Mathias Noe Karlsruher Institut fr Technologie & Joachim Bock, Achim Hobl, Judith Schramm Nexans SuperConductors GmbH EPRI 2011 Nexans SuperConductors
Development Projects
ENSYSTROB ECCOFLOW
Conclusions
EPRI 2011
Nexans SuperConductors
Nexans SuperConductors
bldg. 2728 Assembly of Fault Current Limiter systems Building height allowing crane hook of 7 m Optimisation of the production
EPRI 2011
Nexans SuperConductors
Systems realized
Bi-2212 bulk
EPRI 2011
Y-123 bulk
Nexans SuperConductors
Melting
Metal oxides
Mixing Casting
EPRI 2011
p
current
ultrafast
reacts in 1-2 milliseconds
w/o FCL
automatic
max r td tr
no external trigger necessary, self-recovering
wear-free
ta
time service only for cooling system
EPRI 2011
Nexans SuperConductors
Nexans SuperConductors
EPRI 2011
Nexans SuperConductors
Nexans SuperConductors
EPRI 2011
Nexans SuperConductors
Nexans SuperConductors
Block Q in Boxberg
EPRI 2011
Nexans SuperConductors
EPRI 2011
Nexans SuperConductors
EPRI 2011
Nexans SuperConductors
Auxiliary Power
EPRI 2011
Nexans SuperConductors
Auxiliary Power
63.000 Current [A] Investment
800
rating
fault
High Short Circuit Currents high mechanical and thermal forces No fuses on the MV power distribution level equipment and grid must be short-circuit proof high investment for equipment oversizing
EPRI 2011
Nexans SuperConductors
EPRI 2011
Nexans SuperConductors
Significant savings for extension and new construction Improved safety for personnel and equipment
EPRI 2011
Nexans SuperConductors
BSCCO-2212 tubes
BiSrCaCuO powder
EPRI 2011
Nexans SuperConductors
component
module
set-up of a phase
accomodation in a cryostat
Fault Current Limiter connected in series with the grid Current and voltage adjustable by modular construction
EPRI 2011
Nexans SuperConductors
EPRI 2011
Nexans SuperConductors
EPRI 2011
Nexans SuperConductors
EPRI 2011
Nexans SuperConductors
Specification
ENSYSTROB voltage 12 kV normal operating current 800 Arms inrush current (50 ms) 4100 Ap High current inrush(15 currents inrush s) 1800 Arms Small window for limited current prospective current 60 kA first peak limitation < 30 kAp limitation time 120 ms limitation after 100ms 6.6 - 7 kA
EPRI 2011
Nexans SuperConductors
I
2 twins in, 2 twins out sc-length: 8 x 4.30 Central contact
EPRI 2011
Nexans SuperConductors
inrush currents
1367 Ap / 50 ms 600 Arms / 15 s
EPRI 2011
Nexans SuperConductors
short circuits
partial load I prosp = 2 kAp Erms = 0.05 V/ m
full load I prosp = 32 kAp Erms = 50 V/ m
EPRI 2011
Nexans SuperConductors
3 x 32 =96 components
EPRI 2011
Nexans SuperConductors
Nexans SuperConductors
First system based on cc-tapes was engineered and built in time SFCL device was successfully tested at the certified high power test lab in Berlin in September 2011 SFCL has been installed at the Boxberg power plant
EPRI 2011
Nexans SuperConductors
EU-project: ECCOFLOW
cc-tape based FCL 24-1000 15 partners involved 5 utilities coordinated by
Stockholm
Siegen
Kosice
Barcelona
Mailand
EPRI 2011
First multipurpose system for two sites and applications Nexans SuperConductors
ECCOFLOW is: A project to prepare commercialisation of SFCL The 3-phase resistive limiter with the highest voltage today Including 15 project partners 5 of which are utilities The first SFCL foreseen for two different applications
EPRI 2011
Nexans SuperConductors
Palma de Mallorca
transformer feeder
FCL
Medium voltage
FCL
busbar coupler
EPRI 2011
Koice (VSE)
High voltage
Medium voltage
FCL
busbar coupler
EPRI 2011
Nexans SuperConductors
Endesa Nominal voltage Nominal current AC withstand voltage Lightning impulse Max. prospective current (peak) Max. limited current (peak) Fault duration HTS limitation time Recovery time 16.5 kV 1000 A 50 kV 125 kV 22 kA 10.8 kA 1s 80 ms < 30 s
EPRI 2011
Nexans SuperConductors
Black Box
EPRI 2011
Nexans SuperConductors
New developments: Project 24-1000 ECCOFLOW Component Design 3 x 2 x 2 conductors, about 8 m each 1 kArms / 800 Vrms no parallel connection of components needed excellent use of volume low voltage for the single component small AC losses due to multifilar geometry short single pieces of superconducting tape with mutual protection.
EPRI 2011
Nexans SuperConductors
Stack of 12 components in series Liquid / gaseous nitrogen insulating against cryostat wall
EPRI 2011
Nexans SuperConductors
Nexans SuperConductors
Loss contribution Max. superconductor AC loss Max. current lead loss Cryostat loss Max. additional loss Max. total loss at 77 K Max. electric power at RT
EPRI 2011
Nexans SuperConductors
Nexans SuperConductors
Kick-off Oct. 2011 Study showed project is technically feasible economically reasonable
EPRI 2011
Nexans SuperConductors
Herkules
Dellbrgge
position of joints
EPRI 2011
Nexans SuperConductors
EPRI 2011
Nexans SuperConductors
Conclusions
Full chain mastered from production of HTS material to final FCL system (for bulk)