This document provides the technical specifications for a 1.6 MVA oil filled auxiliary transformer. It includes details of the transformer ratings, insulation levels, losses, efficiencies, cooling system, tank construction, core, coils, tap changer and insulating oil specifications. The transformer is designed for outdoor installation, has an ONAN cooling type and meets IS 2026 and CBIP standards.
This document provides the technical specifications for a 1.6 MVA oil filled auxiliary transformer. It includes details of the transformer ratings, insulation levels, losses, efficiencies, cooling system, tank construction, core, coils, tap changer and insulating oil specifications. The transformer is designed for outdoor installation, has an ONAN cooling type and meets IS 2026 and CBIP standards.
This document provides the technical specifications for a 1.6 MVA oil filled auxiliary transformer. It includes details of the transformer ratings, insulation levels, losses, efficiencies, cooling system, tank construction, core, coils, tap changer and insulating oil specifications. The transformer is designed for outdoor installation, has an ONAN cooling type and meets IS 2026 and CBIP standards.
This document provides the technical specifications for a 1.6 MVA oil filled auxiliary transformer. It includes details of the transformer ratings, insulation levels, losses, efficiencies, cooling system, tank construction, core, coils, tap changer and insulating oil specifications. The transformer is designed for outdoor installation, has an ONAN cooling type and meets IS 2026 and CBIP standards.
1 of 15 Schedule K TECHNICAL PARTICULARS FOR OIL FILLED AUXILIARY TRANSFORMERS
A. OIL FILLED AUXILIARY TRANSFORMERS
1.0 General : 1.1 Make : Voltamp Transformers Ltd. 1.2 Type : Oil filled 1.3 Number of Windings per phase : Two 1.4 Number of Phases : Three 1.5 Service Outdoor 1.6 Reference Standard : IS 2026 & CBIP Publications. 2.0 Rating : 2.1 Type of Cooling : ONAN 2.2 Rated Output
I. With ONAN Cooling MVA
1.6 2.3 Rated Voltage (No-Load) kV H.V. : 6.6 L.V. : 0.433 System Voltage Variation : 10% 2.4 Rated Current A H.V. : 139.96 L.V. : 2133.39 2.5 Rated Frequency Hz : 50 5% 2.6 Connection Project : 2X135 MW Meenakhi Energy Pvt. Lmt. Package: LV Oil filled transformer Bidders Name: M/S.Voltamp Transformers Ltd.
E-50994 Rev. : 00
2 of 15 H.V. : Delta L.V. : Star 2.7 Vector Group Reference : Dyn11 2.8 Voltage withstand Time
s a. 110% of rated voltage : Continuous b. 125% of rated voltage : 60 sec c. 140% of rated voltage : 5sec d. 150% of rated voltage : 1 sec 2.9 Overfluxing Capability a. For Overfluxing Factor 1.1 : Continuous b. 1.25 : 60 sec c. 1.4 : 5 sec 3.0 Temperature 3.1 Reference ambient temperature C 50 3.2 Temperature rise over reference ambient Deg. C :
a. Of Top oil by thermometer
C : 50 b. Of winding by resistance C : 55 3.3 Maximum continuous over loading capacity of the transformer without exceeding the specified winding temperature
At ambient of 40C
&
80% OF Initial loading : % Overload Time At 110%
At 130%
At 150%
At 200% 4 hrs.
1.5hrs
1 hrs
N.A. 3.4 Thermal time constant h Approx. 2.5 Hrs Project : 2X135 MW Meenakhi Energy Pvt. Lmt. Package: LV Oil filled transformer Bidders Name: M/S.Voltamp Transformers Ltd.
E-50994 Rev. : 00
3 of 15 4.0 Tappings 4.1 Type : Off Circuit 4.2 Capacity : 11 KV, 150 Amp 4.3 Range - Steps x % variation : +/-5%in steps of 2.5% 4.4 Taps provided on HV/LV Winding. : HV side 5.0 Insulation Level 5.1 Separate source power frequency voltage withstand. kV rms Winding Bushing H.V : 20 28 L.V. : 3 3 L.V. Neutral (for bushing) : 3 3 5.2 Induced overvoltage withstand. kV rms Winding Bushing H.V : }Twice the rated } voltage and } double } frequency } } L.V. : L.V. Neutral ( for bushing) : 5.3 Full wave lightning impulse withstand voltage kV peak Winding Bushing H.V : 60 75 L.V. : NA NA 6.0 Impedance at Principal Tap at Rated Frequency and 75 C winding temperature with 100% rating : 6.1 Impedance at principal tap % : 6.25% (without negative tolerance with +10% tol.) 6.2 Impedance at maximum voltage tap
% 6.5625 6.4 Reactance at rated current for principal tap
% : 6.148% 6.5 Resistance at 75C. % 1.125% 6.6 Zero Sequence Impedance at 75C at principal tap.
% : 5.94% (Approx.) 6.7 Capacitance of Windings F / phase : a. H.V. - Earth b. L.V. - Earth c. H.V - L.V
: 491 pf 487 pf 600 pf
7.0 Guaranteed Losses at Principal Tap, Full Load and 75C.
7.1 No load losses at rated voltage and at rated frequency and without any +ve tolerances
kW : 1.6 KW (max.) 7.2 Load Losses at rated current without any +ve tolerances
kW : 18.0 kw (max.) 7.3 Total losses kW : 19.6 KW (max.) 8.0 Efficiency at 75C and 0.8 Power Factor Lag and at unity power factor
: 0.8 p.f. unity p.f.
8.1 At full load % : 98.49 98.79 8.2 At 3/4 full load % : 98.79 99.03 8.3 At 1/2 full load % : 99.24 99.06 8.4 Maximum efficiency % : 99.334 8.4.1 Load and Power Factor at which it occures
: 9.1 At unity power factor % : 1.314 9.2 At 0.8 power factor lagging % : 4.679 10.0 No Load Current referred to HV at rated frequency
10.1 At 90% rated voltage A : Approx. 1% of FLRC 10.2 At 100% rated voltage A : Approx.2% of FLRC 10.3 At 110% rated voltage A : Approx.3% of FLRC 11.0 Approximate Maximum Flux Density
11.1 At 90% rated voltage Wb / m 2
: 1.53 11.2 At 100% rated voltage Wb / m 2
: 1.7 11.3 At 110% rated voltage Wb / m 2
: 1.87 12.0 Maximum Current Density : 12.1 H.V. Winding A / cm 2
: 300 12.2 L.V. Winding A / cm 2
: 300 12.3 Maximum Current Density under short circuit : 12.3.1 H.V. Winding A / cm 2
: 4800 12.3.2 L.V. Winding A / cm 2
: 4800 13.0 Withstand Time without injury for
13.1 Three phase dead short circuit at terminal with rated voltage maintained on the other side
6 of 15 13.2 Single phase short-circuit at terminal with rated voltage maintained on other side
s : 2 14.0 Cooling System 14.1 a. Radiators on the main tank
Number of radiators
: Yes
4 15.0 Details of Tank 15.1 Material : Low Carbon Steel 15.2 Thickness of sides mm : 5 15.3 Thickness of bottom mm : 6 15.4 Thickness of cover mm : 10 15.5 Tank Designed for : 15.5.1 Vacuum withstand capability or main tank and accesories
mm of Hg
: 250 15.5.2 Vacuum leak rate of transformer
N.A. 15.5.3 Pressure kN / m 2
: 34.7 16.0 Core 16.1 Type - Core or shell : Core 16.2 Core material : CRGO silicon steel laminations 16.3 Thickness of lamination mm : 0.27 to 0.3 mm 16.4 Insulation of lamination : Carlite 16.5 Equivalent cross-sectional area
cm : 350 16.6 Type of joint between core and yoke Mitred interleaved Project : 2X135 MW Meenakhi Energy Pvt. Lmt. Package: LV Oil filled transformer Bidders Name: M/S.Voltamp Transformers Ltd.
E-50994 Rev. : 00
7 of 15
16.7 Percentage silicon content Approx.4% 17.0 Coils 17.1 Type of Coil : a. H.V : Continuous disc b. L.V. : Spiral 17.2 Conductor Material : Electrolytic copper 17.3 Insulating Material : CLASS - A a. H.V - Turn : Oil impregnated paper b. L.V - Turn Oil impregnated paper c. L.V. - Earth : Press board d. H.V. - L.V. : Press board 17.4 Magnetising inrush current A Approx. 5to 6 times of FLRC 17.5 Magnetising current at rated frequency and at rated voltage
A Approx.2%of FLRC at rated voltage 17.6 Conductor area approx
HV
LV
In sq. mm (approx.)
26.94
711.13 18.0 Off-circuit tap changer details
18.1 Make : Voltamp / Paragon 18.2 Type : Off Circuit 18.3 Rated Voltage class of tap changer
8 of 15 18.4 Rated Current A : 150A 18.5 Auxiliary Power kW : NA 18.6 Step voltage V 165 volts 18.7 Number of steps 4 18.8 Control Manual 18.9 Maximum Short Circuit Current withstand capability :
a. Current A/mm2 : 1.29 b. Time s : 2 18.10 Local indicator furnished for : a. Tap position : NA 18.11 Number of revolutions to complete one step
: NA 18.12 Time to complete one step on Manual operation
s : NA 18.13 Approximate overall weight kg Included in total weight 18.14 Approximate overall dimensions(With 5% Tol.)
mm Included in total weight 18.15 Approximate overall quantity of oil
L Included in total weight 18.16 Whether the following provisions are provided?
11 of 15 22.1 H.V. : Cable box 22.2 L.V. : Bus duct flange 22.3 L.V. Neutral : Inside Bus duct 23.0 Marshalling Box 23.1 Weatherproof, suitable for outdoor duty : Yes 23.2 Degree of protection : IP-55 23.3 Painting shade Siemens Grey RAL- 7032 24.0 Terminal Blocks : 24.1 Make : Elmex / Connect well 24.2 Type : Clip on type 24.3 20% spare terminals furnished? : Yes 25.0 Wiring 25.1 Cable type : FRLS XLPE insulated 25.2 Voltage grade V : 1.1 KV 25.3 Conductor Size
Material
Stranded mm 2
Yes/No. : : : 2.5 sq. mm
Stranded Cu
Yes 26.0 Trip and Alarm Contacts Ratings (OTI and WTI)
26.1 Voltage V : 220 V DC 26.2 Rated : Making current A : 0.25/0.5 A Breaking Current A : 0.25/0.5 A 27.0 Accessories Project : 2X135 MW Meenakhi Energy Pvt. Lmt. Package: LV Oil filled transformer Bidders Name: M/S.Voltamp Transformers Ltd.
E-50994 Rev. : 00
12 of 15 Each transformer furnished with fittings and accessories as per specification ?
Yes / No : Yes. 28.0 Detail of Conservator 28.1 Volume of Conservator L : 90 Ltr. (Approx.) 28.2 Volume of oil between the highest and lowest levels
: As per CBIP b. Duration h : As per CBIP c. Permanent deflection mm : As per CBIP 35.4 Oil leakage test on each transformer
: a. Test pressure kN / m 2
: As per CBIP b. Duration h ; As per CBIP 35.5 Core bolt withstand voltage for 1 minute on each transformer
kV : 2 KV rms 36 GENERAL Minimum draw bar pull required to move the transformer on level track?
-- 37 ACCESSORIES A. NEUTRAL CURRENT TRANSFORMER
37.1 General 37.1.1 Make : PRAGATI/KAPPA/AE 37.1.2 Type : Resin cast 37.1.3 Reference Standard : IS:2705 37.1.4 Use : Back up earth fault 37.2 Rating 37.2.1 C.T.Ratio A : 2500/1
15 of 15 37.2.4 Burden VA : 15 37.3 Insulation Class : A 37.3.1 Temperature rise at rated burden over top oil temperature C : As per IS : 2705 37.4 Characteristics 37.4.1 Secondary resistance R CT at 75C :
N.A.
37.4.2 Knee point voltage V k V : 37.4.3 Excitation current at V k/2 A . : 37.5.0 Dimension and Weights 37.5.1 Dimension(LxBxH) (With 5% Tol.) mm : Included in overall dimensions 37.5.2 Weight kg : Included in overall dimensions 37.6 Tests : As per standard B TEMPERATURE INDICATORS (OTI / WTI )
37.7.1 Manufacturer Prefect Control / Precimeasures 37.7.2 Range 0-150 C 37.7.3 Accuracy % 1.5% of FSD