Cerberus CS1140

Fire detection system control unit with


control console
Operating instructions

Related to software Standard international (EP5)

Fire & Security Products


Siemens Building Technologies Group

Data and design subject to change


without notice. / Supply subject to
availability.
E Copyright by
Siemens Building Technologies AG
Wir behalten uns alle Rechte an
diesem Dokument und an dem in ihm
dargestellten Gegenstand vor. Der
Empfnger anerkennt diese Rechte
und wird dieses Dokument nicht ohne
unsere vorgngige schriftliche
Ermchtigung ganz oder teilweise
Dritten zugnglich machen oder
ausserhalb des Zweckes verwenden,
zu dem es ihm bergeben worden ist.
We reserve all rights in this document
and in the subject thereof. By
acceptance of the document the
recipient acknowledges these rights
and undertakes not to publish the
document nor the subject thereof in
full or in part, nor to make them
available to any third party without our
prior express written authorization,
nor to use it for any purpose other
than for which it was delivered to him.
Nous nous rservons tous les droits
sur ce document, ainsi que sur lobjet
y figurant. La partie recevant ce
document reconnat ces droits et elle
sengage ne pas le rendre
accessible des tiers, mme
partiellement, sans notre autorisation
crite pralable et ne pas
lemployer des fins autres que
celles pour lesquelles il lui a t
remis.
Ci riserviamo ogni diritto relativo al
presente documento e sulloggetto
illustrato in esso. La parte che riceve
il documento si impegna a non
renderlo accessibile a terzi, n per
intero n in parte, senza la nostra
previa autorizzazione scritta ed a non
usarlo per altri scopi di quello per il
quale stato rilasciato.

Content
Quick reference instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Control console layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operating access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Message categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Terminology Area, Section
and Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Normal operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operating states
Present and Absent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Detector zone,
temporary isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Isolation of detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Detector test mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Installation test mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Renovation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Remote transmission OFF/ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Alarm devices OFF/ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Printer OFF/ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Printer: Paper replenishing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Lamp test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Alarm counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Event memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Set clock and date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Overview operating menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

I
Fire & Security Products
Siemens Building Technologies Group

10.1999

II
Fire & Security Products
Siemens Building Technologies Group

10.1999

Quick reference instructions


Alarm, what to do ?
FIRE BRIGADE REQUESTED
Total: 2
01 AUTOM.FIRE ALARM
upper
Main building / 1st floor
section
room 104
02 AUTOM.FIRE ALARM
lower
Main building / 1st floor
section
room 104
select MESSAGE CATEGORY
F1:function

1st message
+ scroll box
last message

ALARM

This display can show 2 messages spontaneously.


A

Acknowledge

=> Upper section shows 1st message

Reset

=> Lower section shows 2nd message


If more than 2 messages have been reported,
scrolling becomes necessary in order to show all
reported messages in the upper section (one after
the other).

Information

Isolation

Alarms

Faults

F1

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

F2

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

ok

Detector
test mode

Control function
off

System
on

System
fault

=> Scrolling is done by pressing key scroll


or with the arrow keys

1. Press the acknowledge key

=> 3 different messages possible

2. Read top line of display


FIRE BRIGADE REQUESTED
01 AUTOM.FIRE ALARM
Main building / 1st floor
room 104

select MESSAGE CATEGORY


FIRE BRIGADE in 2:35
01 AUTOM.FIRE ALARM
Main building / 1st floor
room 104

select MESSAGE CATEGORY


CALL fire brigade: TEL.118
01 AUTOM.FIRE ALARM
Main building / 1st floor
room 104

select MESSAGE CATEGORY

Total: 1

Alarm message to fire brigade already transmitted

F1:function
Total: 1

Alarm message to fire brigade will be sent in


..min ..sec
remaining time shown as countdown

F1:function
Total: 1

F1:function

No transmission to fire brigade


call fire brigade by telephone
either; if
remote transmission isolated
remote transmission device blocked or defective
not connected to fire brigade

3. Read fire location on the display


4. Go to indicated fire location
5. Decide on emergency or minor incident
Emergency:

if fire brigade is already informed:


if time count down runs:
if no transmission to fire brigade:

=> save people, guide fire brigade, fight the fire


=> immediately actuate nearest call point
=> call fire brigade by telephone

Minor incident:

if fire brigade is already informed:


if time count down runs:
if no transmission to fire brigade:

=> try to stop the fire brigade


=> immediately press key reset B
=> press key reset B

Alarm reset:
Alarm reset is only possible via access password (see page 6)
As long as a detector still detects a fire phenomena (smoke, heat) the alarm cannot be reset. In order to remove such
an alarm the corresponding detector zone has to be isolated (see page 8)
1
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Quick reference instructions


How to start operating ?
1. Press key

F1

INFORMATION
01 present
Main building

Total: 1

ALARM

select MESSAGE CATEGORY


WED 21-FEB-1996

F1:function
13:23

Acknowledge

password:or TURN the key switch

Reset

F1

F2

ok

Information

Isolation

Alarms

Faults

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

Detector
test mode

Control function
off

System
on

System
fault

0..9, del:password

ok:enter

c:end

password:CORRECT
authorized access level: 2.1

2. Enter password and press key


or turn key switch (if equipped)

ok

3. Select function in MAIN MENU with arrow keys


then press key ok
option selected is shown inverse

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

Function FIRE detection


to navigate to a fire detection SECTION or ZONE or
ELEMENT (= detector) in order to
isolate or reactivate a detector zone(s)
set a detector zone (s) on mode detector test or to terminate detector test , etc.

F1:function

Function Extinguishing section


to navigate to an extinguishing SECTION in order to
isolate detector zones related to the selected extinguishing section
set detectors related to the selected extinguishing section on mode detector test or to terminate
test the extinguishing alarm horn or warning panel , etc.
Function CONTROL in-/ outputs
to select a control SECTION or ZONE in order to
isolate or reactivate a fire control function (e.g. air-conditioning shut down, etc.)
initiate manually or deactivate a fire control function, etc.
Function GEOGRAPHICAL location
to select any SECTION or ZONE in order to
isolate or reactivate a zone, etc.
Function DEVICE level
to initiate a specific function such as
lamp test
printer test, also to enable or disable the printer, etc.
Function LOGICAL address (CSX. no.)
to jump directly to a known logical location
the complete address (AREA no./ SECTION no./ ZONE no./ELEMENT no.) must be known
2
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Introduction
This Cerberus fire detection installation consists of the following components:

Equipped

System components
Type of operating console ?
Type AlgoPilot

Type CI1145

Series of fire detectors ?

Interactive detectors

Addressable detectors
Collective detectors
Includes also extinguishing SECTIONS ?

CO2
N2
water
..........

p yes
Printer connected ?

Location

p
p
p
p
p
p

no

..............................
..............................

Remote transmission connected ?

p yes

no

Cerberus Alarm Concept activated ?


> operating present / absent used ?

p yes

no

Multi area installation ?

p yes

no

Duration of emergency power operation ?

..........hours

This table to be filled in by the commissioning engineer.


Make sure that all system operators of the fire detection installation are sufficiently instructed. If there is any doubt
about any function or measures to be taken call the local service organization for assistance.

3
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Control console layout


Typ AlgoPilot
User interface to operate the fire detection system.

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- / outputs
GEOGRAPHICAL location
DEVICE level
Logical address (CSX.no.)
v/^ok:selection

ALARM

1a
1b

F1:function

1c

Acknowledge

Reset

8
3
Information

Isolation

Alarms

Faults

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

Detector
test mode

Control function
off

System
on

System
fault

2
0

9
6

F1
F2

ok

AlgoPilot CT11

Text display with red and yellow illumination:


red for danger messages (Alarm)
yellow for status changes or during operator actions (automatically switched off when not operated)
dark, if no danger message (Alarm) is pending and no operator activity is in progress
Example: Main menu
1

1a

Typ of menu list

1b

Selected operating function

1c

Instruction bar

Warning panel ALARM


lights up when an alarm signal is pending

Display fields, partially with command keys :


display the operating states of the fire detection system

Acknowledge key
to confirm that the operator has received a message
message not acknowledged yellow LED is flashing

Reset key
to reset (cancel) all currently reported alarms
message acknowledged, but not reset yellow LED is flashing

Function key pad for menu operation and password input:


The function of F1 and F2 depends on the selected menu
ok key to select or execute a command
and
keys move the line marking (cursor bar with inverted colors) up or down
C (clear) key for cancelling the input
(del) key deletes the character on the left of the cursor

Keylock switch, optional device for access control

Key multi alarms, with version nordic only, to scroll the alarm messages

4
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Control console layout


Typ CI1145
User interface to operate the fire detection system.

1
MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- / outputs
GEOGRAPHICAL location
DEVICE level
Logical address (CSX.no.)
v/^ok:selection

ALARM

1a
1b

F1:function

1c

Acknowledge

Reset

8
3
Information

Alarms

Faults

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

Detector
test mode

Isolation

Control function
off

System
on

System
fault

2
0

9
6

F1
F2

ok

Text display with yellow illumination:


dark, if no danger message (Alarm) is pending and no operator activity is in progress.

Example: Main menu


1a

Typ of menu list

1b

Selected operating function

1c

Instruction bar

LED bar ALARM


lights up when an alarm signal is pending

Display fields, partially with command keys :


display the operating states of the fire detection system

Acknowledge key
message not acknowledged yellow LED is flashing
to confirm that the operator has received a message

Reset key
to reset (cancel) all currently reported alarms
message acknowledged, but not reset yellow LED is flashing

Function key pad for menu operation and password input:


The function of F1 and F2 depends on the selected menu
ok key to select or execute a command
and
keys move the line marking (cursor bar with inverted colors) up or down
C (clear) key for cancelling the input
(del) key deletes the character on the left of the cursor

Keylock switch, optional device for access control

Key multi alarms to scroll the alarm messages


5

Fire & Security Products


Siemens Building Technologies Group

e1033e
10.1999

Operating access
There are the following access levels:
Access level 1
Access level 2.1
Access level 2.2
Access level 3

Everybody
Operator 1
Operator 2
Service

for Acknowledge and Scroll functions


with limited privileges (e.g. janitor)
with limited privileges (e.g. security officer)
with full privileges (for service engineer)

How to get operating access:


Enter the password via the keypad 1 and/or turn the keylock switch 2 (if equipped).

Isolation

Alarms

Faults

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

Detector
test mode

Control function
off

System
on

System
fault

Information

2
0

9
6

F1
F2

ok

Operator access via keylock switch


Insert the key and turn it to the horizontal position.
The operating access (level 2.2) remains while the key is left in the horizontal position

Operator access via password


The operator has to enter:
a password (3...8 digits).
password with a particular access level is defined and released by the service engineer
(system configuration)
Note:
The main menu is only visible after entering a password (default: access level 2.1):
Log in
WED 28-OCT-1997

4. Press F1 key
an entering box is displayed
5. Enter the password and press the

13:23

password:or TURN the key switch


ok

key
0..9, del:password

The confirmation password CORRECT or


password INCORRECT is displayed

To cancel keying errors press the

ok:enter

c:end

password:CORRECT
authorized access level: 2.1

key

6. start operation

Log out

MAIN MENU
FIRE section
EXTINGUISHING section
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

F1:function

Is not required because operating is automatically inhibited if no


key is pressed within a certain time (timeout 2...10 minutes; set
by the service engineer).
6
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Message categories
There are the following message categories:
Alarms

danger messages acquired by the system

Priority 1

Faults

messages that require an immediate response

Priority 2

Isolation

system components out of service

Priority 3

Information

messages that do not require an immediate response

Priority 4

FIRE BRIGADE REQUESTED


01 AUTOM.FIRE ALARM
main building / 1st floor
room 104

ALARM

Total: 1

FAULTS
01 detector
Main building / 1stfloor
room 104

select MESSAGE CATEGORY


select MESSAGE CATEGORY

Total: 1

F1:function

F1:function

ISOLATION
01 detector zone OFF
Acknowledge
Main building / 1stfloor
room 104

Total: 1

Reset

Information

Isolation

Alarms

Faults

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

Detector
test mode

Control function
off

System
on

System
fault

select MESSAGE CATEGORY


7
8
9
F1
INFORMATION
4
5
6
01 absent F2
Main building
1
2
3 ok
0

Total: 1

select MESSAGE CATEGORY

F1:function

F1:function

Information display field


Press key 2 to display the information list.
Certain information messages are displayed spontaneously (for example warnings) if no message with a higher
priority is pending.

Isolation display field


Press key 4 to display the list of disabled system components.
This message type is displayed spontaneously if no message with a higher priority is pending.

Alarms display field


Press key 6 to display the list of alarms.
This message type is always displayed spontaneously and overwrites all other message categories

Faults display field


Press key 8 to display the list of existing faults.
This message type is displayed spontaneously if no message with a higher priority is pending.

Note
Switching from one message category to another is always possible by pressing the corresponding selection key. If a
lower priority is selected, the system always goes back, to that message category with the highest priority after a
short time-out.

7
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Terminology Area, Section and Zone


What is an Area?
It normally covers a whole building or part of a building and represents also the operating level.
This is the logical designation for several, usually adjacent sections

Area Main building

AREA
01 main building
02 factory

ok:section

F2:main menu

F1:function

What is a Section?
It normally covers a floor or part of a floor in a building.
This is the logical designation for several, usually adjacent zones

SECTION fire
01 ground floor
02 first floor
03 second floor

Section 1st floor

ok:zone

F2:area

F1:function

What is a Zone?
It normally comprises one room of a building (with collective detectors => several rooms)
It is the logical designation of a detector group containing at least one detector
Automatic fire detectors, manual call points and control outputs are always assigned to different ZONES
For this reason we have
zones comprising automatic fire detectors
zones comprising manual call points
zones comprising control outputs

ZONESfire
01 room 103
02 room 104
03 room 105
Zone room 104
ok:element

F2:section

F1:function

8
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Normal operation
What is Normal operation?
The system is ready for receiving danger messages
No danger messages (Alarms) and no fault messages are pending and no part of the system is isolated
The green indicator

in the display field System on is ON

The system can either be in state Present or Absent (present / absent see page 10)
The operating states Present / Absent are information messages which means that there is always one
information message pending 2

INFORMATION
01 present
main building

ALARM

Total: 1

select MESSAGE CATEGORY

F1:function
Acknowledge

Reset

select MESSAGE CATEGORY

F1:function

2
Information

Isolation

Alarms

Faults

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

Detector
test mode

Control function
off

System
on

System
fault

F1

F2

ok

9
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Operating states manned and unmanned


Is the Cerberus Alarm Concept activated?

p Yes
p No

Basic rules
The operating states Present and Absent are only relevant for systems in which the signals for automatic fire
detectors and manual call points are processed differently, that means, the Cerberus Alarm Concept is activated.
The switchover is possible manually or automatically.
Operating state manned (=present)
Means: The operating person responsible for Alarm investigation is on site.
Indicator 1 in the display field Premises manned is ON.
Operating state unmanned (=absent)
Means: The responsible operating person is not on site.
Information

Alarms

Faults

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

Detector
test mode

Isolation

Control function
off

System
on

System
fault

F2

ok

F1

Manual switch over from manned (present) to unmanned (absent) or vice versa
(Requires corresponding operator access level)
Note:
For several areas, this function works only, if all areas
are in the same state (absent or present).
With this function you switch over all areas from present
to absent or vice versa.

INFORMATION
01 present
building A
02 present
building B

Total: 2

select MESSAGE CATEGORY

F1:function

actual state: present

1. Switch over by pressing key 2


Confirmation prompt is displayed

switch over ?
ok:switch over

2. Confirm the switchover by pressing the ok key 3


The new operating state is shown in the display
In the Present mode the state indicator 1 is ON

C:cancel

switched over !
actual state: absent

Note:
The switchover from Present to Absent (or vice versa) is also possible via the menu.
If several organizationally autonomous systems are operated via a common multi-area terminal (areas with present
state, other areas with absent state) the state can only be changed via the menu, the Present state indicator 1 is
flashing.

Automatic switchover
From Absent to Present: p No
From Present to Absent: p No

p Yes, time = . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
p Yes, time = . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Alarm
How are alarm messages shown in the text display field?

1st alarm
message

total amount of
pending messages

Zone Room 104


Room
103

Corridor
Room
102
Room
103

2nd alarm
message

FIRE BRIGADE REQUESTED


01 AUTOM.FIRE ALARM
main building / 1stfloor
room 104
02 AUTOM.FIRE ALARM
main building / 1stfloor
room 102
select MESSAGE CATEGORY

Total: 2
1st message
+ scroll box
last message
F1:function

Room
104

bottom line =
instruction bar

Zone Room 102


up to 2 messages can be displayed simultaneously

Supplementary information
(if programmed)

How can an intervention text be


read out?
1. Press the Alarms key and select the
desired message by pressing the
key, if necessary (the selected message is displayed in inverted colors)

FIRE BRIGADE REQUESTED


Total:
2
01 AUTOM.FIRE ALARM
plan:063
main building / 1st floor 01/01/004
room 104
02 AUTOM.FIRE ALARM
plan:064
Main building / 1st floor 01/01/006
room 102
select MESSAGE CATEGORY
F1:function

site plan reference


number
logical address of
the alarming zone

FIRE BRIGADE REQUESTED


Total:
2
01 AUTOM.FIRE ALARM
main building / 1st floor
room 104
02 AUTOM.FIRE ALARM
main building / 1stfloor
room 102
ALM,^/v:scroll F2:interv.text F1:funct.

FIRE BRIGADE REQUESTED


2. Press F2
key
(message
category
DANGER: hazardeous materials
Alarms selected or
-> alert emergency squad
acknowledged
The intervention text is displayed
(if programmed)
F1:function

F2:message

Total:
!!

2
intervention text

C:end

11
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Alarm

cont.

What to do on ALARM ?
Top line on display reports status of remote transmission
FIRE BRIGADE REQUESTED ?
............

ALARM

FIRE BRIGADE in .... ?


............

3
2

CALL fire brigade: TEL.118 ?


............

" FIRE BRIGADE REQUESTED ?


Alarm is already transmitted
yellow LED in the key acknowledge is flashing

1. Press the Acknowledge key

(yellow flashing LED)

2. Read the fire location of the 1st alarm in the upper half of the text display field
3. Go to the fire location
4. Decide on Emergency or Minor incident:
Emergency: . . . . . . . save people, fight the fire
Minor incident: . . . . immediately try to stop the fire brigade, press the Reset key

. . . . . . . . . . . . . . . . . . . the system reverts to normal operation

" FIRE BRIGADE in 4:31 (min) ?


Alarm will be transmitted in the time indicated
yellow LED in the key acknowledge is flashing

1. Press the Acknowledge key

(yellow flashing LED)

before time is 0:00

2. Read the fire location of the 1st alarm in the upper half of the text display field
3. Go to the fire location
4. Decide on Emergency or Minor incident:
Emergency: . . . . . . . immediately actuate manual call point or the key
. . . . . Alarm delay off 2
. . . . . . . . . . . . . . . . . . . the alarm message is transmitted
Minor incident: . . . . immediately press the Reset key 3 (flashing yellow LED)
. . . . . . . . . . . . . . . . . . . the yellow LED becomes dark, the system reverts to normal operation

" CALL fire brigade: TEL. 118 ?


yellow LED in the key acknowledge is flashing

1. Press the Acknowledge key

(yellow flashing LED)

. . . . . . . . . . . . . . . . . . . . . LED in the Acknowledge key becomes dark

2. Read the fire location of the 1st alarm in the upper half of the text display field
3. Go to the fire location
4. Decide on Emergency or Minor incident:
Emergency: . . . . . . . immediately Call the fire brigade (e.g. 118)
. . . . . . . . . . . . . . . . . . . . the alarm message is transmitted

Minor incident: . . . . immediately press the Reset key 3 (flashing yellow LED)
. . . . . . . . . . . . . . . . . . . the yellow LED becomes dark, the system reverts to normal operation
12
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Alarm

cont.

How does the Cerberus Alarm Concept function?


When the system operates in Present mode, manual call points and automatic fire detectors trigger different actions in the event of an alarm.

Danger message

Operating mode Present

Operating mode Absent

Manual call point actuated

Fire brigade is summoned immediately.

Fire brigade is summoned


immediately.
Autom. fire detector responded Fire brigade is summoned only after the pre- Fire brigade is summoned
programmed time.
immediately.
Alarm response procedure:
1. Confirm the alarm within the alarm acknowledgment time (V1) and immediately
go to the fire location.
2. At the fire location decide on whether this is
an emergency or a minor incident.
3. In case of emergency immediately actuate
the nearest manual call point or press the
Alarm delay off key on the console.
4. In case of a minor incident immediately
reset the system, that is, before expiration
of the alarm investigation time (V2).

Alarm acknowledgement time V1


This is a countdown time that is active for automatic detectors when the
system operates in Present mode.
Checks whether someone acknowledges the danger alarm message within
the preprogrammed time.
On expiration of this time the alarm is transmitted to the fire department.
The remaining time is displayed in minutes and seconds.

V1 =

...............

minutes

Alarm investigation time V2


This is a countdown time that is active for automatic detectors when the
V2 =
system operates in Present mode.
Limits the time for investigating the fire location to an individually programmed time.
On expiration of this time the alarm is transmitted to the fire department.
The remaining time is displayed in minutes and seconds.
In case of minor incidents, an alarm must be reset before V2 expires.

...............

minutes

What to do, if an alarm message cannot be reset ?


If this message is displayed on the terminal, you can isolate the
corresponding detector zone by pressing the ok key.
If you dont want to isolate the zone, press the C key or wait until
this message disappears.
As soon as conditions have returned to normal, ISOLATED
ZONES must be immediately switched on again.

** ALARM-RESET currently NOT POSSIBLE**


*** detector ZONE(S) still in alarm***
in order to ISOLATE corresp.ZONE(S)
-> press key ok
NO isolation -> press key C

13
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Detector zone, temporary isolation


When does a ZONE have to be isolated?
ZONES equipped with automatic fire detectors or manual call points can be temporarily switched off (isolated). This
is only necessary in exceptional situations, for example, while major construction is in progress:
ZONE with smoke detectors if smoke or dust is produced by unusual work
ZONE heat detectors
if heat or steam is produced by unusual work
ZONE with manual call point if there is a possibility of inadvertent actuation
As soon as conditions have returned to normal, ISOLATED ZONES must be immediately switched on again.
Note
An isolated zone does not generate any alarm-, warning- or fault messages.

ZONE isolation procedure (Example ZONE fire)


1. Press F1 key
Enter password
The MAIN MENU overview is displayed

2. Press ok key
The AREAS overview is displayed
Press the
key to select the desired AREA

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select
AREAS
01 main building
02 factory

ok:section

3. Press ok key
The SECTIONS overview is displayed
Press the
key to select the desired SECTION

The selected ZONE is isolated


displayed spontaneously (if no messages of higher
priority are pending).

F1:function

F2:main menu

F1:function

ZONESfire
01 room 101
02 room 102
03 storage room
04 conference room
05 corridor
ok:element

5. Press F1 key
The FUNCTION LIST zone is displayed
Select the function set zone > OFF,
Press ok key to confirm

F2:main menu

SECTION fire
01 main building
02 factory

ok:section

4. Press ok key
The ZONES overview is displayed
Press the
key to select the desired ZONE

F1:function

F2:section

FUNCTION LIST zone :


set zone -> OFF
set zone -> ON
set zone -> TEST
set zone -> TEST OFF
set zone -> RENOVATION
set zone -> RENOVATION OFF
ok:execute
F1:zones
ISOLATION
01 detector zone OFF
main building/1st floor
conference room

select MESSAGE CATEGORY

F1:function

C:end
Total: 1

F1:function

14
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Detector zone, temporary isolation

cont.

ZONE reactivation procedure


1. Select the message category by pressing the Isolation key
The message is displayed in inverted colors

ISOLATION
01 detector zone OFF
main building/1st floor
conference room

ISL,^/v:scroll

2. Press F1 key
The FUNCTION LIST zone is displayed
Press the
key to select the function
set zone > ON and press the ok key
The ZONE is reactivated, that is, the isolation is cancelled

Total: 1

F1:function

FUNCTION LIST zone :


set zone -> OFF
set zone -> ON
set zone -> TEST
set zone -> TEST OFF
DISCONNECT all elements within zone
CONNECT all elements within zone
ok:execute
F1:zones
C:end

15
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Isolation of individual detectors


When does a detector have to be isolated ?
Only when it is damaged or defective until it is replaced.
Note
An isolated (element OFF) detector cannot generate any messages.
The isolation of detectors only makes sense if the corresponding ZONE is in position on

Isolate a detector via the menu


Steps 1 to 4 are identical to Zone isolation as described above
5. Press ok key
The ELEMENTS summary is displayed
Press the
key to select the desired ELEMENT

ELEMENTS fire
01 conference room
02 conference room
03 conference room
04 conference room

F2:zone

6. Press F1 key
The FUNCTION LIST element is displayed
Press the
key to select the function set element>OFF
and press the ok key
The selected detector is isolated and displayed spontaneously if no messages of higher priority are pending.
Note
If all elements of a ZONE are OFF, the corresponding
zone is automatically isolated and all element isolation
messages are cancelled.
The reactivation is only on the level ZONE possible.

Reactivate a detector (element)


1. Select the message category by pressing the Isolation key.
The message is displayed in inverted colors.

FUNCTION LIST element:


poll INFORMATION element
set element -> OFF
set element -> ON
ACTIVATE element
DEACTIVATE element
ok:execute

F1:element

ISOLATION
01 detector OFF
main building / 1st floor
conference room

select MESSAGE CATEGORY


ISOLATION
01 detector OFF
main building / 1st floor
conference room

select MESSAGE CATEGORY

2. Press F1 key
The FUNCTION LIST element is displayed
key to select the function set element> ON
Press the
and press the ok key
The detector is reactivated

Isolate a detector when a fault message is pending


1. Select the message category by pressing the Faults key, then
select the desired message by scrolling with the
key, if necessary. The selected message is displayed in inverted colors.

The detector is reactivated

C:end

Total: 1

F1:function
Total: 1

F1:function

FUNCTION LIST element


poll INFORMATION element
set element -> OFF
set element -> ON
ACTIVATE element
DEACTIVATE element
ok:execute

F1:element

C:end

FAULTS
01 detector
main building / 1st floor
room 102

FLT,^/v:scroll

2. Press F1 key
The FUNCTION LIST element is displayed
Press the
key to select the function set element>OFF
and press the ok key to confirm

F1:function

F1:function

FUNCTION LIST element


poll INFORMATION element
set element -> OFF
set element -> ON
ACTIVATE element
DEACTIVATE element
ok:execute

F1:element

C:end

16
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Fault
Wath to do in case of reported fault messages?
1. Confirm the message by pressing the Acknowledge key
2. Read the fault location on the display
3. Go to the fault location
4. If the fault cannot be removed call the Cerberus service organization

What remedies are available to the user?


Defective automatic detector
Go to the location of the defective detector,
if the detector is missing:
reinsert the detector

FAULTS
01 detector
main building / 1st floor
room 102

select MESSAGE CATEGORY

Total: 1

F1:function

if the detector is defective:


replace it with a spare detector
Important: only replace a defective detector with a
unit of the same type.

Defective manual call point


Go the location of the defective call point,
if the glass pane is broken:
replace the glass pane

FAULTS
01 call point GLASS BROKEN
main building / 2ND floor
CORRIDOR

select MESSAGE CATEGORY

Total: 1

F1:function

if there is any other defect:


call the Cerberus service organization

Printer out of paper


Go to the printer,
insert a new paper roll,
see section Printer: Paper replenishing, page 27

FAULTS
01 printer terminal PAPER END
main building / 1st floor
conference room

select MESSAGE CATEGORY

Total: 1

F1:function

Mains supply failure


Mains failure in the public supply network:
no action required
the emergency power battery supplies the system for
at least 12 hours (depending on the users specification up to 72 hours)
Mains supply ok:
check the power fuse (main distribution panel of the building)
and replace the fuse, if it is blown.

FAULTS
01 mains failure
control unit, basement

select MESSAGE CATEGORY

Total: 1

F1:function

For all other faults call the Cerberus service organization

17
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Mode Detector test


What is the Detector test mode for?
The mode Detector test allows individual on-site function testing of automatic fire detectors and manual call points
without generating an alarm message.
Automatic fire detectors
Are actuated with a special detector tester.
Interactive detectors are set to the special parameter set Test in order to achieve a fast activation with the detector
tester.
Manual call points are activated depending on the type:
From externally without breaking the glass pane or opening the housing.
Simply by opening the door of the manual call point.
Test alarm
Is the active state of automatic fire detectors or manual call points in Detector test mode. A test alarm does not
generate a danger message in the control console. That means that neither acoustical alarm devices nor remote
transmission or any other control functions are activated.
Test alarms are recorded in the event memory and logged spontaneously, if a printer is connected.
How to set detectors or manual call points to mode Detector test?
This is normally done on the section level, but also possible on the zone level.
It is not possible to set an individual fire detector or manual call point (element) to Detector test.
Zones or sections set to Detector test are displayed spontaneously as a message in the category Isolation

Set all detector zones within a SECTION to Detector test


1. Press F1 key
Enter the password
Display: Main Menu
Press the
key to select the desired menu item.

2. Press ok key
The AREAS overview is displayed
key to select the desired AREA
Press the

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select
AREAS
01 main building
02 factory

ok:section

3. Press ok key
The SECTIONS overview is displayed
Press the
key to select the desired SECTION

F2:main menu

F1:function

SECTIONS
01 ground floor
02 1st floor
03 lift shaft
04 2nd floor
ok:zone

4. Press F1 key
The FUNCTION LIST section is displayed
With the
key select the function set all DETECTOR zones
> TEST and press the ok key (automatic detectors only).

F1:function

F2:area

F1:function

FUNCTION LIST section :


set all DETECTOR zones -> OFF
set all DETECTOR zones -> ON
set all CALL POINT zones -> OFF
set all CALL POINT zones -> ON
set all DETECTOR zones -> TEST
terminate TEST of all DETECTOR zones
ok:execute
F1:sections
C:end

All zones of automatic detectors that belong to this section


are set to Detector test
Indicator Detector test mode is on
Same procedure for manual call points
18
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Mode Detector test

cont.

Recommendations for detector test


Perform the function test periodically. The interval of this test is determined by the service engineer.
Switch only the fire detectors of one SECTION at a time to Detector test, never the entire building.
For manual call points the function test needs to be performed only based on a spot-check.
Test automatic fire detectors and manual call points of the same room always separately.
Do not set them to Detector test simultaneously.
After the test work has been completed immediately cancel the mode Detector test.

Testing of automatic AlgoRex detectors

Neural smoke detector

1. Set the SECTION (or zone) to Detector test mode.


2. Place the detector tester on the detector.
Observe the marking!
For smoke detectors and multisensor smoke detectors the
detector exchanger and tester DZ1193 is needed:
For heat detectors the detector tester RE6T is required:
The temperature rise is simulated with a hot-air blower

Heat detector
Smoke detector

3. Wait until the response indicator on the detector flashes.


4. Remove the detector tester.
The function test is completed. Go to next detector
Note
Smoke detectors, multisensor smoke detectors and heat detectors have different housings (see illustration).

Detector exchanger
and tester DZ1193

Detector tester
RE6T

Testing of manual call points


Manual call points DM1101, DM1151 (type KAC)
1. Set the manual call point ZONE to Detector test mode.
2. Insert the test key into the opening
Test alarm is simulated.
3. Wait until the response indicator of the manual call point
flashes.
4. Remove the test key.

Test key

The function test is completed

19
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Mode Detector test

cont.

Manual call point (type Cerberus indirect operation)


1. Set the manual call point ZONE to Detector test mode.
2. Open the door of the manual call point with the key.
3. Press in the button Test alarm is simulated.
4. Wait until the response indicator of the manual call point
flashes.
5. Close the door.
key

The function test is completed


Manual call point (type Cerberus direct operation)
1. Set the manual call point ZONE to Detector test mode.
2. Open the door of the manual call point with the key
Test alarm is simulated.
3. Wait until the response indicator of the manual call point
flashes.
4. Close the door.
The function test is completed

Terminate Detector test for all detector zones within a SECTION


1. Press F1 key
The MAIN MENU overview is displayed

2. Press ok key
The AREAS overview is displayed
key to select the desired AREA
Press the

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select
AREAS
01 main building

ok:section

3. Press ok key
The SECTIONS overview is displayed
Press the
key to select the SECTION that is on detector
test

The Detector test is now cancelled for all detector


zones of this section

F2:main menu

F1:function

SECTIONS
01 ground floor
02 1st floor
03 lift shaft
04 2nd floor
ok:zone

4. Press F1 key
The FUNCTION LIST section is displayed
With the
key select the function terminate TEST of all
DETECTOR zones and press the ok key

F1:function

F2:area

F1:function

FUNCTION LIST section :


set all DETECTOR zones -> OFF
set all DETECTOR zones -> ON
set all CALL POINT zones -> OFF
set all CALL POINT zones -> ON
set all DETECTOR zones -> TEST
terminate TEST of all DETECTOR zones
ok:execute
F1:sections
C:end

20
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Mode Detector test

cont.

Poll test alarms in the event memory


1. Press F1 key
Enter the password
Display: Main Menu
Press the
key to select DEVICE level

2. Press ok key
The STATIONS overview is displayed
Press the
key to select the desired STATION

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

STATIONS
01 CC1142 CBUS no1
02 CI1142 CBUS no2
05 CT1142 CBUS no5

ok:function unit

3. Press F1 key
The function list Control unit is displayed
Press the
key to select poll EVENT MEMORY

The TEST Alarms are displayed


use the ^/v to poll the test alarms

F1:function

FUNCTION LIST control unit:


poll INFORMATION control unit
poll EVENT MEMORY (control unit)
set PRINTER
set PRINTER (control unit)-> OFF
set PRINTER (control unit)-> ON
ok:zone

4. Press ok key
The function list Event Memory is displayed
key to select poll all TEST ALARM
Press the
messages

F1:function

F2:area

F1:function

FUNCTION LIST event memory:


poll all messages
poll all DANGER messages
poll all FAULT messages
poll all DISCONNECTION messages
poll all INFORMATION messages
poll all TEST-ALARM messages
ok:execute
F1:station
F2:->date/time
EVENT MEMORY
**** TO OF LIST ****
03-SEPT-1997 16:15:52
INFORMATION
+detector TEST ACTIVATION
main building / 1st floor
room 102
04-SEPT-1997 09:00:59
INFORMATION
^/v:scroll
F1:print
F2:->date/time

21
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Mode Installation test


What is the mode Installation test for?
The mode Installation test allows to test the correct function of the whole fire detection system including fire controls, acoustical alarm devices, etc. All functions remain enabled.
Make sure that the remote transmission is switched off or the fire department is informed about the test activities.
In the mode Installation test interactive detectors become more sensitive and respond faster (response behavior
as in mode Detector test).
The mode Installation test shall be carried out only by security staff and serves basically to test the alarm
organization and fire controls.
After the test work has been completed immediately cancel the mode Installation test.
Mode Installation test is normaly enabled and disabled on the level ZONE but also possible on the level SECTION

Setting a zone to mode Installation test


1. Press F1 key
The MAIN MENU is displayed

2. Press ok key
The AREAS overview is displayed
key to select the desired AREA
Press the

3. Press ok key
The SECTIONS overview is displayed
Press the
key to select the desired SECTION

4. Press ok key
The ZONES overview is displayed
Press the
key to select the desired ZONE

5. Press F1 key
The FUNCTION LIST zone is displayed
key scroll to the function set zone
With the
> INSTALLATION TEST and press ok key
The ZONE is set to mode Installation test

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

F1:function

AREAS
01 main building

ok:section

F2:main menu

F1:function

SECTIONS fire
01 ground floor
02 1st floor
03 lift shaft
04 2nd floor
ok:zone

F2:area

F1:function

ZONES fire
01 room 101
02 1st floor
03 storage room
04 conference room
05 corridor
ok:element

F2:section

F1:function

FUNCTION LIST zone :


set zone -> TEST OFF
set zone -> RENOVATION
set zone -> RENOVATION OFF
ACTIVATE zone
set zone -> INSTALLATION TEST
set zone -> INSTALLATION TEST OFF
ok:execute
F1:zones
C:end

Termination of mode Installation test of a zone


1. Press the Information key and select the desired message by
pressing the
key, if necessary. The selected message is displayed in inverted colors.

INFORMATION
01 detector zone INSTALL. TEST
main building / 1st floor
conference room

INF,^/v:scroll

2. Press F1 key
The FUNCTION LIST zone is displayed
With the
key scroll to the function set zone
> INSTALLATION TEST OFF and press the ok key
The ZONE is set to normal operation mode

F2:detail

Total: 1

F1:function

FUNCTION LIST zone:


set zone -> TEST OFF
set zone -> RENOVATION
set zone -> RENOVATION OFF
ACTIVATE zone
set zone -> INSTALLATION TEST
set zone -> INSTALLATION TEST OFF
ok:execute
F1:zones
C:end

22
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Mode Renovation
What is the Renovation mode for?
In Renovation mode, automatic detectors are much less sensitive. This may be required while unusual work is in
progress (e.g. during renovation of a building).
The fire detection system remains working, the remote transmission of alarm and fault messages is enabled. Manual
call points work as in normal operation mode.
Detectors in the mode Renovation are from the insurance and approval point of view out of order. This is why the
isolation message is generated. Mode Renovation is enabled and disabled on the level ZONE only.
Mode Renovation is enabled and disabled on the level ZONE only.

Setting a zone to mode Renovation


1. Press F1 key
The MAIN MENU is displayed

2. Press ok key
The AREAS overview is displayed
Press the
key to select the desired AREA

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select
AREAS
01 main building

ok:section

3. Press ok key
The SECTIONS overview is displayed
key to select the desired SECTION
Press the

F1:function

F2:area

F1:function

ZONES fire
01 room 101
02 1st floor
03 storage room
04 conference room
05 corridor
ok:element

5. Press
key
The FUNCTION LIST zone is displayed
With the
key scroll to the function set zone
> RENOVATION and press ok key

F2:main menu

SECTIONS fire
01 ground floor
02 1st floor
03 lift shaft
04 2nd floor
ok:zone

4. Press ok key
The ZONES overview is displayed
Press the
key to select the desired ZONE

F1:function

F2:section

F1:function

F1

The ZONE is set to mode Renovation

FUNCTION LIST zone:


set zone -> TEST OFF
set zone -> RENOVATION
set zone -> RENOVATION OFF
ACTIVATE zone
set zone -> INSTALLATION TEST
set zone -> INSTALLATION TEST OFF
ok:execute
F1:zones
C:end

Termination of mode Renovation of a zone


1. Press the Isolation key and select the desired message by
pressing the
key, if necessary. The selected message is
displayed in inverted colors.

ISOLATION
01 detector zone RENOVATION
main building / 1st floor
conference room

ISL,^/v:scroll

2. Press F1 key
The FUNCTION LIST zone is displayed
With the
key scroll to the function set zone
> RENOVATION OFF and press the ok key
The ZONE is set to normal operation mode

Total: 1

F1:function

FUNCTION LIST zone:


set zone -> TEST OFF
set zone -> RENOVATION
set zone -> RENOVATION OFF
ACTIVATE zone
set zone -> INSTALLATION TEST
set zone -> INSTALLATION TEST OFF
ok:execute
F1:zones
C:end

23
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Remote transmission OFF/ON


This system is equipped with a remote transmission facility
for FIRE ALARM

p Yes, destination:
p No

for FAULT

p Yes, destination:
p No

...............................................................................................

...............................................................................................

What is Remote transmission?


Remote transmission establishes a transmission path to the fire department in the event of a FIRE ALARM.
For FAULT there is normally a separate path established.

When is the remote transmission switched off?


Normally the remote transmission operates in active stand-by, it is only switched off in special cases, for example, for
testing the control functions. For this test the Remote alarm off key 1 on the control console is pressed. The
OFF state is signalled by the indicator 2 .

Alarms

Faults

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

Detector
test mode

Control function
off

System
on

System
fault

F1

F2

ok

Isolation

Information

Switching the remote transmission OFF


Press key 1
(Requires corresponding operator access levels)
The corresponding isolation message is displayed
Indicator 2 turns on

ISOLATION
Total: 2
01 remote transmission fire OFF
main building
01
remote transmission channel FIRE
02 remote transmission fire OFF
factory
01
remote transmission channel FIRE
select MESSAGE CATEGORY
F1:function

The FIRE ALARM remote transmission is switched off

Switching the remote transmission ON


Press key 1
Indicator

turns off

The FIRE ALARM remote transmission is switched to standby

Note
The remote transmission can also be switched OFF and ON via the menu, separately for Alarm and Fault.
The remote transmission must be periodically checked by activating a manual call point. The fire department must be
notified before the test is initiated.

24
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Alarm devices OFF/ON


When do alarm devices (horns, sirens, etc.) have to be switched OFF?
Normally the alarm devices operate in active stand-by. They are only switched off in special cases, for example, for
testing the control functions.

Alarms

Faults

Premises
manned

Alarm device
off

Alarm device
active

Alarm device
fault

Alarm delay
off

Remote alarm
off

Remote alarm
active

Remote transmission
fault

Detector
test mode

Control function
off

System
on

System
fault

F1

F2

ok

Isolation

Information

Switching the alarm devices OFF


Press key 1
The corresponding isolation message is displayed
Indicator 2 turns on
The alarm device is switched OFF

ISOLATION
01 external horn OFF
main building
external horn (horn II)
02 internal horn OFF
main building
internal horn (horn I)
select MESSAGE CATEGORY

Total: 8

F1:function

Switching the alarm devices ON


Press key 1
Indicator

turns on

The alarm device is switched to stand-by

Note
The alarm devices can also be switched OFF and ON via the menu.

25
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Printer OFF/ON
This system is equipped with a printer p Yes
p

Level of operating access:


p control unit
p terminal

No

When does the printer have to be switched OFF?


Normally the printer (if installed) operates in active stand-by. It is only switched off in special cases (for example to
change the paper). The printer can be switched OFF and ON via the menu. The OFF state is shown on the display.

Switching the printer OFF


1. Press F1 key
The MAIN MENU is displayed
With the
key choose the function DEVICE level

2. Press ok key
The STATIONS overview is displayed
Press the
key, if necessary, to select the desired station
(control unit or terminal)

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

F1:function

STATIONS
01 control unit CC1140 ground floor
02 terminal CT11 corridor 1st floor

ok:function unit

F1:function

FUNCTION LIST control unit:


poll INFORMATION control unit
poll EVENT MEMORY (control unit)
set printer (control unit) -> OFF
set printer (control unit) -> ON
initiate PRINTER TEST (control unit)

3. Press F1 key
The FUNCTION LIST control unit is displayed
key to select set PRINTER > OFF and
Press the
ok:execute
press the ok key

F1:stations

C:end

The printer is switched OFF

Switching the printer ON


1. Press the Isolation key and select the desired message by
pressing the
key, if necessary. The selected message is
displayed in inverted colors.

ISOLATION
Total: 1
01 printer control unit OFF
control unit CC1140 ground floor

ISL,^/v:scroll

2. Press F1 key
The FUNCTION LIST control unit is displayed
With the
key select the function set PRINTER > ON
and press the ok key
The printer is switched ON

F1:function

FUNCTION LIST control unit:


poll INFORMATION control unit
poll EVENT MEMORY (control unit)
set printer (control unit) -> OFF
set printer (control unit) -> ON
initiate PRINTER TEST (control unit)
ok:execute

F1:stations

C:end

26
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Printer B2Q191: Paper replenishing


p Yes, system equipped with printer B2Q191
p No printer of this type installed

Switch off printer first


Swing out printer unit

Remove the used


paper roll

Valid for this system

Lift the paper flap and and


slide a new paper roll over
the spindle

The paper can be


transported by means of
the knurled wheel

4
7

Press the winding up key


Switch on printer again

Press the leading edge of the paper


lightly against the flap and feed it into the
printer through the slot.
Push down the release lever A to insert
the paper.

Thread the leading edge


of the paper around the
take-up roller and fix it
with the clamp

Print intensity
If the print intensity is too low, call the Cerberus service organization.

Spare paper rolls


Cerberus part no. 379 977 (= 4 pcs.)
or JUJU TP 50KS-A
HONSHU PS 65 B1
MITSUBISHI F-200 U7X

27
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Lamp test
What is the Lamp test used for?
For testing the correct functioning of all indicators (LEDs), the display, and the alarm buzzer.
All visual and audible devices of the control console are activated for a few seconds.

Initiate lamp test


1. Press F1 key
The MAIN MENU is displayed
With the
key choose the function DEVICE level

2. Press ok key
The STATIONS overview is displayed
Press the
key to select the desired station (terminal)

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

STATIONS
01 control unit CC1140 ground floor
02 terminal CT11 corridor 1st floor

ok:function unit

3. Press F1 key
The FUNCTION LIST terminal is displayed
key to select initiate LAMP TEST and press
Press the
the ok key
The lamp test is initiated

F1:function

F1:function

FUNCTION LIST terminal:


poll INFORMATION terminal
initiate LAMP TEST
set contrast of DISPLAY
set sound level of BUZZER
poll EVENT MEMORY (terminal)
set PRINTER (terminal) -> OFF
ok:execute
F1:stations

C:end

28
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Alarm counter
What is the purpose of polling the alarm counter?
The alarm counter shows the number of past alarm events.

Polling alarm counter


1. Press F1 key
The MAIN MENU is displayed

2. Press ok key
The AREAS overview is displayed
Press the
key to select the desired AREA

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select
AREAS
01 main building

ok:section

3. Press F1 key
The FUNCTION LIST area is displayed
key to select poll COUNTER fire alarms or
Press the
poll COUNTER remote alarms and press the ok key
The number of alarms is displayed

F1:function

F2:main menu

F1:function

FUNCTION LIST area:


switching PRESENT/ABSENT
poll COUNTER fire alarms
reset COUNTER fire alarms
poll COUNTER remote alarms
external HORN -> ON
external HORN -> OFF
ok:execute
F1:areas

C:end

COUNTER fire alarms : 4

29
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Event memory
Polling event memory of an AREA
1. Press F1 key
The MAIN MENU is displayed

2. Press ok key
The AREAS overview is displayed
Press the
key to select the desired AREA

MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select
AREAS
01 main building
02 machine building
03 warehouse building

ok:section

3. Press F1 key
The FUNCTION LIST area is displayed
Press the
key to select poll EVENT MEMORY

4. Press ok key
The FUNCTION LIST event memory is displayed
Press the
key, if necessary, to select the desired function
and press the ok key
The display now shows the desired list.
Either the latest entry is visible completely, older entries
(if existing) can be scrolled by pressing the
key
Note
with the key F2 :>date/time a entry of a
particular date/time can be selected and displayed.

F1:function

F2:main menu

F1:function

FUNCTION LIST area:


REMOTE transm. fire -> OFF
REMOTE transm. others -> ON
REMOTE transm. others -> OFF
REMOTE transm. fault -> ON
REMOTE transm. fault -> OFF
poll EVENT MEMORY
ok:execute
F1:areas

C:end

FUNCTION LIST event memory:


poll all messages
poll all DANGER messages
poll all FAULT messages
poll all DISCONNECTION messages
poll all INFORMATION messages
poll all TEST-ALARM messages
ok:execute
F1:areas
F2:->date/time
EVENT MEMORY
machine building
engine room
21-FEB-1996 11:26:43
INFORMATION
-detector zone INSTALL. TEST
machine building
compressor room
^/v:scroll
F1:print
F2:->date/time

Printing selected entries of the event memory


Steps 1..4 are identical to Polling event memory of an area as described above

5. Press F1 key
The printout EVENT MEMORY menu is displayed
Press the F2 key to print all entries or
select desired range of date and time to print
out particular events.
and
keys to set date and time and press
Use the
the F1 key to select the next field.
Press the ok key to print out selected entries.

printout EVENT MEMORY


VV
Printout starts at: 08:00 21-FEB-1996
Printout stops at:
ok:set

08:00 21-FEB-1996

F1:nest field

F2:print all

printout EVENT MEMORY

During the print out procedure on the bottom line


a flashingprinting in inverted coulors is displayed.
... printing ...

Note
The event memory can only be printed out, if the printer is connected to the operated terminal.

30
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Set clock and date


Normally the date and time do not have to be corrected!
The date and time are set by the service engineer when installing the system.
The summer/winter time changeover is performed automatically.
Time and date are always displayed when the password is entered.

Setting the clock


MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

1. Press F1 key
The MAIN MENU is displayed

2. Press F1 key
The FUNCTION LIST installation is displayed

3. Press ok key
An input prompt is displayed
Enter the current time and press the ok key
(2 digits each for hours / minutes / seconds)

F1:function

FUNCTION LIST installation:


set CLOCK
set DATE
re-configuration C-bus

ok:execute

F1:main menu

C:end

SET CLOCK
HHMMSS

The new time is read in and loaded


0..9,del:edit

Setting the date

MAIN MENU
FIRE section
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

1. Press F1 key
The MAIN MENU is displayed

2. Press F1 key
The FUNCTION LIST installation is displayed
Press the
key to select the function set DATE

C:end

F1:function

FUNCTION LIST installation:


set CLOCK
set DATE
re-configuration C-bus

ok:execute

3. Press ok key
An input prompt is displayed
Enter the current date and press the
(2 digits each for day / month / year)

ok:set

F1:zones

C:end

SET DATE
ok

The new date is read in and loaded

key

DDMMYY

0..9,del:edit

ok:set

C:end

31
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Overview operating menus


MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

Note:
F1 = press key F1
ok = press key ok

Access level

F1:function

2.1

2.2

F1

FUNCTION LIST installation


set CLOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4
set DATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4
re-configuration C-bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST area


switching PRESENT/ABSENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll COUNTER fire alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
reset COUNTER fire alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll COUNTER remote alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > STOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
initiate TEST alarm HORN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fire > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fire > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. others > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. others > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fault > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fault > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll EVENT MEMORY . . . . . ok . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
...

........
........
........
........
........
........
........
........
........
........
........
........
........
........
........
........

4 ....... 4 .......
4 ....... 4 .......
......... ........
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
........ 4 .......

FUNCTION LIST event memory


poll all messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll all DANGER messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll all FAULT messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll all DISCONNECTION messages . . . . . . . . . . . . . . . . . . . .
poll all INFORMATION messages . . . . . . . . . . . . . . . . . . . . . . .
poll all TEST-ALARM messages . . . . . . . . . . . . . . . . . . . . . . . .

.......
.......
.......
.......
.......
.......

F1

FUNCTION LIST section


set all DETECTOR zones > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . .
set all DETECTOR zones > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set all CALL POINT zones > OFF . . . . . . . . . . . . . . . . . . . . . . . . . .
set all CALL POINT zones > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set all ZONES > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set all ZONES > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set all DETECTOR zones > TEST . . . . . . . . . . . . . . . . . . . . . . . . . .
terminate TEST of all DETECTOR zones . . . . . . . . . . . . . . . . . . . .
set all CALL POINT zones > TEST . . . . . . . . . . . . . . . . . . . . . . . . .
terminate TEST of all CALL POINT zones . . . . . . . . . . . . . . . . . . .
set all DETECTOR ZONES > INSTALL. TEST . . . . . . . . . . . . .
terminate INSTALL.TEST of all DET.zones . . . . . . . . . . . . . . . . . .

........ 4
........ 4
........ 4
........ 4
. . . . . . . (4)
. . . . . . . (4)
........ 4
........ 4
........ 4
........ 4
........ 4
........ 4

F1

FUNCTION LIST zone


set zone > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > TEST OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > RENOVATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > RENOVATION OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ACTIVATE zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > INSTALLATION TEST . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > INSTALLATION TEST OFF . . . . . . . . . . . . . . . . . . . . .

........
........
........
........
........
........
........
........
........

4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
......... ........
4 ....... 4 .......
4 ....... 4 .......

F1

FUNCTION LIST element


poll INFORMATION element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set element > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set element ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ACTIVATE element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DEACTIVATE element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHANGE parameter set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
parameter set -> DEFAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

........
........
........
........
........
........
........

4 ....... 4 ....... 4
4 ....... 4 ....... 4
4 ....... 4 ....... 4
........ 4 ....... 4
........ 4 ....... 4
. . . . . . . (4) . . . . . . (4)
. . . . . . . (4) . . . . . . (4)

select FIRE section


ok
AREAS...
ok

SECTIONS...
ok

ZONES...
ok

ELEMENTS...

......
......
......
......
......
......

4
4
4
4
4
4

......
......
......
......
......
......

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

....... 4 ....... 4
....... 4 ....... 4
....... 4 ....... 4
....... 4 ....... 4
. . . . . . (4) . . . . . . (4)
. . . . . . (4) . . . . . . (4)
....... 4 ....... 4
....... 4 ....... 4
....... 4 ....... 4
....... 4 ....... 4
....... 4 ....... 4
....... 4 ....... 4

4
4
4
4
4
4
4
4
4

see appendix 2

32
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Overview operating menus


MAIN MENU
FIRE section
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

cont.

Note:
F1 = press key F1
ok = press key ok

Access level

F1:function

2.2

t
F1

2.1

FUNCTION LIST installation


set CLOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4
set DATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4
re-configuration C-bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4

EXTINGUISHING sections (details see App endix 1)


ok

SECTIONS...
ok

FUNCTION LIST area


switching PRESENT/ABSENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll COUNTER fire alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
reset COUNTER fire alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll COUNTER remote alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > STOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
initiate TEST alarm HORN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fire > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fire > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. others > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. others > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fault > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fault > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll EVENT MEMORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ok

........
........
........
........
........
........
........
........
........
........
........
........
........
........
........
........

4 ....... 4 .......
4 ....... 4 .......
......... ........
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
........ 4 .......

FUNCTION LIST event memory


poll all messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll all DANGER messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll all FAULT messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll all DISCONNECTION messages . . . . . . . . . . . . . . . . . . . .
poll all INFORMATION messages . . . . . . . . . . . . . . . . . . . . . . .
poll all TEST-ALARM messages . . . . . . . . . . . . . . . . . . . . . . . .

AREAS...
ok

.......
.......
.......
.......
.......
.......

......
......
......
......
......
......

......
......
......
......
......
......

4
4
4
4
4
4

F1

FUNCTION LIST section


BLOCKING autom.extinguishing . . . . . . . . . . . . . . . . . . . . . . . .
ENABLING autom.extinguishing . . . . . . . . . . . . . . . . . . . . . . . .
BLOCKING autom.& man. extinguishing release . . . . . . . . . .
ENABLING autom.& man. extinguishing release . . . . . . . . . .
set all DETECTOR zones > OFF . . . . . . . . . . . . . . . . . . . . . . .
set all DETECTOR zones > ON . . . . . . . . . . . . . . . . . . . . . . . .
set all DETECTOR zones > TEST . . . . . . . . . . . . . . . . . . . . . .
terminate TEST of all DETECTOR zones . . . . . . . . . . . . . . . . .
set all DETECTOR zones >INSTALL: TEST . . . . . . . . . . . . .
terminate INSTALL.TEST of all DET. zones . . . . . . . . . . . . . . .
set extinguishing control > REVISION . . . . . . . . . . . . . . . . . . .
terminate REVISION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set extinguishing control > TEST . . . . . . . . . . . . . . . . . . . . . . .
terminate TEST of exting. control . . . . . . . . . . . . . . . . . . . . . . . .
initiate TEST horn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
initiate TEST warning panel . . . . . . . . . . . . . . . . . . . . . . . . . . .

.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......

4
4
4
4
4
4
4
4
4
4

...... 4 ......
...... 4 ......
...... 4 ......
...... 4 ......
...... 4 ......
...... 4 ......
...... 4 ......
...... 4 ......
...... 4 ......
...... 4 ......
...... 4 ......
...... 4 ......
....... .......
....... .......
....... .......
....... .......

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

F1

FUNCTION LIST zone


set zone > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > TEST OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > RENOVATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > RENOVATION OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ACTIVATE zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > INSTALLATION TEST . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > INSTALLATION TEST OFF . . . . . . . . . . . . . . . . . . . . .

........
........
........
........
........
........
........
........
........

4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
......... ........
4 ....... 4 .......
4 ....... 4 .......

F1

FUNCTION LIST element


poll INFORMATION element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set element > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set element OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ACTIVATE element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DEACTIVATE element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHANGE parameter set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
parameter set -> DEFAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

........
........
........
........
........
........
........

4 ....... 4 ....... 4
4 ....... 4 ....... 4
4 ....... 4 ....... 4
........ 4 ....... 4
........ 4 ....... 4
. . . . . . . (4) . . . . . . (4)
. . . . . . . (4) . . . . . . (4)

F1

4
4
4
4
4
4

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

see appendix 1

ZONES...
ok

ELEMENTS...

4
4
4
4
4
4
4
4
4

see appendix 2

33
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Overview operating menus


MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

cont.

Note:
F1 = press key F1
ok = press key ok

Access level

F1:function

2.1

2.2

F1

FUNCTION LIST installation


set CLOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4
set DATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4
re-configuration C-bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST area


switching PRESENT/ABSENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll COUNTER fire alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
reset COUNTER fire alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll COUNTER remote alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > STOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
initiate TEST alarm HORN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fire > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fire > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. others > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. others > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fault > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fault > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll EVENT MEMORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ok

control in/outputs
ok
AREAS...
ok

........
........
........
........
........
........
........
........
........
........
........
........
........
........
........
........

4 ....... 4 .......
4 ....... 4 .......
......... ........
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
........ 4 .......

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

FUNCTION LIST event memory


poll all messages
poll all DANGER messages
poll all FAULT messages
poll all DISCONNECTION messages
poll all INFORMATION messages
poll all TEST-ALARM messages

SECTIONS...
ok

ZONES...
ok

F1

FUNCTION LIST section


set all ZONES > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4
set all ZONES> ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST zone


set zone > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set zone > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ACTIVATE zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DEACTIVATE zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

........
........
........
........

4 ....... 4 .......
4 ....... 4 .......
......... ........
......... ........

4
4
4
4

F1

FUNCTION LIST element


poll INFORMATION element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISCONNECT element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONNECT element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ACTIVATE element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DEACTIVATE element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

........
........
........
........
........

4 .......
4 .......
4 .......
........
........

4
4
4
4
4

Note:
for time channels no function available

ELEMENTS...

4
4
4
4
4

.......
.......
.......
.......
.......

34
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Overview operating menus


MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

cont.

Note:
F1 = press key F1
ok = press key ok

Access level

F1:function

2.1

2.2

F1

FUNCTION LIST installation


set CLOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4
set DATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4
re-configuration C-bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST area


switching PRESENT/ABSENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll COUNTER fire alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
reset COUNTER fire alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll COUNTER remote alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alarm HORN > STOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
initiate TEST alarm HORN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fire > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fire > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. others > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. others > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fault > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REMOTE transm. fault > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll EVENT MEMORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ok

........
........
........
........
........
........
........
........
........
........
........
........
........
........
........
........

4 ....... 4 .......
4 ....... 4 .......
......... ........
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
4 ....... 4 .......
........ 4 .......

FUNCTION LIST event memory


poll all messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll all DANGER messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll all FAULT messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll all DISCONNECTION messages . . . . . . . . . . . . . . . . . . . .
poll all INFORMATION messages . . . . . . . . . . . . . . . . . . . . . . .
poll all TEST-ALARM messages . . . . . . . . . . . . . . . . . . . . . . . .

.......
.......
.......
.......
.......
.......

select GEOGRAPHICAL location


ok
AREAS...
ok

SECTIONS...

F1

......
......
......
......
......
......

4
4
4
4
4
4

......
......
......
......
......
......

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

FUNCTION LIST section


same as under
FIRE detection
EXTINGUISHING sections
CONTROL in-/outputs
but includes all types of sections

35
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Overview operating menus


MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

cont.

Note:
F1 = press key F1
ok = press key ok
F1:function

Access level
1

ok

FUNCTION LIST terminal


poll INFORMATION terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
initiate LAMP TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set contrast of DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set sound level of BUZZER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll EVENT MEMORY (terminal) . . . . . ok . . . . . . . . . . . . . . . . . . . . .
...
set PRINTER (terminal) > OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
set PRINTER (terminal) > ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
initiate PRINTER-TEST (terminal) . . . . . . . . . . . . . . . . . . . . . . . . . . .

terminal CT11 (CI11)


ok

2.2

DEVICE level

2.1

........
4 .......
........
........
4 .......
........
........
........

4
4
4
4
4
4
4
4

........
........
........
........
........
........
........
........

.......
.......
.......
.......
.......
.......
.......
.......

4
4
4
4
4
4
4
4

FUNCTION LIST event memory


poll all messages
poll all DANGER messages
poll all FAULT messages
poll all DISCONNECTION messages
poll all INFORMATION messages
poll all TEST-ALARM messages

I/Os of terminal unit B3Q460/80

power supply supervision

keys and indicators of CT11 panel

FBA panel

control unit CC11

F1

FUNCTION LIST function unit


poll INFORMATION function unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST function unit


poll INFORMATION function unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4
initiate BATTERY LOAD TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST function unit


poll INFORMATION function unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST function unit


poll INFORMATION function unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST control unit


poll INFORMATION control unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
poll EVENT MEMORY (control unit) . . . . . . . . . . . . . . . . . . . . . . . . .
set PRINTER (control unit) > OFF . . . . . . . . . . . . . . . . . . . . . . . . . .
set PRINTER (control unit) > ON . . . . . . . . . . . . . . . . . . . . . . . . . . .
initiate PRINTER-TEST (control unit) . . . .ok. . . . . . . . . . . . . . . . . .
..

ok

........
........
........
........
........

........
........
........
........
........

4
4
4
4
4

.......
.......
.......
.......
.......

4
4
4
4
4

FUNCTION LIST event memory


poll all messages
poll all DANGER messages
poll all FAULT messages
poll all DISCONNECTION messages
poll all INFORMATION messages
poll all TEST-ALARM messages

I/Os of control unit E3X100


ok
(device)

power supply supervision

(function unit)
ok
(device)

F1

FUNCTION LIST function unit


poll INFORMATION function unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST device


poll INFORMATION device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST function unit


poll INFORMATION function unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4
initiate BATTERY LOAD TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4

F1

FUNCTION LIST function unit


poll INFORMATION function unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4
...

F1

FUNCTION LIST device


poll INFORMATION device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4
...

36
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Overview operating menus


MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX.no.)
^/v ok:select

cont.

Note:
ok = press key ok

F1:function

Access level
1

2.1

2.2

logical address (CSX. no.)


ok
area / section / zone / element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 . . . . . . . 4 . . . . . . . 4

37
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Notes

38
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Notes

39
Fire & Security Products
Siemens Building Technologies Group

e1033e
10.1999

Siemens Building Technologies AG


Alte Landstrasse 411
CH8708 Mnnedorf
Tel. +41 1 922 61 11
Fax +41 1 922 64 50
www.cerberus.ch

40
Document no. e1033e
Fire & Security Products
Edition 10.1999
Siemens Building Technologies Group

Manual CS11.2

Back

Section 7
10.1999