Professional Documents
Culture Documents
Спецефикация Кондиционера Uniflair SUAV0601A
Спецефикация Кондиционера Uniflair SUAV0601A
txt
AIR CONDITIONING UNIT WITH REMOTE AIR COOLED CONDENSER
Air conditioner model: SUAV0601A
Unit power supply: 460/3ph/60Hz
Refrigerant: R410A
Fan(s): E.C. -Backward curved centrifugal motorfans
Condenser model: CAP0801
Condenser - Power supply: 230/1ph/60Hz
Nr. of condensers: 1
WORKING CONDITIONS
|Dry bulb temperature 24.0C
|Relative humidity 50%
|Wet bulb temperature 16.8C
|
|Altitude a.s.l. 800m
|External static pressure 20 Pa
|
|Outside air temperature 40.0C
|
---------------------------------------------------------
-----------------------------------------------------------------
PERFORMANCE / FEATURES
|Compressor(s) ON 1 -
|Total cooling capacity 16.4 kW
|Sensible cooling capacity 16.1 kW
|Net total cooling capacity 15.6 kW
|Net sensible cooling capacity 15.4 kW
|SHR 98.2%
|EER (total cooling capacity/total system powerconsumpt.)2.4kW/kW
|COP (Compressor Coefficient of Performance) 3.0kW/kW
|Room unit air flow rate 5000 m/h
|Room unit air flow rate 1.4 m/s
|Discharge air temperature off unit 13.7C
|Discharge air relative humidity off unit 93%
|Room unit absorbed power 6.3 kW
|Compressor absorbed power 5.5 kW
|Compressor absorbed current 11.3 A
|Number of fans 2- |
|Fan(s) absorbed power 0.7 kW
Page 1
Submital SUAV0601.txt
|Fan(s) electr. abs. 5.3 A
|Fan(s) speed regulation 83% |
|Max external static pressure 101.4 Pa
|Sound pressure level at 2 m in free field (bottomair suction) 61.5dB(A)
|Sound pressure level at 2 m in free field (frontair suction) 63.5dB(A)
|Condenser absorbed power 0.4 kW
|Condenser absorbed current 1.9 A
|Condenser air flow rate 9127 m/h
|Condenser air flow rate 2.5 m/s
|Condenser sound pressure level at 5 m in free field (with 51.0 dB(A)
|Condenser sound pressure level at 5 m in free field (without 52.7 dB(A)
|(with external static pressure= -
---------------------------------------------------------
-----------------------------------------------------------------
---------------------------------------------------------
-----------------------------------------------------------------
The perfomances mentioned above is obtained by means of theoretical
calculations and they are affected by consequent tolerances
UNIFLAIR S.p.A. - Calculation program "UNICALC" vers. 3.5.2 (user profile)
1/2 09/04/2013
AIR CONDITIONING UNIT WITH REMOTE AIR COOLED CONDENSER
Air conditioner model: SUAV0601A
Unit power supply: 460/3ph/60Hz
Refrigerant: R410A
Fan(s): E.C. - Backward curved centrifugal motorfans
Condenser model: CAP0801
Condenser - Power supply: 230/1ph 60Hz
Nr. of condensers: 1
PERFORMANCE OF OPTIONS
|HUMIDIFIERS
|Number of humidifiers 1-
|Rated electrical power 2.2kW
|Rated electrical current 9.6A
|STANDARD ELECTRICAL HEATERS
|Number of standard heaters 2-
|Total rated electrical power of heaters 6.0 kW
Page 2
Submital SUAV0601.txt
|Total rated electrical current for heaters 8.7 A
|EU4 FILTER
---------------------------------------------------------
-----------------------------------------------------------------
DIMENSIONS
| Air Conditioner Unit
|Height 1740 mm
|Width 1200 mm
|Depth 450 mm
|Weight 260 kg
|Condenser (Without legs)
|Height 720 mm
|Width 1877 mm
|Depth 520 mm
|Weight 67 kg
---------------------------------------------------------
-----------------------------------------------------------------
---------------------------------------------------------
-----------------------------------------------------------------
The perfomances mentioned above is obtained by means of theoretical
calculations and they are affected by consequent tolerances
UNIFLAIR S.p.A. - Calculation program "UNICALC" vers. 3.5.2 (user profile)
2/2 09/04/2013
Page 3