_________________________________________________________________________________________________ 180 S. Washington St. Falls Church, VA 22046 1-800-533-7694, Fax: 703-237-7442, e-mail: naphcc@naphcc.org, URL: http://www.phccweb.org/nspc
180 S. Washington St. Falls Church, VA 22046 1-800-533-7694, Fax: 703-237-7442, e-mail: naphcc@naphcc.org, URL: http://www.phccweb.org/nspc
DIRECTIONS
From New York Take the New Jersey Turnpike to the Garden State Parkway (Exit 11). Proceed south on the Parkway to Exit 38 (Atlantic City Expressway). Take the Atlantic City Expressway east. At the base of the Atlantic City Expressway, take Exit 2 and follow signs to Tropicana Casino and Resort, Home of The Quarter. Continue straight onto Albany Avenue. Turn left onto Atlantic Avenue. Turn right at S. Brighton Avenue. From Philadelphia Cross the Benjamin Franklin Bridge or Walt Whitman Bridge and follow the North-South Freeway (Route 42) to the Atlantic City Expressway. Take Atlantic City Expressway east. At the base of the Atlantic City Expressway, take Exit 2 and follow signs to Tropicana Casino and Resort, Home of The Quarter. Continue straight onto Albany Avenue. Turn left onto Atlantic Avenue. Turn right at S. Brighton Avenue. From Baltimore/Washington D.C. Take I-95 North across the Delaware Memorial Bridge and follow Route 40 east to the Atlantic City Expressway. Take the Atlantic City Expressway east. At the base of the Atlantic City Expressway, take Exit 2 and follow signs to Tropicana Casino and Resort, Home of The Quarter. Continue straight onto Albany Avenue. Turn left onto Atlantic Avenue. Turn right at S. Brighton Avenue.
180 S. Washington St. Falls Church, VA 22046 1-800-533-7694, Fax: 703-237-7442, e-mail: naphcc@naphcc.org, URL: http://www.phccweb.org/nspc
Frank R. Maddalon Executive Committee Liaison F. R. Maddalon Plumbing & Heating 1550 Sylvan Ave Hamilton, NJ 08610-4461 Phone: (609) 587-8317 Fax: (609) 587-9848 fmaddalon@aol.com Charles R. White Secretariat & Staff Liaison Plumbing-Heating-Cooling ContractorsNational Association 180 S. Washington St., Falls Church, VA 22046 Phone: (703) 237-8100 (800) 533-7694 Fax: (703) 237-7442 e-mail: white@naphcc.org URL: http://www.phccweb.org
Alex Tucciarone Old Bridge Plumbing Inspector 58 Lear Ct East Brunswick, NJ 08816-1853 Phone: (732) 721-5600 2420 Fax: (732) 607-7912 ajtucophc@comcast.net
180 S. Washington St. Falls Church, VA 22046 1-800-533-7694, Fax: 703-237-7442, e-mail: naphcc@naphcc.org, URL: http://www.phccweb.org/nspc
Contact Information:
Person Submitting Change 2 _____________________________________ Date 3 _________________ Jurisdiction/Company/ Mailing Address ______________________________________________________________________ City/State/Zip ________________________________________________________________________ Phone __________________ Fax __________________ E-mail ________________________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2015 NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than March 31, 2014.
2014
Cutoff for Proposed Changes 2015 NSPC Committee Meeting Committee Meeting & Public Hearing
2015
January December Publish 2015 NSPC Cutoff for Proposed Changes 2016 Supplement to NSPC March July
2016
Committee Meeting Committee Meeting & Public Hearing
2017
March Cutoff for Proposed Changes 2018 NSPC Committee Meeting January December June
2018
Publish 2018 NSPC Cutoff for Proposed Changes 2019 Supplement to NSPC
2019
March July Committee Meeting Committee Meeting & Public Hearing June September Publish Supplement to 2018 NSPC March
2020
Cutoff for Proposed Changes 2021 NSPC Committee Meeting
180 S. Washington St. Falls Church, VA 22046 1-800-533-7694, Fax: 703-237-7442, e-mail: naphcc@naphcc.org, URL: http://www.phccweb.org/nspc
Matrix of changes for the National Standard Plumbing Code July 2013
Item #
10-77 10-82
Section Number
10.20.8 and Table 3.1.3 XI Certification 12.16 Size and Lengths of Vents
13-1 13-2 13-3 13-4 13-5 13-6 13-7 13-8 13-9 13-10 13-11 13-12 13-13 13-14 13-14a 13-15 13-16 13-16a
1.2 Chemical Dispensing System 1.2 Combination Fixture 1.2 Continuous Pressure 1.2 Plastic Pipe Ratings 1.2 Dead Leg 1.2 Developed and Equivalent Lengths 1.2 Effective Openings 1.2 Existing Work Withdrawn 1.2 Horizontal Drains 1.2 Installed 1.2 Radon Gas 1.2 Subsoil Drain 1.2 Various Vents 1.2 Wash Fountains and Sinks 1.2 Water Temperature Control Valve Table 2.3.1 Footnote 2 2.3.1.a Short Radius Fittiings
NSPC Committee NSPC Committee NSPC Committee NSPC Committee Charles Chalk NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee
3.4.2013 Matrix
13-17 13-18 13-19 13-20 13-21 13-22 13-23 13-24 13-25 13-26 13-27 13-28 13-29 13-30 13-31 13-32 13-33 13-34 13-35 13-36 13-37 13-38 13-39
2.3.3 Back Outlet Fixtures 2.12 Pipe Sleeves 2.12 Pipe Sleeves 2.16.a.2 Building Drains 2.20 Requirements for Washrooms, Toilet Rooms, and Bathrooms 2.23 2.25.5 Sanitary Floor Sinks 3.3.3 Fixtures 3.4.6 Lead Free Plumbing 3.7.5 Plastic Storm Drain Piping Table 3.1.3 Part I Table 3.1.3 Part I Table 3.1.3 Part I Table 3.1.3 Part II Table 3.1.3 Part II Table 3.1.3 Part III Table 3.1.3 Part III Item 69 Table 3.1.3 Part III Item 76 Table 3.1.3 Part III Table 3.1.3 Part IV Table 3.1.3 Part IV Item 10 Table 3.1.3 Part IV Item 11 Table 3.1.3 Part IV Item 28
NSPC Committee NSPC Committee Charles Johnston NSPC Committee NSPC Committee Charles Chalk NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee David Jaffe David Jaffe NSPC Committee Steve Silber ASSE NSPC Committee NSPC Committee NSPC Committee David Ash NSPC Committee David Jaffe David Jaffe David Jaffe
3.4.2013 Matrix
13-40 13-41 13-42 13-43 13-44 13-45 13-46 13-47 13-48 13-49 13-50 13-51 13-52 13-53 13-54 13-55 13-56 13-57 13-58 13-59 13-60 13-61 13-62
Table 3.1.3 Part IV ASTM F1476 Table 3.1.3 Part IV ASMEB16.51 Table 3.1.3 Part V Table 3.1.3 Part V Item 19 Table 3.1.3 Part V ASME A112.19.9M Table 3.1.3 Part V Item 24 Table 3.1.3 Part VI Table 3.1.3 Part VI Item 9 Table 3.1.3 Part VII Table 3.1.3 Part VII Table 3.1.3 Part VII Item 20 Table 3.1.3 Part VIII Table 3.1.3 Part VIII ASME A112.4.14 Table 3.1.3 Part VIII Item 11 Table 3.1.3 Part IX Backflow Devices Table 3.1.3 Part IX Backflow Update Table 3.1.3 Part IX ASSE 1004 Table 3.1.3 Part X Table 3.1.3 Part X Table 3.1.3 Part X Home Laundry Equipment Table 3.1.3 Part XI Table 3.1.3 Part XI ASSE Standards Table 3.1.3 Part XI NFPA 99
NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee Steve Silber ASSE NSPC Committee NSPC Committee NSPC Committee Steve Silber ASSE Sean Mathews NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee Steve Silber ASSE NSPC Committee Steve Silber ASSE Steve Silber ASSE NSPC Committee NSPC Committee NSPC Committee
3.4.2013 Matrix
13-63 13-64 13-65 13-66 13-67 13-68 13-69 13-70 13-71 13-72 13-73 13-74 13-75 13-76 13-77 13-78 13-79 13-80 13-81 13-82 13-83 13-84 13-85
Table 3.1.3 Part XI (1) Table 3.1.3 Part XI (2) Table 3.1.3 Part XI (3) Table 3.1.3 Part XI (4) Table 3.4 ASME B16.51 Table 3.4 Items 11, 15, 16 Table 3.4 AWWA C900 & C901 Table 3.4 Under Water Service Table 3.4 CPVC-AL-CPVC Table 3.4, 3.5, 3.7 Titles Table 3.4.2 Update Table 3.4.2 CPVC-AL-CPVC Table 3.4.3 PEX Table 3.4.3 CPVC-AL-CPVC Table 3.4.3 PP Table 3.5 Table 3.6 Table 3.7 Withdrawn 4.2.8 Brazed NFPA 99C 4.2.12 Ductile Iron 4.2.14.3 Solvent Cement Joints in CPVC Piping 4.2.14.5 Heat Fusion Joints
Steve Silber ASSE Steve Silber ASSE Steve Silber ASSE Steve Silber ASSE NSPC Committee NSPC Committee NSPC Committee NSPC Committee David Ash NSPC Committee NSPC Committee David Ash NSPC Committee David Ash Michael Cudahy NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee Michael Cudahy NSPC Committee
3.4.2013 Matrix
13-86 13-87 13-88 13-89 13-90 13-91 13-92 13-93 13-94 13-95 13-96 13-97 13-98 13-99 13-100 13-101 13-102 13-103 13-104 13-105 13-106 13-107 13-108
4.3.8.f Couplings for Drainage 4.3.8.h Eccentric Couplings for Drainage 4.3.9 Plastic DWV to Other Materials 5.1 Separate Traps Withdrawn Table 5.2 5.3.1 Design of Traps 5.3.6.b ASSE 1072 5.4.3 Change of Direction 5.4.4 Concealed Cleanouts 5.4.5.b Inaccessible Cleanouts Table 5.4.9 5.4.13 Cleanout Equivalent 5.4.14 Floor Drain Cleanouts 5.5.1.d Exception 6.2.1.c Delete Dishwashers from Interceptors 6.2.1.1 6.2.1.3 6.2.1.3 d IAPMO Z1001 6.2.1.4 ASME A112.14.6 6.2.2 6.3.1 b Interceptors and Separators 6.3.1 e Rainwater in Parking Garages
NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee John Heine NSPC Committee Rand Ackroyd Rand Ackroyd NSPC Committee NSPC Committee Rand Ackroyd NSPC Committee NSPC Committee
3.4.2013 Matrix
13-109 13-110 13-111 13-112 13-113 13-114 13-115 13-116 13-117 13-118 13-119 13-120 13-121 13-122 13-123 13-123a 13-124 13-125 13-126 13-127 13-128 13-129 13-130
7.2 ADA Standards Chapter 7 Standards 7.4.4 & 7.4.9 Water Closets 7.5.5 7.5.5 & 7.5.6 Urinals 7.5.6 7.7.1 Bidet 7.7.4 Bidet Water Supply 7.8.4 Bathtub Airgaps 7.10.4 b Bathtubs with Multiple Showerheads 7.11 Kitchen Sinks Withdrawn 7.12 Drinking Water Facilities 7.13.1 Compliance 7.15.1 Compliance 7.15.4 Commercial dishwashers 7.16.1 SS Drains 7.16.4 Required Locations for Floor Drains 7.16.4 a Floor Drains in Toilet Rooms 7.21.4 Editorial 7.21.5 b Editorial 7.21.5 c Laundry Trays 7.21.7 Facilities in Mercantile and Business Occupancies
NSPC Committee NSPC Committee NSPC Committee John Heine NSPC Committee John Heine NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee Dan O'Gorman NSPC Committee NSPC Committee NSPC Committee Dave Bishop NSPC Committee Dan O'Gorman NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee
3.4.2013 Matrix
13-131 13-132 13-133 13-134 13-135 13-136 13-137 13-138 13-139 13-140 13-140a 13-141 13-142 13-143 13-144 13-145 13-146 13-147 13-148 13-149 13-150 13-151 13-152
7.21.7 a 7.21.8 Food Service Establishments 7.21.9 Family and Assisted-Use Toilet Facilities 7.21.10 Fractional Fixtures Table 7.21.1 7.22 Water Treatment Systes 7.22.2 Ultraviolet Lights 7.24 e Plumbed Emergency Eyewash and Shower Equipment 7.24 f ASSE 1071 8.5 Pipe Guides 9.1.12 Relief Valve Discharge Piping 9.3.1 c Condensing Furnace Condensate 9.3.2 Strainers 9.4.1.b Vent Piping for Corrosive Wastes 9.4.3 Air Conditioning Condensate Waste Table 10.5.2 10.5.3 Backflow Devices 10.5.3 (1) 10.5.3 (2) 10.5.3 (3) 10.5.3 a & c (1) 10.5.3 a & c (2) 10.5.3 d
John Heine NSPC Committee NSPC Committee NSPC Committee NSPC Committee John Heine John Heine Steve Silber ASSE NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee Steve Silber ASSE Steve Silber ASSE Steve Silber ASSE Steve Silber ASSE Steve Silber ASSE Steve Silber ASSE
3.4.2013 Matrix
13-153 13-154 13-155 13-156 13-157 13-158 13-159 13-160 13-161 13-162 13-163 13-164 13-165 13-166 13-167 13-168 13-169 13-170 13-171 13-172 13-173 13-174 13-175
10.5.5 a 10.5.5 b Vacuum Breakers for Urinals 10.5.6 ASSE Updates 10.5.6 d 10.5.6 d 10.5.7 Tanks & Vats 10.5.8 Food Establishments 10.5.9 Backflow Prevention 10.5.10 Backflow Prevention 10.5.12 Hose Connections 10.5.13 a Chemical Dispensing System 10.5.13 d Water Powered Backup Sump Pumps 10.5.13 e Laboratory sink Faucets 10.9.2 Disinfecting 10.11 Allowance for Soil and Water Table 10.14.2 b Appendix M 10.14.6 b Excessive Pressure 10.14.6 d Exception Withdrawn 10.15.1 Tempered Water 10.15.2 c 10.15.6 a ASSE 1016 10.15.6 b Delete old ASSE 1016
Steve Silber ASSE NSPC Committee NSPC Committee Steve Silber ASSE Nick Azmo NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee Greg Towsley NSPC Committee NSPC Committee
3.4.2013 Matrix
13-176 13-177 13-178 13-179 13-180 13-181 13-182 13-183 13-184 13-185 13-186 13-187 13-188 13-189 13-190 13-191 13-192 13-193 13-194 13-195 13-195a 13-196 13-197
10.15.6 j 10.15.6 j Withdrawn 10.15.6 Mixed Water Update 10.15.9 Drip Pans 10.15.9.3 Drip Pan Drainage 10.16.6 Relief Valve Piping Withdrawn Withdrawn Withdrawn Withdrawn 10.16.7 Water Heater Vacuum Relief 10.18 Drinking Water Treatment Units Table 10.19 Residential Water Softeners 10.20.2 f Lead Free 10.20.2 g & h NFPA 13 D Systems 10.20.4 10.20.4 b Flux 10.20.4 d Lead Free 10.20.8 ASSE 7010 Table 11.4.1 Shower Stall DFU's 11.4.3 Diversity Factors Withdrawn
NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee
NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee Michael Cudahy NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee
3.4.2013 Matrix
13-197a 13-198 13-199 13-200 13-201 13-202 13-203 13-204 13-205 13-206 13-207 13-208 13-209 13-210 13-211 13-212 13-213 13-214 13-215 13-216 13-217 13-218 13-219
Table 11.4.1 Wash Sink Table 11.5.1 b 15" Pipe DFU's 11.7.10 High Level Alarms 11.7.10 High Level Alarms 11.7.11 Fixture Pumps and Ejectors 11.10 a Branch Connections to Stack Offsets 12.4.1 b Vent Terminals 12.16 Size and Lengths of Vents Table 12.16.4 Size and Lengths of Vent Stacks 12.18.2 Island Sink Vent 13.1.1 Where Required 13.3.1 Storm Drain Traps 13.4.3 Combined Drainage 14.3.1 NFPA 99 14.12 NFPA 99 15.3 15.3 Leak Testing 15.3.2 Exception 17.9.2 Pitless Adapter 17.9.4.2 Pumps Above Wells 17.9.6.3 Protective Pipes 17.15 Supply Connections Appendix B Title
NSPC Committee NSPC Committee Fritz Reuss John Wyckoff NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee Michael Cudahy NSPC Committee NSPC Committee NSPC Committee NSPC Committee John Heine NSPC Committee John Heine NSPC Committee NSPC Committee NSPC Committee NSPC Committee NSPC Committee
10
3.4.2013 Matrix
Figures are editorial changes not subject to public review Figure 1.2.15 and 13.3.2 Figure 4.3.8-D Delete Center Stops Figure 4.3.9-D Figure 5.4.3 Cleanout Spacing Figure 7.3.2 Figure 10.16.6 Notes
Dave Bishop NSPC Committee Michael Cudahy NSPC Committee NSPC Committee NSPC Committee
11
3.4.2013 Matrix
__10_/_77__
Person Submitting Change ______NSPC Committee__________________ Date ___9/24/10_________ Jurisdiction/Company/ Mailing Address ______________180 S. Washington Street, P.O. Box 6808__ ___________________ City/State/Zip ________________Falls Church, VA 1148_____________________________________ Phone _1-703-237-8100____ Fax __________________ E-mail ________________________________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
__10_/_82__
Person Submitting Change ______NSPC Committee__________________ Date ___11-06-10_______ Jurisdiction/Company/ Mailing Address ______________180 S. Washington Street, P.O. Box 6808__ ___________________ Phone _1-703-237-8100____ Fax __________________ E-mail ________________________________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
12.16.4 Size of Stack Vents and Vent Stacks a. The minimum required size of stack vents and vent stacks shall be in accordance with Table 12.16 12.16.4. For the purpose of sizing, the length of a vent stack or stack vent shall be the developed length from its lowest connection with the drainage system to its termination in the open air, including any vent headers. b. Vent stacks shall be sized based on the total drainage fixture unit load (DFU) at the base of the stack that they serve. Connections of vents to the vent stack on floor levels above the base of the stack shall not increase its size. c. For the purpose of sizing, the length of a vent stack in Table 12.16.4 shall be the developed length from its connection to the base of the stack being vented to its termination in the open air, including any vent headers. 12.16.5 Vent Headers a. Vent headers or portions thereof shall be sized according to Table 12.16. b. The number of fixture units (DFU) used to size vent headers shall be the sum of all fixture units (DFU) on all stacks served by each section of the header. c.. The developed length of vent headers shall be the longest vent length from the vent connection at the base of the most distant stack to the vent terminal in the open air. d. The soil and waste stack size used to size the vent headers shall be the equivalent size capable of handling the fixture unit load (DFU) on the vent header; based on Table 11.5.1B. 12.16.6 Aggregate Size of Vent Terminals a. Each building sewer shall be vented by one or more vents extending from the drainage system, or branches thereof, to the open air above the roof. b. Stack vents and vent stacks shall be sized according to Table 12.16. c. b. The aggregate cross-sectional area of all vent terminals serving a sewer shall be not less than the cross-sectional area of the minimum required size of the building drain that they serve, at the point where it connects to the building sewer. (See Table 12.16.6 for the cross-sectional areas of pipes). EXCEPTION: The aggregate cross-sectional area requirement shall be exclusive of any requirements for larger vent terminals to prevent frost closure of the vent terminal under Section 12.5. d. c. One or more vent terminals having the aggregate cross-sectional area of a 3" vent terminal shall be permitted to vent a 4" building drain if the drainage fixture unit load (DFU) and number of bathroom groups served by the building drain does not exceed the maximum number allowed on a 3" building drain, as permitted by Section 12.16.6.c 11.5.6.c. 12.16.7 Underground Vent Piping The minimum size of vent piping installed underground shall be 1-1/2".
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 01
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___8-05-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 02
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___3-24-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 03
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __6-08-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
Continuous Pressure: With regard to the proper application of backflow prevention devices, continuous pressure is if the device is normally subjected to continuous water supply pressure for periods of twelve (12) hours or more.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 04
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___6-08-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
SIDR: An abbreviation for the "standard inside dimension ratio" of ID controlled plastic pipe that is based on the inside diameter of the pipe divided by its minimum wall thickness. Lower SIDR ratings have higher pressure ratings.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 05
Contact Information:
Person Submitting Change 2 ___Charles L Chalk Jr_________ Date 3 _________________ Jurisdiction/Company/ Mailing Address _______1 Kinwall Place Apt 2C____________________ City/State/Zip __Baltimore, Maryland 21236_____________________________________________ Phone __410-665-1522____ Fax ___Same_________ E-mail __mchalk1@comcast.net___________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 06
Contact Information:
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 ___1-18-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_ ___________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
Developed Length of Pipe: The length of a pipe line measured along the center line of the pipe and its fittings. Where pipe sizing tables are based on only the developed length of pipe, verify that there has been an allowance for an equivalent length of fittings. Equivalent Length of Fittings and Valves: The length of straight pipe of a specific diameter that would produce the same frictional resistances as a particular fitting or line compromised of pipe and fittings. The equivalent length of straight pipe that would produce the same resistance to flow as a specific fitting or valve of the same pipe size. Equivalent Length of Pipe, Fittings, and Valves or Total Equivalent Length: The sum of the developed lengths of pipe in a pipe line and the equivalent lengths of the fittings and valves in that line.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 07
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___12-10-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 08
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __3-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 10
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-24-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 11
Contact Information:
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 ___1-18-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_ ___________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows __X__ Delete subsection without substitution
Code Section:
1.2 Installed
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 12
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-11-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 13
Contact Information:
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 ___1-18-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_ ___________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 14
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-18-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: 1.2 Stack Vent; Vent, Branch; Vent Header; Vent Stack
Stack Vent: The extension of the top of a soil or waste stack above the highest horizontal drain connected to the stack to a vent header or outdoor vent terminal. Vent, Branch: A vent connecting one or more individual fixture vents with to a vent stack, or stack vent, or outdoor vent terminal. Vent Header: Vent piping that connects two or more stack vents or vent stacks to an outdoor vent terminal. Vent Stack: A vertical vent pipe that extends through one or more stories and that is intended to provide circulation of air to and from the drainage system from the base of a drain stack to its stack vent or to an outdoor vent terminal.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ___________________________________________________________________________________
13 - 14a
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___2-1-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 15
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___7-27-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
Water Temperature Control Valve: A valve of the pressure balance, thermostatic mixing, or combination pressure balance/thermostatic mixing type that is designed to control water temperature to reduce the risk of thermal shock and/or scalding.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 16
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __4-14-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Change "short and long pattern fittings" to "short and long radius fittings" in the following locations: Figure 2.3.1 - A: Note 3. Figure 2.3.1 - B: Note 1 (2 places). Figure 2.3.1 - C: Note 1 (2 places). Figure 2.3.1 - D: Note 1. Figure 2.3.1 - D: Title. Figure 2.3.1 - D: In the diagram (5 places). Figure 2.3.2: Note 2.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 16a
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___2-1-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
a. Changes in direction of drainage piping shall be made with long radius drainage fittings except where short radius fittings are required or permitted. in Table 2.3.1. Refer to Table 2.3.1 for permissible drainage fittings for changes in direction. 1. Short radius fittings are required to connect individual fixture trap arms to vertical drain and vent piping. 2. Short radius fittings may be used in the drain piping for an individual fixture. 3. Short radius fittings shall not be used in drain piping serving two or more fixtures. 4. Short radius fittings shall not be used at the base of stacks. 5. Short radius fittings may be used in vent piping.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 17
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___4-13-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 18
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-31-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13
19
13 - 20
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __10-2-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 21
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___12-10-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
2.20
WASHROOM & TOILET ROOM REQUIREMENTS REQUIREMENTS FOR WASHROOMS, TOILET ROOMS & BATHROOMS
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 22
Contact Information:
Person Submitting Change 2 ___Charles L Chalk Jr_________ Date 3 _________________ Jurisdiction/Company/ Mailing Address _______1 Kinwall Place Apt 2C____________________ City/State/Zip __Baltimore, Maryland 21236_____________________________________________ Phone __410-665-1522____ Fax ___Same_________ E-mail __mchalk1@comcast.net___________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 23
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-06-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 24
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __3-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
3.3.3 Fixtures
a. Plumbing fixtures shall be constructed from approved materials having smooth, non-absorbent surfaces and, be free from defects, and except as permitted elsewhere in this Code, shall conform to the standards cited listed in Table 3.1.3. b. Refer to Chapter 7 for the requirements for specific plumbing fixtures. b. c. Materials for special use fixtures not otherwise covered in this Code shall be constructed of materials especially suited to the use for which the fixture is intended.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 25
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-11-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
1.2 Lead Content
a. Material used in potable water supply systems, including piping, faucets, and valves, shall be "lead-free" as defined in the current Federal Law. b. Drinking water system components shall comply with the lead leachate requirements of NSF 61. Refer to Section 3.1.5 for components that are within the scope of NSF 61. 1.2 End-Use Device: A water supply device that dispenses potable water such as a faucet, drinking fountain, kitchen hot water dispenser, bathtub and/or shower faucet, shower head, flush valve, hose bibb, or supply connection to an appliance. 1.2 Lead-Free: Lead-free means containing not more than a weighted average of 0.25% lead for the wetted surfaces of pipes, tubes, fittings for pipes and tubes, plumbing supply fittings, and fixtures. "Lead-free" solder and flux contains no more than 0.2% lead. 1.2 Pipe or Tube Fitting: A piping component that connects sections of pipes or tubes, such as a coupling, elbow, reducer, tee, flange, union, or flexible connector. 1.2 Plumbing Supply Fitting: A piping component other than a pipe fitting or tube fitting that performs a required function in potable water supply piping such as a faucet, adapter, valve, strainer, filter, temperature limiting or control device, pressure switch, thermometer well, expansion compensator, or water hammer arrestor. page 1 of 7 1-11-2013
1.2 Weighted Average Lead Content: The weighted average lead content of a "lead-free" pipe, pipe fitting, plumbing fitting, or fixture shall be calculated by using the following formula: For each wetted component, the percentage of lead in the component shall be multiplied by the ratio of the wetted surface area of that component to the total wetted surface area of the entire product to arrive at the weighted percentage of lead of the component. The weighted percentage of lead of each wetted component shall be added together, and the sum of these weighted percentages shall constitute the weighted average lead content of the product. The lead content of the material used to produce wetted components shall be used to determine compliance with "lead-free". For lead content of materials that are provided as a range, the maximum content of the range shall be used.
Table 3.1.3 - X. MISCELLANOUS: 21. Drinking Water System Components - Health Effects: NSF 61 - 2007 2011 22. Weighted Average Lead Content Evaluation Procedure to a 0.25% Lead Requirement NSF 61-Annex G - 2009. 23. Drinking Water System Components - Lead Content NSF 372 - 2010
3.1.5 Health Effects of Drinking Water Components a. The health effects of drinking water components shall comply with NSF 61. Components within the scope of NSF 61 have surfaces in contact with potable water. Components include, but are not limited to, plastic materials, plastic and metallic pipe, pipe-related products, protective materials, joining and sealing materials, process media, treatment devices, transmission devices, distribution devices, and end-point devices. b. Refer to Section 3.4.6 for the limit on the lead content of pipes, tubes, pipe fittings, tube fittings, plumbing supply fittings, fixtures, and end-use devices that are intended to dispense potable water for human consumption by drinking or cooking.
3.3.6 Plumbing Supply Fittings Reserved Plumbing supply fittings covered under the scope of NSF 61 shall comply with its requirements. Refer to Section 3.1.5 for components that are within the scope of NSF 61.
3.4 POTABLE WATER PIPING 3.4.1 Plastic Piping Plastic piping materials used for the conveyance of potable water shall comply with NSF 14 and be marked accordingly.
page 2 of 7
1-11-2013
3.4.2 Water Service Piping Water service pipe and pipe fittings piping to the point of entrance into the building through a foundation wall or floor shall be of materials listed in Table 3.4 and shall be water pressure rated not less than 160 psig at 73 deg F. See Table 3.4.2. Water service pipe and fittings shall comply with NSF 61 Section 3.4.6 for the limits on lead content. 3.4.3 Water Distribution Piping Water piping for the distribution of hot or cold water within buildings shall be of material listed in Table 3.4, and shall be water pressure rated for not less than 100 psi at 180 deg F and 160 psi at 73 deg F. Plastic piping used in hot water distribution shall be installed in accordance with the requirements of Section 10.15.8. Water distribution pipe and pipe fittings shall comply with NSF 61 Section 3.4.6 for the limits on lead content. NOTE: The working pressure rating of certain approved plastic piping materials varies depending on the pipe size, material composition, wall thickness, and methods of joining. See Table 3.4.3. 3.4.4 Fittings a. Fittings for water supply piping shall be compatible with the pipe material used. b. Insert fittings for plastic tubing shall be the metallic or plastic type that comply with the standards listed in Table 3.1.3. 3.4.5 Material Ratings and Installation a. Piping used for domestic potable water shall be suitable for the maximum temperature, pressure, and velocity that may be encountered, including temporary increases and surges. b. Relief valve temperature and pressure relief settings shall not exceed the pipe, tubing tube or fitting manufacturer's recommendations. c. Pipe Piping and fittings shall be installed in accordance with the manufacturer's installation instructions and the acceptable material standards, recognizing any limitations in use. 3.4.6 Limit Limits on Lead Content a. Materials used in potable water supply systems, including piping, faucets and valves, shall be "lead-free" as defined by current Federal Law. b. Drinking water system components shall comply with the lead leachate requirements of NSF 61. Refer to Section 3.1.5 for components that are within the scope of NSF 61. a. Pipes, tubes, fittings for pipes and tubes, plumbing supply fittings, fixtures, and end-use devices that are intended to dispense potable water for human consumption by drinking and cooking shall be "lead-free", containing not more than a weighted average of 0.25% lead with respect to the wetted surfaces, as defined in Section 1.2 of this Code. b. Solder and flux for soldered joints in potable water piping shall be "lead-free", containing not more than 0.2% lead. Flux for making soldered joints in "lead-free" piping shall be rated for the temperatures necessary for making joints in "lead-free" piping. page 3 of 7 1-11-2013
c. Potable water supply components that are within the scope of NSF 61 for drinking water system components and are required to be "lead-free" shall be certified to comply with NSF 61 and either its Annex G or NSF 372. d. Potable water supply components that are not within the scope of NSF 61 for drinking water system components but are required to be "lead-free" shall be certified to comply with NSF 372. e. Potable water supply components that are not required to be "lead-free" shall be rated for use with potable water and shall not contain more than 4% lead by dry weight for plumbing supply fittings and fixtures or more than 8% lead by dry weight for pipes, tubes, and fittings for pipes and tubes. f. The following potable water end-use devices and water supply piping are considered to be intended to convey water for human consumption through drinking or cooking and shall be "lead-free", including their associated supply piping: 1. kitchen sink faucets 2. bar sink faucets 3. private bathroom sink faucets 4. drinking fountain faucets 5. kitchen hot water dispensers 6. point-of-use water treatment devices 7. the water supply to ice makers 8. the water supply to potable water heaters 9. recirculated hot water piping 10. the water supply to misting systems for produce in food markets 11. the water supply to cooking equipment for food in commercial kitchens 12. the water supply to production equipment for processed food containing water 13. any other end-use devices and piping that convey water for human consumption EXCEPTION: Tank-type water heaters shall not be required to be "lead-free" unless there is an industry standard for "lead-free" tank-type water heaters and they are required to be "lead-free" by the Authority Having Jurisdiction. g. The following piping components shall be "lead-free" when associated with "lead-free" end-use devices and piping that is required to be "lead-free:" 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. main service shutoff valves water service backflow prevention devices water meters pressure booster pumps pressure reducing valves strainers water filters check valves control valves vacuum breakers water hammer arrestors master hot water mixing valves in-line tempering valves hot water recirculating pumps branch piping shutoff valves page 4 of 7
1-11-2013
balancing valves fixture shutoff valves solenoid valves tankless water heaters any other piping components associated with end-use devices or piping that are required to be "lead-free"
h. The following potable water end-use devices, water supplies, and components are not considered to be intended to convey water for human consumption through drinking or cooking and are not required to be "lead-free", including their associated water supply piping, unless their associated piping also serves end-use devices and water supplies that must be "lead-free". 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. bathtub faucets shower valves, heads, and adapters tank-type water heaters flush valves for water closets flush valves for urinals flush valves for bidets shutoff valves for clothes washing machines lavatory faucets in public toilet rooms laundry sink faucets service sink faucets faucets for laboratory applications hose bibbs trap seal priming devices backflow prevention devices that supply non-potable applications fire hose valves water hammer arresters the water supply to dish washers the water supply to whirlpools, spas, therapy pools, and swimming pools the water supply to boilers and heating hot water generators the water supply to humidifiers the water supply to irrigation systems and other non-potable applications the water supply to food production equipment that does not contact the food any other end-use devices and water supplies that do not convey water for human consumption EXCEPTION: Tank-type water heaters shall not be required to be "lead-free" unless there is an industry standard for "lead-free" tank-type water heaters and they are required to be "lead-free" by Section 3.4.6, as dictated by the Authority Having Jurisdiction. 3.4.7 Shutoff Valves a. All gate valves, ball valves, butterfly valves, globe valves, and other shutoff valves in water service piping and water distribution piping shall comply with the requirements of NSF 61. that supply potable water for human consumption by drinking or cooking shall be "lead-free" in accordance with Section 3.4.6. b. Shutoff valves that must be "lead-free" and are within the scope of NSF 61 shall comply with the requirements of NSF 61 and either its Annex G or NSF 372.
page 5 of 7
1-11-2013
c. Shutoff valves that must be "lead-free" but are not within the scope of NSF 61 shall comply with NSF 372. d. Shutoff valves that are not required to be "lead-free" shall be rated for use with potable water and shall not contain more than 4% lead by dry weight. Section 4.2.4 Soldered f. Flux for making soldered joints in "lead-free" piping shall be rated for the temperatures necessary for making joints in "lead-free" piping.
7.1 FIXTURE STANDARDS 7.1.1 General Plumbing fixtures, plumbing fixture trim, and plumbing appliances shall comply with the standards listed in Table 3.1.3. Plumbing supply fittings covered under the scope of NSF 61 shall comply with the requirements of NSF 61. 7.1.2 Fixture Faucets and other End-Use Devices a. Fixture faucets and other end-use devices that supply potable water for human consumption by drinking or cooking shall be "lead-free" in accordance with Section 3.4.6. b. Fixture faucets and other end-use devices that must be "lead-free" and are within the scope of NSF 61 shall comply with the requirements of NSF 61 and either its Annex G or NSF 372. c. Fixture faucets and other end-use devices that must be "lead-free" but are not within the scope of NSF 61 shall comply with NSF 372. d. Fixture faucets and other end-use devices that are not required to be "lead-free" shall be rated for use with potable water and shall not contain more than 4% lead.
10.1 QUALITY OF WATER SUPPLY a. Only potable water shall be supplied to plumbing fixtures used for drinking, bathing, culinary use, laundry use, cleaning, or the processing of food, medical, or pharmaceutical products.
10.20 NFPA 13D Multipurpose Residential Fire Sprinkler Systems 10.20.2 General f. NFPA 13D multipurpose piping systems shall comply with the "lead-free" requirements of this Code if the piping, including parallel looped branches, supplies one or more end-use devices or equipment that are required to be "lead-free" by Section 3.4.6. The fire sprinklers in such piping shall be "lead-free". EXCEPTIONS: (1) Sprinkler-only branch supply piping to one or more individual sprinklers. page 6 of 7 1-11-2013
(2) Sprinklers supplied by individual sprinkler-only branch piping. (3) Plumbing-only branch supply piping to end-use devices or equipment that are not required to be "lead-free". 10.20.4 Materials for Combined System Piping d. Piping within combined piping systems that conveys water to outlets for human consumption by drinking or cooking shall be "lead-free" in accordance with Section 3.4.6.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
page 7 of 7
1-11-2013
13 - 26
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
3.7.5 Plastic Piping
a. Pipe and fittings classified as standard dimension ratio that are underground outside of buildings shall be SDR 35 or heavier (lower SDR number). Pipe and fittings within buildings shall be SDR 26 or heavier (lower SDR number), except that SDR 35 fittings shall be permitted. b. Pipe and fittings classified by pipe stiffness that are underground outside of buildings shall be PS46 or heavier (higher PS number). Pipe and fittings within buildings shall be PS-100 minimum.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 27
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-04-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 28
Contact Information:
Person Submitting Change 2 ____David Jaffe_________________ Date 3 ___1/17 /2013___ Jurisdiction/Company/Cast Iron Soil Pipe Institute Mailing Address _1064 Delaware Ave SE ______________ City/State/Zip _____Atlanta, GA Zip Code: 30316___________________
Phone ___404-622-0073____ Fax ___678-973-2845_____ E-mail _______________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__x___ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _____Table 3.1.3 I #1 Hub & Spigot Cast Iron Soil Pipe & Fittings:_____ASTM A74-2006____ ASTM A74-2012_____________ Basis/Reason for Change: To update the National Standard Plumbing Code to reflect the most newest revision ASTM A74-2012
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 29
Person Submitting Change 2 ____David Jaffe___________ Date 3 ________1/17 /2013_________ Jurisdiction/Company/Cast Mailing Address _ Iron Soil Pipe Institute 1064 Delaware Ave SE _________________ City/State/Zip _____Atlanta, GA 30316______________________________ Phone __404-622-0073____ Fax __678-973-2845_____ E-mail ______________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__x_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _____Table 3.13 I #2 Hubless Cast Iron Soil Pipe & Fittings:____CISPI 301-2005 and ASTM A888-2007a__________________
CISPI 301-2012 ASTM A888-2012
Basis/Reason for change To update the National Standard Plumbing Code to reflect the most newest revision.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 30
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-16-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 31
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145_________________________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail _____________________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes. Check All That Apply: _____ Change subsection to read as follows _____ Add new subsection to read as follows __X___ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Contact Information:
Code Section: ____Various editorial changes see below_______________________ 1. Section 3.1.3 Change name of organization from American Society of Sanitary Engineers to ASSE International. 2. Table 3.1.3 Part II Item 17 Change title from Push-Fit Fittings for Copper Water Tube to PushFit Fittings. Change standard designation from ASSE 1061-2006 to ASSE 1061-2011 3. Table 3.1.3 Part III Item 65 Change title from Push-Fit Fittings for Copper Water Tube to Push-Fit Fittings. Change standard designation from ASSE 1061-2006 to ASSE 1061-2011 4. Table 3.1.3 Part IV Item 29 Change title from Dielectric Pipe Unions to Dielectric Pipe Union. Change standard designation from ASSE 1079-2005 to ASSE 1079-2012 5. Table 3.1.3 Part IV Item 30 Change title from Performance Requirements for Removable and Non-Removable Push-Fit Fittings to Push-Fit Fittings. Change standard designation from ASSE 1061-2006 to ASSE 1061-2011 6. Table 3.1.3 Part V Item 1 Change title from Anti-Siphon Fill Valves (Ballcocks) for Gravity Water Closet Flush Tanks to Anti-Siphon Fill Valves for Water Closet Tanks
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
7. Table 3.1.3 Part VI Item 2 Change Designation from ASSE 1016-2005 to ASSE 10162011/ASME A112.1016-2011/CSA B125.16-11 8. Table 3.1.3 Part VI Item 5 Change title from Flushometers (pressurized flushing devices) to Pressurized Flushing Devices (Flushometers) for Plumbing Fixtures 9. Table 3.1.3 Part VI Item 6 Change title from Laboratory Faucet Vacuum Breakers to Laboratory Faucet Backflow Preventers 10. Table 3.1.3 Part VI Item 14 Change title from Temperature Actuated Flow Reduction (TAFR) Valves for Individual Fixture Fittings to Temperature Actuated, Flow Reduction (TAFR) Valves for Individual Supply Fittings 11. Table 3.1.3 Part VII Item 5 Change title from Food Waste Disposal Units, Household to Plumbing Aspects of Residential Food Waste Disposer Units 12. Table 3.1.3 Part VIII Item 2 Change title from Anti-Siphon Fill Valves (Ballcocks) for Gravity Water Closet Flush Tanks to Anti-Siphon Fill Valves for Water Closet Tanks 13. Table 3.1.3 Part VIII Item 7 Change title from Flushometers (pressurized flushing devices) to Pressurized Flushing Devices (Flushometers) for Plumbing Fixtures 14. Table 3.1.3 Part VIII Item 10 Change title from Water Pressure Reducing Valves to Water Pressure Reducing Valves for Domestic Water Distribution Systems 15. Table 3.1.3 Part VIII Item 19 Change title from Wall Hydrants, Vacuum Breaker Type, Freeze Resistant, Automatic Draining to Wall Hydrant with Backflow Protection and Freeze Resistance. Change standard designation from ASSE 1019-2004 to ASSE 1019-2011 16. Table 3.1.3 Part VIII Item 20 Change title from Trap Seal Primer Devices Drainage and Electronic Types to Trap Seal Primer Devices Drainage Types and Electronic Design Types 17. Table 3.1.3 Part VIII Item 21 Change title from Wall Hydrants, Dual Check Backflow Type, Freeze Resistant to Dual Check Backflow Preventer Wall Hydrants Freeze Resistant Type 18. Table 3.1.3 Part VIII Item 22 Change title from Pressure Balancing In-Line Mixing Valves for Individual Fixture Fittings to Individual Pressure Balancing In-Line Valves for Individual Fixture Fittings 19. Table 3.1.3 Part IX Item 2 Change title from Backflow Preventers with Intermediate Atmospheric Vent to Backflow Preventers with an Intermediate Atmospheric Vent 20. Table 3.1.3 Part IX Item 3 Change title from Detector Assembly, Double Check Type to Double Check Detector Fire Protection Backflow Prevention Assemblies. Change standard designation from ASSE 1048-2009 to ASSE 1048-2011 21. Table 3.1.3 Part IX Item 4 Change title from Detector Assembly, Reduced Pressure Type to Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies. Change standard designation from ASSE 1047-2009 to ASSE 1047-2011
22. Table 3.1.3 Part IX Item 5 Change title from Double Check Valve Assembly to Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention Assemblies. Change standard designation from ASSE 1015-2009 to ASSE 1015-2011 23. Table 3.1.3 Part IX Item 6 Change title from Dual Check Valve Type Backflow Preventer to Dual Check Backflow Preventers 24. Table 3.1.3 Part IX Item 8 Change title from Reduced Pressure Principle Backflow Preventer to Reduced Pressure Principle Backflow Preventers and Reduced Pressure Principle Fire Protection Backflow Preventers. Change standard designation from ASSE 1013-2009 to ASSE 1013-2011 25. Table 3.1.3 Part IX Item 9 Change title from Vacuum Breaker, Atmospheric (pipe-applied) to Atmospheric Type Vacuum Breakers 26. Table 3.1.3 Part IX Item 10 Change title from Vacuum Breakers, Hose Connection to Hose Connection Vacuum Breakers 27. Table 3.1.3 Part IX Item 11 Change title from Vacuum Breaker, Laboratory Faucet to Laboratory Faucet Backflow Preventers 28. Table 3.1.3 Part IX Item 12 Change title from Vacuum Breaker, Pressure to Pressure Vacuum Breaker Assembly 29. Table 3.1.3 Part IX Item 14 Change title from Vacuum Breakers, Spill Resistant to Spill Resistant Vacuum Breakers 30. Table 3.1.3 Part IX Item 19 Change title from Outdoor Enclosures for Backflow Prevention Devices to Outdoor Enclosures for Fluid Conveying Components 31. Table 3.1.3 Part IX Item 21 Change title from Backflow Preventors for (Carbonated) Beverage Dispensing Equipment to Backflow Preventer for Beverage Dispensing Equipment 32. Table 3.1.3 Part XI Item 11 Change title from Field Test Procedures for Backflow Prevention Devices to Backflow Prevention Assembly Testers and change designation from ASSE 50102009 to ASSE/IAPMO/ANSI 5110-2009. 33. Table 3.1.3 Part XI Item 12 Change title from Professional Qualification Standard for Backflow Prevention Assembly Testers, Repairers, and Surveyors to Cross-Connection Control Professional Qualifications Standard. Change standard designation from ASSE Series 50002009 to ASSE/IAPMO/ANSI Series 5000-2009. 34. Table 3.1.3 Part XI Item 18 Change title from Professional Qualification Standard for Medical Gas Personnel to Professional Qualifications Standard for Medical Gas Systems Personnel. Change standard designation from ASSE Series 6000-2006 to ASSE/IAPMO/ANSI Series 60002012. 35. Section E.8.6 a. Change standard designation from ASSE 1050-2002 to ASSE 1050-2009
36. Section E.8.6 b. Change standard designation from ASSE 1051-2002 to ASSE 1051-2009. Change title from Individual and Branch Type Air Admittance Valves for Plumbing Drainage Systems to Individual and Branch Type Air Admittance Valves for Sanitary Drainage Systems Basis/Reason for Change: 1. Table 3.1.3 Part II Item 17 Editorial change to correct standard title and designation of current year of edition. 2. Table 3.1.3 Part III Item 65 Editorial change to correct standard title and designation of current year of edition. 3. Table 3.1.3 Part IV Item 29 Editorial change to correct standard title and designation of current year of edition. 4. Table 3.1.3 Part IV Item 30 Editorial change to correct standard title and designation of current year of edition. 5. Table 3.1.3 Part V Item 1 Editorial change to correct standard title. 6. Table 3.1.3 Part VI Item 2 Editorial change to reflect harmonization of standard with ASME and CSA and designation of current year of edition. 7. Table 3.1.3 Part VI Item 5 Editorial change to correct standard title. 8. Table 3.1.3 Part VI Item 6 Editorial change to correct standard title. 9. Table 3.1.3 Part VI Item 14 Editorial change to correct standard title. 10. Table 3.1.3 Part VII Item 5 Editorial change to correct standard title. 11. Table 3.1.3 Part VIII Item 2 Editorial change to correct standard title. 12. Table 3.1.3 Part VIII Item 7 Editorial change to correct standard title. 13. Table 3.1.3 Part VIII Item 10 Editorial change to correct standard title. 14. Table 3.1.3 Part VIII Item 19 Editorial change to correct standard title and designation of current year of edition. 15. Table 3.1.3 Part VIII Item 20 Editorial change to correct standard title. 16. Table 3.1.3 Part VIII Item 21 Editorial change to correct standard title. 17. Table 3.1.3 Part VIII Item 22 Editorial change to correct standard title. 18. Table 3.1.3 Part IX Item 2 Editorial change to correct standard title. 19. Table 3.1.3 Part IX Item 3 Editorial change to correct standard title and designation of current year of edition.
20. Table 3.1.3 Part IX Item 4 Editorial change to correct standard title and designation of current year of edition. 21. Table 3.1.3 Part IX Item 5 Editorial change to correct standard title and designation of current year of edition. 22. Table 3.1.3 Part IX Item 6 Editorial change to correct standard title. 23. Table 3.1.3 Part IX Item 8 Editorial change to correct standard title and designation of current year of edition. 24. Table 3.1.3 Part IX Item 9 Editorial change to correct standard title. 25. Table 3.1.3 Part IX Item 10 Editorial change to correct standard title. 26. Table 3.1.3 Part IX Item 11 Editorial change to correct standard title. 27. Table 3.1.3 Part IX Item 12 Editorial change to correct standard title. 28. Table 3.1.3 Part IX Item 14 Editorial change to correct standard title. 29. Table 3.1.3 Part IX Item 19 Editorial change to correct standard title. 30. Table 3.1.3 Part IX Item 21 Editorial change to correct standard title. 31. Table 3.1.3 Part XI Item 11 Editorial change to correct standard title and designation. 32. Table 3.1.3 Part XI Item 12 Editorial change to correct standard title. 33. Table 3.1.3 Part XI Item 18 Editorial change to correct standard title and designation of current year of edition. 34. Section E.8.6 a. Editorial change to correct designation of current year of edition. 35. Section E.8.6 b. Editorial change to correct standard title and designation of current year of edition. Vote: ___ Accept ___ Accept in Part ___ Defeated ___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
________________________________________________________________________________
13 - 32
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-16-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
50 51 52 53 54 57 59 63 64 69 71 79 83 84
ASTM F877-2007 -2011a ASTM F876-2010 -2010e1 ASTM F1807-2010e1 -2011ae1 ASTM F1960-2010 -2011e1 ASTM F1281-2007 -2011 CSA B137.9-2009 w/update 1 ASTM F714-2010 -2012a ASTM F1335-2004 Reserved ASTM F2080-2009 -2012 ASTM D3261-2010a -2012 ASTM F1055-1998 (2006) -2011 ASTM F2159-2010 -2011 ASTM F1760-2001 (2005) -(2011) ASTM F1760-2001 (2005) -(2011)
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
page 2 of 2
13 - 33
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___8-05-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: Table 3.1.3 - Part III Non-Metallic Pipe and Fittings
34 69 Butt Heat Fusion Polyethylene (PE) Plastic Pipe Fittings for Polyethylene Plastic Pipe and Fittings (1/2" to 48") ASTM D3261-2010a Reserved Butt Heat Fusion Polyethylene (PE) Plastic Fittings for PE Pipe and Tubing (1/2" to 48") ASTM D3261-2010a
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 34
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-24-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
76
Flexible Pre-Insulated Piping: (ASTM D2104, ASTM D2239, ASTM D3035, ASTM F714, ASTM F876, ASTM F877, ASTM F1281, ASTM F1282) ASTM F2165-2002 (2008)
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 35
Contact Information:
Person Submitting Change 2 _David W. Ash_________ Date 3 _September 11, 2012_ Jurisdiction/Company/ Mailing Address _9911 Brecksville Road ___________________ City/State/Zip _Cleveland, Ohio 44141___________ Phone _216-447-7239___ Fax __________________ E-mail _david.ash@lubrizol.com___ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__X_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 36
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-16-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
4 6 7 9 13 15 19 20 21 31
AWS A5.8-2004 -2011 AWWA C606-2006 -2011 ASTM C1173-2008 -2010e1 AWWA C111/A21.11 -2012 ASTM C443-2010 -2011 ASTM D3139-1998 (2005) (2011) ASTM D2235-2004 (2011) ASTM D2564-2004 (2009)e1 -2012 ASTM D3138-2004 (2011) AWWA C606-2006 -2011
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 37
Contact Information:
Person Submitting Change 2 ____David Jaffe___________ Date 3 ___1/17 /2013_____ Jurisdiction/Company/Cast Iron Soil Pipe Institute Mailing Address _1064 Delaware Ave SE________________ City/State/Zip _____Atlanta, GA 30316_________ Phone __404-622-0073_____ Fax _678-973-2845__ E-mail ________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__x_ Amend section with this editorial change ____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _Table 3.13 IV #10 Rubber Gaskets for Cast Iron Soil Pipe And Fittings: ASTM C564-2003a__ ASTM C564-2009a__________________
Basis/Reason for Chan: To update the National Standard Plumbing Code to reflect the newest revision.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
___________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 38
Contact Information:
Person Submitting Change 2 ____David Jaffe____________ Date 3 _1/17 /2013___ Jurisdiction/Company/ Cast Iron Soil Pipe Institute Mailing Address _1064 Delaware Ave SE ___________________ City/State/Zip _____Atlanta, GA 30316________ Phone ___404-622-0073______ Fax ___678-973-2845__ E-mail ___________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__x_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: ______Table 3.1.3Part IV #11 CISPI 310-2006_ ASTM C1277-2006_ __CISPI 310-2012 ASTM C1277-2012_________________ Basis/Reason for Change: To update the National Standard Plumbing Code to reflect the newest revision. Vote: ___ Accept
___ Accept in Part ___ Defeated ___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 39
Contact Information:
Person Submitting Change 2 ____David Jaffe___________ Date 3 __1/17 /2013_____ Jurisdiction/Company/ Cast Iron Soil Pipe Institute Mailing Address _1064 Delaware Ave SE___________________ City/State/Zip _____Atlanta, GA 30316__________________ Phone ___404-622-0073_ Fax _678-973-2845___ E-mail _________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__x_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _____Table 3.1.3 IV #28 Heavy Duty Couplings for Hubless Pipe and Fittings: C1540-2004_______ ASTM C1540-2011__________ Basis/Reason for Change: To update the National Standard Plumbing Code to reflect the newest revision.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 40
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __4-22-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: Table 3.1.3 - Part IV Pipe Joints, Joining Materials, Couplings, Gaskets
6. Grooved and Shouldered Joints (Split Couplings) AWWA C606-2006 ASTM F1476-2007
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 41
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-04-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Table 3.4 - Line Item 5. under Fittings: ASME B16.51 (press-connect) Table 3.4 - Line Item 6, under Fittings: ASME B16.51 (press-connect)
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 42
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-11-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
14 14 16 16 16a 17 17 18 18 20 20 23 25 26 27
ASME A112.19.7-2006 2012 CSA B45.10-2012 IAPMO Z124.9-2004 -2011 CSA B45.5-2002 (2008) -2011 w/update 1 ASME A112.19.19-2006 (2011) ASME A112.19.3-2008 w/updates 1-2 CSA B45.4-2008 w/updates 1-2 ASME A112.19.2-2008 w/updates 1-2 CSA B45.1-2008 w/updates 1-2 IAPMO Z124.6-2007 -2011 CSA B45.5-2002 (2008) -2011 w/update 1 ASME A112.19.15-2005 (2010) -2012 ASME A112.19.14-2006 (2011) ASME A112.19.2-2008 w/updates 1-2 ASME A112.6.7-2001 (2007) -2010
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
13 - 43
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-15-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 44
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-15-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 45
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145 Phone _440-835-3040__ Fax _440-835-3488___ E-mail ______________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
Contact Information:
__X_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __ Table 3.1.3 Part V, Item 24___ Revise Table 3.1.3 Part V Item 24 to read ISEA Z358.1-2009, ASSE 1071-2012 Basis/Reason for Change: ASSE 1071 is ANSI Approved standard developed under the consensus process and establishes performance requirements for plumbed emergency equipment. NOTE: NOTE: ASSE has submitted companion change to add ASSE Standard 1071 to Section 7.24e. This change should only be accepted if the companion change is accepted. Vote: ___ Accept ___ Accept in Part ___ Defeated ___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 46
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-11-2011_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
1 2 2 2 2a 2a 4 4 5 7 7 10 12 13 17 17 18 18 18
CSA B125.3-2005 -2011 ASSE 1016-2005 -2011 ASME A112.1016 - 2011 w/update 1 CSA B125.16 - 2011 w/update 1 ASME A112.18.1-2005 2011 CSA B125.1-2005 -2011 ASME A112.18.1-2005 2011 CSA B125.1-2005 -2011 CSA B125.3-2005 -2011 ASME A112.18.1-2005 2011 CSA B125.1-2005 -2011 CSA B125.3-2005 -2011 ASME A112.19.8b - 2007 w/addendums A-B ASME A112.18.3-2002 (2008) (2012) ASME A112.18.2-2005 -2011 CSA B125.2-2005 -2011 ASTM F409-2002 (2008) -2012 ASME A112.18.2-2005 -2011 CSA B125.2-2005 -2011
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
page 2 of 2
1-11-2013
13 - 47
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-15-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
9. Trim for Water Closet Bowls, Tanks, and Urinals (dimensional standards) Flush Valves and Spuds for Water Closets, Urinals, and Tanks ASME A112.19.5 - 2005 2011 CSA B125.3 - 2005 2011
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 48
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-11-2013_______ Jurisdiction/Company/ Mailing Address _180 S. Washington Street, P.O. Box 6808 City/State/Zip Falls Church, VA 22046_ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
2 5 7
7 8 8 9 10 11 13 14 16 17 18 19
UL 921 Ed.6-2006 (2012) UL 430 Ed.7-2009 (2011) ANSI Z21.10.1a-2009 CSA ANSI Z21.10.1a - 2009 CSA ANSI Z21.10.1b - 2009 CSA ANSI Z21.10.1c - 2009 CSA 4.1 - 2009 CSA 4.1a - 2009 CSA 6.5 - 2011 ANSI Z21.10.3b - 2008 CSA ANSI Z21.10.3 - 2011 CSA 4.3b-2004 4.3 - 2011 UL 174 Ed.11 - 2004 (2012) UL 499 Ed.13 - 2005 (2012) UL 732 Ed.5 - 1995 (2010) NSF 44 - 2009 2012 NSF 58 - 2009 2012 NSF 42 - 2009 2011 NSF 53 - 2009e 2011a NSF 55 - 2009 2012 CSA B483.1-2007 (2012) w/updates 1-2
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 49
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013__ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road__ City/State/Zip __Westlake, OH 44145____________________ Phone _440-835-3040__ Fax _440-835-3488_ E-mail ___________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __Table 3.1.3___ Add ASSE 1057-2012 with title Freeze Resistant Sanitary Yard Hydrant with Backflow Protection to Table 3.1.3, Part VII, Item 24 Basis/Reason for Change: ASSE 1057 is a product standard for performance requirements for Freeze Resistant Sanitary Yard Hydrants with Backflow Protection that has been accepted throughout the industry. NOTE: ASSE has submitted companion change to add ASSE Standard 1057 to Section 10.5.3.This change should only be accepted if the companion change is accepted.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13
50
13 - 51
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-15-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
1 1 1 2 4 5 7 8 12 15 19
ASME A112.14.1 - 2003 (2008) (2012) CSA B181.1-2006 of CSA B1800 Series (ABS) -2011 (ABS) CSA B181.2-2006 of CSA B1800 Series (PVC) -2011 (PVC) CSA B125.3-2005 -2011 MSS SP-71-2005 -2011 ASME A112.36.2M - 1991 (2008) (2012) CSA B125.3-2005 -2011 MSS SP-70-2006 -2011 CSA B125.3-2005 -2011 IAPMO PS 88-2002 -2012 ASSE 1019-2004 -2011
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 52
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-04-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 53
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-15-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 54
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-04-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
IX-7: Reserved
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 55
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-16-2013_______ Mailing Address 180 S. Washington Street, P.O. Box 6808 City/State/Zip Falls Church, VA 22046 Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
16 17
18
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 56
Contact Information: Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145_________________________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail _____________________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes. Check All That Apply: _____ Change subsection to read as follows _X__ Add new subsection to read as follows _____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __Table 3.1.3, Part IX, Item TBD_________________________ Add ASSE 1004-2008 with title Backflow Prevention Requirements for Commercial Dishwashing Machines to Table 3.1.3 Part IX Basis/Reason for Change: ASSE 1004 is referenced in the narrative of the code in Section 7.15.1 and should be included in Reference Table 3.1.3 Part IX.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 57
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-15-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
1 4 5 9 11 12 13 16 17 18 20
ASTM B370-2009 -2012 ASTM D4551-1996 (2008e1) - 2012 ASTM D4551-1996 (2008e1) - 2012 ASME A112.6.1M - 1997 (2008) (2012) NSF 14-2010 -2011 NSF 61-2010a -2012 ASME A112.14.4 - 2001 (2007) (2012) NFPA 13 - 2010 2013 NFPA 13D - 2010 2013 NFPA 13R - 2010 2013 ANSI/ICC A117.1-2009 ICC ANSI A117.1-2009
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 58
Contact Information:
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145__________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail _____________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes. Check All That Apply: _____ Change subsection to read as follows _X__ Add new subsection to read as follows _____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _Table 3.1.3, Part X, Item TBD__________________________ Add ASSE 1006-1986 with title Residential Use Dishwashers to Table 3.1.3 Part X
Basis/Reason for Change: ASSE 1006 is referenced in the narrative of the code in Section 7.15.1 and should be included in Reference Table 3.1.3 Part X.
Vote:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 59
Contact Information:
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145____________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail ____________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes. Check All That Apply: _____ Change subsection to read as follows _____ Amend section with this editorial change _____ Delete subsection and substitute as follows
_X__ Add new subsection to read as follows _____ Delete subsection without substitution
Code Section: __Table 3.1.3, Part X, Item TBD_________________________ Add ASSE 1007-1986 with title Home Laundry Equipment to Table 3.1.3 Part X
Basis/Reason for Change: ASSE 1007 is referenced in the narrative of the code in Section 7.13.1 and should be included in Reference Table 3.1.3 Part X.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 60
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-15-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
3 5 6 8 11 14 16 18
ASTM F402 - 2005 (2012) ASTM D2774 - 2008 2012 ASTM D2321-2009 -2011 ASTM D3311-2009a -2011 ASSE 5010 5130 - 2009 ASTM F1290-1998a (2004) (2011) NFPA 99 - 2005 2012 ASSE Series 6000 - 2006 2012
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 61
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-04-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
__X__ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 62
Contact Information:
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 ___6-12-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_ ___________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
16:
Standard for Health Care Facilities (for medical gas and vacuum) NFPA 99 - 2005 Health Care Facilities Code (for medical gas and vacuum piping systems) NFPA 99 - 2012 NFPA 99C - 2005
17: Gas and Vacuum Systems (in health care facilities) Reserved
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 63
Contact Information:
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee_ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_____ City/State/Zip __Westlake, OH 44145_________________________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail _____________________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __ Table 3.1.3 Part XI, Item TBD_____________ Add ASSE Series 7000-2008 with title Professional Qualifications Standard for Plumbing-Based Residential Fire Protection Systems Installers and Inspectors to Table 3.1.3, Part XI, Item TBD Basis/Reason for Change: ASSE Series 7000 is an ANSI Approved standard developed under the consensus process and establishes minimum criteria for installers and inspectors for fire protection systems in one-and twofamily dwellings.
Vote:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 64
Contact Information:
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee__ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145__________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail ___________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __ Table 3.1.3 Part XI, Item TBD_____________ Add ASSE/IAPMO/ANSI Series 8000-2010 with title Self-Contained Breathing Apparatus (SCBA) Replenishment Systems Professional Qualifications Standard to Table 3.1.3, Part XI, Item TBD Basis/Reason for Change: ASSE/IAPMO/ANSI Series 8000 is an ANSI Approved standard developed under the consensus process and establishes minimum criteria for installers, inspectors and verifiers for self-contained breathing apparatus replenishment systems.
Vote:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 65
Contact Information:
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145_________________________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail _____________________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __ Table 3.1.3 Part XI, Item TBD_____________ Add ASSE/IAPMO/ANSI Series 10000-2010 with title Professional Qualifications Standard for Green Plumbing Systems Installers to Table 3.1.3, Part XI, Item TBD Basis/Reason for Change: ASSE/IAPMO/ANSI Series 10000 is an ANSI Approved standard developed under the consensus process and establishes the level of competency necessary for the installation of sustainable plumbing and mechanical systems and products to protect public health, safety and the environment.
Vote:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 66
Contact Information:
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road______ City/State/Zip __Westlake, OH 44145__________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail ___________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes. Check All That Apply: _____ Change subsection to read as follows _X__ Add new subsection to read as follows _____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __ Table 3.1.3 Part XI, Item TBD_____________ Add ASSE/IAPMO/ANSI Series 16000-2012 with title Professional Qualifications Standard for the Plumbing Inspector to Table 3.1.3, Part XI, Item TBD Basis/Reason for Change: ASSE/IAPMO/ANSI Series 16000 is an ANSI Approved standard developed under the consensus process and references the experience, education, training and general knowledge requirements for Plumbing Inspectors.
Vote:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 67
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-04-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Table 3.1.3 - Part II Non-Ferrous Metallic Pipe and Fittings II-10. Reserved Copper and Copper Alloy Press-Connect Pressure Fittings
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 68
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 _________________ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 69
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __7-14-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows
__X_ Add new subsection to read as follows _____ Delete subsection without substitution
xx.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 70
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___7-14-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Item 19a: Polyethylene of Raised Temperature (PE-RT) Plastic Hot and Cold-Water Tubing and Distribution Systems - ASTM F2769 Item 22 PEX Plastic Hot and Cold Water Distribution - ASTM F877 (SDR 9)
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 71
Contact Information:
Person Submitting Change 2 _David W. Ash_____________ Date 3 _September 11, 2012_ Jurisdiction/Company/ Mailing Address _9911 Brecksville Road ______________________ City/State/Zip _Cleveland, Ohio 44141____________________ Phone _216-447-7239______ Fax __________________ E-mail _david.ash@lubrizol.com___ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__X_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Part ___ Accept in Principle ___ Accept in Part and Principle ___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 72
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-07-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 73
13 - 74
Contact Information:
Person Submitting Change 2 _David W. Ash______________ Date 3 _September 11, 2012_ Jurisdiction/Company/ Mailing Address _9911 Brecksville Road ______________________ City/State/Zip _Cleveland, Ohio 44141_____ Phone _216-447-7239___ Fax __________________ E-mail _david.ash@lubrizol.com___ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__X_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Part ___ Accept in Principle ___ Accept in Part and Principle ___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 75
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___10-06-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: Table 3.4.3 Plastic Hot and Cold Water Distribution Piping
PEX (ASTM F876) PEX 1006 PEX 1008 PEX SDR 9 not threaded all sizes PEX (ASTM F877) PEX 1006 PEX 1008 PEX SDR 9 not threaded all sizes Composite Pipe (ASTM F1335) PE-AL-PE ASTM F1335 compression all sizes Composite Pipe (ASTM F1335) PEX-AL-PEX ASTM F1335 compression all sizes
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 76
Contact Information:
Person Submitting Change 2 _David W. Ash___________ Date 3 _September 11, 2012_ Jurisdiction/Company/ Mailing Address _9911 Brecksville Road ________________________ City/State/Zip _Cleveland, Ohio 44141_____________________ Phone _216-447-7239______ Fax __________________ E-mail _david.ash@lubrizol.com___ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__X_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Part ___ Accept in Principle ___ Accept in Part and Principle ___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 77
Person Submitting Change 2 _____Michael Cudahy__________________ Date 3 ___Aug 25 2012____ Jurisdiction/Company/ Mailing Address Plastic Pipe and Fittings Association City/State/Zip __Glen Ellyn / IL / 60137 Phone ___630 363 7933______ Fax __630 858 654___ E-mail__mikec@cmservnet.com_______ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _____Table 3.4.3 Plastic Hot and Cold Water Distribution Piping PP (ASTM F2389) | PP | Metric SDR 7.4, 6, 5 | fusion welded | all sizes Basis/Reason for Change:
PP made in metric dimensions and SDR 7.4, 6 and 5 wall thicknesses to ASTM F2389 is suitable for potable and hot and cold water systems. Per the standard, This specification establishes the requirements for polypropylene (PP) piping system components such as pipe, fittings, valves, and manifolds used in water service lines, hot-and-cold water distribution, hydronic heating, and irrigation systems to transport industrial process fluids, effluents, slurries, municipal sewage, etc. The piping system components covered here are made to metric sizes and IPS schedule 80 sizes, and pressure rated for water service and distribution supply.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 78
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___6-08-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: Table 3.5 Materials for Sanitary Waste and Drain
Item 16: PIPE: ASTM F891 (2) Item 17: Sewers Outside of Buildings: (change "A" to "X") Item 19: PVC Plastic Sewer Pipe (PSM) and Fittings Type PSM PVC Sewer Pipe and Fittings ASTM D3034 (1) ASTM D3034 (1)
Item 27: Underground Within Buildings: (change "A" to "X") PIPE: ASTM F1760, Sewer-Drain, PS 46 NOTES FOR TABLE 3.5 (1) Plastic waste and drain piping classified by standard dimension ratio shall be SDR 26 or heavier (lower SDR number). (1) ASTM D3024 PVC sewer and drain piping shall be SDR 26, SDR 35, or SDR 41, as required by the Authority Having Jurisdiction. (2) Plastic sewer pipe classified by pipe stiffness shall be PS-46 or stiffer (higher PS number). (2) ASTM F891 PVC sewer and drain piping shall be PS 100 or PS 50, as required by the Authority Having Jurisdiction. (4) PS-100 pipe or stiffer (higher PS number) is required for underground cellular core PVC sewer and drain pipe underground within buildings. (4) ASTM 891 PVC sewer and drain piping underground within buildings shall be PS-100.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 79
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___6-08-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 80
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___6-08-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 82
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __4-13-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 83
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___11-10-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 84
Contact Information:
Person Submitting Change 2 _____Michael Cudahy__________________ Date 3 ___July 5 2012____ Jurisdiction/Company/ Mailing Address Plastic Pipe and Fittings Association City/State/Zip __Glen Ellyn / IL / 60137 Phone ___630 363 7933______ Fax __630 858 654___ E-mail__mikec@cmservnet.com_______ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 85
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-12-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
4.2.14.5 Heat Fusion Joints in PE Water Piping Heat fusion joints in PE water piping complying with ASTM F714, ASTM D3035, AWWA C901, or AWWA C906 shall be made in accordance with the applicable requirements of ASTM F2620.
Table 3.1.3 - Part XI 21. Heat Fusion Joining of Polyethylene Pipe and Fittings
ASTM F2620-2011e1
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 86
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-25-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 87
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 88
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___6-05-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 89
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __3-25-2012_______ Mailing Address 180 S. Washington Street, P.O. Box 6808 City/State/Zip Falls Church, VA 22046 Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
__X__ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
___________________________________________________________________________________
13 - 89a
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-31-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 91
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___3-24-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows __X__ Delete subsection without substitution
NOTES FOR TABLE 5.2 (1) Separate trap required for wash tray and separate trap required for sink compartment with food waste grinder.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 91a
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-31-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 92
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___12-10-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
__X__ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 93
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___7-28-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
b. Floor drains that comply with ASME A112.6.3 shall be permitted to be fitted with a barrier type floor drain trap seal protection device complying with ASSE 1072. The device shall have an application designation marking for the type of floor and environment it has been designed and tested for (AF, AFGW, SF, CF, CT, WF).
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 93a
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-31-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
b. The distance distances referred to in Sections 5.4.1a Section 5.4.1.a shall include the developed length of the cleanout pipe from a cleanout opening to the connection of the next downstream cleanout or cleanout pipe.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 94
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-11-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 95
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
5.4.4 Cleanouts for Concealed Piping Cleanouts for concealed piping shall be extended through and terminate flush with the finished wall or floor. If in pits or chases. cleanouts may be left in the wall or floor provided they are of sufficient size to permit removal of the cleanout plug and proper cleaning of the system. Cleanouts for concealed piping in finished walls or ceilings shall be accessible through access doors or cover plates which provide clearance for removal of the cleanout plug and insertion of the drain cleaning equipment. See Figure 5.4.4
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 96
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___10-2-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 97
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___10-1-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 98
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___12-10-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 99
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-24-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows __X__ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 100
Contact Information:
Person Submitting Change 2 __John Heine_____________________ Date 3 1/7/13 Jurisdiction/Company/ NJ PHCC Code Committee, (Chairman) / PO Box 2067 Mailing Address ______________________________________________________________________
Princeton, NJ 08543 City/State/Zip ________________________________________________________________________
Phone ___609-987-0500_______________ Fax _ 609-987-0511 E-mail Director@nj-phcc.org IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows ___ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 101
Contact Information:
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 ___1-18-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_ ___________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
6.2.1 General
c. Grease interceptors shall be provided to receive the waste discharges from fixtures in food handling areas that introduce grease into the sanitary drainage system. Fixtures include, but are not limited to pot washing sinks, utensil soak sinks, pre-rinse sinks at dishwashers, dishwashers, wok range stations, drains from wash-down ventilation hoods, can washing drains, floor drains and floor sinks around grease producing fixtures, and similar fixtures.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 102
Contact Information:
Person Submitting Change 2 __Rand Ackroyd__________________ Date 3 Jan. 23, 2013_________ Jurisdiction/Company/ Mailing Address _____290 High St_________________________ City/State/Zip Newburyport, Ma 01950____________________
Phone 978 985 6980 Fax ___________ E-mail rackroyd@comcast.net________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
X_
_____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Basis/Reason for Change: Type I is not the title of the grease interceptors in the Standards PDI G101, ASME A112.14.3, it is simple Hydro-Mechanical
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 103
Contact Information:
Person Submitting Change 2 __Rand Ackroyd_______________ Date 3 Jan. 23, 2013_________ Jurisdiction/Company/ Mailing Address _____290 High St_____________________ City/State/Zip Newburyport, Ma 01950________________
Phone: 978 985 6980 Fax _________ E-mail: rackroyd@comcast.net___________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
X _ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Basis/Reason for Change: Type II is not the title of the grease interceptors in the Standards IAPMO Z1001, it is simple Gravity Grease Interceptor
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 104
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-04-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Table 3.1.3 - Part X - Miscellaneous X-22: Prefabricated Gravity Grease Interceptors IAPMO/ANSI Z1001 - 2007
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 105
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-04-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 106
Contact Information:
Person Submitting Change 2 __Rand Ackroyd______________ Date 3 Jan. 23,2013_____ Jurisdiction/Company/ Mailing Address: _____290 High St_________________________________ City/State/Zip: Newburyport, Ma 01950_________________________
Phone: 978 985 6980 Fax: ______________ E-mail: rackroyd@comcast.net______ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
X _ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _602.2 Compliance for Hydro- Mechanical Grease Interceptors Sizes Up to 100GPM a. Type I hydro-mechanical grease interceptors shall comply ASME A112.14.3 and Sections 6.2.1.1 and be installed in accordance with the recommendations of PDI G101 and the manufactures instructions. They shall have a grease retention capacity of not less than two pounds for each gpm of rated flow. Basis/Reason for Change: This section only applies to Hydro-Mechanical grease interceptors. Standard for Hydro-mechanical like PDI G101 no longer restrict size to 100 gpm Vote: ___ Accept
___ Accept in Part ___ Defeated ___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 107
Person Submitting Change 2 ______NSPC Committee________________ Date 3 ___9-24-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 ____________________ City/State/Zip _________________Falls Church, VA 22046__________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail _naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
6.3.1 Where Required and Approved Point of Discharge b. Sand interceptors and oil separators shall be provided wherever floors, pits, or surface areas subject to accumulation of grease or oil from service or repair operations are drained and washed into a drainage system. Such locations include, but are not limited to, car and truck washing facilities, engine cleaning facilities, and similar operations. The drainage and effluent from the interceptors and separators in such locations shall be connected to the sanitary sewer.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 108
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-24-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
6.3.1 Where Required and Approved Point of Discharge e. Where parking garages without provisions for vehicle washing or floor rinsing require storm water drainage, drains shall be permitted to connect to the storm sewer without a sand interceptor and oil separator. Such drainage, including rainwater, melting snow, and ice or rainwater runoff from vehicles, shall not be connected to the sanitary sewer.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 109
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-15-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.2 FIXTURES FOR ACCESSIBLE USE a. Plumbing fixtures for accessible use and their installation shall conform to the requirements of the 2010 ADA Standards for Accessible Design, ANSI/ICC ICC ANSI A117.1, or the Authority Having Jurisdiction. b. Exposed waste and water supply piping for accessible fixtures shall be covered with protectors or insulators that comply with ASME A112.18.9. TABLE 3.1.3 VI-20: Reserved Protectors/Insulators for Exposed Waste and Supplies for Accessible Fixtures ASME A112.18.9 - 2011 X-21: 2010 ADA Standards for Accessible Design ADA Standards - 2010
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 110
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __2-25-2012_______ Mailing Address 180 S. Washington Street, P.O. Box 6808 City/State/Zip Falls Church, VA 22046 Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: Chapter 7 - Plumbing Fixtures, Fixture Fittings, and Plumbing Appliances
7.4.1 7.4.2 Vitreous china water closets shall comply with ASME A112.19.2M 19.2. Plastic water closets shall comply with ANSI IAPMO Z124.4. Water closets, whether operated by flush tank, flushometer tank, or flushometer valve, shall comply with ASME A112.19.2M 19.2 or ANSI IAPMO Z124.4 and shall be the lowconsumption type having an average consumption of not more than 1.6 gallons per flush when tested in accordance with ASME A112.19.6 19.2 or IAPMO Z124.4. EXCEPTION: Blow-out water closets and clinical sinks. Seats for water closets shall be of smooth, non-absorbent materials, be properly sized to fit the water closet bowl, and comply with ANSI IAPMO Z124.5. EXCEPTION: Water closets in single dwelling units are not required to comply with ANSI IAPMO Z124.5. Water closets in hotels, motels, dormitories, boarding houses, and similar occupancies shall be the elongated type complying with ASME A112.19.2 or ANSI IAPMO Z124.4, and ASME A112.19.6 and with open-front seats complying with ANSI IAPMO Z124.5. EXCEPTIONS: (1) Closed-front seats shall be permitted in hotel and motel guest rooms. (2) Closed-front seats that are provided with automatic seat cover protection. a. b. c. d. Water-fed vitreous china urinals shall comply with ASME A112.19.2. Non-water vitreous china urinals shall comply with ASME A112.19.19. Water-fed and non-water plastic urinals shall comply with ANSI IAPMO Z124.9. Non-water urinals shall have a liquid trap seal as required by Section 5.3.2, ASME A112.19.19, and ANSI IAPMO Z124.9. e. Water-fed urinals with a concealed trap seal and/or an outlet strainer shall be supplied by an automatic flushing device. Water-fed urinals shall be the low-consumption type having an average water consumption of not more than 1.0 gallons per flush when tested in accordance with ASME A112.9.6 19.2.
7.4.5
7.4.6
7.5.1
7.5.2
7.6.1
a. Lavatories shall comply with the following standards: 1. Ceramic, non-vitreous; ASME A112.19.9M 19.2 2. Enameled cast-iron; ASME A112.19.1M 19.1 3. Enameled steel; ASME A112.19.4M 19.1 4. Plastic; ANSI IAPMO Z124.3 5. Stainless steel; ASME A112.19.3M 19.3 6. Vitreous china; ASME A112.19.2M 19.2 Vitreous china bidets shall comply with ASME A112.19.2M 19.2. Bidet faucets shall comply with ASME A112.18.1/CSA B125.1. a. Bathtubs shall comply with the following standards: 1. Plastic, cultured, and other synthetic products or finishes; ANSI IAPMO Z124.1 1.2 2. Enameled cast-iron; ASME A112.19.1 3. Enameled steel; ASME A112.19.4 19.1 4. Bathtubs with pressure sealed doors; ASME A112.19.15 Unless equipped with an atmospheric backflow preventer in accordance with ASSE 1001 or ASME A112.18.7 or ASSE 1001, the bathtub filler shall be equipped with an air gap between the end of the over-rim tub filler spout and the overflow rim of the tub that complies with Section 10.5. Whirlpool bathtubs shall comply with ASME A112.19.7M 19.7.
7.7.1 7.8.1
7.8.4
7.9.2
7.10.1 Plastic shower receptors and stalls shall comply with ANSI IAPMO Z124.2 1.2. 7.11.1 a. Sinks shall comply with the following standards: 1. Enameled cast-iron; ASME A112.19.1M 19.1 2. Enameled steel; ASME A112.19.4M 19.1 3. Stainless steel; ASME A112.19.3M 19.3 4. Plastic; ANSI IAPMO Z124.6. 7.15.1 Domestic dishwashing machines shall comply with UL 749 and either AHAM DW-2PR or ASSE 1006. Commercial dishwashing machines shall comply with UL 921 and ASSE 1004. The water supply to dishwashing machines shall be protected from back-siphonage by an integral air gap or other internal means.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 111
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___11-19-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.4.4 Bowl Height
The height of water closet bowls shall be a minimum of 13-1/2 inches 13-1/2 to 17 inches from the finished floor to the top of the rim. EXCEPTIONS EXCEPTION: (1) Bowls intended for children's use (5 years and younger) are permitted to be 9-1/2" to 10-1/2" high to the rim and juvenile use (6-12 years) are permitted to be 10-1/2" to 13-1/2" to the rim. (2) The height of bowls intended specifically for children's accessible use (12 years and younger) shall be such that the top of the rim is 11" to 17" above the floor and comply with Section 7.2. (3) The height of bowls intended for adult accessible use (13 years and older) shall be such that the top of the seat is 17" to 19" above the floor and comply with Section 7.2.
7.4.9 Water Closets for Accessible Use (a) Water closets for accessible use shall comply with Section 7.2. (b) For adult use (13 years and older): 1. The height of water closet bowls shall be such that the top of the seat is 17 to 19 inches above the finished floor.
2. Wheelchair accessible water closets shall be located so that their centerlines are 16 to 18 inches from a side wall or partition with a grab bar. 3. Ambulatory accessible water closets shall be located so that their centerlines are 17 to 19 inches from a side wall or partition with a grab bar. (c) For children's use, the toilet seat height and centerline to a side wall or partition with a grab bar shall be in accordance with Table 7.4.9.
Table 7.4.9 DIMENSIONS FOR ACCESSIBLE WATER CLOSETS FOR CHILDREN Dimension Ages 3 and 4 Years 5 thru 8 Years 9 thru 12 Years Seat Height above the Finished Floor 11" to 12" 12" to 15" 15" to 17" Centerline to a Side Wall (1) 12" 12" to 15" 15" to 18" NOTES FOR TABLE 7.4.9 (1) Clearance to a side wall or partition with a grab bar.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 112
Contact Information:
Person Submitting Change 2 __John Heine_____________________ Date 3 1/7/13 Jurisdiction/Company/ NJ PHCC Code Committee, (Chairman) / PO Box 2067 Mailing Address ______________________________________________________________________
Princeton, NJ 08543 City/State/Zip ________________________________________________________________________
Phone ___609-987-0500_______________ Fax _ 609-987-0511 E-mail Director@nj-phcc.org IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows __X___ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 113
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-24-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 114
Person Submitting Change 2 __John Heine_____________________ Date 3 1/7/13 Jurisdiction/Company/ NJ PHCC Code Committee, (Chairman) / PO Box 2067 Mailing Address ______________________________________________________________________
Princeton, NJ 08543 City/State/Zip ________________________________________________________________________
Phone ___609-987-0500_______________ Fax _ 609-987-0511 E-mail Director@nj-phcc.org IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 115
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___3-04-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.7.1 Compliance
7.7 BIDETS
Vitreous china bidets shall comply with ASME A112.19.2/CSA B45.1. Non-vitreous ceramic bidets shall comply with ASME A112.19.9M/CSA B45.1. Bidet faucets shall comply with ASME A112.18.1/CSA B125.1. Bidet sprays shall comply with ASME A112.4.2.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 116
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___11-07-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.7 Bidets
7.7.4 Control of Mixed Water Temperature The control of mixed water temperature from for bidets shall comply with Section 10.15.6.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 117
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ____1-24-2013_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 118
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-26-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
a. b.
c. d. e.
(No change) Showers with multiple shower heads shall have a 2" waste outlet pipe size for up to 10 5 gpm, a 3" waste outlet pipe size for up to 20 10 gpm, or a 4" waste outlet pipe size for up to 50 15 gpm. Multiple waste outlets shall be provided where necessary to handle the total water flow from the shower heads. EXCEPTION: Bathtubs Combination bath/showers with multiple two 2.5 gpm shower heads. (No change) (No change) (No change)
COMMENT: Increased waste outlet pipe sizes are not required for combination bath/showers with multiple shower heads because of the depth of bathtubs compared to possible overflow from shower pans.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 119
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 121
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-15-2013______ Mailing Address 180 S. Washington Street, P.O. Box 6808 City/State/Zip Falls Church, VA 22046 Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.12.1 Compliance Refrigerated drinking fountains and water coolers shall comply with ARI 1010 and UL 399. 7.12.2 Prohibited Locations Drinking fountains and water coolers shall not be located in public toilet rooms. EXCEPTION: Convertible lavatory faucets and fixture fittings that provide a discharge stream similar to a drinking fountain shall be permitted in bathrooms in dwelling units. 7.12.3 Outdoor Drinking Fountains Freeze-resistant drinking fountains shall be the sanitary type. Weep hole drains that form a cross connection between ground water and the potable water supply shall not be permitted. 7.12.1 Compliance a. Drinking water facilities shall comply with the lead limits of NSF 61. b. Drinking water facilities for accessible use shall comply with Section 7.2. c. Drinking fountains shall comply with ASME A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4, or ASME A112.19.9. d. Drinking water coolers with self-contained refrigeration units shall comply with UL 399 and ASHRAE Standard 18. e. Water bottle filling stations shall comply with applicable standards. Stations with self-contained refrigeration units for chilled water shall comply with UL 399 and ASHRAE Standard 18. 7.12.2 Prohibited Locations Drinking water facilities shall not be located in public toilet rooms. EXCEPTION: Convertible lavatory faucets that provide a discharge stream similar to a drinking fountain shall only be permitted in bathrooms in dwelling units.
7.12.3 Minimum Number of Required Facilities a. The minimum number of drinking water facilities shall be in accordance with Table 7.21.1. EXCEPTIONS: (1) No fewer than two drinking water facilities shall be provided, one for accessible wheelchair use and one for standing persons. (2) Where a drinking water facility provides service for two people simultaneously, one for accessible wheelchair use and one for standing persons, it may be counted as two drinking water facilities. b. Water bottle filling stations shall be permitted to substitute for up to 50% of the required drinking water facilities. c. Bottled water dispensers shall not be permitted to substitute for required drinking water facilities. 7.12.4 Outdoor Drinking Fountains Freeze-resistant drinking fountains shall be the sanitary type. Weep hole drains that form a cross connection between ground water and the potable water supply shall not be permitted. Section 1.2 Definition of Terms Water Bottle Filling Station: A drinking water supply fixture that is connected to the domestic water supply and drain piping and provides for individuals to fill personal-use water bottles. Stations can be recessed or wall-mounted and can include filtration units, self-contained refrigeration units, and drinking fountains. Table 3.1.3 - Part V V-4: Drinking Fountains and Water Coolers, Self-Contained, Mechanically Refrigerated: Drinking-Water Coolers ARI 1010-2002, UL 399 Edition 7 - 2008 UL 399 Ed.7 - 2008 (2012)
V-15: Reserved Methods of Testing for Rating Drinking-Water Coolers with Self-Contained Mechanical Refrigeration..ASHRAE Standard 18 - 2008.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 122
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-11-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Table 3.1.3 - Part VII VII-20: Electric Clothes Washing Machines and Extractors VII-21: Electric Commercial Clothes-Washing Equipment UL 2157 Edition 2 - 1997 (2010) UL 1206 Edition 4 - 2003
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
Section 7.13.1
page 2 of 2
1-11-2013
13 - 123
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-13-2013______ Mailing Address 180 S. Washington Street, P.O. Box 6808 City/State/Zip Falls Church, VA 22046 Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.15.1 Compliance
a. Domestic dishwashing machines shall comply with UL 749 and either AHAM DW-2PR or ASSE 1006 or AHAM DW-1. Commercial dishwashing machines shall comply with UL 921 and ASSE 1004. The water supply to domestic dishwashing machines shall be protected from back-siphonage by an internal air gap, vacuum breaker, or other internal means. b. Commercial dishwashing machines shall comply with UL 921 or NSF 3. Backflow prevention shall comply with ASSE 1004. 7.15.2 Residential Sink and Dishwasher (no change) 7.15.3 Residential Sink, Dishwasher, and Food-Waste-Grinder (no change) 7.15.4 Commercial Dishwashing Machine (no change) Table 3.1.3 - Part VII VII-2: Dishwashing Machines, Commercial UL 921 Edition 6-2006 (2012) NSF 3 - 2010 ASSE 1004 - 2008
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 123a
Contact Information:
Person Submitting Change 2 ___Dave Bishop___________________ Date 3 _1/31/13____________ Jurisdiction/Company/ Mailing Address _________1001 Parsippany Blvd________________________________ City/State/Zip _______Parsippany New Jersey 07054____________________ Phone __973-229-4735____ Fax _973-263-1488_____ E-mail ____dbishop@parsippany.net___ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 124
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-15-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.16.1 Compliance
Floor and trench drains shall comply with ASME A112.6.3 or, if stainless steel, ASME A112.3.1.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 125
Contact Information:
Person Submitting Change 2 Dan OGorman Date 3 January 27, 2013 Jurisdiction/Company/ Mailing Address 10 Albany Street City/State/Zip Edison, New Jersey 08837 Phone 732-661-1935 Fax 732-661-9326 E-mail Danogorman@verizon.net
IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 126
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.16.4 Required Locations for Floor Drains a. Floor drains shall be installed in the following areas: 1. Toilet rooms containing either two or more water closets or wall hung urinals or a combination of one or more water closets and one or more wall hung urinals, except in a dwelling unit. 2. Commercial kitchens. 3. Common laundry rooms in commercial buildings and buildings having more than two dwelling units.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 127
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-18-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.21.4.(4)
(4) In mercantile occupancies with a net occupiable floor area of 1500 square feet or less that is accessible to customers, one toilet facility designed for use by only one person at a time shall satisfy the requirements for serving customers and employees of both sexes. person at a time, shall be permitted for use by both sexes. Comment: Net occupiable floor area in mercantile occupancies does not include display cases and space occupied by merchandise.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 128
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___7-27-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
b. Drinking Water Facilities: A kitchen or bar sink shall be considered as meeting the requirements for drinking water facilities for employees who have access to the facilities.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 129
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ____1-18-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 130
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-19-2013______ Mailing Address 180 S. Washington Street, P.O. Box 6808 City/State/Zip Falls Church, VA 22046 Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: 7.21.7 Facilities in Mercantile and Business Occupancies Serving Customers
a. Within a single establishment, facilities for customers and employees shall be permitted to be met with a single set of restrooms accessible to both groups. The required number of fixtures shall be based on the total number of customers and employees. b. Fixtures for customer and employee use shall be permitted to be met by providing centrally located facilities accessible to several multiple establishments. The maximum distance of entry from each of the several establishments to these facilities shall not exceed 500 feet from the entrance of any establishment served. c. In establishments with a floor area of 150 square feet or less, the requirement to provide facilities for employees shall be permitted to be met by providing centrally located facilities accessible to several establishments. The maximum distance of entry from each of the several establishments to these facilities shall not exceed 300 feet. d. c. Drinking water facilities are not shall not be required for customers where normal occupancy is short term. e. d. For establishments less than 1500 square feet in total floor area, one water closet and one lavatory in a restroom shall be permitted to provide the requirements for serving both customers and employees.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 131
Contact Information:
Person Submitting Change 2 __John Heine_____________________ Date 3 1/7/13 Jurisdiction/Company/ NJ PHCC Code Committee, (Chairman) / PO Box 2067 Mailing Address ______________________________________________________________________
Princeton, NJ 08543 City/State/Zip ________________________________________________________________________
Phone ___609-987-0500_______________ Fax _ 609-987-0511 E-mail Director@nj-phcc.org IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 132
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-18-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
a. Restaurants and other food service establishments with an a seated occupant load exceeding 100 customers shall be provided with separate toilet facilities for employees and customers. Customer and employee toilet facilities may be combined for seated customer loads of 100 or less. For employees of 15 or less, one employee toilet facility, designed for use by no more than one person at a time, shall be permitted to be used by both sexes. b. Where food service establishments and food courts are open to public areas in malls and transportation terminals, toilet facilities that serve both customers and employees may be centrally located and serve multiple establishments. The maximum distance of entry to central toilet facilities shall be 500 feet from any establishment or food court served. b. c. Drinking water facilities are not shall not be required in restaurants or other food service establishments if drinking water service is provided or available on request.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 133
Contact Information:
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 ___1-18-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_ ___________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
7.21.9 Family and Assisted-Use Toilet Rooms a. Accessible family or assisted-use toilet rooms containing one water closet and one lavatory shall be provided as required by the applicable building code. b. In assembly and mercantile occupancies, the plumbing fixtures within family and assisted-use toilet rooms may be counted as part of the minimum required fixtures for males or for females.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 134
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-18-2012______ Mailing Address 180 S. Washington Street, P.O. Box 6808 City/State/Zip Falls Church, VA 22046 Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows
__X_ Add new subsection to read as follows _____ Delete subsection without substitution
Code Section:
a. In Table 7.21.1, where the number of persons of each sex is less than 100% of a particular group, the number of fixtures required for that group may be reduced by the fraction of the persons in that group. The fraction of the required fixtures shall be rounded up to the next whole number. b. Where a facility includes two or more different occupancy classifications with access to the same installed plumbing fixtures, the fraction of the required fixtures for each classification may be added and the total combined fraction of the required fixtures shall be rounded up to the next whole number. COMMENTS (for the NSPC Illustrated) If a group of 101 - 200 persons of each sex requires 2 additional fixtures and the group only consists of 35 persons, then only 35/100 = 0.35 x 2 fixtures = 0.70 additional fixtures required, which can be rounded up to 1 additional fixture for each sex. If a facility includes two different occupancy classifications with access to the same installed fixtures, if one group requires 0.6 additional fixture and the other group requires 0.2 additional fixture, the total of 0.8 additional fixture for the two occupancy classifications can be rounded up to 1 additional fixture for each sex.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 135
13 - 136
Contact Information:
Person Submitting Change 2 _John H. Heine, L.M.P___________________ Date 3 1/7/13 Jurisdiction/Company/ Mailing Address Heine Plumbing and Heating/ 270 Sparta Ave., Suite 104, PMB 139______ City/State/Zip _Sparta, NJ 07871 Phone 973-383-0392 _ Fax 973-383-0536_ E-mail john@heineplumbing.com ______________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows ___ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 137
Contact Information:
Person Submitting Change 2 _John H. Heine, L.M.P.___________________ Date 3 1/7/13 Jurisdiction/Company/ Mailing Address Heine Plumbing and Heating/ 270 Sparta Ave., Suite 104, PMB 139______ City/State/Zip _Sparta, NJ 07871 Phone 973-383-0392 _ Fax 973-383-0536_ E-mail john@heineplumbing.com IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows ___Delete subsection without substitution
1. Ultra-violet tubes shall be jacketed so that a temperature of 105 degrees Fahrenheit is maintained. 2. The jacket on the ultra-violet light tubes shall be quartz or high-silica glass with similar optical characteristics. 3. The ultra-violet light disinfection unit shall be designed and installed to permit frequent cleaning of the water contact surface of the ultra-violet light tube jacket. 4. The maximum water depth in the disinfection chamber, measured from the ultra-violet light tube surface to the outer walls of the chamber, shall not exceed three inches. 5. Ultra-violet radiation at a level of 2,537 Angstrom shall be applied at all points throughout the disinfection chamber at a minimum rate of 16,000 microwatt seconds per square centimeter. 6. An automatic flow control valve, accurate within the expected pressure range, shall be installed to restrict flow to the maximum design flow of the ultra-violet disinfection unit. An accurately calibrated ultra-violet light intensity meter, filtered to confine its sensitivity to the range of disinfection spectrum, shall be installed in the wall of the disinfection chamber at the point of greatest water depth from the light transmitting source. 8. A flow diversion valve or automatic shut-off valve controlled by the ultra-violet light intensity meter shall be installed so as to permit water flow into the water system only when the minimum radiation level specified at (c)5 is applied. When power is not being supplied to the unit, the valve shall be in a closed (fail-safe) position to prevent the flow of water into the water system. 9. The ultra-violet light disinfection unit shall be installed in a manner such that it cannot be bypassed. 10. The ultra-violet light disinfection unit shall be installed downstream of any other water conditioning/filtering equipment.
contaminated public and nonpublic water systems as well as to ensure all disinfection equipment is properly
protected and can be properly maintained to prevent significant health risks from drinking contaminated water.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 138
Person Submitting Change 2 Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145___________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail _____________________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Revise 7.24 e. to read as follows: 7.24 Plumbed Emergency Eyewash and Shower Equipment e. The temperature of the flushing fluid shall be from 65F to 95F in accordance with ASSE 1071, unless the facility designer has indicated that other specific temperatures are required to provide protection for a particular hazard. Basis/Reason for Change: ASSE 1071 is ANSI Approved standard developed under the consensus process and establishes performance requirements for plumbed emergency equipment. The temperature requirement for flushing fluid is consistent with ASSE 1071. NOTE: ASSE has submitted a companion change to this proposal that affects Table 3.1.3 Part V Item 24. Vote: ___ Accept ___ Accept in Part ___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 139
Contact Information:
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 __1-19-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_ ___________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
Add the following:
7.24.f. Temperature actuated mixing valves for plumbed emergency equipment shall comply with ASSE 1071.
Add to Table 3.1.3 - Part VIII: Temperature Actuated Mixing Valves for Plumbed Emergency Equipment: ASSE 1071 - 2012
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 140
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-24-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 140a
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-24-2013______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
TABLE 9.1.12 SIZE OF DRAINS OR WASTE PIPES RECEIVING RELIEF VALVE DISCHARGE Relief Valve Discharge Pipe Size (1) Minimum Drain or Indirect Waste Pipe Size (ID Area sq. in.) (ID Area sq. in.) 1/2 (0.2 sq. in.) 3/4 (0.4 sq. in.) 1 (0.8 sq. in.) 1 1/4 (1.2 sq. in.) 1 1/2 (1.8 sq. in.) 2 (3.1 sq. in.) 2 1/2 (4.9 sq. in.) 3 (7.1 sq. in.) 4 (12.6 sq. in.) 1 1/4 (1.2 sq. in.) 2 (3.1 sq. in.) 3 (7.1 sq. in.) 3 (7.1 sq. in.) 4 (12.6 sq. in.) 4 (12.6 sq. in.) 5 (19.6 sq. in.) 6 (28.3 sq. in.) 8 (50.3 sq. in.) 12 (113.1 sq. in.) 15 (176.7 sq. in.) NOTES FOR TABLE 9.1.12 (1) Where 2 or more discharge pipes discharge into the same indirect waste pipe, Add their ID areas, multiply by five, and select a drain or indirect waste pipe size That has not less than that total area.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 141
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-24-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
9.3.1 General
c. Plumbing fixtures that are used for domestic or culinary purposes shall not be used as receptors for indirect wastes except as follows: 1. In a dwelling unit, a kitchen sink trap or food waste grinder, shall be permitted to receive the discharge from a dishwasher. 2. In a dwelling unit, a laundry sink, provided that an air gap is maintained for any potable clear-water waste, shall be an acceptable receptor for: a) Air conditioning condensate. b) Automatic clothes washer. c) Water treatment unit. d) Water heater relief discharge. e) Condensing furnace condensate. 3. A service sink or mop basin shall be an acceptable receptor for air conditioning and condensing furnace condensate and any infrequent potable clear-water waste if the required air gap is provided for the potable clear water waste. See Figures 7.15.2, 7.15.3, 7.15.4, 9.1.5-A, 9.1.5-B, and 9.1.10.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 142
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 143
Contact Information:
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 ___1-18-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_ ___________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows
__X_ Add new subsection to read as follows _____ Delete subsection without substitution
Code Section:
a. Corrosive liquids, spent acids, or other harmful chemicals that may damage a drain, sewer, soil or waste pipe, create noxious or toxic fumes, or interfere with sewage treatment processes shall not be discharged into the plumbing system without being thoroughly neutralized or treated by passing through a properly constructed and approved neutralizing device. Such devices shall be provided automatically with a sufficient supply of neutralizing medium, so as to make its contents non-injurious before discharge into the drainage system. The nature of the corrosive or harmful waste and the proposed method of treatment shall be submitted to and approved by the Authority Having Jurisdiction prior to installation. b. Vent piping for corrosive waste drainage piping shall be separate from vent piping for sanitary waste and drainage piping and shall terminate outdoors in accordance with Section 12.4.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 144
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___4-13-2012______ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 145
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __8-05-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 146
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-25-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
10.5.3
10.5.3 Required Backflow Prevention Devices The following requirements shall apply: A. Backsiphonage, Non-Continuous Pressure, Non-Health Hazard 1. Atmospheric vacuum breaker - ASSE 1001 (AVB) 2. Hose connection vacuum breaker - ASSE 1011 3. Any backflow protection device approved for protection against backsiphonage with non-continuous or continuous pressure and a non-health hazard or health hazard. B. Backsiphonage, Continuous Pressure, Non-Health-Health Hazard 1. Pressure vacuum breaker - ASSE 1020 (PVB) 2. Spill-resistant vacuum breaker - ASSE 1056 (SVB) 3. Backflow preventer with intermediate atmospheric port - ASSE 1012 4. Double check valve assembly ASSE 1015 (DC and DCVA) 5. Any backflow protection device approved for protection against backsiphonage with continuous pressure and a non-health hazard or health hazard. C. Backsiphonage, Non-Continuous Pressure, Health Hazard 1. Atmospheric vacuum breaker - ASSE 1001 (AVB) 2. Hose connection backflow preventer - ASSE 1052 3. Any backflow protection device approved for protection against backsiphonage with non-continuous or continuous pressure and a health hazard. D. Backsiphonage, Continuous Pressure, Health Hazard 1. Pressure vacuum breaker - ASSE 1020 (PVB) 2. Spill-resistant vacuum breaker - ASSE 1056 (SVB) 3. Reduced pressure backflow preventer assembly - ASSE 1013 (RP, RPZ, and RPBA) 4. Any backflow protection device approved for protection against backsiphonage with continuous pressure and a health hazard.
E. Back Pressure, Non-Health Hazard 1. Dual check backflow preventer - ASSE -1024 (DuCh) 2. Double check valve assembly - ASSE 1015 (DC)(DCVA) 3. Reduced pressure backflow preventer assembly - ASSE 1013 (RP)(RPZ)(RPBA) F. Back Pressure, Health Hazard 1. Reduced pressure backflow preventer assembly - ASSE 1013 (RP)(RPZ)(RPBA) 10.5.3 Backflow Prevention Devices, Assemblies, and Devices that Include Backflow Protection A. Back Siphonage Only, Non-Continuous Water Pressure, Non-Health Hazards 1. Hose connection vacuum breaker - ASSE 1011 2. Backflow prevention devices for hand-held showers - ASSE 1014 3. Wall hydrant with backflow protection and freeze resistance - ASSE 1019 4. Backflow preventer for beverage dispensing equipment - ASSE 1022 5. Laboratory faucet backflow preventer - ASSE 1035 6. Hose connection backflow preventer - ASSE 1052 7. Dual check backflow preventer wall hydrant - freeze resistant - ASSE 1053 8. Freeze resistant sanitary yard hydrants with backflow protection - ASSE 1057 B. Back Siphonage Only, Non-Continuous Water Pressure, Health and Non-Health Hazards 1. Air gaps in plumbing systems - ASME A112.1.2 2. Air gap fittings for use in plumbing fixtures, appliances, and appurtenances - ASME A112.1.3 3. Atmospheric type vacuum breaker - ASSE 1001 C. Back Siphonage Only, Continuous Water Pressure, Health or Non-Health Hazards 1. Pressure vacuum breaker assembly - ASSE 1020 2. Spill resistant vacuum breaker - ASSE 1056 (SVB) D. Back Siphonage and Back Pressure, Continuous Water Pressure, Non-Health Hazards 1. Backflow preventer with intermediate atmospheric vent - ASSE 1012 2. Double check backflow prevention assembly - ASSE 1015 (DC) 3. Double check fire protection backflow prevention assembly - ASSE 1015 (DCF) 4. Dual check backflow preventer - ASSE 1024 5. Double check detector fire protection backflow prevention assembly - ASSE 1048 (DCDA) 6. Double check detector fire protection backflow prevention assembly - type II - ASSE 1048 (DCDA-II) E. Back Siphonage and Back Pressure, Continuous Water Pressure, Health and Non-Health Hazards 1. Reduced pressure principle backflow preventer - ASSE 1013 (RP) 2. Reduced pressure principle fire protection backflow preventer - ASSE 1013 (RPF) 3. Reduced pressure detector fire protection backflow prevention assembly - ASSE 1047 (RPDA) 4. Reduced pressure detector fire protection backflow prevention assembly - type II ASSE 1047 (RPDA-II)
F. Restrictions 1. Backflow prevention devices shall be applied within the ratings of their standard and their manufacturer's instructions. 2. Backflow prevention devices with atmospheric vents shall not be located where discharge from their vent will cause water damage. 3. The following devices must not be subjected to more than 10 feet of water back pressure from elevated hoses: a. ASSE 1011 hose connection vacuum breakers b. ASSE 1019 wall hydrants with backflow protection and freeze resistance c. ASSE 1052 hose connection backflow preventers d. ASSE 1053 dual check backflow preventer wall hydrant - freeze resistant e. ASSE 1057 freeze resistant sanitary yard hydrants with backflow prevention 4. ASSE 1035 laboratory faucet backflow preventers must not be subjected to more than 6 inches of water back pressure from elevated discharge hoses.
2. To add the backflow prevention devices covered by ASME A112.1.2, ASME A112.1.3, ASSE 1014, ASSE 1019, ASSE 1022, ASSE 1035, ASSE 1047, ASSE 1048, ASSE 1053, and ASSE 1057. 3. To indicate that ASSE 1013 and ASSE 1015 now each include a fire protection model. 4. To indicate that ASSE 1047 and ASSE 1048 now each include two variations of the detector portion.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 147
Contact Information:
Person Submitting Change 2 _Steve Silber, International President representing ASSE Code Committee_ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail ____________________
IMPORTANT: Please review the attached instruction sheet regarding proposed code changes. Check All That Apply: _____ Change subsection to read as follows _____ Amend section with this editorial change _____ Delete subsection and substitute as follows
_X__ Add new subsection to read as follows _____ Delete subsection without substitution
Code Section: ___________________________ Add ASSE 1014 to Section 10.5.3 under category A & C to read Backflow Prevention Devices for Hand-Held Showers ASSE 1014
Basis/Reason for Change: ASSE 1014 is referenced in Table 3.1.3, Part IX, Item 20 and should be included in the narrative of the code. Vote: ___ Accept ___ Accept in Part ___ Defeated ___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 148
Contact Information:
Person Submitting Change 2 _Steve Silber, International President representing ASSE Code Committee_ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_____ City/State/Zip __Westlake, OH 44145_________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail ___________________
IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: ___________________________ Add ASSE 1019 to Section 10.5.3 under category A & C to read Wall Hydrant with Backflow Protection and Freeze Resistance ASSE 1019 Basis/Reason for Change: ASSE 1019 is referenced in Table 3.1.3, Part VIII, Item 19 and should be included in the narrative of the code.
Vote:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 149
Contact Information:
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee__ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145_________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail _______________________
IMPORTANT: Please review the attached instruction sheet regarding proposed code changes. Check All That Apply: _____ Change subsection to read as follows _X__ Add new subsection to read as follows _____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: ___________________________ Add ASSE 1035 to Section 10.5.3 under category A & C to read Laboratory Faucet Backflow Preventers ASSE 1035
Basis/Reason for Change: ASSE 1035 is referenced in Table 3.1.3, Part VI, Item 6 and Table 3.1.3, Part IX, Item 11 and should be included in the narrative of the code.
Vote:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 150
Contact Information:
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee___ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145_________________________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail _____________________________
IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __Section 10.5.3 Category A & C_________________________ Add ASSE 1053 to Section 10.5.3 under category A & C to read Dual Check Backflow Preventer Wall Hydrants Freeze Resistant Type ASSE 1053 Basis/Reason for Change: ASSE 1053 is referenced in Table 3.1.3, Part VIII, Item 21 and should be included in the narrative of the code.
Vote:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 151
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee__ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145__________________________ Phone _440-835-3040__ Fax _440-835-3488__ E-mail ____________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __ Section 10.5.3 Category A & C_____________ Add ASSE 1057 to Section 10.5.3 under category A & C to read Freeze Resistant Sanitary Yard Hydrant with Backflow Protection ASSE 1057 Basis/Reason for Change: ASSE 1057 is a product standard for performance requirements for Freeze Resistant Sanitary Yard Hydrants with Backflow Protection that has been accepted throughout the industry. NOTE: ASSE has submitted a companion change to this proposal that affects Table 3.1.3. Part VII, Item 24.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 152
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee_ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145__________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail ___________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__X_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __Section 10.5.3 d. and Table 3.1.3 Part XI, Item TBD_____________ In Section 10.5.3 d., the reference to ASSE 5030 is incorrect and should be replaced with ASSE/IAPMO/ANSI 5130 Add to Table 3.1.3, Part XI, Item TBD with title Backflow Prevention Assembly Repairers and designation of ASSE/IAPMO/ANSI 5130-2009 Basis/Reason for Change: ASSE 5030 is incorrect as a reference to ASSE certification for repair. The correct reference is 5130. Once corrected as per above, the ASSE 5130 Certification reference will be included correctly in the narrative of the code and should be included in the Reference Table. Vote: ___ Accept ___ Accept in Part ___ Defeated ___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 153
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee__ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145___________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail ______________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes. Check All That Apply: _____ Amend section with this editorial change
__X_ Change subsection to read as follows _____ Delete subsection and substitute as follows _____ Add new subsection to read as follows _____ Delete subsection without substitution
Code Section: __Section 10.5.5 a.___________________________________ Revise 10.5.5 a. to read as follows: 10.5.5 Installation of Backflow Preventers a. Devices of All Types: All backflow prevention devices shall be accessible for testing (if testable), maintenance, repair and replacement. Clearances shall be as recommended by the manufacturer. Backflow prevention devices having atmospheric vents shall not be installed in pits, vaults, or similar potentially submerged locations. Vacuum breakers and other devices with vents shall not be located with fume hoods. Where required by the Authority Having Jurisdiction, backflow prevention devices and assemblies shall be installed in an enclosure in accordance with ASSE 1060. Basis/Reason for Change: ASSE 1060 is referenced in Table 3.1.3, Part IX, Item 19 and should be included in the narrative of the code. Vote: ___ Accept ___ Accept in Part ___ Defeated ___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 154
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___8-05-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 155
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-15-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
c. d. Where tests indicate that the device is not functioning properly, it shall be serviced or repaired in accordance with the manufacturers instructions and be retested. d. e. Testing and repair of devices shall be performed by certified individuals approved by an agency acceptable to the Authority Having Jurisdiction. Certification for testing shall be in accordance with ASSE 5000 or equivalent Certification for repair shall be in accordance with ASSE 5030 or equivalent. Certification shall include not less than 32 hours of combined classroom and practice training and successful completion of a written and practical examination. f. Certification for testing and repair shall be in accordance with the appropriate sections of ASSE 5000 Cross-Connection Control Professional Qualification Standard. Testing shall be in accordance with ASSE 5110 Backflow Prevention Assembly Testers. Repair shall be in accordance with ASSE 5130 Backflow Prevention Assembly Repairers. e. g. Copies of test reports for the initial installation shall be sent to the Authority Having Jurisdiction and the water supplier. Copies of annual test reports shall be sent to the water supplier. f. h. Where a continuous water supply is critical and cannot be interrupted for the periodic testing of a backflow prevention device, multiple backflow prevention devices or other means of maintaining a continuous supply shall be provided that does not create a potential cross connection. Table 3.1.3 - Part XI XI-11: Field Test Procedures for Backflow Prevention Devices Reserved ASSE 5010-2009
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 156
Person Submitting Change 2 __Steve Silber, International President representing ASSE Code Committee_ Date 3 _1/29/2013______ Jurisdiction/Company/ Mailing Address __ASSE International, 901 Canterbury Road_______ City/State/Zip __Westlake, OH 44145_________________________________________ Phone _440-835-3040__ Fax _440-835-3488___ E-mail _____________________________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
__X_ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: __Section 10.5.6 d. and Table 3.1.3 Part XI, Item TBD_____________ In Section 10.5.6 d., the reference to ASSE 5030 is incorrect and should be replaced with ASSE/IAPMO/ANSI 5130 Add to Table 3.1.3, Part XI, Item TBD with title Backflow Prevention Assembly Repairers and designation of ASSE/IAPMO/ANSI 5130-2009 Basis/Reason for Change: ASSE 5030 is incorrect as a reference to ASSE certification for repair. The correct reference is 5130. Once corrected as per above, the ASSE 5130 Certification reference will be included correctly in the narrative of the code and should be included in the Reference Table. Vote: ___ Accept ___ Accept in Part ___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013
13 - 157
Contact Information:
Person Submitting Change 2
Nick Azmo
Date 3 1/25/2013
Jurisdiction/Company/ Mailing Address: 447 So. Washington Ave. City/State/Zip: Piscataway, NJ 08854 Phone: (732) 424-9700 Fax: (732) 424-9345 E-mail: azmomechanical@hotmail.com
IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
Basis/Reason for Change: These are typographical errors. Devices are not testable, Standard 5000 refers to the overall backflow prevention and crossconnection control standards, standard 5110 specifically refers to the testing standard and standard 5130 specifically refers to the repair standard. Vote: ___ Accept
___ Accept in Part ___ Defeated ___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2015 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, January 31, 2013
13 - 158
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __8-05-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 159
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___6-25-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
10.5.8
10.5.8 Connections to Carbonated Beverage Dispensers a. The water supply to a carbonated beverage dispenser shall be protected against backflow with an integral backflow preventer conforming to ASSE 1022 or an air gap. Carbonated beverage dispensers and carbonated beverage systems without an integral backflow preventer conforming to ASSE 1022 or an air gap shall have the water supply protected by a double check valve with atmospheric vent conforming to ASSE 1022. b. When an ASSE 1022 device must be installed in the water supply piping external to the carbonated beverage dispenser, the piping from the device to the beverage dispenser shall be acid resistant and not copper. 10.5.8 Protection from Equipment in Food Establishments a. Food preparation and service equipment in food establishments that is connected to potable water piping or drained to waste piping shall be protected from backflow to the potable water system and from contamination of equipment, food, and utensils. b. Fixtures that require an air gap in their water supply above the flood level rim of the fixture include, but are not limited to, sink faucets, dipper wells, pot fillers, and spray arms in dish areas. c. Equipment that requires an air gapped waste line includes, but is not limited to, walk-in coolers, food prep sinks, dipper wells, ice machines, ice bins, steam tables, bains-marie, Chinese ranges (woks), combination steamer/ovens, rethermalizers, steamers, kettles, non-evaporating reach-in coolers, soda gun holsters, and water treatment systems.
d. Equipment that requires a pressure vacuum breaker or spill resistant vacuum breaker in its water supply includes, but is not limited to, Chinese ranges (woks), rethermalizers, hoses with a pressure nozzle, and pasta cookers. e. Equipment that requires an atmospheric vacuum breaker in its water supply includes, but is not limited to, garbage disposals, automatic dishwashers, dish machine automatic detergent feeders, detergent feeders for 3-compartment sinks, wall-mounted chemical feeders, garbage can washers, mop sinks, steam tables with submerged inlets, and dish troughs with submerged inlets. f. Equipment that requires a vented double check valve or equivalent in its water supply includes, but is not limited to, untreated boilers such as expresso machines, the oven in combination steamer/ovens, carbonated beverage machines, beverage carbonators, non-carbonated beverage machines, coffee machines, iced tea machines, hot chocolate machines, cappuccino machines, instant hot water dispensers, slushy machines, and any other beverage equipment. g. The water supply to a post-mix carbonated beverage dispenser shall be protected against backflow with an integral backflow preventer conforming to ASSE 1022 or an air gap. 1. Post-mix carbonated beverage dispensers and carbonated beverage systems with an integral dual check backflow preventer without an atmospheric vent (ASSE 1032) or without an integral backflow preventer conforming to ASSE 1022 or without an integral air gap shall have the water supply connection to the dispenser protected by a double check valve with atmospheric vent port conforming to ASSE 1022. 2. When an ASSE 1022 device must be installed in the water supply piping external to the carbonated beverage dispenser, the piping from the device to the beverage dispenser shall be acid resistant and not copper. 3. ASSE 1012 backflow preventers with intermediate atmospheric vents are not constructed for use with carbonated beverages and shall not be used for backflow prevention from post-mix carbonated beverage dispensers. h. All backflow prevention devices shall be installed in accordance with their manufacturer's instructions for the particular application.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 160
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __6-30-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
(3) ASSE 1024 dual check valves backflow preventers shall be permitted in limited area fire sprinkler systems that comply with NFPA 13 and do not have a fire department connection. (4) Where fire protection systems include a fire department connection, ASSE 1013 reduced pressure assemblies (RPF or RPDF) fire protection principle backflow preventers (RPF) or ASSE 1047 reduced pressure detector fire protection backflow prevention assmblies (RPDA or RPDA-II) shall be required. (5) Where fire protection systems are filled with solutions that are considered to be health hazards as defined in Section 1.2, reduced pressure assemblies (RPF or RPDF) ASSE 1013 reduced pressure fire protection principle backflow preventers (RPF) or ASSE 1047 reduced pressure detector fire protection backflow prevention assemblies (RPDA or RPDA-II shall be required. b. Whenever a backflow protection prevention device is installed in a potable water supply to a fire protection system, the hydraulic design of the fire protection system shall account for the pressure drop through the backflow protection prevention device. c. If a backflow protection prevention devices are device is retrofitted for an existing fire protection system, the hydraulics of the fire protection system shall be checked to verify that there is will be sufficient water pressure available for satisfactory operation of the fire protection system with the backflow prevention device in place.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 161
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __6-25-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
d. Where systems include a chemical injector or any provisions for chemical injection, the potable water supply shall be protected by the following: 1. Reduced pressure principle backflow preventer assembly (RP, RPZ, RPBA) - ASSE 1013 (RP)
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
Section 10.5.10
page 2 of 2
6-25-2012
13 - 162
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___6-25-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
A pressure-type or atmospheric-type vacuum breaker or permanently attached hose connection vacuum breaker shall protect hose bibbs, sill-cocks, wall hydrants and other openings with outlets having a hose connection. The backflow preventer shall not be subjected to continuous pressure and shall be limited to low-head backpressure of not more than 10 feet of water from an elevated hose. EXCEPTIONS: (1) Water heater and boiler drain valves that are provided with hose connection threads and that are intended only for tank or vessel draining shall not be required to be equipped with a backflow preventer. (2) This section shall not apply to water supply valves intended for connection to clothes washing machines where backflow prevention is otherwise provided or is integral with the machine.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 163
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___8-05-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 164
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 ___6-30-2012 ______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
d. Water Powered Back-up Sump Pumps 1. The potable water supply to water powered back-up sump pumps shall be protected against backflow by an ASSE 1013 (RP) reduced pressure principle backflow preventer. Vacuum breakers shall not be permitted. 2. Pump control valves, ejectors, and discharge piping shall be installed in accordance with the manufacturer's instructions.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
13 - 165
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___6-25-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 166
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __8-05-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 167
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___4-13-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 168
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __3-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
Table 10.14.2B
NOTES FOR TABLE 10.14.2B: 4. Refer to Appendix M for WSFU values that are interpolated between the values listed in Table 10.14.2B to the degree that the WSFU increments are close enough that they do not produce GPM differences that would be significant in sizing water supply distribution piping.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 169
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-24-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
b. The requirement of Section 10.14.6.a above shall not prohibit supply pressures higher than 80 psi to from water pressure booster systems under Section 10.14.4 or in high pressure distribution systems, provided that the pressure at the fixtures served is subsequently reduced to 80 psi maximum. Where operating water pressures exceed 80 psi, the working pressure rating of materials and equipment shall be suitable for the maximum pressure that may be encountered, including temporary increases or surges.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 170
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___7-28-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
d. When a pressure reducing valve is installed, a gauge port or pressure gauge with pressure range of 0-150 psi shall be installed within 24 inches downstream from the reducing valve. EXCEPTION: In one- and two-family dwelling units, gauge ports or pressure gauges shall not be required if there is a hose bibb or hose-end drain valve to which a pressure test gauge can be connected.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 172
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __4-20-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 173
Person Submitting Change 2 ____Greg Towsley_________________ Date 3 ___22 January 2013_____ Jurisdiction/Company/ Mailing Address _____Grundfos, 17100 W 118th Terrace______________________________________ City/State/Zip ____Olathe, KS 66061_____________________________________________________ Phone __913-227-3414___ Fax _559-346-6414_______ E-mail __gtowsley@grundfos.com__________ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - 174
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-04-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 175
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __3-04-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13
176
13 177
13 - 179
Person Submitting Change 2 ______NSPC Committee________________ Date 3 ____1-11-2013 Jurisdiction/Company/ Mailing Address _________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip Falls Church, VA 22046___________________________________ Phone_1-800-533-7694____Fax_1-703-237-7442____E-mail naphcc@naphcc.org
__X__ Change subsection to read as follows _____ Delete subsection and substitute as follows _____ Add new subsection to read as follows_____ Delete subsection without substitution
10.15.6
page 1
1-11-2013
and field-adjusted in accordance with the manufacturer's instructions to a temperature no higher than 105F. No further mixing of water shall be permitted downstream of the automatic temperature control mixing valve. b. f. Bathtubs and Whirlpool Baths: The water discharged into bathtubs and whirlpool baths, with or without deck-mounted hand sprays, shall be controlled to a temperature no higher than 120F by a water temperature limiting device complying with ASSE 1070, CSA B125.3, or ASSE 1016. c. g. Bidets: The hot water supply to the faucet on bidet plumbing fixtures shall be limited to 110F by water temperature limiting device complying with ASSE 1070. Where bidets are incorporated into toilet seats or consist of a heated water tank and nozzle, their controls shall limit the discharge temperature to no more than 110F. d. h. Public-Use Hand Washing Facilities: Water discharged from public-use hand washing facilities in public toilet rooms, hotel and motel guest rooms, and hospital patient rooms shall be limited to a temperature no higher than 110F. Water temperature limiting devices serving one or more fixtures and thermostatic faucets shall comply with ASSE 1070. Control valves controlling more than one fixture shall be sized for the required total water flow. e. i. Commercial Hair/Shampoo Sink Sprays: The temperature of water from commercial hair/shampoo sink sprays and pedicure basins shall be limited to a temperature no higher than 110F by a temperature limiting device complying with ASSE 1070, ASME A112.18.1/CSA B125.1, or CSA B125.3. g. Automatic temperature control mixing valves that supply gang showers shall comply with ASSE 1069. h. j. Water Temperature Limiting Devices: Where ASSE 1070 water temperature limiting devices are required, they shall be point-of-use for a single fixture or used for distribution to multiple fixtures having the same maximum water temperature requirement, depending on the maximum flow rate of the device. EXCEPTION: ASSE 1070 devices shall not be used for gang showers. i. k. Temperature Actuated Flow Reduction (TAFR) Devices: Where temperature actuated flow reduction (TAFR) devices are installed to limit the maximum discharge temperature to 120F for individual fixture fittings, such devices shall comply with ASSE 1062. These devices shall not supersede the other requirements of Section 10.15.6. j. l. In-Line Pressure Balancing Valves: Where in-line pressure balancing valves are installed to compensate for water pressure fluctuations to stabilize the temperature discharges from their individual faucet or fixture fitting, such devices shall comply with ASSE 1066. These devices shall be installed in an accessible location and alone shall not supersede the other requirements of Section 10.15.6.
k. m. Where a mixed water temperature control device supplies one or more outlets that can be shutoff downstream from the control device, the control device shall include integral check valves or check valves shall be provided in the hot and cold water supplies to the control device or at its inlets to prevent cross flow through the device. EXCEPTION: In one- and two-family dwellings, check valves shall not be required for an ASSE 1017 device installed at the water heater and directly connected to its hot and cold water piping. m. Alternate Methods: The use of combination water temperature control or limiting devices that comply with the standards listed in Table 3.1.3 and satisfy the performance requirements of Section 10.15.6 shall be subject to the approval of the Authority Having Jurisdiction.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled___ Withdrawn___ Other ______________________________________________________________________________
13 - 180
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-07-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
10.15.9.1 Where Required (no change) 10.15.9.2 Construction a. Drip pans shall be watertight and constructed of corrosion-resistant materials. Metallic Galvanized steel pans shall be 24 gage gauge (0.0276-inch) minimum thickness. Aluminum pans shall be 20 gauge (0.0320-inch) minimum thickness. Non-metallic pans shall be 0.0625-inch minimum thickness. Pans shall be not less than 1-1/2" deep but shall not be deeper than the bottom of the water heater tank or hot water storage tank. and They shall be of sufficient size to hold the heater or tank without interfering with drain valves, burners, controls, and any required access. b. High impact plastic pans shall be permitted under gas-fired water heaters where the heater is listed to zero clearance to combustible floors and the application is recommended by the pan manufacturer.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 181
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___5-10-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
10.15.9.3 Drainage
a. Drip pans shall have drain outlets not less than 3/4" size, with indirect drain pipes extending to an approved point of discharge, a suitably located indirect waste receptor, or floor drain, or extend to within 2 to 6 inches above the adjacent floor. b. Discharge from a relief valve into a water heater drip pan shall be permitted if the drain size for the drip pan is the same diameter or greater than the P&T not less than the relief valve discharge pipe size and the P&T discharge pipe into the drip pan is between 2 inches and 6 inches to extends to within 2 to 6 inches above the bottom of the pan. c. For drip pans installed under water heaters that are located above ceilings, the drain pipe from the drip pan shall extend to a point of disposal or indirect waste that is readily observable in an area below the heater.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 182
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___3-15-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
EXCEPTION: g. Where water heaters are located above ceilings, the relief valve discharge pipe shall extend to a point of disposal or indirect waste that is readily observable in an area below the heater. g. h. Where two or more relief valves serving independent systems are located in the same area, each shall be discharged separately. Where such relief valves for independent systems are discharged into a common gravity drain or indirect waste pipe, the drain or waste pipe shall be sized according to the largest discharge pipe served. i. For drain and indirect waste piping associated with relief valve discharge piping, refer to Section 9.1.12. Delete Table 10.16.6 DISCHARGE SIZE OF DRAINS OR WASTE PIPES RECEIVING RELIF VALVE
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 187
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __6-05-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: 10.16.7 Vacuum Relief Valves for Water Heaters and Water Storage Pressure Tanks
a. Where water distribution piping can siphon water from a water heater and cause dry-firing or cause a water heater or water storage pressure tank to collapse or be damaged by vacuum, a vacuum relief valve shall be installed on the cold water inlet piping to the water heater vacuum relief shall be provided. b. The vacuum relief valve requirements for water heaters shall depend on the type of water heater, the relative elevation of its inlet and outlet piping, the relative elevation of its water supply source, and the relative elevation of the lowest hot and cold water supply outlets connected to the piping associated with the water heater, in accordance with the following: 1. Where the heating element for the water heater is located in or below the lower half of its tank and the water heater has top water pipe connections, vacuum relief shall not be required if the piping associated with the water heater is not connected to any hot and cold water outlets on floor levels below that on which the water heater is installed. If the water heater serves outlets on a floor level below that on which it is installed, a vacuum relief valve shall be installed on either the cold water inlet pipe or the hot water outlet pipe that is above the top of the heater. 2. Where a water heater has a heating element in the upper half of its tank and the piping associated with the water heater is connected to any hot or cold water outlets on the same floor level on which the water heater is installed or on a lower floor level, its cold water supply and hot water discharge pipes shall be above the top of the water heater and a vacuum relief valve shall be installed on either the cold water inlet pipe or the hot water outlet pipe with its inlet at least 6-inches above the top of the heater.
3. Where a water heater has a bottom inlet, the cold water supply pipe to the heater shall be above the top of the heater tank before it drops to the bottom inlet and a vacuum relief valve shall be installed on that supply line before it drops with the relief valve inlet at least 6-inches above the top of the heater tank. EXCEPTION: Vacuum relief shall not be required if the elevation of the water supply source for the facility is above the top of the heater tank and there are no cold water outlets in the supply piping from that source that are below the top of the heater tank. 4. Where a water heater has a bottom outlet, the hot water outlet pipe from the heater shall be extended up to above the top of the heater and a vacuum relief valve shall be installed on that outlet pipe above the top of the tank with the relief valve inlet at least 6-inches above the top of the heater tank. EXCEPTION: Vacuum relief shall not be required if there are no outlets in the hot water piping from the water heater that are below the top of the heater tank. 5. Where a water heater is subject to vacuum from its hot water discharge piping, a dip tube with a vent opening shall not be considered as adequate vacuum relief. b. c. 210F. Vacuum relief valves shall comply with ANSI Z21.22/CSA 4.4 and be rated for not less than
c. d. Valves Vacuum relief valves shall be the full size of the water heater inlet pipe connection that it is associated with and shall be installed at an elevation on piping that is above the top of the heater tank. e. Vacuum relief valves shall not be isolated from the water heater by shutoff valves for the water heater. f. Vacuum relief for a water storage pressure tank shall be the same as required for a water heater unless the tank, including any lining, is rated for full vacuum.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 188
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 189
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __4-13-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 190
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___5-07-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 191
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-07-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 192
Contact Information:
Person Submitting Change 2 _____Michael Cudahy__________________ Date 3 ___Aug 25 2012____ Jurisdiction/Company/ Mailing Address Plastic Pipe and Fittings Association City/State/Zip __Glen Ellyn / IL / 60137 Phone ___630 363 7933______ Fax __630 858 654___ E-mail__mikec@cmservnet.com_______ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _____10.20.4 Materials for Combined Systems Piping c. Plastic piping shall be CPVC, PP, or PEX in accordance with table 3.4.3 Plastic piping shall be rated for 160 psig at 73 deg F, 130 psig at 120 F, and 100 psig at 180 deg F. Basis/Reason for Change:
Polypropylene piping systems designed for combined fire sprinkler / hot and cold water distribution now also exist in the market.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 193
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __3-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
b. Copper piping shall be ASTM B88 copper water tube, Type L or K. Fittings shall be the solder joint type, ASME B16.22 wrought or ASME B16.18 cast. Solder shall comply with ASTM B32. with not more than 0.2% lead. Flux shall comply with ASTM B813. Solder and flux shall contain no more than 0.2% lead. Soldered joints shall comply with ASTM B828.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 194
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___5-07-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 195
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___9-04-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
10.20.8 Installer Qualifications Installers of NFPA 13D multipurpose residential fire sprinkler systems and individuals who provide layouts, details and calculations shall be certified to ASSE 7010.
Table 3.1.3 - Part XI XI-9: Reserved Plumbing-Based Residential Fire Protection Systems Installers for One-and TwoFamily Dwellings ASSE 7010 - 2008
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 195a
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___1-25-2013______ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
Under INDIVIDUAL DWELLING UNITS Shower Stall, 1-1/2" Trap, single 2.5 GPM shower head = 2 DFU Shower Stall, 2" Trap, multiple shower heads up to 5 GPM total = 2 DFU 3 DFU Shower Stall, 3" Trap, multiple shower heads up to 10 GPM total = 5 DFU Shower Stall, 4" Trap, multiple shower heads up to 15 GPM total = 6 DFU Under FOR SERVING 3 OR MORE DWELLING UNITS Shower Stall, 1-1/2" Trap, single 2.5 GPM shower head = 2 DFU Shower Stall, 2" Trap, multiple shower heads up to 5 GPM total = 2 DFU 3 DFU Shower Stall, 3" Trap, multiple shower heads up to 10 GPM total = 5 DFU Shower Stall, 4" Trap, multiple shower heads up to 15 GPM total = 6 DFU Under OTHER THAN DWELLING UNITS Shower Stall, 1-1/2" Trap, single 2.5 GPM shower head = 2 DFU Shower Stall, 2" Trap, multiple shower heads up to 5 GPM total = 2 DFU 3 DFU Shower Stall, 3" Trap, multiple shower heads up to 10 GPM total = 5 DFU Shower Stall, 4" Trap, multiple shower heads up to 15 GPM total = 6 DFU
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 196
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___8-05-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 197a
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ____1-31-2013_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 198
13 - 199
Person Submitting Change 2: Fritz Reuss_________________ Date 3: January 31, 2013____ Jurisdiction/Company/ Mailing Address: 20 Vail Lane____________________ City/State/Zip: Flemington, NJ 08822______________ Phone: 908-510-0838_______ Fax: N/A___________ E-mail: freuss@comcast.net____ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 200
Contact Information:
Person Submitting Change 2 _John Wyckoff_______________________ Date 1/7/13______ Jurisdiction/Company/ Mailing Address _____Hardyston Twp. Plumbing Inspector, 149 Wheatsworth Rd., Suite A, City/State/Zip __ Hardyston, NJ 07419 Phone (973)823-7020 X9001 Fax 973-823-7023 E-mail plumberjohn@hotmail.com IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: 11.7.10 High Water Alarms. Sewage pumping units for other than single dwelling
units shall include on audible, visual, or combination high liquid level alarm.
Basis/Reason for Change: To protect single family houses from damage & costly sewer back-ups
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 201
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-04-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
11.7.1 General a. Equipment for pumping or lifting sewage shall be in accordance with the following: 11.7.2 Building Subdrains 11.7.3 Sewage Pumps and Ejectors 11.7.4 Pneumatic Sewage Ejectors 11.7.5 Grinder Pumps 11.7.6 Macerating Toilet Systems 11.7.7 Sump Pits, Basins, and Receptors 11.7.8 Discharge Piping 11.7.9 Controls 11.7.10 High Level Alarm 11.7.11 Individual Fixture Pumps and Ejectors 11.7.3 Sewage Pumps and Ejectors a. Sewage pumps and ejectors shall: 1. be installed in a sump pit, basin, or receptor in accordance with Section 11.7.7. 2. in single dwelling units, be capable of passing a solid at least 1-1/2 inches in diameter and have a 2" minimum discharge pipe size. 3. in other than single dwelling units, be capable of passing a solid at least 2 inches in diameter and have a 3" minimum discharge pipe size. 4. have a minimum capacity of 20 gallons per minute if they remove drainage from a water closet or urinal. b. Discharge piping shall comply with Section 11.7.8. EXCEPTION: Individual fixture pumps and ejectors shall comply with Section 11.7.11.
11.7.11 Individual Fixture Pumps and Ejectors a. Individual fixtures other than water closets, urinals, and similar fixtures may discharge directly into an approved fixture-mounted pump or ejector, or into a receptor having a pump or ejector. b. The discharge piping from a sewage pump or ejector for an individual fixture shall be sized to suit the discharge rate of the fixture and include a backwater valve and full-way shutoff valve. c. Direct-mounted equipment may be manually or automatically controlled. d. The installation of manually or automatically operated equipment shall not be subject to the venting requirements of this Code, but shall be vented only as required for proper operation of the equipment in accordance with the manufacturer's instructions. e. If the equipment provides a proper liquid trap for the fixture, additional traps are not required. f. A vent on the fixture side of a trap may terminate locally in the area served.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 202
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ____12-03-2012____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 203
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-10-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
12.4 Vent Terminals 12.4.1 Extension Above Roofs a. Vent pipes shall terminate not less than 6 inches above the roof, measured from the highest point where the vent intercepts the roof. See Figure 12.4.1 EXCEPTION: Where a roof is used for any purpose other than weather protection or maintaining equipment, vents within ten (10) feet of the area being utilized shall extend at least seven (7) feet above the roof, shall be properly supported, and shall also comply with Section 12.4.4 for location. b. Where vent pipes penetrate a flat roof in a location that is subject to ponding of storm water, the vent pipe shall terminate not less than 2 inches above the highest level of ponded storm water.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 204
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __1-24-2013_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Section 12.16
page 1
1-24-2013
12.16.3 Size of Relief Vents a.. The size of relief vents for circuit or loop vents of the drainage system shall be not less than one-half the size of the branch drain being served. b. Relief vents, where provided for drain stacks having ten or more branch intervals and relief vents for horizontal offsets in such drain stacks shall be the same size as the vent stack to which they connect. 12.16.4 Size of Stack Vents and Vent Stacks The minimum required size of stack vents and vent stacks shall be in accordance with Table 12.16. For the purpose of sizing, the length of a vent stack or stack vent shall be the developed length from its lowest connection with the drainage system to its termination in the open air, including any vent headers. a. Stack vents shall be the full size of the drain stack that they serve. b. Vent stacks shall be sized based on the total drainage fixture unit load (DFU) at the base of the stack that they serve. Connections of vents to the vent stack on floor levels above the base of the stack shall not increase its size. c. For the purpose of sizing vent stacks, the length of a vent stack in Table 12.16.4 shall be its developed length from its connection to the base of the stack being vented to its connection to its stack vent or, if not connected to its stack vent, its extension to an outdoor vent terminal. 12.16.5 Size of Vent Headers a. Vent headers or and portions thereof shall be sized according to Table 12.16 12.16.6. b. The number of drainage fixture units (DFU) used to size sections of vent headers shall be the sum of all fixture units (DFU) on for all drain stacks served by each that section of the header. c. The total developed length of all sections of vent headers a vent header shall be the longest vent length from the vent stack connection at the base of the most distant drain stack to the outdoor vent terminal in the open air. d. The soil and waste stack size used to size the vent headers shall be the equivalent size capable of handling the fixture unit load (DFU) on the vent header; based on Table 11.5.1B. d. Where two or more vent headers are connected before reaching an outdoor vent terminal, each vent header shall have its own total developed length to the outdoor vent terminal with regard to sizing per Table 12.16.6. 12.16.6 Size of Branch Vents a. Branch vents and portions thereof shall be sized according to Table 12.16.6.
Section 12.16
page 2
1-24-2013
b. The number of drainage fixture units (DFU) used to size sections of branch vents shall be the sum of all drainage fixture units (DFU) for the individual fixture vents or branch vents served by that section of the branch vent. c. The total developed length of all sections of a branch vent shall be the longest length from its connection to the most distant individual fixture vent being vented to its connection to an outdoor vent terminal.
Table 12.16.6 SIZE OF BRANCH VENTS (1) AND VENT HEADERS (2) DFU Vent Pipe Size (minimum) Vent Pipe Size (minimum) Being For 40 Feet Maximum For Greater than 40 Feet Vented Total Developed Length Total Developed Length 1 1-1/4" 1-1/2" 3 1-1/4" 1-1/2" 6 1-1/4" 1-1/2" 20 1-1/2" 2" 160 2" 3" 360 3" 4" 620 3" 4" 1400 4" 5" 2500 5" 6" 3900 6" 8" 7000 8" 10" NOTES FOR TABLE 12.16.6 (1) The total developed length of branch vents shall comply with Section 12.16.6.c. (2) The total developed length of vent headers shall comply with Section 12.16.5.c or d.
12.16.7 Underground Vent Piping The minimum size of vent piping installed underground shall be 1-1/2". 12.16.6 12.16.8 Aggregate Size of Vent Terminals a. Each building sewer shall be vented by one or more vents extending from the drainage system, or branches thereof, to the open outside air above the roof. b. Stack vents and vent stacks shall be sized according to Table 12.16. c. b. The aggregate cross-sectional area of all vent terminals serving a sewer shall be not less than the cross-sectional area of the minimum required size of the building drain that they serve, at the point
Section 12.16
page 3
1-24-2013
where it connects to the building sewer. (See Table 12.16.6 12.16.8 for the cross-sectional areas of pipes). EXCEPTION: The aggregate cross-sectional area requirement shall be exclusive of any requirements to increase the size of a vent terminal to prevent frost closure of the vent terminal under Section 12.5. d. c. One or more vent terminals having the aggregate cross-sectional area of a 3" vent terminal shall be permitted to vent a 4" building drain if the drainage fixture unit load (DFU) and number of bathroom groups served by the building drain does not exceed the maximum number allowed on a 3" building drain, as permitted by Section 12.16.6.c 11.5.6.c.
CHANGE EXISTING TABLE 12.16.6 TO TABLE 12.16.8. Table 12.16.6 12.16.8 NOMINAL PIPE CROSS SECTIONAL AREA (Sq. Inches)
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
Section 12.16
page 4
1-24-2013
13 205
13 - 206
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-07-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 207
Contact Information:
Person Submitting Change 2 _____Michael Cudahy__________________ Date 3 ___Aug 25 2012____ Jurisdiction/Company/ Mailing Address Plastic Pipe and Fittings Association City/State/Zip __Glen Ellyn / IL / 60137 Phone ___630 363 7933______ Fax __630 858 654___ E-mail__mikec@cmservnet.com_______ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _____Chapter 13, 13.1.1 Where Required Exception: Where precipitation is collected by a rainwater harvesting system installed according to Appendix G, or storm water from one- and two-family dwellings may be discharged on lawns or streets provided that the storm water flows away from the dwelling and does not otherwise create a nuisance. Basis/Reason for Change:
It would seem that some exceptions in the NSPC could be needed if Appendix G is used. A conflict between storm water requirements and rainwater harvesting systems appears to be one of these times.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - 208
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-31-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 209
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___5-31-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 210
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __11-07-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 211
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-10-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
14.12.1 General
Provisions for drainage from medical, surgical, dental, and similar central vacuum systems shall be as required by either NFPA 99 - Health Care Facilities Code or NFPA 99C - Gas and Vacuum Systems. In addition, drainage from dental and other vacuum systems that collect fluid waste centrally shall comply with Sections 14.12.2 through 14.12.4. 14.12.2 Positive Pressure Drainage from Air/Waste Separators in Dental Vacuum Systems a. The waste outlet .as required by NFPA 99 and NFPA 99C. b. (no change)
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 212
Contact Information:
Person Submitting Change 2 __John Heine_____________________ Date 3 1/7/13 Jurisdiction/Company/ NJ PHCC Code Committee, (Chairman) / PO Box 2067 Mailing Address ______________________________________________________________________
Princeton, NJ 08543 City/State/Zip ________________________________________________________________________
Phone ___609-987-0500_______________ Fax _ 609-987-0511 E-mail Director@nj-phcc.org IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as
Basis/Reason for Change: Clarifies what needs to be tested and method. Wording was repetitive.
This eliminates redundant language.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 213
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-21-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 214
Contact Information:
Person Submitting Change 2 __John Heine_____________________ Date 3 1/7/13 Jurisdiction/Company/ NJ PHCC Code Committee, (Chairman) / PO Box 2067 Mailing Address ______________________________________________________________________
Princeton, NJ 08543 City/State/Zip ________________________________________________________________________
Phone ___609-987-0500_______________ Fax _ 609-987-0511 E-mail Director@nj-phcc.org IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows __X___ Delete subsection without substitution
Basis/Reason for Change: Clarifies what needs to be tested and method. Wording was repetitive.
This eliminates redundant language.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other ____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 - 215
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-21-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 216
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___5-21-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
__X__ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 217
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ____5-21-2012_____ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 218
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-21-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - 219
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-08-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 220
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __4-13-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 221
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __4-13-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - 222
Person Submitting Change 2 ______NSPC Committee__ ______________ Date 3 ___8-05-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808_ ___________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone __1-800-533-7694___ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
Add the following to F.2 References: Table 3.5: Table 3.7: 5.3.4: 6.3.2.e: 10.15.1 12.5 14.13 SDR and PS ratings of PVC building sewers. SDR and PS ratings of PVC building storm sewers. Building traps. Waste oil tanks for oil separators. Tempered water supply systems. Frost closure of vent terminals. Water-supplied medical aspirators
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
13 - F1
Contact Information:
Person Submitting Change 2 ___Dave Bishop___________________ Date 3 _1/31/13____________ Jurisdiction/Company/ Mailing Address _________1001 Parsippany Blvd________________________________ City/State/Zip _______Parsippany New Jersey 07054____________________ Phone __973-229-4735____ Fax _973-263-1488_____ E-mail ____dbishop@parsippany.net___ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit, upon committee request, 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than January 31, 2013.
13 - F2
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __9-24-2012_______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
Figure 4.3.8-D A Transition Connection Using A Flexible Unshielded Coupling NOTES: 1. Flexible unshielded couplings are limited to underground sewer, drain, and vent piping. Center stops are required except for repair couplings. The couplings cannot support the pipe. The pipe must be properly backfilled to avoid stresses on the couplings.
___ Accept as Amended ___ Accept in Principle ___ Accept in Part and Principle
___ Defeated ___Failed Lack of Second ___ Tabled ___ Withdrawn ___ Other __________________________________________________________________________________
13 - F3
Contact Information:
Person Submitting Change 2 _____Michael Cudahy__________________ Date 3 ___Aug 25 2012____ Jurisdiction/Company/ Mailing Address Plastic Pipe and Fittings Association City/State/Zip __Glen Ellyn / IL / 60137 Phone ___630 363 7933______ Fax __630 858 654___ E-mail__mikec@cmservnet.com_______ IMPORTANT: Please review the attached instruction sheet regarding proposed code changes.
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section: _____Figure 4.3.9-D__________________ NOTES: 1. Plastic fittings pipes that are lead caulked must be solid plastic. Molten lead will melt cellular pipe fittings. Basis/Reason for Change:
In the Illustrated 2012 NSPC, PPFA recommends to delete fittings from this section. There are no cellular fittings, only pipe.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
____________________________________________________________________________________
1) Proposed Code Changes gaining acceptance will appear in the 2013 Supplement to the NSPC. 2) Proponent must submit 20 copies of Supporting Data for review by the NSPC Committee. 3) Proposed Code Changes must be submitted no later than Thursday, September 27, 2012
13 F4
13 - F5
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 ___4-02-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________
13 - F6
Contact Information:
Person Submitting Change 2 ______NSPC Committee_________________ Date 3 __5-04-2012______ Jurisdiction/Company/ Mailing Address _______________180 S. Washington Street, P.O. Box 6808 _____________________ City/State/Zip _________________Falls Church, VA 22046___________________________________ Phone _1-800-533-7694____ Fax _1-703-237-7442____ E-mail __naphcc@naphcc.org_____________
_____ Amend section with this editorial change _____ Delete subsection and substitute as follows _____ Delete subsection without substitution
Code Section:
1. Relief valves can discharge to the floor where permitted by the Authority Having Jurisdiction. 2. A shutoff valve in the hot water supply is permitted. 3. Shutoff valves must not isolate relief valves from the tank that they are protecting. 4. Threads are prohibited on the ends of the relief valve discharge pipes to prevent the installation of a pipe cap if the relief valve begins to leak. 5. Drains or indirect waste pipes Indirect waste receptors that receive the discharge from relief valves must be sized according to Table 10.16.6, based on the size of the relief valve discharge pipe size. 6. The inlet to indirect waste piping must be elevated to establish sufficient static head above the horizontal portion of the drain to prevent spillage. The horizontal portion of drain piping from indirect waste receptors must be far enough below the inlet to the receptor to establish sufficient static head to prevent spillage. 7. Where two indirect waste pipes from relief valves are joined, the cross-sectional area of the common drain must be equal to or larger than the sum of the areas of the individual waste pipes. Where the discharge pipes from separate pressure and temperature relief valves on a water heating or storing pressure vessel terminate at the same indirect waste receptor, it must be sized for the simultaneous discharge of both relief valves according to Section 10.16.6.g.
___ Accept as Amended ___ Accept in Principle ___Failed Lack of Second ___ Accept in Part and Principle ___ Tabled ___ Withdrawn ___ Other
__________________________________________________________________________________