Professional Documents
Culture Documents
District Cooling Plant Size Estimate
District Cooling Plant Size Estimate
Check
500,277
500,636
167,200
31,270
8,120
236,000
44,800
11,800
7,442
2,726
4,176
7,076
29,500
1,345,923
1,551,022
Local Cooling
36,327
10,776
District Cooling
Chilled water at 8.5 delta T
47,103 kW
27,000
22,557
62,928
4,500
4,800
13,011
25,924
11,520
760
635
1,771
127
135
366
730
324
172,240 kW
4,848
DURRAT ISLAND
PROVISIONAL COOLING LOAD ESTIMATE FOR DISTRICT COOLING
BASED ON REVISED MASTERPLAN AND AREAS FROM UK
ie
Buildings
m2
w/m2
VILLAS
431,273
160
APARTMENTS
444,000
160
HOUSING
144,000
160
RETAIL
26,500
180
COMMERCIAL
7,000
160
HOTEL
200,000
180
INDUSTRIAL
40,000
120
CONFERENCE
10,000
180
MOSQUE
6,100
220
CLINIC
2,350
160
BLUE LIGHT
3,600
160
SCHOOL
6,100
160
SPORTS
25,000
180
180
TOTAL
1,345,923
Check
Athols m2
kW
Petals m2
kW
Hotel island m2
kW
Golf course m2
kW
Crescent Island m2kW
Sport club m2
kW
Support services m2kW
Marina m2
kW
Mainland crescent m2
kW
Employees Village m2
kW
449,400 71,904
96,495 15,439
0
151,950 24,312
0
0
0
0
40950
0
0
0
0
0
0
390,960 62,554
0
0
92,848 14,856
190,512 30,482
0
0
0
0
0
0
0
0
0 inc
0
72,000 11,520
0
0
0
0
26,500 4,770
0
0
0
0
0
0
0
0
0
7,000 1,120
0
0
0
0
0
0
0
34,314 6,177
15,750 2,835
0
0
0
0
0
0
0
0
0
0
0
0
40,000 4,800
0
0
0
0
0
0
0
10,000 1,800
0
0
0
0
0
0
0
0
0
6,100 1,342
0
0
0
0
0
0
0
0
0
2,350
376
0
0
0
0
0
0
0
0
0
3,600
576
0
0
0
0
0
0
0
0
0
6,100
976
0
0
0
0
0
0
0
0
4,450
801
0
25,000 4,500
0
0
0
0
0
0
0
9,504 1,711
0
0
0
0
850,450
751,729
83,680
31,270
8,120
59,076
44,800
11,800
7,442
2,726
4,176
7,076
34,751
1,897,096
Local Cooling
71,904
15,439
24,312
111,655 kW
District Cooling
6,177
3,636
75,224
4,500
4,800
14,856
30,482
11,520
151,194 kW
174
102
2,117
127
135
418
858
324
4,255 l/s
43050.81 TR