6.821 6.731 6.639 6.545 6.448 6.351 6.251 6.150 6.047 5.943 5.838 5.732 5.624 5.516 5.408 5.299 5.189 5.079 4.969 4.859 4.750 4.641 4.532 4.423 4.316 4.209 4.103
12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53
18.087 17.252 16.46 15.708 14.995 14.319 13.678 13.068 12.49 11.94 11.418 10.921 10.449 10 9.572 9.165 8.777 8.408 8.057 7.722 7.402 7.098 6.808 6.531 6.267 6.015 5.775 5.546 5.327 5.117 4.917 4.726 4.543 4.369 4.202 4.042 3.889 3.743 3.603 3.469 3.34 3.217
3.998 3.894 3.792 3.690 3.591 3.492 3.396 3.300 3.207 3.115 3.025 2.937 2.850 2.767 2.684 2.603 2.524 2.447 2.372 2.299 2.228 2.159 2.091 2.025 1.962 1.900 1.840 1.781 1.724 1.669 1.616 1.564 1.514 1.465 1.418 1.373 1.329 1.286 1.244 1.204 1.166 1.128
54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95
3.099 2.986 2.878 2.774 2.675 2.579 2.488 2.4 2.316 2.235 2.158 2.083 2.011 1.943 1.877 1.813 1.752 1.694 1.637 1.583 1.531 1.481 1.433 1.387 1.342 1.299 1.258 1.218 1.179 1.142 1.107 1.072 1.039 1.007 0.976 0.947 0.918 0.89 0.863 0.838 0.813 0.789
1.092 1.057 1.023 0.990 0.959 0.928 0.898 0.870 0.842 0.815 0.790 0.765 0.740 0.718 0.695 0.673 0.652 0.632 0.612 0.593 0.575 0.557 0.541 0.524 0.508 0.493 0.478 0.464 0.450 0.436 0.423 0.411 0.399 0.387 0.375 0.365 0.354 0.344 0.334 0.324 0.315 0.306
96 97 98 99 100
EN1Z-0921GE51 R0709
90
LION System
PT 3000
Temp. [C] Resistance [k] Terminal voltage [V]
-50 -45 -40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150
2.823 2.868 2.913 2.957 3.002 3.046 3.090 3.134 3.178 3.222 3.266 3.310 3.353 3.397 3.440 3.484 3.527 3.570 3.613 3.656 3.699 3.742 3.784 3.827 3.869 3.912 3.954 3.996 4.038 4.080 4.122 4.164 4.206 4.247 4.289 4.330 4.371 4.413 4.454 4.495 4.536
1.018 1.033 1.047 1.061 1.076 1.090 1.104 1.118 1.132 1.146 1.160 1.173 1.187 1.200 1.214 1.227 1.241 1.254 1.267 1.280 1.293 1.306 1.319 1.332 1.345 1.358 1.370 1.383 1.395 1.408 1.420 1.433 1.445 1.457 1.469 1.481 1.493 1.505 1.517 1.529 1.541
91
EN1Z-0921GE51 R0709
LION
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Srl, Rolle, Z.A. La Pice 16, Switzerland by its Authorized Representative:
CentraLine Honeywell GmbH Bblinger Strasse 17 71101 Schnaich, Germany Tel +49 7031 637 845 Fax +49 7031 637 846 info@centraline.com www.centraline.com
CentraLine Honeywell Control Systems Ltd. Arlington Business Park UK-Bracknell, Berkshire RG12 1EB Tel +44 13 44 656 565 Fax +44 13 44 656 563 info-uk@centraline.com www.centraline.com