Siemens S5
Siemens S5
Hardware
Siemens PLC 115U, CPU 941, 942, 943
CP 523 card, 6ES5 523-3UA11
Please note:
for 135U the CPU 928B is used
for 115U the CP 523 card is used
2
Function
In DB100 is keyed in how many values that are wanted read/written in the connected
compressors. The compressors are keyed in succession: 1-2-3-4 etc. and no holes
must occur. Each compressor has its own DB (DB70 DB83). Here is keyed in the
wanted values to be read/written (HEX-number, see York Comsab II manual).
Further, the values that are wanted transferred to the compressor are keyed in.
Max
Max
Max
14 compressors
29 reading points per compressor
10 writing points per compressor
/var/www/apps/conversion/tmp/scratch_5/239579271.doc
DW 150:
DW 151:
-:
-:
DW 159:
KF
KF
+12
+2
In general
DW 1
DW 14
DW 31
DW 44
If the contents in one of these data words = 0, then the driver restarts from 1.
5.2
/var/www/apps/conversion/tmp/scratch_5/239579271.doc
5.3
6.
Compressor 7
wants to read A:
B:
To Comsab
DB 76
DW 1
DW 2
KH
KH
26
26
22
20
From Comsab
DB 76
DW 50 KF value (oil temperature)
DW 51 KF value (suction temperature)
6.2
Compressor 3
Wants to write A:
B
To Comsab
DB 72
set point 1
set point 2
DW 100
DW 101
DW 150
DW 151
KH
KH
KF 234
KF 325
2F
30
(-23.4 C)
(- 32.5 C)
7.
Cable
Comsab II
No connec.
Pin no. 8 (Rx)
Pin no. 2(Tx)
Pin no. 1(Gnd)
Plug
(9 pole)
Screen
-
/var/www/apps/conversion/tmp/scratch_5/239579271.doc