Samsung CAC 2011 (Slim Duct) Service Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 112

Refer to the service manual in the GSPN(see the rear cover) for the more information.

AIR CONDITIONER CONTENTS


SYSTEM AIR CONDITIONER
Model : NS100SSXEA
NS090SDXEA
NS090SSXEA
NS090SSXEX
NS100SSXEX
NS100SDXEA
NS125SDXEA
NS140SDXEA
RC100SHXEA
RC090SHXEA
RC090DHXEA
RC100DHXEA
RC100DHXGA
RC125DHXEB
RC125DHXGA
RC140DHXEB
RC140DHXGA
INDOOR UNIT OUTDOOR UNIT
1. Precautions
2. Product Specifications
3. Disassembly and Reassembly
4. Troubleshooting
5. Exploded Views and Parts List
6. PCB Diagram
7. Wiring Diagram
8. Schematic Diagram
9. Reference Sheet
NS090SDXEA, NS100SSXEA
NS090SSXEA, NS090SSXEX, NS100SSXEX
NS100SDXEA
NS125SDXEA
NS140SDXEA
RC090DHXEA
RC090SHXEA
RC100SHXEA
RC100DHXEA
RC100DHXGA
RC125DHXEB
RC125DHXGA
RC140DHXEB
RC140DHXGA
NS100SSXEA_E_33623A(1)_co.indd 1 2011-04-08 10:52:44


Contents
11. Precautions
........................................................................................................................................
1-1
1-1 Precautions for the Service
..............................................................................................................
1-1
1-2 Precautions related to static electricity and PL
............................................................................
1-1
1-3 Precautions related to product safety
...........................................................................................
1-2
1-4 Other precautions
..............................................................................................................................
1-2

12. Product Specifications
...............................................................................................................
2-1
2-1 The Feature of Product
.....................................................................................................................
2-1
2-2 Product Specifications
......................................................................................................................
2-2
2-3 Specifications of optional items
......................................................................................................
2-6
2-3-1 Accessories
...............................................................................................................................
2-6
13. Disassembly and Reassembly ............................................................................................... 3-1
3-1 Indoor Unit ......................................................................................................................................... 3-2
3-2 Outdoor Unit ..................................................................................................................................... 3-7

14. Troubleshooting
............................................................................................................................
4-1
4-1 Indoor Display Error and Check Method ..................................................................................... 4-1
4-1-1 Wired Remocon Error Display(COM2) ................................................................................ 4-2
4-2 Outdoor LED Error Display and Check Method ........................................................................... 4-3
4-3 Setting Option Setup Method ........................................................................................................ 4-4
4-3-1 Type A(Setting Option) ......................................................................................................... 4-4
4-3-2 Type B(Setting Option Setup Method) ............................................................................... 4-6
4-3-3 Option code for each model ................................................................................................ 4-16
4-4 Items to be checked first ................................................................................................................. 4-17
4-5 Fault Diagnosis by Symptom .......................................................................................................... 4-18
4-5-1 No Power(completely dead) - Initial diagnosis
.................................................................
4-18
4-5-2 The Outdoor unit Power Supply error
................................................................................
4-19
4-5-3 The Outdoor unit Fan error
..................................................................................................
4-20
4-5-4 Total current trip error
...........................................................................................................
4-21
4-5-5 In case of heating at the cooling mode or cooling at the heating mode
....................
4-22
4-5-6 Outdoor temperature sensor error
.....................................................................................
4-24
4-5-7 Discharge temperature sensor error
..................................................................................
4-25
4-5-8 Coil temperature sensor error
..............................................................................................
4-26
4-5-9 Fan error
...................................................................................................................................
4-27
4-5-10 DC-Link voltage sensor error
.............................................................................................
4-28
4-5-11 O.C.(Over Current) error
......................................................................................................
4-29
NS090SDXEA_E_SM_33623A(1)_1.indd 1 2011-04-08 10:54:25

Contents
4-5-12 Communication error
..........................................................................................................
4-30
4-5-13 Compressor start error
........................................................................................................
4-31
4-5-14 Compressor lock error
.........................................................................................................
4-32
4-5-15 DC Link Over voltage/ Low voltage error
........................................................................
4-33
4-6 PCB Inspection Method ................................................................................................................... 4-34
4-6-1 Pre-inspection Notices
...........................................................................................................
4-34
4-6-2 Inspection Procedure
............................................................................................................
4-34
4-6-3 Indoor Detailed Inspection Procedure
...............................................................................
4-34
4-6-4 Outdoor Detailed Inspection Procedure
...........................................................................
4-35
4-7 Main Part Inspection Method ......................................................................................................... 4-36
15. Exploded Views and Parts List
.............................................................................................
5-1
5-1 Indoor Unit
.........................................................................................................................................
5-1
5-2 Outdoor Unit
.....................................................................................................................................
5-7
5-3 Ass'y Control Out
..............................................................................................................................
5-11
16. PCB Diagram
.....................................................................................................................................
6-1
6-1 PCB Diagram
......................................................................................................................................
6-1
6-1-1 Indoor Unit
..............................................................................................................................
6-1
6-1-2 Outdoor Unit PCB
...................................................................................................................
6-3

17. Wiring Diagram
..............................................................................................................................
7-1
6-1 Indoor Unit
.........................................................................................................................................
7-1
6-1 Outdoor Unit
.....................................................................................................................................
7-2
18. Schematic Diagram
......................................................................................................................
8-1
8-1 Indoor Unit
.........................................................................................................................................
8-1
8-1-1 MAIN PCB
.................................................................................................................................
8-1
8-1-2 Outdoor Unit PCB
...................................................................................................................
8-2
1
9. Reference Sheet
..............................................................................................................................
9-1
9-1 Index for Model Name
......................................................................................................................
9-1
9-2 Refrigerating Cycle Diagram
............................................................................................................
9-3
9-3 Pressure Graph
...................................................................................................................................
9-4
NS090SDXEA_E_SM_33623A(1)_1.indd 2 2011-04-08 10:54:25
Samsung Electronics 1-1
1. Precautions
1-1 Precautions for the Service
Use the standard parts when replacing the electric parts.
Confirm the model name, rated voltage, rated current of the electric parts.
When repairing the equipment, connection of the harness parts must be firm and solid.
A loose connection may cause noise or other malfunction.
When assembling and disassembling the equipment while it is laid down, lay it on soft cloth.
Otherwise it may scratch the back of the exterior of the product.
Remove dust or dirt completely from the housing block, wiring block and service parts during repair.
This helps prevent the danger of fire caused by tracking or short circuit.
Fasten the valve caps of service valves and charging valves of outdoor unit as much as possible using adjustable wrenches.
Check the status of the components assembly after repair service.
The status must be the same as before the repair service.
1-2 Precautions related to static electricity and PL
The PCB power supply block is susceptible to static electricity. Therefore, care must be taken during repair or measuring
while the power is on.
Wear insulation gloves for PCB repair or measuring.
Check whether the installation location is at least two meters away from other electronic products such as TV, video, or
audio.
Otherwise, the video quality might be degraded or noise might be generated.
Do not let end users repair the products themselves.
Unauthorized disassembly might cause electric shock or fire.
NS090SDXEA_E_SM_33623A(1)_1.indd 1 2011-04-08 10:54:26
1-2 Samsung Electronics
1-3 Precautions related to product safety
Do not pull the power cord and do not touch the power plug or aux power switch with wet hands.
It might cause electric shock or fire.
A damaged power line or power plug must be replaced to prevent danger.
Do not bend the power cable with excessive force, and do not place a heavy weight on the case as it might damage the
cable.
It might cause electric shock or fire.
Do not use multiple electric outlets.
This might cause electric shock or fire.
Connect the ground terminal when necessary.
You must connect the ground terminal if you determine that there is a danger of electric leakage due to moisture or water.
Unplug the power cable or turn off the auxiliary power switch for electric part replacement and repair service.
Otherwise it might cause electric shock.
Instruct end users to separate the batteries from the remote controllers and store them separately when the product is not
used for long time.
Otherwise leakage from the dry cell may cause problems with the remote controller.
1-4 Other precautions
The pipes should have no leaks during installation, and the compressor must be stopped before removing connecting
pipes for pump down work. Operating the compressor while the service valve is open and coolant pipe is not properly
connected may cause explosion or injury due to abnormal high pressure created inside the coolant cycle as the air can be
absorbed through the pipe.
Pump Down work procedure (When uninstalling the product)
Turn on the air conditioner, select cooling operation, and run the compressor for more than three minutes.
Release the high pressure and low pressure valve caps.
Close the high pressure valve completely using an L-wrench
After about two minutes, close the low pressure valve completely.
Stop running the air conditioner.
Separate the connecting pipe.
NS090SDXEA_E_SM_33623A(1)_1.indd 2 2011-04-08 10:54:26
Samsung Electronics 2-1
2. Product Specifications
2-1 The Feature of Product
Built-in Cassette Type
After installed, the air conditioner can be harmonized with a room interior.
High Performance & Energy Saving
With the advanced BLDC inverter technology, it makes a room cool with highly energy saving and arises the efficiency of
air conditioner.
Long Piping(Length & Height)
It can give the benefit to the installers and aries the reliability of the air conditioner.
Long Ambient Operation(In Low Temperature)
It can arise the reliability and the capacity of the air conditioner, especially operated in low temperature.
Eco-friendly Product(Lead-Free, RoHS, WEEE)
NS090SDXEA_E_SM_33623A(1)_1.indd 1 2011-04-08 10:54:26
2-2 Samsung Electronics
ITEM
NS090SDXEA
/RC090DHXEA
NS090SSXEA
NS090SSXEX
/RC090SHXEA
NS100SSXEA
NS100SSXEX
/RC100SHXEA
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 1, 220~240V/50Hz 1, 220~240V/50Hz 1, 220~240V/50Hz
Indoor L x H x D mm 1150x480x320 1150x480x260 1150x480x260
Outdoor L x H x D mm 940x330x998 940x330x998 940x330x998
Indoor Product kg(Net) 39.0 34.0 34.0
Outdoor Product kg(Net) 72.0 72.0 72.0
Capacity
Cooling(STD) W 9000 9000 10000
Heating(STD) W 10000 9500 11200
Power
Consumption
Cooling(STD) W 2800 3200 3560
Heating(STD) W 2770 2780 3720
Operation
current
Cooling(STD) A 13.0 14.0 16.0
Heating(STD) A 12.5 13.0 15.0
Noise
(Cooling/
Heating)
Indoor unit
In case of strongest air
blow
A 48/49 49/50 49/50
Outdoor unit
In case of strongest air
blow
A 58/60 59/62 59/62
Refrigerant g 3000 2500 2500
Connecting Pipe
Liquid mm 9.52 9.52 9.52
Gas mm 15.88 15.88 15.88
Additional Refrigernat g/m 50 50 50
Standard m 5 5 5
Extension length(Total) m 50 50 50
Extension length(Elevation) m 30 30 30
Option Code
Product Option
011044-156299-
275A64-350000
011044-156293-
275A64-370000
011044-156293-
276470-370000
Installation Option
020000-100000-
200000-300000
020000-100000-
200000-300000
020000-100000-
200000-300000
2-2 Product Specifications
NS090SDXEA_E_SM_33623A(1)_1.indd 2 2011-04-08 10:54:26
Samsung Electronics 2-3
ITEM NS100SDXEA/RC100DHXEA NS100SDXEA/RC100DHXGA
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 1, 220~240V/50Hz 3, 380~415V/50Hz
Indoor L x H x D mm 1200x650x360 1200x650x360
Outdoor L x H x D mm 940x330x998 940x330x998
Indoor Product kg(Net) 55.0 55.0
Outdoor Product kg(Net) 72.0 81.0
Capacity
Cooling(STD) Btu or W 10000 10000
Heating(STD) Btu or W 11200 11200
Power
Consumption
Cooling(STD) W 3120 3120
Heating(STD) W 3100 3100
Operation
current
Cooling(STD) A 13.8 5.0
Heating(STD) A 13.5 5.0
Noise
(Cooling/
Heating)
Indoor unit
In case of strongest air
blow
dB 49/50 49/50
Outdoor unit
In case of strongest air
blow
dB 59/63 59/63
Refrigerant g 3000 3100
Connecting Pipe
Liquid mm 9.52 9.52
Gas mm 15.88 15.88
Additional Refrigernat g/m 50 50
Standard m 5 5
Extension length(Total) m 50 50
Extension length(Elevation) m 30 30
Option Code
Product Option 011044-1560E8-276470-370000 011044-1560E8-276470-370000
Installation Option 020000-100000-200000-300000 020000-100000-200000-300000
Product Specifications (cont.)
NS090SDXEA_E_SM_33623A(1)_1.indd 3 2011-04-08 10:54:27
2-4 Samsung Electronics
Product Specifications (cont.)
ITEM NS125SDXEA/RC125DHXEB NS125SDXEA/RC125DHXGA
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 1, 220~240V/50Hz 3, 380~415V/50Hz
Indoor unit Product L x H x D mm 1200x650x360 1200x650x360
Outdoor unit Product L x H x D mm 940x330x1210 940x330x1210
Indoor unit Product kg(Net) 55.0 55.0
Outdoor unit Product kg(Net) 88.0 91.0
Capacity
Cooling(STD) Btu or W 12500 12500
Heating(STD) Btu or W 14000 14000
Power consumption
Cooling(STD) W 3890 3890
Heating(STD) W 3880 3880
Operation current
Cooling(STD) A 17.8 6.0
Heating(STD) A 17.8 6.0
Noise
(Cooling/Heating)
Indoor
unit
In case of strongest
air blow
dB 50/51 50/51
Outdoor
unit
In case of strongest
air blow
dB 59/61 59/61
Refrigerant g 2900 2900
Connecting Pipe
Liquid mm 9.52 9.52
Gas mm 15.88 15.88
Additional Refrigerant(g/m) g/m 50 50
Standard m 5 5
Extension length(Total) m 75 75
Extension length(Elevation) m 30 30
Option Code
Product
Option
011044-1570F8-277D8C-370000 011044-1570F8-277D8C-370000
Installation
Option
020000-100000-200000-300000 020000-100000-200000-300000
NS090SDXEA_E_SM_33623A(1)_1.indd 4 2011-04-08 10:54:29
Samsung Electronics 2-5
ITEM NS140SDXEA/RC140DHXEB NS140SDXEA/RC140DHXGA
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 1, 220~240V/50Hz 3, 380~415V/50Hz
Indoor unit Product L x H x D mm 1200x650x360 1200x650x360
Outdoor unit Product L x H x D mm 940x330x1210 940x330x1210
Indoor unit Product kg(Net) 55.0 55.0
Outdoor unit Product kg(Net) 88.0 91.0
Capacity
Cooling(STD) Btu or W 14000 14000
Heating(STD) Btu or W 16000 16000
Power consumption
Cooling(STD) W 4650 4650
Heating(STD) W 4430 4430
Operation current
Cooling(STD) A 21.3 7.2
Heating(STD) A 20.3 6.9
Noise
(Cooling/Heating)
Indoor
unit
In case of strongest
air blow
dB 50/51 50/51
Outdoor
unit
In case of strongest
air blow
dB 60/62 60/62
Refrigerant g 3400 3400
Connecting Pipe
Liquid mm 9.52 9.52
Gas mm 15.88 15.88
Additional Refrigerant(g/m) g/m 50 50
Standard m 5 5
Extension length(Total) m 75 75
Extension length(Elevation) m 30 30
Option Code
Product
Option
011044-167208-278CA0-370000 011044-167208-278CA0-370000
Installation
Option
020000-100000-200000-300000 020000-100000-200000-300000
Product Specifications (cont.)
NS090SDXEA_E_SM_33623A(1)_1.indd 5 2011-04-08 10:54:31
2-6 Samsung Electronics
Item Description Code No. Qty Remark
Users manual DB98-28944A 1
Essential Offer
Installation manual DB98-28943A 5
Insulation
DB62-03439J 1
DB62-03439H 1
Insulation Drain In DB62-03440H 1
Insulation Install Inlet
DB72-00143E 1
DB72-00143G 1
Ass'y Holder Drain Pipe DB90-02064A 1
Ass'y Drain Hose Joint DB94-00758A 1
2-3 Specifications of optional items
2-3-1 Accessories
NS090SDXEA_E_SM_33623A(1)_1.indd 6 2011-04-08 10:54:32
Samsung Electronics 2-7
Product Specifications
Item Descriptions Code-No. Q'TY Remark
Receiver & display unit
DB93-00449A
(MRK-B00)
1
Concealed type
STS 2S-2x10 Tapped Screw - 4
2S-4x12 Tapped Screw - 2
Users manual DB98-05160A 1
Installation manual DB98-05186A 1
Wire kit
DB39-00223A
(MRW-10A)
1
Receiver & display unit
DB93-01066A
(MRK-A00)
1
Standard type
M4x12 Tapped Screw - 7
Cable-tie - 2
Users manual DB98-04184A 1
Installation manual DB98-04189A 1
Wire kit
DB39-00223A
(MRW-10A)
1
Accessories (cont.)
Receiver & display unit & Wire kit
NS090SDXEA_E_SM_33623A(1)_1.indd 7 2011-04-08 10:54:33
2-8 Samsung Electronics
Product Specifications
Item Descriptions Code-No. Q'TY Remark
Wireless remote controller
DB93-00251G
(ARH-401)
1
Optional
Batteries for remote controller
(specification: "AAA" type)
DB47-90024A 2
Remote controller holder DB61-00204A 1
STS 2S-2x10 Tapped Screw 6002-000581 2
Users manual DB98-05156A 1
Installation manual DB98-05184A 1
Accessories (cont.)
Wireless Remote controller
NS090SDXEA_E_SM_33623A(1)_1.indd 8 2011-04-08 10:54:34
Samsung Electronics 2-9
Product Specifications
Accessories (cont.)
Wireless Remote Controlle
Item Descriptions Code-No. Q'TY Remark
Wireless remote controller
DB93-04858C
(MR-BH01)
1
Optional
Batteries for remote controller
(specification: "AAA" type)
DB47-90024A 2
Remote controller holder DB61-03147A 1
STS 2S-2x10 Tapped Screw 6002-000581 2
Users manual DB98-27999A 1
Installation manual DB98-27997A 1
NS090SDXEA_E_SM_33623A(1)_1.indd 9 2011-04-08 10:54:34
2-10 Samsung Electronics
Product Specifications
Accessories (cont.)
Wireless remote controller
Item Descriptions Code-No. Q'TY Remark
2-12 Samsung Electronics
Wired remote controller
DB97-14333C
(MWR-WH02)
1
Optional
Cable tie DB65-10088B 2
Cable clamp DB65-10074E 5
M416 Tapped Screw 6002-000474 7
Indoor unit power drawing cable DB39-00221A 1
Communication cable of thewired remote
controller
DB39-00933A 1
Wire joint DB39-90020A 1
Users manual DB98-25179A 1
Installation manual DB98-25180A 1
2-12 Samsung Electronics
2-12 Samsung Electronics
2-12 Samsung Electronics
NS090SDXEA_E_SM_33623A(1)_1.indd 10 2011-04-08 10:54:35
Samsung Electronics 2-11
Product Specifications
Accessories (cont.)
Centralized controller
Item Descriptions Code-No. Q'TY Remark
Centralized controller
DB93-03425C
(MCM-A202)
1
Optional
Cable tie DB65-10088B 2
Cable clamp DB65-10074E 5
M4x16 Tapped Screw 6002-000474 7
Users manual DB98-12721A 1
Installation manual DB98-25773A 1
NS090SDXEA_E_SM_33623A(1)_1.indd 11 2011-04-08 10:54:36
2-12 Samsung Electronics
Product Specifications
Accessories (cont.)
Function controller
Item Descriptions Code-No. Q'TY Remark
Function controller
DB97-01077A
(MCM-A100)
1
Optional
Cable tie DB65-10088B 2
Cable clamp DB65-10074E 6
M4x16 Tapped Screw 6002-000474 7
Users manual DB98-27317A 1
Installation manual DB98-27315A 1
Transmitter
Item Descriptions Code-No. Q'TY Remark
Transmitter
DB97-00647P
(MIM-B04A)
1
Optional Transmitter power cable DB39-00378D 1
Transmitter communication cable DB39-00253D 1
NS090SDXEA_E_SM_33623A(1)_1.indd 12 2011-04-08 10:54:36
Samsung Electronics 2-13
Product Specifications
Accessories (cont.)
DMS(Date Management Server)
Item Descriptions Code-No. Q'TY Remark
DMS
DB93-03709B
(MIM-D00)
1
Optional
Cable tie DB65-10088B 2
Cable clamp DB65-10074D 2
M4x16 Tapped Screw 6002-000474 5
Bottom hook DB73-00320A 4
Users manual DB98-27317A 1
Installation manual DB98-27315A 1
NS090SDXEA_E_SM_33623A(1)_1.indd 13 2011-04-08 10:54:36
3-1 Samsung Electronics
Item Remarks
+SCREW DRIVER
Adjustable Wrench
(8mm, 10mm, 13mm)
Necessary Tools
3. Disassembly and Reassembly
NS090SDXEA_E_SM_33623A(1)_1.indd 1 2011-04-08 10:54:36
Operating Instructions and Installation
Samsung Electronics 3-2
No Parts Procedure Remark
1 Blower & Motor 1) After disassembling 16 places indicating
screws, detach Ass'y Cabi Bottom Blower.
(Use +Screw Driver)
2) Detach from Ass'y Control In the capacitor
connection wire between the Motor Fan and
housing connector.
3) After disassembling 2 places indicating screws,
detach the 2 Fan Case. (Use +Screw Driver)
3-1 Indoor unit
NS090SDXEA_E_SM_33623A(1)_1.indd 2 2011-04-08 10:54:37
3-3 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
4) After disassembling 2 places indicating
screws, detach Fan Motor and Blower
from the set.
2 Control In 1) After disassembling 1 Indicating screw, detach
the Cover control. (Use +Screw Driver)
2) Detach the Motor-Fan and Sensor Connector
from the PCB.
NS090SDXEA_E_SM_33623A(1)_1.indd 3 2011-04-08 10:54:38
Samsung Electronics 3-4
Disassembly and Reassembly
No Parts Procedure Remark
3) Disassemble 4 indicating screws and detach
Control In from the set.
3 Drain Pan Work is possible when Disassembling the Ass'y
Cabi Bottom Blower.
1) Disassemble 7 indicating screws and detach
Ass'y Cabi Bottom Drain..
NS090SDXEA_E_SM_33623A(1)_1.indd 4 2011-04-08 10:54:39
3-5 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
1) Disassemble 4 indicating screws and detach
the Drain Pan. (Use +Screw Driver)
(2 screws each at left and right side).

4 Evap Work is possible when Disassembling the Ass'y
Drain Pan.
1) Disassemble 5 indicating screws to detach
Cover Pipe. (Use +Screw Driver)
NS090SDXEA_E_SM_33623A(1)_1.indd 5 2011-04-08 10:54:40
Samsung Electronics 3-6
Disassembly and Reassembly
No Parts Procedure Remark
2) Disassemble Sensor on the Evap.
3) Disassemble 4 indicating screws which are in
the near of Hanger Plate to detach the Evap.
(Use +Screw Driver)
(2 screws each at left and right side)
It needs 2 peoples..
NS090SDXEA_E_SM_33623A(1)_1.indd 6 2011-04-08 10:54:41
3-7 Samsung Electronics
No Parts Procedure Remark
1 Cabi Front RH You must turn off the Power before
disassembly.
1) Unscrew and remove two mounting screw
in the Cabinet Front RH. (Use +Screw Driver)
2 Cabi Top 1) Unscrew and remove 9 screws
on each side of the Cabinet-Top.
(Use +Screw Driver)
3 Cabi Install Front 1) Unscrew and remove 1 screw
in the Cabinet-Install Front.
(Use +Screw Driver)
RC090DH*/RC090SH*/RC100DH*/RC100SH*
3-2 Outdoor Unit
NS090SDXEA_E_SM_33623A(1)_1.indd 7 2011-04-08 10:54:41
Samsung Electronics 3-8
Disassembly and Reassembly
No Parts Procedure Remark
4 Guard Cond 1) Pull the sensor from Guard Cond.
2) Unscrew and remove 4 screws
in the Guard Cond.
(Use +Screw Driver)
5 Cabi Back RH 1) Pull the sensor from Cabi Back RH.
2) Unscrew and remove 4 screws
on each side of the Cabinet Back RH.
(Use +Screw Driver)
NS090SDXEA_E_SM_33623A(1)_1.indd 8 2011-04-08 10:54:42
3-9 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
6 Cabi Install Back 1) Unscrew and remove 1 screw
in the Cabinet-Install Back.
(Use +Screw Driver)
7 Cabi Front LF 1) Unscrew and remove 10 screws
in the Cabinet-Front LF.
(Use +Screw Driver)
NS090SDXEA_E_SM_33623A(1)_1.indd 9 2011-04-08 10:54:42
Samsung Electronics 3-10
Disassembly and Reassembly
No Parts Procedure Remark
8 Fan 1) Turn 2 mounting nuts as shown in the
picture and remove it. (Use Adjustable
Wrench)
NS090SDXEA_E_SM_33623A(1)_1.indd 10 2011-04-08 10:54:42
3-11 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
9 Motor 1) Separate the Fan Propeller.
2) Unscrew and remove the 8 Motor mounting
screws. (Use +Screw Driver)
3) Disconnect the Motor wire From
Ass'y Control Out.
10 Bracket Motor 1) Unscrew and remove 2 mounting screws
in Bracket Motor. (Use +Screw Driver)
NS090SDXEA_E_SM_33623A(1)_1.indd 11 2011-04-08 10:54:43
Samsung Electronics 3-12
Disassembly and Reassembly
No Parts Procedure Remark
11 Control Out 1) Disconnect 4 Connecters From
Ass'y Control Out.
2) Unscrew and remove 1 mounting screw
in Control Out. (Use +Screw Driver)
3) Separate Ass'y Control Out.
NS090SDXEA_E_SM_33623A(1)_1.indd 12 2011-04-08 10:54:44
3-13 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
12 Ass'y 4way Valve 1) Purge the Coolant first.
2) Unscrew and remove 2mounting screws
in muffler.
3) Unscrew and remove 2 mounting screws
in Service Valve. (Use +Screw Driver)
4) Separate the pipe from the Entrance/Exit
using a welder.
When removing the compressor,
Heat Exchanger, and Pipe, purge the
Coolant inside the Compressor
completely and remove the pipe
with a welding flame.
NS090SDXEA_E_SM_33623A(1)_1.indd 13 2011-04-08 10:54:44
Samsung Electronics 3-14
Disassembly and Reassembly
No Parts Procedure Remark
13 Ass;y EEV Valve 1) Unscrew and remove 2 mounting screws
in Service Valve. (Use +Screw Driver)
2) Separate the pipe from the Entrance/Exit
using a welder.
14 Compressor 1) Unscrew and remove 1 mounting nut
in Cover Terminal. (Use Adjustable Wrench)
2) Separate the Compressor Felt Sound.
NS090SDXEA_E_SM_33623A(1)_1.indd 14 2011-04-08 10:54:45
3-15 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
3) As shown in the picture, unscrew and
remove 3 mounting screws from the
bottom. (Use Adjustable Wrench)
15 Cond Out 1) Unscrew and remove 3 screws
on each side of the Assy Cond Out.
(Use +Screw Driver)
2) Separate the Compressor Felt Sound.
NS090SDXEA_E_SM_33623A(1)_1.indd 15 2011-04-08 10:54:46
Samsung Electronics 3-16
Disassembly and Reassembly
No Parts Procedure Remark
1 Cabi Front RH You must turn off the Power before
disassembly.
1) Unscrew and remove 2 mounting screw
in the Cabinet Front RH.
(Use +Screw Driver)
2 Cabi Top 1) Unscrew and remove 9 screws
on each side of the Cabinet-Top.
(Use +Screw Driver)
3 Cabi Install Front 1) Unscrew and remove 1 screw
in the Cabinet-Install Front.
(Use +Screw Driver)
RC125DH*/RC140DH*
NS090SDXEA_E_SM_33623A(1)_1.indd 16 2011-04-08 10:54:47
3-17 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
4 Guard Cond 1) Pull the sensor from Guard Cond.
2) Unscrew and remove 4 screws
in the Guard Cond.
(Use +Screw Driver)
5 Cabi Back RH 1) Pull the sensor from Cabi Back RH.
2) Unscrew and remove 4 screws
on each side of the Cabinet Back RH.
(Use +Screw Driver)
NS090SDXEA_E_SM_33623A(1)_1.indd 17 2011-04-08 10:54:48
Samsung Electronics 3-18
Disassembly and Reassembly
No Parts Procedure Remark
6 Cabi Install Back 1) Unscrew and remove 1 screw
in the Cabinet-Install Back.
(Use +Screw Driver)
7 Cabi Front LF 1) Unscrew and remove 10 screws
in the Cabinet-Front LF.
(Use +Screw Driver)
NS090SDXEA_E_SM_33623A(1)_1.indd 18 2011-04-08 10:54:49
3-19 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
8 Fan 1) Turn 2 mounting nuts as shown in the
picture and remove it. (Use Adjustable
Wrench)
NS090SDXEA_E_SM_33623A(1)_1.indd 19 2011-04-08 10:54:49
Samsung Electronics 3-20
Disassembly and Reassembly
No Parts Procedure Remark
9 Motor 1) Separate the Fan Propeller.
2) Unscrew and remove the 8 Motor mounting
screws. (Use +Screw Driver)
3) Disconnect the Motor wire From
Ass'y Control Out.
10 Bracket Motor 1) Unscrew and remove 2 mounting screws
in Bracket Motor. (Use +Screw Driver)
NS090SDXEA_E_SM_33623A(1)_1.indd 20 2011-04-08 10:54:50
3-21 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
11 Control Out 1) Disconnect 4 Connecters From
Ass'y Control Out.
2) Unscrew and remove 1 mounting screw
in Control Out. (Use +Screw Driver)
3) Separate Ass'y Control Out.
NS090SDXEA_E_SM_33623A(1)_1.indd 21 2011-04-08 10:54:51
Samsung Electronics 3-22
Disassembly and Reassembly
No Parts Procedure Remark
12 Ass'y 4way Valve 1) Purge the Coolant first.
2) Unscrew and remove 2 mounting screws
in Service Valve. (Use +Screw Driver)
3) Separate the pipe from the Entrance/Exit
using a welder.
When removing the compressor,
Heat Exchanger, and Pipe, purge the
Coolant inside the Compressor
completely and remove the pipe
with a welding flame.
13 Ass;y EEV Valve 1) Unscrew and remove 2 mounting screws
in Service Valve. (Use +Screw Driver)
2) Separate the pipe from the Entrance/Exit
using a welder.
NS090SDXEA_E_SM_33623A(1)_1.indd 22 2011-04-08 10:54:52
3-23 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
14 Compressor 1) Unscrew and remove 1 mounting nut
in Cover Terminal. (Use Adjustable Wrench)
2) Separate the Compressor Felt Sound.
3) As shown in the picture, unscrew and
remove 3 mounting screws from the
bottom. (Use Adjustable Wrench)
NS090SDXEA_E_SM_33623A(1)_1.indd 23 2011-04-08 10:54:53
Samsung Electronics 3-24
Disassembly and Reassembly
No Parts Procedure Remark
15 Cond Out 1) Unscrew and remove 3 screws
on each side of the Assy Cond Out.
(Use +Screw Driver)
NS090SDXEA_E_SM_33623A(1)_1.indd 24 2011-04-08 10:54:54
4-1 Samsung Electronics
4. Troubleshooting
4-1 Indoor Display Error and Check Method
Error detection and reoperation
If error occurs during the operation, badness is indicated by LED ickering and all operation is stopped except LED.
When reoperating by remote control and switch determine the error mode after normal operation.
: ON, : Flickering, X : OFF
If you turn o the air conditioner when the LED is ickering, the LED is also turned o.
Indoor unit LED lamp display at error detecting
Error type
LED Iamp display
Remarks
Operation Defrost Timer Air flow Filter
Power reset X X X X
Error of temperature sensor in the indoor unit(Open/Short) X X X X
Error of heat exchanger sensor in the indoor unit X X X
Error of the outdoor temperature sensorError of the condensor
temperature sensor
Error of the discharge temperature sensorPower reset
X X X
1. No communication for 2 minutes between indoor units
(Communication error for more than 2 minutes)
2. Indoor unit receiving the communication error from
outdoor unit
3. Outdoor unit tracking 3 minutes error
4. When sending the communication error from the outdoor
unit, the mismatching of the communication numbers
and installed numbers after completion of tracking4.
(Communication error for more than 2 minutes)
X X X
1. Error of electronic expansion valve close
2. Error of electronic expansion valve open
3. 2'nd detection of high temperature cond
4. 2'nd detection of high temperature discharge
5. Error of reverse phase
6. Compressor down due to 6'th detection of freezing
X X
Detection of the float switch X X X
Error of setting option switches for optional accessories X X X
EEPROM option error
NS090SDXEA_E_SM_33623A(1)_1.indd 1 2011-04-08 10:54:54
Samsung Electronics 4-2
Troubleshooting
If an error occurs, is displayed on the wired remote controller. If you would like to see an error code, press the Test button.
4-1-1 Wired Remocon Error Display(COM2)
Display Explanation Remark
Indoor unit Communication Error
Communication Error
Indoor/Outdoor unit Communication Time Out Error 60 Packet Over data
Indoor unit is not connected
Communication Error between Outdoor Main and Inverter Micom
(Occurred after 1 minute detection in Main and Inverter)
Indoor Temp. Sensor(Open/Short Error)
Indoor Sensor Error Indoor Unit Eva in Sensor(Open/Short Error)
Indoor Unit Eva in Sensor Separation
Outdoor Temp. Sensor Error(Open/Short Error)
Outdoor Sensor Error
COND Temp. Sensor Error(Open/Short Error)
Inverter Compressor Discharge Temp. sensor Error(Open/Short Error)
Power cable miss connection error
Indoor Float Switch 2nd Detection
Self Diagnosys Error
Outdoor unit - indoor unit communication wire miss connection
(Connected to Power terminal)
Outdoor unit refrigerant Full leakage(Gas leak)
Outdoor Fan 1 Error
Outdoor Fan 2 Error
Discharge over temperature
Outdoor UnitProtetion Control Error
[Inverter] Compressor starting error
Primary Current Over Trip error
[Inverter]IPM Over Current(O.C)
[Inverter] Compressor Rotation error
[Inverter] Current Sensor error
[Inverter] DC LINK Sensor error
[Inverter] EEPROM Read/Write Error
[Inverter] Heatsink temperature over Error
Outdoor UnitProtetion Control Error
Outdoor unit Capacity Setup option error
Communication error between Indoor unit and wired remote control
Wired remote control error
Communication error between Master and Slave wired remote control
COM1/COM2 Cross-installed error
Error of setting option for wired remote control COM2
NS090SDXEA_E_SM_33623A(1)_1.indd 2 2011-04-08 10:54:56
4-3 Samsung Electronics
4-2 Outdoor LED Error Display and Check Method
No.
LED Display
Explanation Error Code
Yellow Green Red
1 Power off/ VDD NG -
2 IPM Over Current(O.C)
3

Abnormal Serial communication/Power Cable Miss Connection

4 Compressor Starting error
5 Normal Operation -
6 Compressor Lock error
7 DC-Link voltage under/over error
8 Outdoor temperature sensor error
9 Discharge over temperature
10 Discharge temperature sensor error
11 Current sensor error
12 Compressor Limit error
13 Coil temperature sensor error
14 1min. Time out Communication
15 Fan error
16 OTP error
17 Compressor rotation error
18 Operation condition secession
19 DC-Link voltage sensor error
20 I_Trip error
21 GAS Leak error
22 Power Cable miss connection
23 Power ON reset(1sec) -
24 Capacity miss match
25 Test Operation at Cooling Mode -
26 Test Operation at Heating Mode -
Off Blink On
NS090SDXEA_E_SM_33623A(1)_1.indd 3 2011-04-08 10:54:58
Samsung Electronics 4-4
4-3 Setting Option Setup Method
4-3-1 Type A(Setting Option)
Option No. :
Step 1 : Enter the Option Setup mode.
1
st
Take out the batteries of remote control.
2
nd
Press the temperature

button simultaneously
and insert the battery again.
3
rd
Make sure the remocon display shown as .
Step 2 : Enter the Option Setup mode and select your option according to the following procedure.
1
2
3
4
5
6
The default value is .
Otherwise, push the button to .
Every time you push the button, the display panel reads or repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
Setting is not required if you must
a volue which has a default.
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
1
2
3
4
5
6
NS090SDXEA_E_SM_33623A(1)_1.indd 4 2011-04-08 10:55:05
4-5 Samsung Electronics
Troubleshooting
7
8
9
10
11
12
Press button, then the default value is .
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
Setting is not required if you must
a volue which has a default.
Push the button to set the display panel to .
Every time you push the button, the display panel reads . . .
repeatedly.
7
8
9
10
11
12
Step 3 : Upon completion of the selection, check you made right selections.
Press the Mode Selection key, to set the display part to and check the display part.
The display part shows .
Press the Mode Selection key, to set the display part to and check the display part.
The display part shows .
Step 4 :
Pressing the ON/OFF button( ).
When pressing the operation ON/OFF key with the direction of remote control for unit, the sound Ding or
Diriring is heard and the OPERATION ICON( ) lamp of the display is flickering at the same time, then the input
of option is completed. (If the diriring sound isnt heard, try again pressing the ON/OFF button.)
Step 5 : Unit operation test-run.
First, Remove the battery from the remote control.
Second, Re-insert the battery into the remote control.
Third, Press ON/OFF button( ) withthe direction of remote control for set.
Error Mode
1
st
If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry.
2
nd
If the unit is not working properly or all lamps are continuously flickering after setting the option code, see
if the correct option code is set up for its model.
NS090SDXEA_E_SM_33623A(1)_1.indd 5 2011-04-08 10:55:14
Samsung Electronics 4-6
Troubleshooting
4-3-2 Type B(Setting Option Setup Method)
Operation method Applicable button Indicating state
Step 1
Method)
Remove the battery of remote controller.
Push the Off Timer and Cancel button
simultaneously.
Insert the battery.
Result)
When the display of remote controller
is indicated as shown in the right,
then go to the step 2.
Step 2
Method)
If the first digit of remote controller
shows "0", go to the step 3.
If it shows 1, press the Mode button one
time to change it into 0 and
then go to step 3.
Step 3
Method)
Input the second digit of option code
by pressing the High Temp button.
example) 021E311422852A311439421F
Result)
If 2 is displayed, go to the step 4
(whenver pressing the button, 1~9,
A,B,C,D,E,F are lit in order.)
NS090SDXEA_E_SM_33623A(1)_1.indd 6 2011-04-08 10:55:15
4-7 Samsung Electronics
Troubleshooting
Operation method Applicable button Indicating state
Step 4
Method)
Input the third digit of option code by
pressing the Low Temp button.
example) 021E311422852A311439421F
Result)
If 1 is displayed, go to the step 5.
Step 5
Method)
Input the third digit of option code by
pressing the High Fan button.
example) 021E311422852A311439421F
Result)
If E is displayed, go to the step 6.
Step 6
Method)
Input the third digit of option code by
pressing the On Timer button.
example) 021E311422852A311439421F
Result)
If 3 is displayed, go to the step 6.
NS090SDXEA_E_SM_33623A(1)_1.indd 7 2011-04-08 10:55:16
Samsung Electronics 4-8
Troubleshooting
Operation method Applicable button Indicating state
Step 7
Method)
Input the sixth digit by pressing the Cancel
button.
example) 021E311422852A311439421F
Result)
If 1 is displayed, go to the step 8.
Step 8
Method)
After completion up to step 7, pressing
Mode button.
1~7 steps are saved internally.
If the first number is 1 at the time,
it is correct. So go to step 9.
If wanting to see the screen of 2~7 steps,
press the mode button repeatedly
to make the first digit 0.
Step 9
Method)
Input the eighth digit by pressing the
High Temp button.
example) 021E311422852A311439421F
Result)
If 4 is displayed, go to the step 10.
NS090SDXEA_E_SM_33623A(1)_1.indd 8 2011-04-08 10:55:17
4-9 Samsung Electronics
Troubleshooting
Operation method Applicable button Indicating state
Step 10
Method)
Input the ninth digit by pressing the
Low Temp button.
example) 021E311422852A311439421F
Result)
If 2 is displayed, go to the step 11.
Step 11
Method)
Input the tenth digit by pressing the
High Fan button.
example) 021E311422852A311439421F
Result)
If 2 is displayed, go to the step 12.
Step 12
Method)
Input the 11st digit by pressing the
On Timer button.
example) 021E311422852A311439421F
Result)
If 8 is displayed, go to the step 13.
NS090SDXEA_E_SM_33623A(1)_1.indd 9 2011-04-08 10:55:18
Samsung Electronics 4-10
Troubleshooting
Operation method Applicable button Indicating state
Step 13
Method)
Input the 12th digit by pressing the Cancel
button.
example) 021E311422852A311439421F
Result)
If 5 is displayed, go to the step 14.
Step 14
Method)
After completion up to step 13, pressing
Mode button.
Previous steps are saved internally.
If the first number is 2 at the time,
it is correct. So go to step 15.
If wanting to see previous screen, press
the mode button repeatedly to
make the first digit to with digit.
Error

If the On/Off, Timer and Fan indicator
is flickering, the wrong option code
is input. Put off the power of
indoor unit and turn it on again
and then input the option code again.
If the same error occurs, it is the
EEPROM is defective or not inserted.
Replace the PCB.
If all of On/Off, Timer, Fan and Filter
Sign indicator are flickering along with
the "Tiriring" sound, there is
option code already input which are
different from the current ones.
Check the option code and press
the button again if correct.
Option code will be input.
(Check the option code correctly.
At the time, if the same error
continues to occur, the
option code is out of input range.
Check the option code again and
repeat the step 1~14.
NS090SDXEA_E_SM_33623A(1)_1.indd 10 2011-04-08 10:55:18
4-11 Samsung Electronics
Troubleshooting
Operation method Applicable button Indicating state
Step 15
Method)
Input the 14th digit by pressing the
High Temp button.
example) 021E311422852A311439421F
Result)
If A is displayed, go to the step 16.
Step 16
Method)
Input the 15th digit by pressing the Low
Temp button.
example) 021E311422852A311439421F
Result)
If 3 is displayed, go to the step 17.
Step 17
Method)
Input the 16th digit by pressing the
High Fan button.
example) 021E311422852A311439421F
Result)
If 1 is displayed, go to the step 18.
NS090SDXEA_E_SM_33623A(1)_1.indd 11 2011-04-08 10:55:19
Samsung Electronics 4-12
Troubleshooting
Operation method Applicable button Indicating state
Step 18
Method)
Input the 17th digit by pressing the On Timer
button.
example) 021E311422852A311439421F
Result)
If 1 is displayed, go to the step 19.
Step 19
Method)
Input the 18th digit by pressing the
Cancel button.
example) 021E311422852A311439421F
Result)
If 4 is displayed, go to the step 20.
Step 20
Method)
After completion up to step 20, pressing
Mode button.
Previous steps are saved internally.
If the first number is 3 at the time,
it is correct. So go to step 22.
If wanting to see previous screen, press
the mode button repeatedly to
make the first digit to with digit.
NS090SDXEA_E_SM_33623A(1)_1.indd 12 2011-04-08 10:55:20
4-13 Samsung Electronics
Troubleshooting
Operation method Applicable button Indicating state
Step 21
Method)
Input the 20th digit by pressing the
High Temp button.
example) 021E311422852A311439421F
Result)
If 9 is displayed, go to the step 22.
Step 22
Method)
Input the 21th digit by pressing the Low
Temp button.
example) 021E311422852A311439421F
Result)
If 4 is displayed, go to the step 23.
Step 23
Method)
Input the 22th digit by pressing the
High Fan button.
example) 021E311422852A311439421F
Result)
If 2 is displayed, go to the step 24.
NS090SDXEA_E_SM_33623A(1)_1.indd 13 2011-04-08 10:55:21
Samsung Electronics 4-14
Troubleshooting
Operation method Applicable button Indicating state
Step 24
Method)
Input the 23th digit by pressing the On Timer
button.
example) 021E311422852A311439421F
Result)
If 1 is displayed, go to the step 25.
Step 25
Method)
Input the 24th digit by pressing the
Cancel button.
example) 021E311422852A311439421F
Result)
If F is displayed, go to the step 26.
Step 26
Method)
Turn the remote controller toward the indoor
unit and press the Power button, and if the
"Ting" or "Tiriring" sounds, the input of option
is completed.
If error displays, solve the problem with
reference to the right side.
Error
If the On/Off, Timer and Fan indicator
is flickering, the wrong option code
is input. Put off the power of
indoor unit and turn it on again
and then input the option code again.
If the same error occurs, it is the
EEPROM is defective or not inserted.
Replace the PCB.
If all of On/Off, Timer, Fan and Filter
Sign indicator are flickering along with
the "Tiriring" sound, there is
option code already input which are
different from the current ones.
Check the option code and press
the button again if correct.
Option code will be input.
(Check the option code correctly.
At the time, if the same error
continues to occur, the
option code is out of input range.
Check the option code again and
repeat the step 1~26.
NS090SDXEA_E_SM_33623A(1)_1.indd 14 2011-04-08 10:55:21
4-15 Samsung Electronics
Troubleshooting
Operation method Applicable button Indicating state
Step 27
Method)
If the steps 1 to 26 are completed, remove
the battery and insert it again to return to
the original display of remote controller.
(Operation mode/SET TEMP. /fan speed
displays.)
If error displays, solve the problem with
reference to the right side.
Error
If the On/Off, Timer and Fan indicator
is flickering, the wrong option code
is input. Put off the power of
indoor unit and turn it on again
and then input the option code again.
If the same error occurs, it is the
EEPROM is defective or not inserted.
Replace the PCB.
If all of On/Off, Timer, Fan and Filter
Sign indicator are flickering along with
the "Tiriring" sound, there is
option code already input which are
different from the current ones.
Check the option code and press
the button again if correct.
Option code will be input.
(Check the option code correctly.
At the time, if the same error
continues to occur, the
option code is out of input range.
Check the option code again and
repeat the step 1~26.
rear side
If you are going to use up to SEG 24, please refer to following instruction.
SEG 17 : 0 1 : Using high ceiling kit for 4way.
SEG 18 :
Not in use Use
Change temperature display 0(Celsius) 1(Fahrenheit)
Sound Mute 0 2
Mixed operation control 0 4
If you want to use multiple functions, add each of the use value of the function you want to used and input the
final addition as option value.
(Use Fahrenheit + Sound mute + Mixed operation control : 1 + 2 + 4 = 7)
Ex) 044217-1d00e6-200000-300000When using Sound mute : 044217-1d00e6-200002-300000
When using high ceiling kit for 4way and mixed operation error preventing function : 044217-1d00e6-200014-300000
NS090SDXEA_E_SM_33623A(1)_1.indd 15 2011-04-08 10:55:22
Samsung Electronics 4-16
Troubleshooting
4-3-3 Option code for each model
Model SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Remocon
display
NS100SSXEA 0 1 1 0 4 4 1 5 6 2 9 9
NS090SDXEA 0 1 1 0 4 4 1 5 6 2 9 9
NS090SSXEA 0 1 1 0 4 4 1 5 6 2 9 3
NS090SSXEX 0 1 1 0 4 4 1 5 6 2 9 3
NS125SDXEA 0 1 1 0 4 4 1 5 7 0 F 8
NS140SDXEA 0 1 1 0 4 4 1 6 7 2 0 8
Model SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Remocon
display
NS100SSXEA 2 7 5 A 6 4 3 5 0 0 0 0
NS090SDXEA 2 7 5 A 6 4 3 5 0 0 0 0
NS090SSXEA 2 7 5 A 6 4 3 7 0 0 0 0
NS090SSXEX 2 7 5 A 6 4 3 7 0 0 1 0
NS100SDXEA 2 7 6 4 7 0 3 7 0 0 0 0
NS125SDXEA 2 7 7 D 8 C 3 7 0 0 0 0
NS140SDXEA 2 7 8 C A 0 3 7 0 0 0 0
NS090SDXEA_E_SM_33623A(1)_1.indd 16 2011-04-08 10:55:29
4-17 Samsung Electronics
4-4 Iterms to be checked first
1. The input voltage should be rating voltage 10% range.
The air conditioner may not operate properly if the voltage is out of this range.
2. Is the link cable linking the indoor unit and the outdoor unit linked properly?
The indoor unit and the outdoor unit shall be linked by 4 cables.
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
Otherwise the air conditioner may not operate properly.
3. When a problem occurs due to the contents illustrated in the table below it is a symptom not related to the
malfunction of the air conditioner.
No Operation of air conditioner Explanation
1 In a COOL operation mode, the compressor does not
operate at a room temperature higher than the setting
temperature that the INDOOR FAN should operate.
[In case of heat pump model]
In a HEAT operation mode, the compressor does not
operate at a room temperature lower than the setting
temperature that indoor fan should operate.
In happens after a delay of 3 minutes when the
compressor is reoperated.
The same phenomenon occurs when a power is
on.
As a phenomenon that the compressor is
reoperated after a delay of 3 minutes, the
indoor fan is adjusted automatically with
reference to a temperature of the air blew.
2 Compressor stops operation intermittently in
DRY( ) mode.
Compressor operation is controlled automatically
in DRY mode depending on the room temperature
and humidity.
3 [In case of heat pump model]
Compressor of the outdoor unit is operating although
it is turned off in a HEAT mode.
When the unit is turned off while de-ice is
activated, the compressor continues operation
for up to 12 minutes(maximum) until the deice
is completed.
4 [In case of heat pump model]
The compressor and indoor fan stop intermittently
in HEAT mode.
The compressor and indoor fan stop intermittently
if room temperature exceeds a setting
temperature in order to protect the compressor
from overheated air in a HEAT mode.
5 [In case of heat pump model]
Indoor fan and outdoor fan stop operation
intermittently in a HEAT mode.
The compressor operates in a reverse cycle to
remove exterior ice in a HEAT mode, and
indoor fan and outdoor fan do not operate
intermittently for within 20% of the total heater
operation.
NS090SDXEA_E_SM_33623A(1)_1.indd 17 2011-04-08 10:55:29
Samsung Electronics 4-18
4-5 Fault Diagnosis by Symptom
4-5-1 No Power(completely dead) - Initial diagnosis
1. Checklist :
1) Is Power source voltage normal?
2) Is AC power linked correctly? ( miss-wiring, wire detaching etc. )
3) Is any LED on the MAIN PCB of Outdoor unit lit?
4) Is terminal voltage for indoor unit normal? (230Vac nominal)
5) Is Wired remote controller installed correctly?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Check outdoor unit terminal
block voltage on each N-R,N-S,N-T
(230Vac nominal)
Check outdoor unit terminal
block voltage on L-N for indoor unit
(230Vac nominal)
Check indoor unit terminal
block voltage on L-N
(230Vac nominal)
Check indoor unit terminal
block voltage on V1-V2
(12Vdc nominal)
Press the On/Off button on
the wired remote controller to operate the
air conditioner
Check DC power voltage of remote
controller(V1,V2)
Check DIP SW in the wired remote controller
Is there any error display on the wired
remote controller
Turn off the breaker and turn it on after 30 seconds
Check AC power source. Reconnect wires correctly.
Check Inner wiring of outdoor unit.
Check cable and connection of wire between
indoor and outdoor unit.
Check Indoor control PCB, Transformer,
and FUSE on PCB and replace one which is broken.
Check cable and connection of wire between
remote controller and indoor unit.
Replace wired remote controller.
Set DIP SW correctly.
Check each item according to error code list.
Check the setting temperature
No
No
No
No
No
No
No
No
NS090SDXEA_E_SM_33623A(1)_1.indd 18 2011-04-08 10:55:29
4-19 Samsung Electronics
Troubleshooting
4-5-2 The Outdoor unit Power Supply error
1. Checklist :
1) Are the input power voltage and power connection correct?
2) Is there any Fuse Short of the indoor or outdoor unit?
3) Is any LED lit on both MAIN PCB and INVERTER PCB?
4) Are Reactor wires of the outdoor unit connected correctly?
2. Troubleshooting procedure
Yes
Yes
No
No
No
Yes
Yes
No
Yes
Yes
No
Yes
Check LEDs on both MAIN PCB and
INVERTER PCB after1 minutesfrom
power on
Is voltage on N-T of terminal
block over 300V?
Are wire and socket connected
correctly? Power line N and
T wire(Terminal block -
reactor - EMI PCB), CN9(EMI PCB),
CN80(MAIN PCB)
Is there miss connection of
power andcommunication wire
betweenindoor and outdoor?
Is there any power wire
detachingespecially
phase R and S?
Are wire and socket connected
correctly? CN31(MAIN PCB),
CN10(INVERTER PCB)
Is the FUSE on INVERTER PCB
blown?
Is R100 on INVERTER PCB
open?(200ohm moninal)
Check INVERTER PCB
Are wire and socket connected
correctly? CN05,06,07 TAB
terminal(EMI PCB),
CN20(INVERTER PCB)
Check and correct the power cable wiring
Check and correct the wire or socket
connection
Check Fuses listed blow FUSE3(EMI PCB),
FUSE(MAIN PCB)
Correct the cable wiringbetween indoor and
outdoor
Check F1,F2 communication line wiring.
CN50(MAIN PCB)
Check and correct the power cable wiring
Check Fuses listed blow FUSE1(EMI PCB),
FUSE2(EMI PCB)
Check and correct the wiring
Replace the FUSE
Replace INVERTER PCB
Also check each BLDC FAN motoshort or not,
by resistance betweenpin #1 and #3
Check and correct the wiring
Check the M/C
No
Yes
No
No
MAIN PCB INVERTER PCB
ALL OFF ALL OFF
Error 202 display
(Table No. 14)
Normal
Error 425 display
(Table No. 22)
ALL OFF
Error 203 display
(Table No. 3)
ALL OFF
Error 466 display
(Table No. 7)
Error 466 display
(Table No. 7)
Error 469 display
(Table No. 19)
Error 469 display
(Table No. 19)
NS090SDXEA_E_SM_33623A(1)_1.indd 19 2011-04-08 10:55:29
Samsung Electronics 4-20
Troubleshooting
4-5-3 The Outdoor unit Fan error
1. Checklist :
1) Are the input power voltage and power connection correct?
2) Is the motor wire connected to the outdoor PCB correctly?
3) Is there no obstacle at the surrounding of motor and propeller?
4) Does the driver in the motor case broken?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Is the connection of FAN housing certainly to
PCB socket?(CN40, CN41)
Take off each Fan motor housing after 1 minutes from
turning off the power
Is each resistance of FAN cable housing pin #1-#3 over
1Mohm, pin #4-#3, #5-#3 and #6-#3 over 1Kohm on
each FAN motor?
Mount each Fan housing to PCB socket and turn
on the power
Is the Pin voltage #1 - #3 of CN40 and 41over 250V?
Is the Pin voltage #5 - #3 of CN40 and 41 15V?
Is the Pin voltage #5 - #3 of CN40 and 41within 1-6V
during the operation?
Is the Fan in rotation during TEST operation in
cooling mode
Is the Pin voltage #6 - #3 of CN40 and 41changed
high(4-5V) and low(0-1V) in case ofmaking manual
rotation slowly?
Is the Pin voltage #7 - #3 of CN40 and 41 low(0-1V) in
normal rotation?
Check AC power source. Reconnect wires correctly
Exchange the FAN motor because of driver inside
of the motor case broken
Follow the check procedure of outdoor unit power
supply error check
Exchange INVERTER PCB
Exchange INVERTER PCB
Exchange the FAN motor not in rotation
Exchange INVERTER PCB
Exchange the FAN motor
Exchange the FAN motor
No
No
No
No
No
No
Yes
No
# TEST operation #
press K900 button on the
MAIN PCB after power on.
- once : cooling mode
- twice in a second : heating mode
NS090SDXEA_E_SM_33623A(1)_1.indd 20 2011-04-08 10:55:29
4-21 Samsung Electronics
Troubleshooting
4-5-4 Total current trip error
1. Checklist :
1) Is the input power voltage proper?
2) Is the refrigerant charged properly?
3) Does the compressor rotate normally?(Reverse rotation, Locking etc.)
4) Does the outdoor fan operate normally?(Fan propeller loss, Motor error ect.)
5) Is the installation condition of outdoor unit good?(Piping, Space etc.)
6) Is there no ventilation obstruction at the surrounding of outdoor unit?(Outdoor unit cover, Fan front obstruction etc.)
7) Is there no ventilation obstruction at the surrounding of indoor unit?(Overload condition in heating mode)
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Yes
Is the installation of outdoor unit good?
Is the installation of indoor unit good?
Does the compressor rotate normally?
Are the service valves full opened?
Is AC power voltage normal during
thecompressor in operation?
Reinstall and remove the obstruction
Reinstall and remove the obstruction
Exchange the compressor
Open valve screw to the end
Check AC power source
Exchange INVERTER PCB
No
No
No
No
No
NS090SDXEA_E_SM_33623A(1)_1.indd 21 2011-04-08 10:55:29
Samsung Electronics 4-22
Troubleshooting
4-5-5 In case of heating at the cooling mode or cooling at the heating mode
1. Troubleshooting procedure
No
No
No
No
Yes
Yes
Yes
Is the Thermo off?
Is the unit in the defrosting
operation?
Is the compressorin 3 minutes off?
Is much frostin the indoor
heat exchanger?
Does the 4-WAY valve
operate normally?
Is the outdoor air sensor and
outdoor heat exchanger
attachedcorrectly?
Is the 4-WAY valve
connectorconnected
correctly?
Dose thevoltage of
AC220V apply to the
connector of
4-WAY valve coil during
the operation?
Change the setting temperature of remote control
Check Inner wiring of outdoor unit.
After 3 minutes, coolingand heating start automatically
Attach the sensor correctly
Connect the connecter
correctly
Over shortage of the
refrigerant
4-WAY valve coil error
Exchangethe outdoor PCB
Check the resistance value of 4-WAY
valve coil
4-WAY valve main body error Go to the next page
No
Yes
Yes
Yes
Yes
No
No
No
No
Yes
NS090SDXEA_E_SM_33623A(1)_1.indd 22 2011-04-08 10:55:30
4-23 Samsung Electronics
Troubleshooting
4-5-5 In case of heating at the cooling mode or cooling at the heating mode(cont.)
Yes
Yes
Yes
Yes
No
Yes
Yes
No
Does theEEV
operatenormally?
Doesthe outdoor fan
operate at the operation
of compressor?
Is theoutdoor fan
connectedcorrectly?
Is theoutdoor fan
connectedcorrectly?
Is much frostin the heat
exchanger?
Is much frostin the heat
exchanger?
Connect the connector.
Exchangethe out PCB
The over shortage of refrigerant, Insufficient Capacity,
Load estimation error
Connect the connector
Outdoor fan error
Check the motor wire
EEV coil error
EEV main body error
Check the resistance value of
EEV coil
Check the resistance value of
outdoor fan
Outdoor PCB error
No No
No
Yes
No
No
Yes
No
Go to the next page
NS090SDXEA_E_SM_33623A(1)_1.indd 23 2011-04-08 10:55:30
Samsung Electronics 4-24
Troubleshooting
4-5-6 Outdoor temperature sensor error
1. Checklist :
1) Is the sensor connector connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull_up correct?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Is the sensor connector connectedcorrectly in
accordance with a color?
Is the temperature sensor connectedcorrectly
without separation?
Does the both terminal of sensorsatisfy the
resistance value in accordance with temperature?
(Refer to the R/T TABLE)
Is the resistance valueof sensor connection
pull_up 18K?
Reconnect the sensor connector
Change the position of sensor
Exchange the sensor
Exchange the PCB
Exchange the PCB Normal operation
Exit
No
No
No
No
No
-
5
0
-
4
1
-
3
2
-
2
3
-
1
4
-
54
1
3
2
2
3
1
4
0
4
9
5
8
6
7
7
6
8
5
9
4
1
0
3
400.0
350.0
300.0
250.0
200.0
150.0
100.0
50.0
0.0
NS090SDXEA_E_SM_33623A(1)_1.indd 24 2011-04-08 10:55:30
4-25 Samsung Electronics
Troubleshooting
4-5-7 Discharge temperature sensor error
1. Checklist :
1) Is the sensor connector connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull_up correct?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Is the sensor connector connectedcorrectly in
accordance with a color?
Is the temperature sensor connectedcorrectly
without separation?
Does the both terminal of sensorsatisfy the
resistance value in accordance with temperature?
(Refer to the R/T TABLE)
Is the resistance valueof sensor connection
pull_up 24K?
Reconnect the sensor connector
Change the position of sensor
Exchange the sensor
Exchange the PCB
Exchange the PCB Normal operation
Exit
No
No
No
No
No
08
1
6
2
4
3
2
4
0
4
8
5
6
6
4
7
2
8
0
8
8
9
6
1
0
4
1
1
2
1
2
0
1
2
8
1
3
6
1
4
4
1
5
2
1
6
0
600.0
500.0
400.0
300.0
200.0
100.0
0.0
NS090SDXEA_E_SM_33623A(1)_1.indd 25 2011-04-08 10:55:30
Samsung Electronics 4-26
Troubleshooting
4-5-8 Coil temperature sensor error
1. Checklist :
1) Is the sensor connector connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull_up correct?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Is the sensor connector connectedcorrectly in
accordance with a color?
Is the temperature sensor connectedcorrectly
without separation?
Does the both terminal of sensorsatisfy the
resistance value in accordance with temperature?
(Refer to the R/T TABLE)
Is the resistance valueof sensor connection
pull_up 18.2K?
Reconnect the sensor connector
Change the position of sensor
Exchange the sensor
Exchange the PCB
Exchange the PCB Normal operation
Exit
No
No
No
No
No
-
5
0
-
4
1
-
3
2
-
2
3
-
1
4
-
54
1
3
2
2
3
1
4
0
4
9
5
8
6
7
7
6
8
5
9
4
1
0
3
400.0
350.0
300.0
250.0
200.0
150.0
100.0
50.0
0.0
NS090SDXEA_E_SM_33623A(1)_1.indd 26 2011-04-08 10:55:31
Samsung Electronics 4-27
Troubleshooting
4-5-9 Fan error
1. Checklist :
1) Isnt the fan locked?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull_up correct?
2. Troubleshooting procedure
Yes
Yes
Yes
Isn't the Fan locked?
Is the connector connected correctly?
Is the color of Fan wire matched correctly?
Remove the Fan lock
Connect the connector
Exchange the Fan
Exchange the PCB Normal operation
Exit
No
No
No
NS090SDXEA_E_SM_33623A(1)_1.indd 27 2011-04-08 10:55:31
Samsung Electronics 4-28
Troubleshooting
4-5-10 DC-Link voltage sensor error
1. Checklist :
1) Is the connection of R, S, T power wire normal?
2) Are Relay RY21 and R200 on the INVERTER PCB mounted normally?
2. Troubleshooting procedure
Yes
Are connection of the wire from INVERTER PBA to
EMI PBA normal?
Exchange INVERTER PCB
Check and correct the wire connection
No
NS090SDXEA_E_SM_33623A(1)_1.indd 28 2011-04-08 10:55:31
4-29 Samsung Electronics
Troubleshooting
4-5-11 O.C.(Over Cirrent) error
1. Checklist :
1) Is the refrigerant charged properly?
2) Does the compressor rotate normally?(Reverse rotation, Locking etc.)
3) Is connection of compressor wire normal?
4) Is compressor motor normal?(Insulation, Coil resistance etc.)
5) Does a temporary cycle overload condition happened?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Yes
Yes
No
Is the installation of outdoor unit good?
Is the installation of indoor unit good?
Are the service valves full opened?
Does the compressor wire connected to
the compressor normally?
Is insuration resistance between each compressor
terminal and body normal?
Does the compressor rotate normally?
Did AC power voltage interruption happen during
the compressor in operation?
Reinstall and remove the obstruction
Reinstall and remove the obstruction
Open valve screw to the end
Correct the compressor wire connection
Exchange the compressor
Exchange the compressor
Check AC power source
Exchange INVERTER PCB
No
No
No
No
No
No
Yes
NS090SDXEA_E_SM_33623A(1)_1.indd 29 2011-04-08 10:55:31
Samsung Electronics 4-30
Troubleshooting
4-5-12 Communication error
1. Checklist :
1) Is the communication cable between the indoor unit and outdoor unit connected correctly?
2) Isnt the power cable and communication cable wiring error?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Restart after power off
Is the communication erroroccurred again?
Isn't the power cable andcommunication
cable wiring error?
Is the connection of communication cable normal?
Is insuration resistance between each compressor
terminal and body normal?
Exchange the outdoor unit PCB
Terminate the service
Correct the wrong wiring
Correct the compressor wire connection
Correct the connection of communication cable
No
No
No
No
NS090SDXEA_E_SM_33623A(1)_1.indd 30 2011-04-08 10:55:31
4-31 Samsung Electronics
Troubleshooting
4-5-13 Compressor start error
1. Checklist :
1) Is the connection of cable for the compressor and power?
2) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Restart after power off
Is the restart error occurred again?
Is the interphase resistance value of compressor
(u v, v w, w u) normal?
Is the compressor body and interphase
resistance insulated?
Is the connection cable for thecompressor and
power terminal normal?
Exchange the PCB
Terminate the service
Exchange the compressor
Exchange the compressor
Correct the cable connection
No
No
No
No
NS090SDXEA_E_SM_33623A(1)_1.indd 31 2011-04-08 10:55:31
Samsung Electronics 4-32
Troubleshooting
4-5-14 Compressor lock error
1. Checklist :
1) Is the connection of cable for the compressor and power?
2) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Yes
Yes
Yes
Yes
Restart after power off
Is the lock error occurred again?
Is the interphase resistance value ofcompressor
(u v, v w, w u) normal?
Is the compressor body and interphase
resistance insulated?
Is the connection cable for the compressor and
power terminal normal?
Exchange the outdoor unit PCB
Terminate the service
Exchange the compressor
Exchange the compressor
Correct the cable connection
No
No
No
No
NS090SDXEA_E_SM_33623A(1)_1.indd 32 2011-04-08 10:55:31
4-33 Samsung Electronics
Troubleshooting
4-5-15 DC Link Over voltage/Low voltage error
1. Checklist :
1) Is the power voltage normal?(Lightning, Power interruption etc.)
2) Is AC Power cable connection normal?(Detaching the wire)
2. Troubleshooting procedure
Yes
Yes
No
Yes
No
Is the AC Power cable connection to the
outdoor unit terminal block good?
Is the connection of reactor terminal good?
Are the FUSEs on EMI PCB blown?
Push the center bar of M/C and mesure
the resis-tance of each contact
Is each contact resistance normal? (less than 0.1ohm)
Does the error reappear frequently
The cause of this error may be power source trouble
as like power interruption.Check the power source
Check and reconnecting the reactor wireat
the TAB terminal
Check and reconnecting the AC power cable wire
Replace the blown FUSE
Exchange M/C
Exchange INVERTER PCB
No
No
Yes
No
Yes
NS090SDXEA_E_SM_33623A(1)_1.indd 33 2011-04-08 10:55:31
Samsung Electronics 4-34
4-6 PCB Inspection Method
4-6-1 Pre-inspection Notices
4-6-2 Inspection Procedure
4-6-3 Indoor Detailed Inspection Procedure
1. Turn off the breaker, AC power source, before disassembling the unit because of electrical hazard.
2. Confirm the complete discharge of capacitor C102, C702, C703, C704, C705, C706, C707 on the INVERTER PCB when you touch
the PCB. Especially dischargeing speed of C702-C707 is very slow because of little load in stand-by condition. To confirm
the voltae of 702-C707, measure the DC link voltage at the IGBT module pins near C701 at which applying voltage (450-510Vdc) is
marked. To confirm discharging of C102, measure the voltage of non mounted C103 solder hole or check if all LEDs are off.
3. Dont touch the metal body of electrolytic capacitor for avoiding electrical shock before confirming discharge.
4. To discharging the capacitor use power resistor of about 1 Kohm 10W. Soldering tool(non electronic temperature control type)
can be used as a discharging resistor.
5. Dont pull the lead wire but hold the whole housing to disconnect or connect a housing from or to the PCB.
1. Check the connection of each housing to the connector first and the peeling of PCB copper pattern.
2. The PCB is composed of the 3 part in the indoor unit.
INDOOR Main PCB part : Indoor unit control, MICOM and surrounding circuit, relay, fan motor driving circuit, sensor reading
circuit, buzzer driving circuit and DC power supplying circuit.
Display PCB part : LED lamps, Switch,Remocon module.
INDOOR EMI PCB part : Line filter, Noise Capacitor and Varistor
3. The PCB is composed of the 3 part in the outdoor unit.
EMI PCB part : Line filter for electrical noise, Varistors for surge and Fuses.
MAIN PCB part : Refrigeration cycle controller with MICOM
INVERTER PCB part : Compressor driving inverter and BLDC fan controller
No Procedure Inspection Method Cause
1
Open the electronic
component box and
check the PCB fuse
Turn off the power
1) Is the Fuse F701 on the EMI PCB blown?
2) Is the Fuse F702 on the MAIM PCB blown?
Over current
Indoor fan motor short
PCB AC Part pattern short
2
Check the LEDs for
DC power and
communication condition
Turn off the power
1) Is RED LED blinking?
his led means micom is running normally
2) Is GREEN LED blinking?
This means communication between
Indoor and Outdoor unit is on
3) Is YELLOW LED blinking?
This means communication between
Indoor and wired remote controller is on
It may take one minute to start
communication
Communication ciucuit trouble
Communication wire
connection trouble
Wrong connection for
power supply wire of
remote controller
3
Check the DIP and rotary
switch on the PCB
1) Is the setting of each switch proper? Wrong setting of switch
4
Check the DC voltage 1) Is the voltage of CN32 pin #1-#2 12V?
2) Is the voltage of C109 V?
SMPS on MAIN PBA trouble
Load short
5
FAN operation checking
Press the ON/OFF button.
1. FAN Speed[HIGH]
2. FAN mode
1) Is the FAN motor running?
2) Is the connection of CN73 normal?
Controller trouble inside of
the fan motor
Connector trouble of CN73
NS090SDXEA_E_SM_33623A(1)_1.indd 34 2011-04-08 10:55:31
4-35 Samsung Electronics
4-6-4 Outdoor Detailed Inspection Procedure
No Procedure Inspection Method Cause
1
Turn OFF the powerand
check wire and socket
connection on each part
Wait until C702-C707 discharged
1) Is connection of housing to socket normal?
2) Is connection of each wire to terminal
block normal?
3) Is the reactor wire connection normal?
4) Is there no miss-wiring of each cable?
Installation mistake
Miss assembling
2
FUSE check Is the fuses on each PCB normal?
3 fuese on EMI PCB
1 fuse on MAIN PCB
1 fuse on INVERTER PCB
Wire short
Overload
BLDC FAN short error
3
Turn on the powerand
check voltage of
terminal block
Is N-R,N-S,N-T around 230Vac?
Is R-S,S-T,T-R around 400Vac?
Is L-N(to indoor unit) around 230Vac?
Is F1-F2 within 5Vdc?
Miss wiring of power cable
Wire detaching
4
Check LED display on
AIN P
1) Is RED LED ON?
2) Is GREEN LED Blinking once a second?
3) Is LEDs displaying error code pattern?
MAIN PCB power trouble
Bad communication between
indoor and outdoor unit
Error detection
5
Check LED display on
INVERTER PCB
1) Is RED LED ON?
2) Is GREEN LED Blinking once a second?
3) Is LEDs displaying error code pattern?
INVERTER PCB power trouble
NO communication between
MAIN and INVERTER PCB
Error detection
6
Check DC voltage of
SMPS output
MAIN PCB
1) Is voltage of CN51 pin#1-#2 12-14.5V?
2) Is voltage of C108 5V?
INVERTER PCB
3) Is voltage of CN51 pin#1-#2 5V?
4) Is voltage of C124 12V?
5) Is voltage of each ZD100,ZD101,ZD102,
ZD103 17-18V?
SMPS circuit trouble
7
Check INVERTER PCB 1) Is resistance of R100 200ohm?
To check this, touch one probe to
CN10 pin#1(N) and the other to D101
upper side pin of '~' marking pins
2) Is DC Link voltage 450-510V?
Check IGBT module pins marking voltage
near C70
Resister
Wire connection between
EMI PCB and INVERTER PCB
8
Check BLDC fan 1) See 12-2-3 The Outdoor unit Fan error
(Fault Diagnosis)
Troubleshooting
NS090SDXEA_E_SM_33623A(1)_1.indd 35 2011-04-08 10:55:31
Samsung Electronics 4-36
4-7 Main Part Inspection Method
Part Breakdown Inspection Method
Indoor Unit Temperature Sensor
Measure sensor resistance with a multimeter
Normal At the normal temperature 37k~8.3k(-7C~+30C)
Abnormal ,0...Open or Short
Indoor Unit BLDC FAN Motor
Measure terminal resistance with a multimeter
Normal
At the normal temperature(10C~30C)
Wire Pin number Resistance Remark
RED - BLACK 1-3 Over 1M +300V motor power
WHITE - BLACK 4-3 1K ~ 2K +15V control power
YELLOW - BLACK 5-3 200K ~ 300K control
BLUE - BLACK 6-3 10K ~ 50K pulse
Abnormal ,0...Open or Short
Outdoor Unit
Outdoor Temperature Sensor
&
Cond Temperature Senso
Measure terminal resistance with a multimeter
Normal
At the normal temperature 37k~8.3k(-7C~+30C)
see 12-2-6 and 12-2-8
Abnormal ,0...Open or Short
Outdoor Unit Discharge
Temperature Sensorr
Measure terminal resistance with a multimeter
Normal
At the normal temperature 563k~157k(0C~+30C)
see 12-2-7
Abnormal ,0...Open or Short
Outdoor Unit BLDC FAN MOTOR
Measure terminal resistance with a multimeter
Normal
At the normal temperature(10C~30C)
Wire Pin number Resistance Remark
RED - BLACK 1-3 Over 1M +300V motor power
WHITE - BLACK 4-3 1K ~ 2K +15V control power
YELLOW - BLACK 5-3 200K ~ 300K control
BLUE - BLACK 6-3 10K ~ 50K pulse
ORANGE - BLACK 7-3 10K ~ 50K reverse
Abnormal ,0...Open or Short
Outdoor Unit 4way Valve Solenoid
Measure sensor resistance with a multimeter
Normal At the normal temperature(10C~30C) 1.6K15%
Abnormal ,0...Open or Short
NS090SDXEA_E_SM_33623A(1)_1.indd 36 2011-04-08 10:55:31
5-1 Samsung Electronics
5. Exploded Views and Parts List
5-1 Indoor Unit
13
19
2
18
5
3
9
6
15
17
14
1
15-1
15-3
15-2
15-7
15-6
15-5
15-8
23
23
20
22
21
24
4
8
12
11
7
15-4
16
10
26
NS090SDXEA
NS090SDXEA_E_SM_33623A(1)_2.indd 1 2011-04-08 11:02:08
Samsung Electronics 5-2
Exploded Views and Parts List
Parts List
No. SA/SNA Description Specification Code No. Q'TY
1 DB90-02402A ASS'Y CABINET FRONT ASS'Y 1 SA
2 DB90-02403A ASS'Y CABINET-TOP ASS'Y 1 SA
3 DB90-02404A ASS'Y COVER-PIPE ASS'Y 1 SA
4 DB90-02405A ASS'Y CABINET-BOTTOM BLOWER ASS'Y 1 SA
5 DB90-02406A ASS'Y CABINET-SIDE RH ASS'Y 1 SA
6 DB90-02407A ASS'Y CABINET-SIDE LF ASS'Y 1 SA
7 DB90-02408A ASS'Y-BRACKET OUTLET PART ASS'Y 1 SNA
8 DB90-02409A ASS'Y CABINET-BOTTOM DRAIN ASS'Y 1 SA
9 DB61-01282A HOLDER-SIDE CABI SGCC-M,T3.0,45.2,65 4 SNA
10 DB61-02374A BRACKET-FILTER SGCC-M,T1.0,50,250 4 SA
11 DB61-02378A HOLDER-PIPE SGCC-M,T1.0 1 SNA
12 DB63-01297A COVER-HOLDER SGCC-M,T0.8 1 SNA
13 DB63-01299B FILTER-PRE ASS'Y 1 SA
14 DB96-06727B ASS'Y EVAP-UNIT ASS'Y 1 SNA
15 DB93-05008A ASS'Y CONTROL IN ASS'Y 1 SNA
15-1 DB90-01992A ASS'Y CASE-CONTROL ASS'Y 1 SA
15-2 DB00-00000A CASE PCB ABS V0,T2.5 1 SA
15-3 DB26-00080A TRANS POWER AC 230V, 50HZ,DC 17V,DC 0.6A,VDE,ICE 1 SNA
15-4 3502-001035 SSR DC 12V,-,10A,1ms 1 SNA
15-5 2301-001381 C-FILM,LEAD-OTHER 8000nF,+10-5%,450V,BK,58x30x44mm 1 SA
15-6 DB65-00105L TERMINAL BLOCK DAF-S6P 1 SA
15-7 DB65-00105M TERMINAL BLOCK DAF-S6P 1 SA
15-8 DB61-00250A HOLDER-WIRE CLAMP ABS,BLK,ISI,SAMLINE 2 SNA
16 DB93-03213H ASS'Y PCB MAIN-IN ASS'Y 1 SNA
17 DB63-01296A COVER-CONTROL SGCC-M,T0.8 1 SA
18 DB91-00346A ASS'Y DRAIN PAN ASS'Y 1 SA
19 DB61-02331A BRACKET MOTOR SGCC-M,T2.0 1 SA
20 DB31-00355B MOTOR FAN YSK140-200-4,DC42GTVA,0.71/1.4A,50HZ 1 SNA
21 DB61-02332A CASE BLOWER-UPPER ABS,T2.0 2 SA
22 DB61-02333A CASE BLOWER-BOTTOM ABS,T2.0 2 SA
23 DB67-00583B BLOWER-D ABS 2 SA
24 DB97-03751A ASS'Y-BAND MOTOR ASS'Y 1 SNA
25 DB32-00142B THERMISTOR-IN 10Kohm,103AT,-20~+100 1 SA
26 DB95-01987B ASS'Y THERMISTORIN ASSY 1 SA
NS090SDXEA_E_SM_33623A(1)_2.indd 2 2011-04-08 11:02:09
5-3 Samsung Electronics
Exploded Views and Parts List
1
5
6
15
16
9
8
10
4
14
13
7
18
21
2
3
17
12
11
17-8
17-4
17-10
17-6
17-3
17-9
17-7
17-1
17-2
18-1
18-8
18-4
18-7
18-2
18-5
17-5
18-6
19
18-3
20
22
NS140SDXEA/NS100SDXEA/S125SDXEA
NS090SDXEA_E_SM_33623A(1)_2.indd 3 2011-04-08 11:02:09
Samsung Electronics 5-4
Exploded Views and Parts List
Parts List
No. SA/SNA Description Specification Code No. Q'TY
1 DB90-02006A ASS'Y CABINET TOP ASS'Y,SGCC-M T1.0 - SA
2 DB90-02007A ASS'Y CABI BOTTOM DRAIN ASS'Y,SGCC-M T1.0 1 SA
3 DB90-02008A ASS'Y CABI BOTTOM BLOWER ASS'Y,SGCC-M T1.0 1 SA
4 DB90-02009A ASS'Y CABI SIDE RH ASS'Y,SGCC-M T1.0 1 SA
5 DB61-01282A HOLDER SIDE CABI ASS'Y,SGCC-M T3.0 4 SNA
6 DB90-02010A ASS'Y CABI SIDE LF ASS'Y,SGCC-M T1.0 1 SA
7 DB90-02011A ASS'Y COVER PIPE ASS'Y,SGCC-M T1.0 1 SA
8 DB91-00317A ASS'Y DRAIN PAN ASS'Y,ABS/GF10 T3.0 1 SA
9 DB61-02374A BRACKET FILTER ASS'Y,SGCC-M T1.0 4 SNA
10 DB61-02380A BRACKET EVAP RH ASS'Y,SGCC-M T1.5 1 SA
11 DB61-02379A BRACKET EVAP LF ASS'Y,SGCC-M T1.5 1 SA
12 DB63-01297A COVER HOLDER ASS'Y,SGCC-M T1.0 1 SNA
13 DB61-02378A HOLDER PIPE ASS'Y,SGCC-M T1.0 1 SNA
14 DB73-00270A RUBBER COVER WIRE NBR 2 SNA
15 DB63-01299A FILTER PRE ASS'Y 1 SA
16 DB96-06728C ASS'Y EVAP UNIT 3R16C WAVE 1.5,OD7.0 1 SA
17 DB94-00742A ASS'Y BLOWER ASS'Y 1 SA
17-1 DB90-02028A ASS'Y CABI FRONT ASS'Y,SGCC-M T1.5 1 SNA
17-2 DB90-02013A ASS'Y BRACKET OUTLET PART ASS'Y,SGCC-M T1.0 1 SA
17-3 DB61-02372A BASE MOTOR ASSY,SGCC-M T2.5 1 SNA
17-4 DB61-02375A BRACKET MOTOR ASS'Y,SGCC-M T2.5 1 SNA
17-5 DB72-00710A BAND MOTOR ASS'Y,SGCC-M T1.6 4 SA
17-6 DB61-00540B BRACKET MOTOR GUIDE ASS'Y,SGCC-M T1.6 1 SNA
17-7 DB61-02382A CASE FAN LOW ASS'Y,ABS/GF10 T3.0 2 SA
17-8 DB61-02381A CASE FAN UP ASS'Y,ABS/GF10 T3.0 2 SA
17-9 DB67-00594A BLOWER ASS'Y,ABS/GF10 OD230 2 SA
17-10 DB31-00321B MOTOR FAN OSM4524SAC (S334) 1 SA
18 DB93-05008A ASS'Y CONTROL IN ASS'Y 1 SA
18-1 DB90-01992A ASS'Y CASE CONTROL ASS'Y,SGCC-M T1.0 1 SNA
18-2 DB61-02287A CASE PCB ABS V0 1 SA
18-3 DB26-00080A TRANS POWER DC17V 1 SNA
18-4 3502-001035 SSR OMRON G3NA-210BPL 1 SNA
18-5 2301-001381 C-FILM,LEAD-OTHER 8uF 450VAC 1 SA
18-6 DB65-00105M TERMINAL BLOCK 6P 250V,20A 1 SNA
18-7 DB65-00105L TERMINAL BLOCK 6P 250V,20A 1 SNA
18-8 DB61-00250A HOLDER-WIRE CLAMP NYLON 2 SNA
19 DB63-01296A COVER CONTROL ASS'Y,SGCC-M T0.8 1 SA
20 DB00-00000A ASS'Y PCB MAIN DH140EAV 1 SA
21 DB32-00142B THERMISTOR-ASS'Y 103AT,103FW 1 SA
22 DB95-01987B ASS'Y THERMISTOR IN ASS'Y 1 SA
NS090SDXEA_E_SM_33623A(1)_2.indd 4 2011-04-08 11:02:09
5-5 Samsung Electronics
NS090SSXEA/NS090SSXEX/NS100SSXEA/NS100SSXEX
10
11
15-3
14-7
14-8
14-4
15-2
15-6
15-1
15-5
15-4
15-7
15-8
1
13
12
9
4
7
11
15
10
8
2
14
5
6
2
3
14-6
14-1
14-2
14-3
14-5
16
17
Exploded Views and Parts List
NS090SDXEA_E_SM_33623A(1)_2.indd 5 2011-04-08 11:02:11
Samsung Electronics 5-6
Exploded Views and Parts List
Parts List
No. SA/SNA Description Specification Code No.
Q'TY
NS090SSXEX
NS090SSXEA
NS100SSXEA
NS100SSXEX
1 DB90-02927B ASS'Y CABINET-TOP MA0 PJT,SSEC 1 1 1 SNA
2 DB90-02405C ASS'Y CABINET-BOTTOM BLOWERMA1,SSEC 1 1 1 SA
3 DB90-02409D ASS'Y CABINET-BOTTOM DRAIN MA1,SSEC 1 1 1 SA
4 DB90-02929A ASS'Y CABINET-SIDE RH MA0 PJT,SSEC 1 1 1 SA
5 DB61-01282A HOLDER-SIDE CABI ADC6000TG,SGCC-M,T3.0 4 4 4 SA
6 DB90-02930A ASS'Y CABINET-SIDE LF MA0 PJT,SSEC 1 1 1 SA
7 DB90-02928B ASS'Y COVER-PIPE MA0 PJT,SSEC 1 1 1 SA
8 DB94-02001B ASS'Y DRAIN PANDH42BTA,SSEC 1 - - SA
DB94-02001A ASS'Y DRAIN PANDH42BTA,SSEC - 1 1 SA
9 DB61-02643A BRACKET-FILTER SGCC-M,T0.8 4 4 4 SA
10 DB95-01710A ASS'Y THERMISTOR IN ASS'Y 1 1 1 SA
11 DB63-01657B COVER-CONTROLMAO DUCT,SGCC-M,T0.8 1 1 1 SA
12 DB63-01299D FILTER-PR EASS'Y,T4.5,178,985,NATURE 1 1 1 SA
13 DB96-07024C ASS'Y EVAP-UNIT DH094EAMC,220-240V, 50HZ, 9.4KW 1 - - SA
DB96-07024G ASS'Y EVAP-UNIT DH094EAMC,220-240V, 50HZ, 9.4KW - 1 - SA
DB96-07024A ASS'Y EVAP-UNIT DH094EAMC,220-240V, 50HZ, 9.4KW - - 1 SA
14 DB94-01274A ASS'Y FAN IN PART SH094EAMC, 220-240V, 50HZ, 9.4KW 1 1 1 SNA
14-1 DB90-02926A ASS'Y CABI FRONT MA0 PJT,SSEC 1 1 1 SA
14-2 DB90-03030B ASS'Y-BRACKET OUTLET PART DH90EAMC,SSEC,GLOBAL PJT 1 1 1 SA
14-3 DB61-03058A BRACKET MOTOR SGCC-M,T2.5 1 1 1 SA
14-4 DB97-03751B ASS'Y-BAND MOTORSLIM DUCT 3,SSEC 1 1 1 SA
14-5 DB61-03059A CASE BLOWER-UP ABS+10%GF 2 2 2 SA
14-6 DB61-03060A CASE BLOWER-LOW ABS+10%GF 2 2 2 SA
14-7 DB67-00583B BLOWER-D EH140EZMC,ABS 2 2 2 SA
14-8 DB31-00355B MOTOR FAN YSK140-200-4 1 1 1 SA
15 DB93-12487A ASS'Y CONTROL IN ASS'Y 1 1 1 SA
16 DB93-12406A ASS'Y MAIN PCB ASS'Y 1 1 1 SA
17 DB95-01983B ASS'Y THERMISTOR IN ASS'Y 1 1 1 SA
NS090SDXEA_E_SM_33623A(1)_2.indd 6 2011-04-08 11:02:11
5-7 Samsung Electronics
RC090DHXEA/RC090SHXEA/RC100SHXEA/RC100DHXEA/RC100DHXGA
7
7-1
14
15
13
22
21
16
9
8
1
11
5
18 23
23-1
23-2
4
3
19
20
17
6
2
23-3
10
12
5-2 Outdoor Unit
NS090SDXEA_E_SM_33623A(1)_2.indd 7 2011-04-08 11:03:07
Samsung Electronics 5-8
Exploded Views and Parts List
Parts List
1 DB63-02730A GUARD-COND MSWR-6B, TOUCH GRAY 1 1 SA
2 DB64-02525A CABI INSTALL BACK EGI, T0.7 1 1 SA
3 DB64-02526A CABI INSTALL FRONT EGI, T0.7 1 1 SA
4 DB90-05873A ASS'Y BASE OUT ASS'Y 1 1 SA
5 DB90-05903A ASS'Y CABI BACK RH ASS'Y 1 1 SA
6 DB90-05904A ASS'Y CABI FRONT RH ASS'Y 1 1 SA
7 DB90-05971A ASS'Y CABI FRONT LF ASS'Y 1 1 SA
7-1 DB63-02743A GUARD FAN PP, MT72TG 1 1 SA
8 DB90-05902A ASS'Y CABINET TOP ASS'Y 1 1 SA
9 DB94-02720A ASS'Y PARTITION ASS'Y 1 1 SA
10 DB93-08235E ASS'Y CONNECTOR WIRE COMP ASS'Y, 1 1 - SNA
DB93-08235D ASS'Y CONNECTOR WIRE COMP ASS'Y, 3 - 1 SNA
11 DB93-11292A ASS'Y CONTROL OUT ASS'Y, 1 1 - SNA
DB93-11349A ASS'Y CONTROL OUT ASS'Y, 3 - 1 SNA
12 DB95-04522A ASS'Y THERMISTOR OUT ASS'Y 1 1 SA
13 DB31-00579A MOTOR FAN DAO335130ZRC, CLASS E 1 1 SA
14 DB60-00405A FASTENER WASHER M8 1 1 SNA
15 DB67-01061A FAN PROPELLER PP+MICA+GF, 520PI 1 1 SA
16 DB90-05918A ASS'Y BRACKET MOTOR ASS'Y 1 1 SA
17 DB60-30028A SCREW HEX HWH,WP,M8,ZPC(WHT),SWRCH18A 3 3 SNA
18 DB63-02953A CLOTH COMP TOP FELT, BLACK,1 1 - SNA
DB63-02987A CLOTH COMP TOP FELT, BLACK,3 - 1 SNA
19 DB63-02954A CLOTH COMP SIDE FELT, BLACK,1 1 - SNA
DB63-02954B CLOTH COMP SIDE FELT, BLACK,3 - 1 SNA
20 UG8T300FUBJUSG COMPRESSOR ASS'Y, 1 1 - -
UG5T450FUFJXSG COMPRESSOR ASS'Y, 3 - 1 -
21 DB90-02316E ASS'Y HOLDER PLATE COND ASS'Y 2 2 SA
22 DB96-15469A ASS'Y COND OUT ASS'Y 1 1 SA
23 DB96-15476A ASS'Y VALVE ASS'Y, 1 1 - SA
DB96-15476B ASS'Y VALVE ASS'Y, 3 - 1 SA
23-1 DB90-05874B ASS'Y BRACKET VALVE ASS'Y 1 1 SA
23-2 DB96-14880A ASS'Y VALVE 4WAY RC100DHXEA, R410A, 1 1 - SA
DB96-14886A ASS'Y VALVE 4WAY RC100DHXGA, R410A, 3 - 1 SA
23-3 DB96-14885A ASS'Y TUBE EEV RC100DHXEA, R410A 1 1 SA
No. SA/SNA Description Specification
Q'TY
RC100SHXEA
RC090DHXEA
RC090SHXEA
RC100DHXEA
RC100DHXGA
Code No.
NS090SDXEA_E_SM_33623A(1)_2.indd 8 2011-04-08 11:03:08
5-9 Samsung Electronics
Exploded Views and Parts List
14
18
19
23
5
11
1
8
23-1
23-2
23-3
17
20
3
10
12
4
2
6
15
13
16
21
22
9
7
7-1
RC125DHXEB/RC125DHXGA/RC140DHXEB/RC140DHXGA
NS090SDXEA_E_SM_33623A(1)_2.indd 9 2011-04-08 11:04:29
Samsung Electronics 5-10
Exploded Views and Parts List
Parts List
1 DB63-02706A GUARD COND MSWR-6B, TOUCH GRAY 1 1 SA
2 DB64-02525A CABINET-INSTALL BACK EGI, T0.7 1 1 SA
3 DB64-02526A CABINET-INSTALL FRONT EGI, T0.7 1 1 SA
4 DB90-05873A ASS'Y BASE OUT ASS'Y 1 1 SA
5 DB90-05876A ASS'Y CABI BACK-RH ASS'Y 1 1 SA
6 DB90-05877A ASS'Y CABI FRONT RH ASS'Y 1 1 SA
7 DB90-05878A ASS'Y CABI FRONT-LF ASS'Y 1 1 SA
7-1 DB63-02696A GUARD FAN PP, MT72TG 2 2 SA
8 DB90-05902A ASS'Y CABINET-TOP ASS'Y 1 1 SA
9 DB94-02697A ASS'Y PARTITION ASS'Y 1 1 SA
10 DB93-08235G ASS'Y CONNECTOR WIRE-COMP ASS'Y, 1 1 - SNA
DB93-08235F ASS'Y CONNECTOR WIRE-COMP ASS'Y, 3 - 1 SNA
11 DB93-11292A ASS'Y CONTROL OUT ASS'Y, 1 1 - SNA
DB93-11349A ASS'Y CONTROL OUT ASS'Y, 3 - 1 SNA
12 DB95-04522B ASS'Y THERMISTOR OUT-MANU ASS'Y 1 1 SA
13 DB31-00579A MOTOR FAN DAO335130ZRC, CLASS E 2 2 SA
14 DB60-00405A FASTENER-WASHER M8 2 2 SNA
15 DB67-01057A FAN-PROPELLER PP+MICA+GF, 480PI 2 2 SA
16 DB90-05875A ASS'Y BRACKET MOTOR ASS'Y 1 1 SA
17 DB60-30028A SCREW-HEX HWH,WP,M8,ZPC(WHT),SWRCH18A 3 3 SNA
18 DB63-02832A CLOTH-COMP TOP FELT, BLACK 1 1 SNA
19 DB63-02834A CLOTH-COMP SOUND FELT, BLACK 1 1 SNA
20 UG5T450FUEJXSG COMPRESSOR ASS'Y, 1 1 - -
UG5T450FUFJXSG COMPRESSOR ASS'Y, 3 - 1 -
21 DB90-02316E ASS'Y HOLDER-PLATE COND ASS'Y 2 2 SA
22 DB96-14661A ASS'Y COND OUT ASS'Y 1 1 SA
23 DB96-14898A ASS'Y-VALVE ASS'Y 1 1 SA
23-1 DB90-05874A ASS'Y BRACKET-VALVE RC100PHXEA,ManU 1 1 SA
23-2 DB96-14488A ASS'Y-VALVE 4WAY RC100PHXEA,R410A 1 1 SA
23-3 DB96-14510A ASS'Y TUBE-EEV RC100PHXEA,R410A 1 1 SA
No. SA/SNA Description Specification
Q'TY
RC125DHXEB
RC140DHXEB
RC125DHXGA
RC140DHXGA
Code No.
NS090SDXEA_E_SM_33623A(1)_2.indd 10 2011-04-08 11:04:30
5-11 Samsung Electronics
3
4
5
2
6
12
11
1
7
8
13
10
9
12-2
8-5
8-4
8-3
8-2
8-1
12-4
12-1
12-3
5-3 ASS'Y CONTROL OUT
RC125DHXEB/RC125DHXGA/RC140DHXEB/RC140DHXGA
NS090SDXEA_E_SM_33623A(1)_2.indd 11 2011-04-08 11:04:32
Samsung Electronics 5-12
Exploded Views and Parts List
Parts List
1 DB59-00016A AC REACTOR-1PHASE 30A 30A, 1 1 - SA
DB59-00015A AC REACTOR-3PHASE 20A 20A, 3 - 1 SA
2 DB61-04504A CASE-INV ABS, BLACK, 1 1 - SNA
DB61-04657A CASE-INV ABS, BLACK, 3 - 1 SNA
3 DB62-09441A HEAT SINK AL, 1 1 - SA
DB62-09441C HEAT SINK AL, 3 - 1 SA
4 0205-000178 GREASE-SILICON YG1111,TOSHIBA(NTR) 7g 7g SNA
5 6001-001054 SCREW-MACHINE TH,M4,L10 4 4 SNA
6 6002-000635 SCREW-TAPPING PH,M4,L8 2 2 SNA
7 6002-001149 SCREW-TAPPING TH,M4,L12 8 8 SNA
8 DB90-06115A ASS'Y CASE-PCB ASS'Y, 1 1 - SA
DB90-06115B ASS'Y CASE-PCB ASS'Y, 3 - 1 SA
8-1 DB61-04502A CASE-EMI ABS, BLACK 1 1 SNA
8-2 DB61-04503A CASE-MAIN ABS, BLACK 1 1 SNA
8-3 DB93-10809A ASS'Y CONNECTOR WIRE ASS'Y 1 1 SA
8-4 DB93-11109A ASS'Y PCB MAIN-OUT Inverter Platform #4, #5, #6 MAIN 1 1 SA
8-5 DB93-11110A ASS'Y PCB SUB-EMI Inverter Platform #4, #5 EMI, 1 1 - SA
DB93-11111A ASS'Y PCB SUB-EMI Inverter Platform #6 EMI, 3 - 1 SA
9 DB91-00306A ASS'Y-SCREW MACHINE M3, L16 2 2 SA
10 DB91-00307A ASS'Y-SCREW MACHINE M4, L16 2 2 SA
11 DB93-10807A ASS'Y CONNECTOR WIRE ASS'Y, MAIN TO INVERTER 1 1 SA
12 DB93-10966A ASS'Y CONTROL OUT-PLATE ASS'Y, 1 1 - SA
DB93-10966B ASS'Y CONTROL OUT-PLATE ASS'Y, 3 - 1 SA
12-1 DB65-00296A TERMINAL BLOCK-POWER 4P, 1 1 - SNA
DB65-00185C TERMINAL BLOCK-POWER 6P, 3 - 1 SNA
12-2 DB65-00297A TERMINAL BLOCK-COMM 2P 1 1 SA
12-3 DB90-05889A ASS'Y CASE CONTROL OUT ASS'Y 1 1 SA
12-4 DB93-10808A ASS'Y CONNECTOR WIRE ASS'Y, TERMIANL TO MAIN 1 1 SA
13 DB93-11112A ASS'Y PCB MAIN-INVERTER Inverter Platform #4, 1 1 - SA
DB93-11114A ASS'Y PCB MAIN-INVERTER Inverter Platform #6, 3 - 1 SA
14 DB93-10864A ASS'Y CONNECTOR WIRE RST AWG #14 - 1 SA
15 DB93-11241A ASS'Y CONNECTOR WIRE REATOR AWG #12 - 1 SA
No. SA/SNA Description Specification
Q'TY
RC125DHXEB
RC140DHXEB
RC125DHXGA
RC140DHXGA
Code No.
NS090SDXEA_E_SM_33623A(1)_2.indd 12 2011-04-08 11:04:32
6-1 Samsung Electronics
6. PCB Diagram
6-1 PCB Diagram
6-1-1 Indoor Unit
Samsung Electronics
19 18 15 20 17 16 21 14 22 23 24 25 11
1 2 3 4 9 5 6 7 8 10
12 13
Floating S/W : SMW250-02(BLK) Wired Remote Controller Communication : YW396-02(BLU)
Indoor Pipe In Temperature Sensor : SMW250-04(WHT) Option Load Connector : SMW250-05(YEL)
Indoor Room Temperature Sensor : SMW250-04(WHT) Heater : YW39607AV(WHT)
Indoor Pipe Out : SMW250-02(WHT) Indoor Address S/W
Temperature Sensor : SMW250-02(WHT) Indoor Option S/W
Heater Discharge : SMW250-02(YEL) Indoor Fan(TAP) : YW396-09AV(WHT)
Temperature Sensor : SMW250-02(YEL) Ventilator : YW396-03AV(BLK)
Wired Remote Controller Power : YW396-02(WHT) Drain Pump : YW396-03AV(YEL)
External Control(S/W Part) : SMW250-02(RED) Hot Coil : YW396-03AV(RED)
EEV : SMW250-05(BLU) : SMW250-05(BLU) Indoor Fan(SSR) : YW396-03AV(RED)
Display : SMW200-11(WHT) : SMW200-11(WHT) Power : YW396-03AV(WHT)
External Control(Display Part) : SMW250-04(RED) Transformer Out : YW396-03AV(WHT)
HALL IC : SMW250-03(BLU) Main Power In : YW396-03AV(BLU)
MICOM Download : SMW200-10(WHT) Power : YW396-03AV(BLU)
Indoor/Outdoor Communication : YW396-02(RED) Transformer In : SMW250-03(RED)
1
2
3
4
5
9
11
12
14
15
16
17
18
19
20
21
22
23
24
25
10
8
7
6
13
NS090SDXEA_E_SM_33623A(1)_2.indd 1 2011-04-08 11:04:33
Samsung Electronics 6-2
PCB Diagram
Samsung Electronics
19 18 15 20 17 16 21 14 22 23 24 25 11
1 2 3 4 9 5 6 7 8 10
12 13
Floating S/W : SMW250-02(BLK) Wired Remote Controller Communication : YW396-02(BLU)
Indoor Pipe In Temperature Sensor : SMW250-04(WHT) Option Load Connector : SMW250-05(YEL)
Indoor Room Temperature Sensor : SMW250-04(WHT) Heater : YW39607AV(WHT)
Indoor Pipe Out : SMW250-02(WHT) Indoor Address S/W
Temperature Sensor : SMW250-02(WHT) Indoor Option S/W
Heater Discharge : SMW250-02(YEL) Indoor Fan(TAP) : YW396-09AV(WHT)
Temperature Sensor : SMW250-02(YEL) Ventilator : YW396-03AV(BLK)
Wired Remote Controller Power : YW396-02(WHT) Drain Pump : YW396-03AV(YEL)
External Control(S/W Part) : SMW250-02(RED) Hot Coil : YW396-03AV(RED)
EEV : SMW250-05(BLU) : SMW250-05(BLU) Indoor Fan(SSR) : YW396-03AV(RED)
Display : SMW200-11(WHT) : SMW200-11(WHT) Power : YW396-03AV(WHT)
External Control(Display Part) : SMW250-04(RED) Transformer Out : YW396-03AV(WHT)
HALL IC : SMW250-03(BLU) Main Power In : YW396-03AV(BLU)
MICOM Download : SMW200-10(WHT) Power : YW396-03AV(BLU)
Indoor/Outdoor Communication : YW396-02(RED) Transformer In : SMW250-03(RED)
1
2
3
4
5
9
11
12
14
15
16
17
18
19
20
21
22
23
24
25
10
8
7
6
13
NS090SDXEA_E_SM_33623A(1)_2.indd 2 2011-04-08 11:04:33
6-3 Samsung Electronics
PCB Diagram
6-1-2 Outdoor Unit PCB
Main PCB
1 5 6 2 3 4
15
7 16 9 11 13
8 10 12 14
NS090SDXEA_E_SM_33623A(1)_2.indd 3 2011-04-08 11:04:44
Samsung Electronics 6-4

#1-#3 : 220~240Vac

#1-#3 : 220~240Vac

#1-#3 : 220~240Vac

#1-#3 : 220~240Vac

#1 : RXD_INV
#2 : TXD_INV
#3, #8 : N.C
#4 ~ #7 : Data signal
#9 : GND
#10 : DC 5V

#1 : DC 5V
#2 : MODE
#3 : Reset
#4~#6 : GRID_3/1/2
#7 : GND

#1-#2 : Outdoor Temp.
#3-#4 : Cond. Temp.
#5-#6 : Discharge Temp.
#7-#8 : OLP Temp.

#1~#4 : Motor signal


#5 : DC 12V

#1~#4 : Motor signal
#5 : DC 12V

#1~#4 : Motor signal


#5 : DC 12V

#1 : TXD
#2 : RXD
#3 : GND
#4 : DC 5V
#5 : DC 12V
#6 : INV. SMPS signal

#1 : Temp. signal
#2 : GND

#1 : High Pressure temp. signal


#3 : GND
#4 : DC 5V

#1 : DC 12V
#2 : GND

#1 : COM1
#2 : COM2

#1 : DC 12V
#2 : GND
#3 : DC 5V
#4 : COM1
#5 : COM2
CN11-AC POWER CN74-AC LOAD1 CN75-4WAY V/V CN71-AC LOAD2(Option)
CN37-Micom Download
CN82-EEV 2(Option)
CN42-High Pressure(Option)
CN35-AS-PRO
CN83-EEV 3(Option)
CN12-DC12V
CN43-Sensor
CN39-COMM-INV
CN31-Comm.
CN81-EEV 1
CN44-TEMP OPTION(Option)
CN33-Sub Comm.
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 4 2011-04-08 11:04:45
6-5 Samsung Electronics
Outdoor Unit PCB (cont.)
Inverter PCB : 1Phase I
- RC090DHXEA/RC100SHXEA/RC100DHXEA/RC125DHXEB/RC140DHXEB
2 3 4
6
5 8
7

#Reactor-A2 : WHT
#Reactor-B2 : WHT

#Reactor-A2 : BLK
#Reactor-B2 : BLK

#1 : RXD, #2 : TXD
#3 : GND, #4 : DC 5V
#5 : DC 12V, #6 : INV. SMPS signal

#1 : RXD_ATARO, #2 : TXD_ATARO
#3, #8 : N.C, #4~#7 : DATA signal
#9 : GND, #10 : DC 5V

For S/W engineer debugging

#1 : DC 360V
#2 : N.C
#3 : GND
#4 : DC 15V
#5 : FAN RPM
#6 : FAN RPM feedback

#1 : DC 360V
#2 : N.C
#3 : GND
#4 : DC 15V
#5 : FAN RPM
#6 : FAN RPM feedback

#1 : COMP. U-phase(RED)
#2 : COMP. V-phase(BLU)
#3 : COMP. U-phase(YEL)
Reactor-A1/B1 Reactor-A2/B2 CN50(2PIN/RED)-Communication CN22-Downloader
CN21-DAC/ENCODER CN91-FAN2 CN90-FAN1 CN71-COMP.
1
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 5 2011-04-08 11:04:46
Samsung Electronics 6-6
Outdoor Unit PCB (cont.)
Inverter PCB : 3Phase
- RC100DHXGA/RC125DHXGA/RC140DHXGA

2 6 7 3 4 5
9 8

#R : AC 380~400V : WHT
#S : AC 380~400V : BRN
#T : AC 380~400V : BLK

#1-#3 : AC 220~240V


#1 : RXD , #2 : TXD
#3 : GND, #4 : DC 5V
#5 : DC 12V, #6 : INV. SMPS signal

#1 : RXD_ATARO, #2 : TXD_ATARO
#3, #8 : N.C, #4~#7 : DATA signal
#9 : GND, #10 : DC 5V

For S/W engineer debugging


#1 : DC 360V , #2 : N.C
#3 : GND, #4 : DC 15V
#5 : FAN RPM, #6 : FAN RPM feedback

#1 : DC 360V, #2 : N.C
#3 : GND, #4 : DC 15V
#5 : FAN RPM, #6 : FAN RPM feedback

#1 : COMP. U-phase(RED)
#2 : COMP. V-phase(BLU)
#3 : COMP. U-phase(YEL)

#1-#2 : DCL Reactor
RST-AC POWER 3phase CN100-AC POWER CN31-MAIN COMM CN22-Downloader
CN21-DAC/ENCODER
CN600-REACTOR
CN91-FAN2 CN90-FAN1 CN800-COMP.
1
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 6 2011-04-08 11:04:59
6-7 Samsung Electronics
Outdoor Unit PCB (cont.)
EMI PCB : 1Phase
- RC***XE*

L1 : BRN

N1 : SKY-BLU

#1-#3 : AC 220~240V
L1-AC POWER L phase N1-AC POWER N phase CN01-AC POWER
3 1 2
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 7 2011-04-08 11:05:08
Samsung Electronics 6-8
Outdoor Unit PCB (cont.)
EMI PCB : 3Phase
- RC***XGA

#R : AC 380~400V : WHT
#S : AC 380~400V : BRN
#T : AC 380~400V : BLK

#1-#3 : AC 220~240V
RST-AC POWER 3phase CN100-AC POWER
2 1
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 8 2011-04-08 11:05:17
7-1 Samsung Electronics
7. Wiring Diagram
7-1 Indoor Unit
This Document can not be used without Samsungs authorization.
NS090SDXEA_E_SM_33623A(1)_2.indd 1 2011-04-08 11:05:18
Samsung Electronics 7-2
Wiring Diagram
7-2 Outdoor Unit
Outdoor Unit : RC***XE*
This Document can not be used without Samsungs authorization.
NS090SDXEA_E_SM_33623A(1)_2.indd 2 2011-04-08 11:05:20
7-3 Samsung Electronics
Outdoor Unit : RC***XGA
Outdoor Unit (cont.)
This Document can not be used without Samsungs authorization.
NS090SDXEA_E_SM_33623A(1)_2.indd 3 2011-04-08 11:05:23
MEMO
Samsung Electronics 7-4
NS090SDXEA_E_SM_33623A(1)_2.indd 4 2011-04-08 11:05:23
8. Schematic Diagram
8-1 Indoor Unit
8-1-1 MAIN PCB
Samsung Electronics 8-1
This Document can not be used without Samsungs authorization.
NS090SDXEA_E_SM_33623A(1)_2.indd 1-2 2011-04-08 11:09:12
This Document can not be used without Samsungs authorization.
Schematic Diagram
MAINPCB
Samsung Electronics
Schematic Diagram
8-7
8-1-2 OUTDOOR UNIT PCB
NS090SDXEA_E_SM_33623A(1)_2.indd 3-4 2011-04-08 11:09:34
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
Inverter PCB : 1Phase I
- RC***HXE*
Samsung Electronics
Schematic Diagram
8-8
NS090SDXEA_E_SM_33623A(1)_2.indd 5-6 2011-04-08 11:09:38
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
EMI PCB : 1Phase
- RC***XE*
Samsung Electronics
Schematic Diagram
8-10
NS090SDXEA_E_SM_33623A(1)_2.indd 7-8 2011-04-08 11:09:38
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
EMI PCB : 3Phase
- RC***XGA
Samsung Electronics
Schematic Diagram
8-11
NS090SDXEA_E_SM_33623A(1)_2.indd 9-10 2011-04-08 11:09:38
9-1 Samsung Electronics
Model Code
H
E

H
X

H
A

H
SER

H
/

H
100

H
NS

H
H

H
H

9. Reference Sheet
9-1 Index for Model Name
9-1-1 Indoor Unit
Product Type
N S Single
Capacity (3 DIGIT)
KW / BTU / Liter
Chassis Category
1 1 WAY
CST
2 2 WAY
M MINI 4 WAY
4 4 WAY
H
High Static
Pressure
Duct
S
Middle Static
Pressure
L
Low Static
Pressure(Slim)
E Air handler
G CCD (Slim)
C Ceiling
Conv J Console
F Floor type
P FAC & Mid/Large Size
B Mont Blanc
RAC
V Vivace
Q Neo Forte (EEV)
N Neo-Forte
W
Korean market
use
R Crystal
A Max
Rating Voltage
A 115V, 60Hz
B 220V, 60Hz
C 208~230V, 60Hz
D 200~220V, 50Hz
E 220~240V, 50Hz
F 208~230V, 60Hz, 3Phase
G 380~415V, 50Hz, 3Phase
M 127V, 50Hz
H 380V, 60Hz, 3Phase
J 460V, 60Hz, 3Phase
Version
1~9
Change point
(Korean market)
A~Z
Change point
(export/foreign market)
Z
The Z version is a
high-efficiency EEV Mode
indoor unit.
Mode
C C/O
H H/P
T Tender
V Value
When grade
classification is necessary
Z H/P (Flagship)
P H/P (Premium)
D H/P (Deluxe)
S H/P (Standard)
CP H/P (Premium)
Refrigerant
R R-22
X R410A
"/" can be removed from the buyer card if there are not enough digits.
Buyer Name
NS090SDXEA_E_SM_33623A(1)_2.indd 1 2011-04-08 11:06:05
Samsung Electronics 9-2
Reference Sheet
Index for Model Name (cont.)
Model Code
H
X

H
H

H
G

H
A

H
SER

H
/

H
140

H
RC

H
V

H

9-1-2 Outdoor Unit

MCD: Dummy mock-up model


/ can be removed from the buyer card if there are not enough digits.

Buyer Name
Product Type
N C Single (CAC)
Capacity (3 DIGIT)
HP / KW / BTU / TON
Chassis Category
P Inverter RPM
D Inverter DLX
S Inverter STD
F Constant rate (value)
X Constant rate (tender)
Z Flagship
T Tower (Top Discharge)
U Ice box
Refrigerant
R R-22
X R410A
Separator
1 Universal
1 1 WAY
CST
2 2 WAY
M MINI 4 WAY
4 4 WAY
H
High Static
Pressure
Duct S
Middle Static
Pressure
L
Low Static
Pressure(Slim)
C Ceiling
Conv J Console
F Floor type
P FAC & Mid/Large Size
Mode
C C/O
H H/P
T TROPICAL C/O
Q TROPICAL H/P
Rating Voltage
A 115V, 60Hz
B 220V, 60Hz
C 208~230V, 60Hz
D 200~220V, 50Hz
E 220~240V, 50Hz
F 208~230V, 60Hz, 3Phase
G 380~415V, 50Hz, 3Phase
M 127V, 50Hz
H 380V, 60Hz, 3Phase
J 460V, 60Hz, 3Phase
Version
1~9
Change point
(Korean market)
A~Z
Change point
(export/foreign market)
NS090SDXEA_E_SM_33623A(1)_2.indd 2 2011-04-08 11:06:05
9-3 Samsung Electronics
CONDENSER
High temperature and high pressure gas state coolant discharged from the compressor is converted to a liquid state as it is cooled
down by the heat emission in the outdoor condenser unit, and sent to the evaporator.
COMPRESSOR
Low temperature and low pressure coolant is compressed and sent to the cycling system
EVAPORATOR
Liquid coolant sucked in through the capillary tubes cools down the room by absorbing the surrounding heat as it evaporates
(converting from liquid to gas). (Absorbing heat required for evaporation)
SERVICE VALVE
You can open the valve by turning the need valve counterclockwise using hex wrench, and it is used for vacuum, gas purging, coolant
injection, coolant purging, and indoor-outdoor unit connection.
ACCUMULATOR
Accumulator prevents the flow of liquid-state coolant into the compressor. (Liquid-state coolant flowing into the compressor will
overload the compressor.)
Indoor Unit Outdoor Unit
Heat exchanger
Evaporator
Liquid pipe
Gas pipe
3-way valve
3-way valve
Electronic expansion valve
Compressor
Oil separator
4-way valve
Cooling
Heating
Leak check points
Aux accumulator
Fan
Heat exchanger
Evaporator
Fan
9-2 Refrigerating Cycle Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 3 2011-04-08 11:06:06
Samsung Electronics 9-4
9-3 Pressure Graph
-10
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
0 10 20 30 40 50 60
Outdoor Temp.(C)
Cooling
P
r
e
s
s
u
r
e
(
k
g
f
/
c
m

G
)
Cooling
32/23 27/19 21/15
50 10.0 9.1 8.0
35 9.0 8.3 7.2
20 6.8 6.3 6.4
7 7.6 7.1 6.5
-5 7.7 7.2 6.5
Indoor (C)
Outdoor(C)
Outdoor Temp.(C)
Waiting Mode
P
r
e
s
s
u
r
e
(
k
g
f
/
c
m

G
)
Waiting Mode
32/23 27/19 21/15
50 18.5 16.7 15.9
35 15.7 14.7 13.4
20 15.2 14.3 13.6
7 9.1 9.1 9.1
-5 5.6 5.6 5.6
-20 3.0 3.0 3.0
Indoor (C)
Outdoor(C)
Outdoor Temp.(C)
Heating
P
r
e
s
s
u
r
e
(
k
g
f
/
c
m

G
)
Heating
28/18 27/19 20/15
20 33.6 33.3 30.1
7 27.9 27 23.5
-5 24.2 23.9 19.9
-20 22.5 22.2 17.9
Indoor (C)
Outdoor(C)
NS090SDXEA_E_SM_33623A(1)_2.indd 4 2011-04-08 11:06:06
This Service Manual is a property of Samsung Electronics Co., Ltd.
Any unauthorized use of Manual can be punished under applicable
International and/or domestic law.
Samsung Electronics Co., Ltd. Apr. 2011.
Printed in Korea.
Code No. DB98-33623A(1)
GSPN(Global Service Partner Network)
Area Web Site
North America http://service.samsungportal.com
Latin America http://latin.samsungportal.com
CIS http://cis.samsungportal.com
Europe http://europe.samsungportal.com
China http://china.samsungportal.com
Asia http://asia.samsungportal.com
Mideast & Africa http://mea.samsungportal.com
NS100SSXEA_E_33623A(1)_co.indd 2 2011-04-08 10:52:44

You might also like