1. Technical specifications.

I supply of 5 switches of SF6 (hexafluoruro of sulphur) of 230Kv for 5 generating units

Please indicate in the box Offered if requested switches meet the requirements.

No 1 2

Descriptions Nominal voltage Maximum operation voltage

Required 230V of 245V

Offered 230V 245V

3 4 5

nominal frequency Nominal current Short-circuit disconnection

60 hz 2500 amperes current 40 KA

60 hz 2500 amperes 40 KA

Voltage of test to industrial 460 Kv to 1 min/50Hz frequency

460

Kv

to

min/50Hz Kv 1.2/50

Voltage of test with shock 1050 Kv 1.2/50 microseconds 1050 wave

microseconds 2500 mm phase to phase 2152 mm phase to land

Disruptive distance in the 2500 mm phase to phase air

Disruptive distance in the 2152 mm phase to land air

10

Maximum interruption

time

of 50 milliseconds (break time)

50

milliseconds

(break time) 28 time) milliseconds (opening 274 9515

11

Own time of disconnection

12

Maximum connection

time

of 70 milliseconds

13

Time of investment

60

milliseconds

(contract 60

milliseconds

reversing time)

(contract reversing time)

14

Insulating

and

way

of SF6

SF6

extinction of the arch 15 Sequence of operation O-0.3 s-CO-3 min. CO/CO- O-0.3 15 s-CO s-CO-3

min.Or CO/CO-15 s-CO

16

Height of operation of the 300 m.s.n.m. plant

300 m.s.n.m.

17

Distance of escape

25 mm/Kv, between phases

25 mm/Kv, between phases

18 19

Type of switch

Three-phase

Three-phase Single-pole

Type of control of the Single-pole switch

20

Type of mechanisms

tensioning spring motor and tensioning manual

spring

motor and manual 110v DC 208v AC 0.3g

21 22 23

Control voltage voltage auxiliary circuits Level of

110v DC 208v AC

seismic 0.3g

classification 24 Auxiliary connections 6889 mm (25*245=6125 31*245=7595) 25 Auxiliary contacts 10 NO y 10 NC (Minimum) 10 NO y 10 NC (Minimum) 26 Capacity contacts 27 28 Voltage of heating office Bobbins of shot 208v AC Double of auxiliary 10 amperes minimum 10 minimum 208v AC Double amperes

29 30

Bobbin of closing

One

One contact of

Monitoring pressure of the With contact of alarm and With SF6 block

alarm and block local

31

Measurement of pressure local

of the gas 32 33 anti-pumping relay Quality of the included gas IEC 376 included IEC 376

according to norm

2. Environmental local conditions.

No 1 2

Description Speed of the wind Seismic force

Local conditions. 100 km/h

Offered 100 km/h

Acceleration, 0.5 g Acceleration, 0.5 g horizontal, vertical 0,5 g horizontal, vertical 50 C 0,5 g

Maximum

long 50 C

temperature of the day 4 Maximum humidity 5 installation height 300 msnm 300 msnm relative 100% 100%

3. Other requirements of the supply.

No 1

Requirements The technical rating plates must be in Spanish language, made of steel Stainless with inscriptions of low relief for outdoor and of easy reading.

Offered Yes

The switches must bring own structure of material resistant to the environment galvanized in warmly, according to procedure EN-ISO 1461, CASH 50976 or ASTM A153 and with capacity of static load and suitable dynamics

Yes

The stature of every switch will Yes have to be adapted to the current base of the concrete one

The structure of every switch must Yes have his point of connection of earthing

Every switch must bring the Yes connectors of high tension,

necessary and adapted for the installation of the equipment 6 The height of every switch must Yes be similar to nowadays installed in such a way that there are not modified in risky form the

distances and current heights of the installation 7 Every switch must rely on Yes

sufficient auxiliary contacts that they allow to connect all the circuits of control that allow the

current operation of the switches in sure form and that are fulfilled by the scheme of current

protection 8 In his offer it must guarantee in Yes form written by a company

qualified and independent from the quality of the materials used in the switches and the quality of the smelting of the fixed parts and mobiles of the switch 9 Must be submitted to international Yes standards both mechanical and electrical applied in the

manufacture of equipment and components, if they use their own rules of the country of origin must be comparable or better than most current international standards 10 In the assembly of the equipment Yes the use of adjustments is not allowed in the structure that alters the quality of the equipment 11 It is necessary to deliver the full Yes equipment of SF6 with all the accessories 12 It is necessary to deliver a lot of minimal supplies, attend to any damage that is generated in the first operations, this lot must include: - 3 relays monitoring SF6 gas Yes pressure.

- 3 engines of tightened of spring, - 6 bobbins of closing. - 6 bobbins of opening. - Relays of control. - Switchboards. - Switches you die of career.

Motor Yes Yes Yes NA NA

Bobbins signaling to attend a NA switch 13 Densimeter of SF6 per pole to Yes floor height for easy viewing, indicating scale shall have

temperature compensated pressure. so it must be Equipped with lowstage press indication, the first one as alarm and the second for blockade. 14 The protections of the elements of Yes the switch must effect by means of thermomagnetic switch. They

were not accepted protections by means of fuses 15 It must possess a counter of Yes operations of the type that does not adjust

4. Testing.

All switches must bring manufactures testing protocol prior to delivery and receipt of the same.

5. Manuals and documentation. No A) Required Manuals of technical Offered Yes

information it completes. Dimensions. screws and Torque of

packing

protocol of tests with his typical values and realized

measurements

during the tests. Important information for his storage and managing during the assembly. B) Manuals of operation and maintenance, where it Yes

includes measurements and calibrations and parameters of functioning, in Spanish language C) Fault identification manual, indicating the most likely failures and maintenance program to prevent Yes

6. Warranty.

The contractor must deliver the original certificate of guarantee of the manufacturer, whose term must be equal or bigger than 18 months, from the definitive receipt of the supply and service. Reply:confirm. 7. Delivery time.

With a maximum of 24 months, counted from the day of the notification to the beneficiary of the letter of credit. In the same term the contractor has 20 days calendar for every field of switches, from the notification in writing of the from date of the works for the supervisor of the contract or the chief of plant. Reply:confirm.