Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

PRESSURE TRANSMITTER WITH 2 SET POINTS ATM/GR

27

Features
Compact and robust stainless steel assembly 1.4435 (316L) Piezoresistive measuring element Gauge, absolute or sealed gauge Standard DIN pressure ranges from 0100 mbar to 01000 bar 2 limit switches adjustable over 0100% of the pressure range Additional 0/420 mA analog output Complies with the EMC directive 89/336/EEC High reliability Short delivery time Customized versions due to modular assembly Reverse polarity and short circuit protected Media temperature up to 150C (optional)

Typical applications
Machine installations Industrial process control Heating and ventilation Environmental monitoring Food industry Mobile hydraulics Test and calibration systems

- feel the Dif ference

Specifications
Pressure range Overpressure [bar] 0.1 0.5 3 bar > 0.5 2 3 x FS
(min. 3 bar)

> 2 25 3 x FS

> 25 600 3 x FS
(max. 850 bar, optional 1500 bar)

> 600 1000 1500 bar

Burst pressure Accuracy1) Thermal shift Zero Span

[bar] [ % FS] [ % FS/C] 070C -2585C 070C -2585C

> 200 0.5

> 200 0.5

> 200 0.5

> 850
(optional 1500 bar)

1500 1

(optional 0.25)

(optional 0.25, 0.1)

(optional 0.25, 0.1)

(optional 0.25, 0.1)

0.5

(optional 0.5, 0.25)

0.06 0.08 0.015 0.02 < 4 mbar

0.03 0.04 0.015 0.02 < 4 mbar

0.015 0.02 0.015 0.02 < 0.2% FS

0.015 0.02 0.015 0.02 < 0.2% FS

0.015 0.02 0.015 0.02 < 0.2% FS

Long term stability (1 year)


1)

Zero based non-conformity according to DIN 16086, including hysteresis and repeatability

Output signal Analog output Load resistance and circuit diagram Output signal 0/420 mA
[Ohm] RL< 1000 UB[V] - 6V , 1kOhm max 0.02A

+Vin

P I

Pout GND

500

RL
0 10 20 30 [V]

UB

Power supply Supply voltage Supply current

1033 V DC
[mA]

reverse polarity and short circuit protected

70 60 50 40 30 20 10
0 10 20 30 [V]

IS

both relays selected without output signal (0/420 mA)

UB

Switches Switching voltage Switching current Switching power Switching functions

Switching difference 0100% of the pressure range, potentiometer-adjustable 2 independent relay outputs (change over) 48 V DC max. 2 A max. 60 W max.
N01 COM1 NC1 N02 COM2 NC2 COM2 COM1 N01 NC1 N02 NC2 COM2 COM1 N01 NC1 N02 NC2

The pressure is below both set points: both relais are selected.

The pressure is over the set point 1 (relay 1 is The pressure is over both set points: released), but below the set point 2 (relay 2 is both relais are released selected). or the supply voltage is missing.

Emission Generic emission standard Emission

fulfill the requirements described in the EMC directive 89/336/EEC EN 50081-1:1992 EN 50082-2:1995 Materials

Process conection, diaphragm, housing Seals (standard)

Stainless steel 1.4435 (316L) Viton

(other materials on request) (other materials see ordering information)

Ordering Information
Type Pressure type ATM/GR Gauge Absolute Sealed gauge 0100 mbar 0160 mbar 0250 mbar 0400 mbar 0600 mbar 01.0 bar 01.6 bar 02.5 bar 04.0 bar 06.0 bar 010 bar 016 bar 025 bar 040 bar 060 bar 0100 bar 0160 bar 0250 bar 0400 bar 0600 bar 01000 bar Special calibration

27 X . XXXX . XXXX . XX . XXX


27 1 2 3 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 99

Pressure range

3 3 3 3 3 3 3 3

Process connection

Electrical connection

G 1/4 female G 1/4 M G 1/4 M, Manometer DIN 16288 G 1/2 M G 1/2 M, frontal diaphragm G 1/2 M, flush diaphragm G 1/2 M, Manometer DIN 16288 1/4 NPT M 1/2 NPT M Special process connection Connector Binder 723, 12-pin 1) PVC cable 3) Special electrical connection 020 mA 420 mA 0.5 % FS 0.25 % FS 0.1 % FS (on request)

(Fig. 1) (Fig. 2) (Fig. 3) (Fig. 4) (Fig. 5) (Fig. 6) (Fig. 7) (Fig. 8) (Fig. 10) IP 67 (Fig. 11) IP 67

00 11 12 13 14 15 16 10 19 99 45 10 99 14 15

Output signal

Accuracy

0 1 2 0 1 2 9

Temperature range

Compensated 070C (media temperature 0 80C) Compensated -2585C (media temperature -25100C) Compensated -2585C (media temperature -25150C) Special temperature range

Options

Throttle 2) Electronis packed in gel: Gauge pressure Absolute and sealed gauge pressure Special oil filling: ASEOL Food Halocarbon Seals: EPDM Kalrez Special options

A C D G H S T Z

1) 2)

Cable socket connector not included Available only with fig. 2, fig. 4 or fig. 7 3) Please specify the required cable length

Pressure Connection

Dimensions
Version for media temperature up to 100C

Electrical Connection
74.5

G 1/4 F

SW27

Cable socket connector


G M F E D K L B C

32,5

Fig. 1

24

94

H J

12
G 1/4 M

SW27

Version for media temperature up to 150C

Fig. 10
Pin
24

32,5 16
G 1/4 M

Fig. 2

35,5 13,5

SW27

121

A L B E D F H G J

+Vin Pout GND NC1 COM1 NO1 NC2 COM2 NO2

Fig. 3

G 1/2 M

SW27

Colour
32,5
20,5

Fig. 4

white brown yellow green orange violett red blue

+Vin Pout GND NC1 COM1 NO1 NC2 COM2

G 1/2 M 18,4

SW27

34,5

Fig. 11 Fig. 5

19,5

G 1/2 M

18,4

SW27

33,5

Fig. 6
GND Set point 1 Set point 2

25
G 1/2 M

SW27

43

Fig. 7

Connector side

17
1/2 NPT M

31,5

SW27

Fig. 8

Specifications may change without notice. Release 06/01