A PRODUCT OF

E-LABS
EL AM-101
ANNUNCIATION MODULES
Contact us:
TEL : 042-5884232 Fax : 042-5868145
Email : info@epesol.com URL : www.epesol.com
EPESOL (Pvt) Ltd
HIGHLIGHTINGFEATURES:

Self-contained microprocessor based multi channel


alarmannunciator unit
16contact operatedon/off alarm
Multiple LEDs for visual alarm indication for each
windowprovide redundancy
Alarm channels activated by normally open or
normallyclosedcontact
Compact Design, highly reliable, allows
incorporationof customchanges withease
Meets IEC60255-5 Ratings
AlarmDisplaywindows selectionavailable
Voltage type selectionoptionavailable (ACor DC)
Long life super bright multiple LEDs installed in
eachwindowtoensure longmaintenance free period
Input voltage selectionrange available
Lamptest input available
An output toactuate audible alarm(buzzer / Hooter)
Alarmacknowledge input
Highly reliable switch mode power supply to
accommodate wide range ofACor DCvoltage.
Composed of three modules (Annunciation, I/O
module, power module) mountedona single PCB
8
8
Protection:
Accessories:

Over voltage
Mountingscrews
Floor Stand
INTRODUCTION:
EL AM-101 is highly reliable microprocessor based
annunciator unit that is used in Power Plants, Grid Station,
Substations & industrial Panels for providing supervisory
control
The general purpose is to provide supervision in the
process occurring in IPPs, Grid Stations, industries & to
generate an alarm for any abnormal condition by
illuminating respecting LED based window, common
audible alarm by using any audible device (bell, hooter,
siren)
OPERATIONCRITERIA:
The annunciation event is indicated by the input signal
changing fromlowto high voltage level. Each event has a
dedicated display Windowwith user Defined text message
written on it. AM-101can be modified to handle different
input signal voltage levels.Contrary to conventional
annunciator AM-101 is equipped in For illuminating the
display windows the light bulbs have been replaced by
longer life super bright LEDs, thus practically eliminating
the needof frequent bulbreplacement.
In order to distinguish between noise signals &
fault signals, it takes 200msec to annunciate fault window
&actuate the audible alarm.
NOTE:
DISTANCE RELAY
SET-A TRIPPED
DISTANCE RELAY
SET-B TRIPPED
LINE OC & EF
RELAY TRIPPED
50BF DIRECT
TRIP SEND
CB + Q1
50BF TRIP
CB + Q1
TRIP
R3 PANEL LOR(s)
OUT OF SERVICE
CB + Q3
TRIP
R4 PANEL LOR(s)
OUT OF SERVICE
CB + Q2
TRIP
R5 PANEL LOR(s)
OUT OF SERVICE
R1 PANEL LOR(s)
OUT OF SERVICE
R6 PANEL LOR(s)
OUT OF SERVICE
CB + Q3
50BF TRIP
CB + Q2
50BF TRIP
132 kV
CB TRIP
TS101 EL AM-101

Number of fault windows selection


Operating Voltage selection
Casing Selection
LEDs color selection
Fault window initiation on pickup or dropout
Fault window flash rate selection
Fault window input voltage selection
Hooter silence independent input selection
For all available optional features please see
the Specifications section on next page.
OPTIONAL PARAMETERS
Utility & Communications
Manufacturing:

Power Houses
Power Substations
Protection and Control Systems
Microwave Relay Sites
Switchgears control
Control signaling of the process
Alarm Systems
Commercial:

Alarm Systems
Solar Systems control signaling
Uninterruptible power Systems
DC Control Systems
APPLICATIONS
AProduct of ELABS
EP SOL(Pvt) Ltd
ELECTRICAL POWER ENGINEERING SOLUTIONS
50BF DIRECT
TRIP SEND
CB + Q2
50BF TRIP
CB + Q2
TRIP
R4 PANEL LOR(s)
OUT OF SERVICE
DISTANCE RELAY
SET-A TRIPPED
132 kV
CB TRIP
R1 PANEL LOR(s)
OUT OF SERVICE
R5 PANEL LOR(s)
OUT OF SERVICE
CB + Q1
50BF TRIP
CB + Q1
TRIP
R2 PANEL LOR(s)
OUT OF SERVICE
R6 PANEL LOR(s)
OUT OF SERVICE
CB + Q3
50BF TRIP
CB + Q3
TRIP
R3 PANEL LOR(s)
OUT OF SERVICE
SPARE
MOUNTING & DIMENSIONS
DISTANCE RELAY
SET-A TRIPPED
DISTANCE RELAY
SET-B TRIPPED
LINE OC & EF
RELAY TRIPPED
50BF DIRECT
TRIP SEND
CB + Q1
50BF TRIP
CB + Q1
TRIP
CB + Q3
TRIP
CB + Q2
TRIP
R1 PANEL LOR(s)
OUT OF SERVICE
CB + Q3
50BF TRIP
CB + Q2
50BF TRIP
132 kV
CB TRIP
150
1
1
0
10 155
130
FRONT VEIW SIDE VEIW TOP VIEW
EL AM-101
AProduct of ELABS
SPECIFICATIONS
Power Supply:
Input Voltage/ Frequency:
Display Windows:
8
8

Single Phase:
Output Power:
Numbers:
Lighting devices:
Flash Rate:
100 Vac to 275 Vac @ 50Hz / 60Hz (STM)
100 Vdc to 375 Vdc (STM)
Customized (SPMs)
25 Watts (STM)
8 or 12 (STM)
4 or 6 (SPMs)
LEDs of amber color (STM)
LEDs of red, yellow, green, blue and white
(SPMs)
3 different color LEDs in a single window, the
color selection can be done through field (SPMs)
40 flashes per minute (STM)
Variable flash rate where flash frequency changes
in case of fault persistence and fast events.
(SPMs)

Pickup:
Temperature:
Relative Humidity:
Power Consumption:
Input Voltage:
Input Voltage:
Inputs change from Low to high (STM)
Inputs change from High to low (SPMs)
-100C to 550C (STM)
100% (STM)
10 Watts approx (STM)
Universal type input AC or DC (STM)
100 Vac to 275 Vac or 100 Vdc to 375 Vdc (SPMs)
137mm x 97 mm independent of no. of windows
Environmental:
Fault Signals:
Panel Cutout:
8
8
8
STM Standard Model
SPMs Special Models
THEORY OF OPERATION:
Due to the flexible architecture, all the standard sequences
can be incorporated. The basic function of anAM-101 is to
detect faults or events at its inputs, (terminated outside the
case) and indicate that, by flashing pertinent windows,
followedbyACKNOWLEDGE, andRESETetc
Once an input is energized, the lights on the relevant
window start flashing and the hooter comes on. The
duration of flash rate is sufficient for the inscription of
the functiontobe readeasily
On pressing the ACKNOWLEDGE button, the
indication flashing will be stopped, and light on the
fault window will be kept ON continuously. If fault
signal is removed before the RESET push button is
pressed, the windowstarts flashingagain.
But in a special model under above scenario the flash
rate will be half of the initial flash rate, to indicate the
removal of fault

The RESET is then pressed to extinguish the window


LEDs
In case of persistence of fault, the window shall
continue to stay lit even when the reset button is
pressed.
If another fault is energized before having the previous
event cleared the scheme re-functions the same way as
describedabove.
The LAMP TEST push button is pressed (when
required) to test all window LEDs by lighting them
simultaneously
8Others:

Independent hooter reset input available other than


available inSTM
ACKNOWLEDGE, RESET and LAMP TEST inputs
available in STM, a separate independent input for
hooter silence operationis available inSPMs.
Built-in memory to display the order of occurrence of
events (SPMs).
EP SOL(Pvt) Ltd
ELECTRICAL POWER ENGINEERING SOLUTIONS
EL AM-101
?? For other NON - LISTED/Optional requirement, please contact factory.
8-Windows 12-Windows 16-Windows Size
Single Window
Overall size
Dimensions:
71-B Garden Block New Garden Town Lahore
TEL:+92 42 588 4232 FAX-+92 42 586 8145
Email: URL: www.epesol.com info@epesol.com
EP SOL(Pvt) Ltd
ELECTRICAL POWER ENGINEERING SOLUTIONS
MODELDEFINITION (ORDERING) :
AM 101
- - - - -
- -
* * ** ** ** * **
Base Unit / Model
A
D
1
2
3
N
L
H
0
1
2
Input Volt Level to power up fault windows A
B
C
1
2
Input Frequency
Input Volts
No. of Annunciation windows
Input Volt Level to power up annunciator
Control Arrangement
Special Model
00
01
(Consult factory for listed special
models / options)
DC Operated
50Hz
60Hz
AC Voltage
DC Voltage
8- Windows
12- Windows
16- Windows
User Defined
24V DC
48V DC
Universal (AC / DC )
24V DC
48V DC
Control Facility on TB
Control Facility on Front
Standard model
Customized order
Universal (AC / DC)