Form - Product Investigation Checklist
Form - Product Investigation Checklist
Time In:
Work description :
Single Wall Double Wall Pressurize Suction Single Wall Double Wall Remote Direct
Not
S/N LOCATION REFERENCE CHECKS OK OK NA Remarks
1 ATG & LEAK Figure 1 Check for any activated alarm displayed on Veeder Root console
DETECTION SYSTEM *Print a copy of inventory / sensor status report for reference & attached
2 TANK AREA
2a Tank Type
Single Wall Tank Figure 1.1 Conduct manual dip check for any presence of water in tank
Double Wall Tank Figure 2.1 to 2.2 Conduct manual dip check for any presence of water in tank
*Please indicate findings in REMARKS, if lower volume of BRINE is found, please check tank
for any BRINE residue found. Any increase in volume, please check for liquid in IS.
If it is water or product. Observation for the BRINE may varies IF there has a leak, many
factors / observation is dependant on several condition, example product level and
groundwater level at the moment of inspection, and which tank wall has failed
2c Tank Sump Figure 3.1 to 3.2 Visual check for product / Vapour presence in sump Yes No
2d Monitoring Well Figure 4 Visual check for product / vapour presence in monitoring well
(Observation Well)
Check and measure water table level
Measure from ground flooring level to water surface level.
*Please indicate in remarks for findings
*Water table level will be important information for Single wall tank system,losses.
IF available for inspection. Information will arrive useful; IF tank has any frequent water in tank
history or product
For:
2e Pressure System Figure 5 Conduct line pressure test at shear valve test port with pressure
gauge for operating pressure
General guide: (Please refer to your zone standard if varies)
Check for operating pressure of STP
For 0.75 HP, 27 to 30 psi
For 1.5 HP, 29 to 33 psi
For 2 HP, 29 to 43 psi
Check pipe fitting in tank sump / STP assembly and other related fittings
in sump
*If any doubt, please refer to your STP inspection checklist
For:
2f Suction System Figure 6 Please indicate if site is using Safe Suction system Yes No
3 PIPE MANIFOLD SUMP Figure 7.1 to 7.3 Check for presence of product / vapour in sump
FORECOURT AREA
8a Dispenser / Pump Figure 12 Visual check for product / vapour presence in sump
sump (applicable for Double wall pipe - For Pressure OR suction system)
Time out: