Professional Documents
Culture Documents
Samsung CAC 2011 (Slim Duct) Service Manual
Samsung CAC 2011 (Slim Duct) Service Manual
Samsung CAC 2011 (Slim Duct) Service Manual
#1-#3 : 220~240Vac
#1-#3 : 220~240Vac
#1-#3 : 220~240Vac
#1 : RXD_INV
#2 : TXD_INV
#3, #8 : N.C
#4 ~ #7 : Data signal
#9 : GND
#10 : DC 5V
#1 : DC 5V
#2 : MODE
#3 : Reset
#4~#6 : GRID_3/1/2
#7 : GND
#1-#2 : Outdoor Temp.
#3-#4 : Cond. Temp.
#5-#6 : Discharge Temp.
#7-#8 : OLP Temp.
#1 : Temp. signal
#2 : GND
#1 : DC 12V
#2 : GND
#1 : COM1
#2 : COM2
#1 : DC 12V
#2 : GND
#3 : DC 5V
#4 : COM1
#5 : COM2
CN11-AC POWER CN74-AC LOAD1 CN75-4WAY V/V CN71-AC LOAD2(Option)
CN37-Micom Download
CN82-EEV 2(Option)
CN42-High Pressure(Option)
CN35-AS-PRO
CN83-EEV 3(Option)
CN12-DC12V
CN43-Sensor
CN39-COMM-INV
CN31-Comm.
CN81-EEV 1
CN44-TEMP OPTION(Option)
CN33-Sub Comm.
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 4 2011-04-08 11:04:45
6-5 Samsung Electronics
Outdoor Unit PCB (cont.)
Inverter PCB : 1Phase I
- RC090DHXEA/RC100SHXEA/RC100DHXEA/RC125DHXEB/RC140DHXEB
2 3 4
6
5 8
7
#Reactor-A2 : WHT
#Reactor-B2 : WHT
#Reactor-A2 : BLK
#Reactor-B2 : BLK
#1 : RXD, #2 : TXD
#3 : GND, #4 : DC 5V
#5 : DC 12V, #6 : INV. SMPS signal
#1 : RXD_ATARO, #2 : TXD_ATARO
#3, #8 : N.C, #4~#7 : DATA signal
#9 : GND, #10 : DC 5V
For S/W engineer debugging
#1 : DC 360V
#2 : N.C
#3 : GND
#4 : DC 15V
#5 : FAN RPM
#6 : FAN RPM feedback
#1 : DC 360V
#2 : N.C
#3 : GND
#4 : DC 15V
#5 : FAN RPM
#6 : FAN RPM feedback
#1 : COMP. U-phase(RED)
#2 : COMP. V-phase(BLU)
#3 : COMP. U-phase(YEL)
Reactor-A1/B1 Reactor-A2/B2 CN50(2PIN/RED)-Communication CN22-Downloader
CN21-DAC/ENCODER CN91-FAN2 CN90-FAN1 CN71-COMP.
1
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 5 2011-04-08 11:04:46
Samsung Electronics 6-6
Outdoor Unit PCB (cont.)
Inverter PCB : 3Phase
- RC100DHXGA/RC125DHXGA/RC140DHXGA
2 6 7 3 4 5
9 8
#R : AC 380~400V : WHT
#S : AC 380~400V : BRN
#T : AC 380~400V : BLK
#1-#3 : AC 220~240V
#1 : RXD , #2 : TXD
#3 : GND, #4 : DC 5V
#5 : DC 12V, #6 : INV. SMPS signal
#1 : RXD_ATARO, #2 : TXD_ATARO
#3, #8 : N.C, #4~#7 : DATA signal
#9 : GND, #10 : DC 5V
For S/W engineer debugging
#1 : DC 360V , #2 : N.C
#3 : GND, #4 : DC 15V
#5 : FAN RPM, #6 : FAN RPM feedback
#1 : DC 360V, #2 : N.C
#3 : GND, #4 : DC 15V
#5 : FAN RPM, #6 : FAN RPM feedback
#1 : COMP. U-phase(RED)
#2 : COMP. V-phase(BLU)
#3 : COMP. U-phase(YEL)
#1-#2 : DCL Reactor
RST-AC POWER 3phase CN100-AC POWER CN31-MAIN COMM CN22-Downloader
CN21-DAC/ENCODER
CN600-REACTOR
CN91-FAN2 CN90-FAN1 CN800-COMP.
1
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 6 2011-04-08 11:04:59
6-7 Samsung Electronics
Outdoor Unit PCB (cont.)
EMI PCB : 1Phase
- RC***XE*
L1 : BRN
N1 : SKY-BLU
#1-#3 : AC 220~240V
L1-AC POWER L phase N1-AC POWER N phase CN01-AC POWER
3 1 2
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 7 2011-04-08 11:05:08
Samsung Electronics 6-8
Outdoor Unit PCB (cont.)
EMI PCB : 3Phase
- RC***XGA
#R : AC 380~400V : WHT
#S : AC 380~400V : BRN
#T : AC 380~400V : BLK
#1-#3 : AC 220~240V
RST-AC POWER 3phase CN100-AC POWER
2 1
PCB Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 8 2011-04-08 11:05:17
7-1 Samsung Electronics
7. Wiring Diagram
7-1 Indoor Unit
This Document can not be used without Samsungs authorization.
NS090SDXEA_E_SM_33623A(1)_2.indd 1 2011-04-08 11:05:18
Samsung Electronics 7-2
Wiring Diagram
7-2 Outdoor Unit
Outdoor Unit : RC***XE*
This Document can not be used without Samsungs authorization.
NS090SDXEA_E_SM_33623A(1)_2.indd 2 2011-04-08 11:05:20
7-3 Samsung Electronics
Outdoor Unit : RC***XGA
Outdoor Unit (cont.)
This Document can not be used without Samsungs authorization.
NS090SDXEA_E_SM_33623A(1)_2.indd 3 2011-04-08 11:05:23
MEMO
Samsung Electronics 7-4
NS090SDXEA_E_SM_33623A(1)_2.indd 4 2011-04-08 11:05:23
8. Schematic Diagram
8-1 Indoor Unit
8-1-1 MAIN PCB
Samsung Electronics 8-1
This Document can not be used without Samsungs authorization.
NS090SDXEA_E_SM_33623A(1)_2.indd 1-2 2011-04-08 11:09:12
This Document can not be used without Samsungs authorization.
Schematic Diagram
MAINPCB
Samsung Electronics
Schematic Diagram
8-7
8-1-2 OUTDOOR UNIT PCB
NS090SDXEA_E_SM_33623A(1)_2.indd 3-4 2011-04-08 11:09:34
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
Inverter PCB : 1Phase I
- RC***HXE*
Samsung Electronics
Schematic Diagram
8-8
NS090SDXEA_E_SM_33623A(1)_2.indd 5-6 2011-04-08 11:09:38
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
EMI PCB : 1Phase
- RC***XE*
Samsung Electronics
Schematic Diagram
8-10
NS090SDXEA_E_SM_33623A(1)_2.indd 7-8 2011-04-08 11:09:38
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
EMI PCB : 3Phase
- RC***XGA
Samsung Electronics
Schematic Diagram
8-11
NS090SDXEA_E_SM_33623A(1)_2.indd 9-10 2011-04-08 11:09:38
9-1 Samsung Electronics
Model Code
H
E
H
X
H
A
H
SER
H
/
H
100
H
NS
H
H
H
H
9. Reference Sheet
9-1 Index for Model Name
9-1-1 Indoor Unit
Product Type
N S Single
Capacity (3 DIGIT)
KW / BTU / Liter
Chassis Category
1 1 WAY
CST
2 2 WAY
M MINI 4 WAY
4 4 WAY
H
High Static
Pressure
Duct
S
Middle Static
Pressure
L
Low Static
Pressure(Slim)
E Air handler
G CCD (Slim)
C Ceiling
Conv J Console
F Floor type
P FAC & Mid/Large Size
B Mont Blanc
RAC
V Vivace
Q Neo Forte (EEV)
N Neo-Forte
W
Korean market
use
R Crystal
A Max
Rating Voltage
A 115V, 60Hz
B 220V, 60Hz
C 208~230V, 60Hz
D 200~220V, 50Hz
E 220~240V, 50Hz
F 208~230V, 60Hz, 3Phase
G 380~415V, 50Hz, 3Phase
M 127V, 50Hz
H 380V, 60Hz, 3Phase
J 460V, 60Hz, 3Phase
Version
1~9
Change point
(Korean market)
A~Z
Change point
(export/foreign market)
Z
The Z version is a
high-efficiency EEV Mode
indoor unit.
Mode
C C/O
H H/P
T Tender
V Value
When grade
classification is necessary
Z H/P (Flagship)
P H/P (Premium)
D H/P (Deluxe)
S H/P (Standard)
CP H/P (Premium)
Refrigerant
R R-22
X R410A
"/" can be removed from the buyer card if there are not enough digits.
Buyer Name
NS090SDXEA_E_SM_33623A(1)_2.indd 1 2011-04-08 11:06:05
Samsung Electronics 9-2
Reference Sheet
Index for Model Name (cont.)
Model Code
H
X
H
H
H
G
H
A
H
SER
H
/
H
140
H
RC
H
V
H
9-1-2 Outdoor Unit
Buyer Name
Product Type
N C Single (CAC)
Capacity (3 DIGIT)
HP / KW / BTU / TON
Chassis Category
P Inverter RPM
D Inverter DLX
S Inverter STD
F Constant rate (value)
X Constant rate (tender)
Z Flagship
T Tower (Top Discharge)
U Ice box
Refrigerant
R R-22
X R410A
Separator
1 Universal
1 1 WAY
CST
2 2 WAY
M MINI 4 WAY
4 4 WAY
H
High Static
Pressure
Duct S
Middle Static
Pressure
L
Low Static
Pressure(Slim)
C Ceiling
Conv J Console
F Floor type
P FAC & Mid/Large Size
Mode
C C/O
H H/P
T TROPICAL C/O
Q TROPICAL H/P
Rating Voltage
A 115V, 60Hz
B 220V, 60Hz
C 208~230V, 60Hz
D 200~220V, 50Hz
E 220~240V, 50Hz
F 208~230V, 60Hz, 3Phase
G 380~415V, 50Hz, 3Phase
M 127V, 50Hz
H 380V, 60Hz, 3Phase
J 460V, 60Hz, 3Phase
Version
1~9
Change point
(Korean market)
A~Z
Change point
(export/foreign market)
NS090SDXEA_E_SM_33623A(1)_2.indd 2 2011-04-08 11:06:05
9-3 Samsung Electronics
CONDENSER
High temperature and high pressure gas state coolant discharged from the compressor is converted to a liquid state as it is cooled
down by the heat emission in the outdoor condenser unit, and sent to the evaporator.
COMPRESSOR
Low temperature and low pressure coolant is compressed and sent to the cycling system
EVAPORATOR
Liquid coolant sucked in through the capillary tubes cools down the room by absorbing the surrounding heat as it evaporates
(converting from liquid to gas). (Absorbing heat required for evaporation)
SERVICE VALVE
You can open the valve by turning the need valve counterclockwise using hex wrench, and it is used for vacuum, gas purging, coolant
injection, coolant purging, and indoor-outdoor unit connection.
ACCUMULATOR
Accumulator prevents the flow of liquid-state coolant into the compressor. (Liquid-state coolant flowing into the compressor will
overload the compressor.)
Indoor Unit Outdoor Unit
Heat exchanger
Evaporator
Liquid pipe
Gas pipe
3-way valve
3-way valve
Electronic expansion valve
Compressor
Oil separator
4-way valve
Cooling
Heating
Leak check points
Aux accumulator
Fan
Heat exchanger
Evaporator
Fan
9-2 Refrigerating Cycle Diagram
NS090SDXEA_E_SM_33623A(1)_2.indd 3 2011-04-08 11:06:06
Samsung Electronics 9-4
9-3 Pressure Graph
-10
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
0 10 20 30 40 50 60
Outdoor Temp.(C)
Cooling
P
r
e
s
s
u
r
e
(
k
g
f
/
c
m
G
)
Cooling
32/23 27/19 21/15
50 10.0 9.1 8.0
35 9.0 8.3 7.2
20 6.8 6.3 6.4
7 7.6 7.1 6.5
-5 7.7 7.2 6.5
Indoor (C)
Outdoor(C)
Outdoor Temp.(C)
Waiting Mode
P
r
e
s
s
u
r
e
(
k
g
f
/
c
m
G
)
Waiting Mode
32/23 27/19 21/15
50 18.5 16.7 15.9
35 15.7 14.7 13.4
20 15.2 14.3 13.6
7 9.1 9.1 9.1
-5 5.6 5.6 5.6
-20 3.0 3.0 3.0
Indoor (C)
Outdoor(C)
Outdoor Temp.(C)
Heating
P
r
e
s
s
u
r
e
(
k
g
f
/
c
m
G
)
Heating
28/18 27/19 20/15
20 33.6 33.3 30.1
7 27.9 27 23.5
-5 24.2 23.9 19.9
-20 22.5 22.2 17.9
Indoor (C)
Outdoor(C)
NS090SDXEA_E_SM_33623A(1)_2.indd 4 2011-04-08 11:06:06
This Service Manual is a property of Samsung Electronics Co., Ltd.
Any unauthorized use of Manual can be punished under applicable
International and/or domestic law.
Samsung Electronics Co., Ltd. Apr. 2011.
Printed in Korea.
Code No. DB98-33623A(1)
GSPN(Global Service Partner Network)
Area Web Site
North America http://service.samsungportal.com
Latin America http://latin.samsungportal.com
CIS http://cis.samsungportal.com
Europe http://europe.samsungportal.com
China http://china.samsungportal.com
Asia http://asia.samsungportal.com
Mideast & Africa http://mea.samsungportal.com
NS100SSXEA_E_33623A(1)_co.indd 2 2011-04-08 10:52:44