Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3

Wc

1200
600
Time
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
0:00

Load Profile
(TR)
552
538
465
432
465
565
698
785
890
968
1112
1183
1262
1286
1288
1310
1297
1255
1145
1101
1005
861
726
659

275

Base Load
Balance load
Base Load
Load on
Water Chillers
on Brine Circuit Brine Chillers TES tanks
(TR) 600 X 2
nos
552
648
538
662
465
735
432
768
465
735
565
635
698
502
785
415
890
310
968
232
1112
88

Charging 600 TR 1
no
648
662
735
768
735
635
502
415
310
232

21848
Peak
Load

1310
1048

SUMMARY OF DESIGN:
1) 2 NOS. 675TR WC CHILLER CONVERTED TO BRINE CHILLER WHICH IS ASSUMED TO
PRODUCE 624TR AT NORMAL MODE(7.5% CAPACITY REDUCTION) AND 468 TR AT ICE
MAKING MODE (75% CAPACITY OF NORMAL MODE)
2) BALANCE 2 NOS. 675TR WC CHILLER WILL SERVE TO PRODUCE THE REQUIRED
COOLING IN DAY TIME ALONG WITH THE 2 NOS. BRINE CHILLER 624TR.
3. 11239 TRH OF STORAGE IS PRODUCE DURING OFF PEAK TIME. CHARGING TIME IS 12
HRS.
4) STORAGE IS ENTIRELY UTILIZED DURING 18 HRS TO 22 HRS WHICH IS INCLUDING THE
POWER SHUT DOWN TIME AND NO CHILLERS (WATER & BRINE) WILL BE IN OPERATION.
5) TOTAL REQUIREMENT TES TANKS IS 80 NOS. EACH TANK STORAGE CAPACITY IS
ASSUMED TO BE 140 TRH WHICH MAY VARY BASED ON THE TEMPERATURE
CONSIDERATIONS.

1400

1200
1000
800
600
400

200
0
1:00 3:00 5:00 7:00 9:00 11:0013:00

Series1

11:0013:0015:0017:0019:0021:0023:00

You might also like