technical data
ERHQ011-016AA
Altherma
Altherma
Altherma
Daikins unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.
Het ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..
Daikin units comply with the European regulations that guarantee the safety of the product.
Naamloze Vennootschap Zandvoordestraat 300 B-8400 Ostend, Belgium www.daikin.eu BTW: BE 0412 120 336 RPR Oostende
Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.
EEDEN0 8 - 7 2 0
EEDEN08-720
technical data
ERHQ011-016AA
Altherma
Altherma
1 2
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 6 8
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cooling capacity tables Heating capacity tables
.............................................. 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 6
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure spectrum quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16 17 18
8 9
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service space
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 19
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
A iA n6 1u 0 a - r m 1 o r 1 o e 0 dh Q t H ulR OEA
Features
Cost effective alternative to a fossil fuel boiler Low energy bills and low CO2 emissions
1
1
Specifications
ERHQ011AA
ERHQ014AA
ERHQ016AA
3 1
2
EKHBH016AB
11.2 13.9 2.46 3.79 4.55 3.67 10.3 10.0 3.06 3.60 3.37 2.78
14.0 17.3 3.17 5.78 4.42 2.99 13.1 12.5 3.88 5.29 3.38 2.36
16.0 17.8 3.83 6.77 4.18 2.63 15.2 13.1 4.66 5.95 3.26 2.20
Heating capacity Nominal Cooling capacity Nominal Heating PI Cooling PI COP EER Nominal Nominal Nominal Nominal
Notes
Condition 1: cooling Ta 35C - LWE 18C - heating Ta DB/WB 7C/6C - LWC 35C ( DT = 5C ) Condition 2: cooling Ta 35C - LWE 7C ( DT = 5C ) - heating Ta DB/WB 7C/6C - LWC 45C ( DT = 5C )
2-2
Casing
TECHNICAL SPECIFICATIONS
Colour Material Unit Height Width Depth Packing Height Width Depth mm mm mm mm mm mm kg kg
ERHQ011AA
ERHQ014AA
ERHQ016AA
Ivory white Painted galvanised steel plate 1,170 900 320 980 420 103 114 900 320 1,349 980 420 103 114 EPS Carton Wood PP (Straps) 980 420 103 114 900 320
Dimensions
Weight Packing
kg mm mm
Nr of Passes Face Area m Nr of Stages Tube type Fin Fan Type Quantity Air Flow Rate Heating (nominal at 230V) Cooling High High m/min m/min Type Treatment
2 90 96
2 90 100
2 90 97
2
2-2
Fan
Specifications
TECHNICAL SPECIFICATIONS
Discharge direction Motor Quantity Model Steps Heating Cooling Output Drive rpm rpm W 2 8 760 800 70 1 Model Type Motor Output W
ERHQ011AA ERHQ014AA ERHQ016AA
Horizontal 2 Brushless DC motor 8 760 850 70 Direct drive 1 JT100G-VD Hermetically sealed scroll compressor 2,200 Inverter driven 33 -20 35 10 46 -20 43 64 49 64 50 42 45 33 -20 35 10 46 -20 43 64 51 66 52 42 45 R-410A kg 3.7 1 l 1.0 1 mm 1 mm 3 mm m 26 5 75 95 30 30 3.7 Expansion valve(electronic type) 1 Daphne FVC68D 1.0 1 Flare connection 9,52 1 Flare connection 15,9 3 Hole 26 5 75 95 30 See installation manual outdoor unit 4PW37976-1B 30 Both liquid and gas pipes 30 26 5 75 95 30 3 1 1.0 1 1 3.7 33 -20 35 10 46 -20 43 66 53 69 54 43 46 1 8 760 830 70 2
1
2
Motor
Fan Compressor
Starting Method Crankcase W Heater Operation Range Heating Cooling Sanitary water Sound Level (nominal) Heating Min Max Min Max Min Max Sound Power Sound Pressure Cooling Sound Power Sound Pressure Sound Level (Night quiet) Heating Cooling Refrigerant Type Charge Control Nr of Circuits Refrigerant Oil Piping connections Type Charged Volume Liquid (OD) Quantity Type Diameter (OD) Gas Quantity Type Diameter (OD) Drain Quantity Type Diameter (OD) Piping Length Minimum Sound Pressure Sound Pressure CWB CWB CDB CDB CDB CDB dBA dBA dBA dBA dBA dBA
Maximum m Equivalent m Chargeless m Additional Refrigerant Charge kg/m Installation Maximum m height difference Heat Insulation
2
2-2
Specifications
TECHNICAL SPECIFICATIONS
ERHQ011AA ERHQ014AA ERHQ016AA
Pressure equalising Sensor for outdoor heat exchanger temperature Inverter controlled Fan motor thermal protector Fuse High pressure switch
3 1
2
Standard Accessories
Tie-wraps 2 Installation manual 1 1 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Down to 3m with recharging of the outdoor unit. Refer to the installation manual of the outdoor unit. 2
Notes
2-3
ELECTRICAL SPECIFICATIONS
Name Phase Frequency Voltage Voltage range Minimum Hz V V kVa A A Maximum V
ERHQ011AA
ERHQ014AA
ERHQ016AA
Power Supply
V3 1~ 50 230 50 230 -10% +10% Equipment complying with EN/IEC 61000-S-12 (1) 22.8 32 27.4 32 See installation manual outdoor unit 4PW37976-1B See installation manual outdoor unit 4PW37976-1B Outdoor unit only (1) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase. 31.9 32 50 230
Current
Wiring connections
Remark
3
3-1
Capacity tables
Cooling capacity tables
Tamb (C) LWE (C) 7 10 13 15 18 22 7 10 13 15 18 22 7 10 13 15 18 22 20 CC 11.7 12.9 14.1 14.9 16.2 18.0 14.5 16.0 17.6 18.6 20.2 22.5 15.3 16.9 18.5 19.6 21.0 23.3 PI 2.56 2.58 2.59 2.60 2.61 2.62 3.85 3.94 4.02 4.08 4.17 4.29 4.37 4.48 4.60 4.68 4.97 5.21 CC 11.2 12.3 13.4 14.2 15.5 17.2 13.9 15.3 16.8 17.8 19.3 21.5 14.7 16.2 17.7 18.7 20.0 22.2 25 PI 2.86 2.89 2.92 2.93 2.96 2.99 4.27 4.37 4.47 4.54 4.65 4.80 4.84 4.97 5.10 5.19 5.52 5.79 CC 10.6 11.6 12.8 13.5 14.7 16.4 13.2 14.6 15.9 16.9 18.4 20.4 13.9 15.3 16.7 17.7 18.9 21.0 30 PI 3.21 3.25 3.29 3.31 3.35 3.40 4.75 4.86 4.98 5.06 5.18 5.36 5.37 5.51 5.66 5.76 6.12 6.42 CC 10.0 11.0 12.1 12.8 13.9 15.5 12.5 13.7 15.0 15.9 17.3 19.3 13.1 14.4 15.7 16.6 17.8 19.7 35 PI 3.60 3.65 3.70 3.73 3.79 3.86 5.29 5.42 5.55 5.64 5.78 5.98 5.95 6.11 6.27 6.38 6.77 7.10 CC 9.39 10.3 11.3 12.0 13.1 14.7 11.7 12.9 14.1 14.9 16.2 17.0 12.2 13.3 14.6 15.4 16.4 17.0 40 PI 4.03 4.09 4.15 4.20 4.26 4.35 5.90 6.04 6.18 6.28 6.44 5.33 6.59 6.75 6.93 7.04 6.69 5.33 CC 8.75 9.65 10.6 11.3 12.3 13.3 11.1 11.2 11.9 12.2 12.9 13.3 11.1 11.2 11.9 12.2 12.9 13.3 45 PI 4.50 4.58 4.65 4.70 4.78 3.93 5.92 5.46 5.04 4.79 4.42 3.93 5.92 5.46 5.04 4.79 4.42 3.93
1
3
ERHQ11
ERHQ14
ERHQ16
3TW57752-1B
Symbols
CC PI LWE Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (C) : Ambient temperature (C) RH=85% 1
Conditions
Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 38C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511).
Note
1 For the optional model with heatertape (V38) when ambient temperature becomes lower than 4C: add power input of 95W
3
3-2
Model
Capacity tables
Heating capacity tables
LWC Tamb -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 LWC Tamb -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 30 HC 5.66 6.48 8.04 9.18 10.2 11.6 13.1 14.1 15.9 7.24 8.19 10.1 11.5 12.7 14.4 16.3 17.6 19.9 8.35 9.38 11.5 13.0 14.4 16.3 18.5 20.0 22.5 30 HC 5.04 5.77 6.89 7.43 8.16 11.6 13.1 14.1 15.9 6.45 7.29 8.06 9.27 10.0 14.4 16.3 17.6 19.9 7.44 8.35 8.91 10.5 11.1 16.3 18.5 20.0 22.5 PI 2.17 2.21 2.24 2.11 2.16 2.21 2.18 2.15 2.10 2.72 2.78 2.84 2.70 2.78 2.88 2.86 2.85 2.82 3.25 3.33 3.34 3.26 3.15 3.50 3.51 3.51 3.50 HC 4.88 5.56 6.63 7.16 7.86 11.2 12.7 13.6 15.4 6.35 7.13 7.84 9.00 9.71 14.0 15.9 17.1 19.3 7.39 8.30 8.77 10.3 10.9 16.0 18.1 19.5 22.0 PI 2.17 2.21 2.24 2.24 2.23 2.21 2.18 2.15 2.10 2.72 2.78 2.84 2.87 2.87 2.88 2.86 2.85 2.82 3.25 3.33 3.42 3.46 3.48 3.50 3.51 3.51 3.50 HC 5.48 6.25 7.74 8.84 9.81 11.2 12.7 13.6 15.4 7.14 8.01 9.78 11.1 12.3 14.0 15.9 17.1 19.3 8.31 9.33 11.3 12.7 14.1 16.0 18.1 19.5 22.0 35 PI 2.37 2.42 2.46 2.33 2.39 2.46 2.43 2.41 2.36 2.97 3.04 3.11 2.96 3.05 3.17 3.16 3.15 3.13 3.54 3.63 3.64 3.56 3.45 3.83 3.85 3.86 3.85 HC 4.84 5.49 6.54 7.06 7.75 10.8 12.2 13.2 14.9 6.28 6.99 7.62 8.95 9.65 13.5 15.4 16.5 18.7 7.36 8.26 8.63 10.1 10.6 15.6 17.6 19.0 21.4 35 PI 2.37 2.42 2.46 2.47 2.47 2.46 2.43 2.41 2.36 2.97 3.04 3.11 3.14 3.16 3.17 3.16 3.15 3.13 3.54 3.63 3.73 3.78 3.81 3.83 3.85 3.86 3.85 HC 5.44 6.17 7.63 8.71 9.68 10.8 12.2 13.2 14.9 7.05 7.85 9.51 11.1 12.2 13.5 15.4 16.5 18.7 8.27 9.28 11.1 12.5 13.8 15.6 17.6 19.0 21.4 40 PI 2.61 2.67 2.72 2.58 2.65 2.74 2.72 2.70 2.65 3.26 3.34 3.43 3.26 3.37 3.50 3.50 3.50 3.48 3.86 3.98 4.00 3.91 3.79 4.22 4.24 4.25 4.25 HC 6.43 6.94 7.63 10.3 11.8 12.7 14.4 7.42 8.65 9.32 13.1 14.9 16.0 18.1 8.49 9.91 10.4 15.2 17.2 18.5 20.8 40 PI 2.61 2.67 2.72 2.74 2.74 2.74 2.72 2.70 2.65 3.26 3.34 3.43 3.47 3.48 3.50 3.50 3.50 3.48 3.89 3.98 4.10 4.15 4.19 4.22 4.24 4.25 4.25 HC 7.50 8.57 9.52 10.3 11.8 12.7 14.4 9.25 10.7 11.8 13.1 14.9 16.0 18.1 10.9 12.2 13.5 15.2 17.2 18.5 20.8 45 PI 3.02 2.87 2.96 3.06 3.04 3.03 2.99 3.79 3.52 3.64 3.88 3.89 3.89 3.87 4.41 4.31 4.18 4.66 4.69 4.69 4.70 HC 45 PI 3.02 3.05 3.06 3.06 3.04 3.03 2.99 3.79 3.74 3.76 3.88 3.89 3.89 3.87 4.52 4.58 4.62 4.66 4.69 4.69 4.70 HC 50 PI HC 55 PI
3 1
3.77 3.82 3.81 3.81 3.78
ERHQ11
ERHQ14
ERHQ16
Model
PI
HC
PI
ERHQ11
ERHQ14
ERHQ16
3TW57752-1B
Symbols
HC PI LWC Tamb : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Condensor temperature (C) : Ambient temperature (C) RH=85% 1
Conditions
Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 38C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511).
Note
1 For the optional model with heatertape (V38) when ambient temperature becomes lower than 4C: add power input of 95W
10
4
4-1
ERHQ011-016
1
4
1 2 3 4 5 6 7 8
Gas pipe connection 15.9 flare Liquid pipe connection 9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole 34) control wiring intake (knock out hole 27) Drain outlet
3TW57764-1
11
4
4-2
ERHQ011-016
3 1
4
4TW57919-5
12
5
ERHQ
Piping diagram
1
5
Filter
Filter
Heat exchanger
4-Way-Valve
EKHB 016 Field Piping 9.5 C 1220T-0 Compressor Field Piping 15.9 C 1220T-0 Accumulator Indoor Unit Stop Valve (With Service Port 5/16 Flare) Check Valve Flare Conn. Screw Conn. Flange Conn. Pinched Pipe Spinned Pipe Outdoor Unit Service Port 5/16
Heating Cooling
3TW57765-1
13
6
6-1
Wiring diagram
Wiring diagram
ERHQ011-016AAV3
Option EKBPHT16Y Only for *RHQ01*AAV3(7)
3
Indoor A1P A2P A3P A4P BS1BS4 C1C4 DS1 E1H E1HC F1U, F3U, F4U F6U H1P7P (A2P) HAP (A1P) K1R K4R K10R K11R L1R M1C M1F M2F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T RC R10T S1NPH S1PH TC V1R V2R, V3R V1T X1M Y1E Y1S Z1CZ3C Z1FZ4F Optional Connector X1Y Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Electrical heatertape (fuse: 5A/250V) Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.0A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Magnetic relay (Y1S) Magnetic relay (E1HC) Magnetic relay Magnetic relay Reactor Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Field earth leakage breaker (300mA) Resistor Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Signal receiver circuit Thermistor (Fin) Pressure sensor Pressure switch (High) Signal transmission circuit Power module Diode module IGBT Terminal strip for power source Electronic expansion valve Solenoid valve (4 way valve) Noise filter (ferrity core) Noise filter Connector
1
6
Outdoor
(Note 4)
HAP
Notes: 1 This wiring diagram only applies to the outdoor unit 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Relay connector p : Noiseless earth G : Terminal 4 Refer to the option manual, for connecting wiring to x6A. 5 Refer to the Wiring diagram sticker (on back of front plate) on how to use BS1 BS4 and DS1 switch. 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches by service. When the unit is shipped by factory all switches are set to be off. 9 Option Wiring dependent on model
(Back)
(Front)
2TW57986-1A
14
6
6-2
Wiring diagram
External connection diagram
ELECTRICAL CONNECTION DIAGRAM ALTHERMA (011/014/016 CLASS) Standard parts
1
6
Optional power supply: backup heater power supply (3kW): 400V or 230V + earth
X1M:1-2-3 earth
Applicable for the following models: OUTDOOR UNIT: ERHQ011/014/016AAV3 INDOOR UNIT: EKHBH/X016AA3V3 EKHBH/X016AA6V3 EKHBH/X016AA6W1 EKHBH/X016AA6T1 EKHBH/X016AA9W1 EKHBH/X016AA9T1 For more details please check unit wiring diagram
3 or 4 core
3 core
Field supply
X7M F2B
Room thermostat
A3P
X6M
X4M:1-2 earth
X2M:1-2-3-4
2way valve
M25 (EKHBX units) for cooling mode
X2M:13-14
NO valve: X2M:6-7 NC valve: X2M:5-7 spring return: X2M:9-10 SPST: X2M: 8-9-10
2 core X9A (PCB A1P) signal Thermistor cable NOTE: min. distance to power cable = 3 cm
3way valve
M3S (When EKSWW is installed) selection sanitary-floorheating
INDOOR UNIT
user interface
3TW57746-7
EKHB-A
Standard parts Power supply Outdoor unit
Unit power supply: 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth 3 core X1M:L-N-Earth
Optional power supply Booster heater power supply (3kW): 400V or 230V + earth
X2M:1-2-3-Earth
4 core
3 or 4 core
3 core
Optional parts
Field supply
X1M:9-10-11-Earth
230V or 400V
NO valve: NC valve:
2 core
2 way valve
M2S (EKHBX Units) for cooling mode
2 core Signal Thermistor cable Note: min. distance to power cable = 3cm
2 core
3 way valve
M3S (when EKSWW is installed) selection sanitary-floorheating
Indoor unit
User interface
3TW56719-6
15
7
7-1
Sound data
Sound pressure spectrum
ERHQ011AAV3 COOLING ERHQ014AAV3 COOLING ERHQ016AAV3 COOLING ERHQ011-016
3 1
7
NOTES
1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
NOTES
1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
16
7
7-2
Sound data
Sound pressure spectrum quiet mode
ERHQ011AAV3 COOLING ERHQ014AAV3 COOLING ERHQ016AAV3 COOLING ERHQ011-016
1
7
Sound pressure level (dB) Sound pressure level (dB) Sound pressure level (dB) Octave band center frequency (Hz)
NOTES
1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
NOTES
1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
17
8
8-1
Installation
Service space
3 1
8
In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models.
B. Stacked installation
1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet
Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor units drain pipe. Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral connection per row
3TW26739-4
18
Operation range
ERHQ011-016AAV3
Outdoor temp. (CDB)
1
9
Cooling mode
4TW57753-1A
19