DESIGN BASIS REPORT

FOR
CABLE TRAY

KUMPP
(4000 MW)

DESIGN BASIS REPORT


FOR
CABLE TRAY

Document No. RINFRA-KUMPP-NEE-220-R-0001-R00

COASTAL ANDHRA POWER LIMITED

RELIANCE INFRASTRUCTURE LIMITED


A31, SECTOR 64, NOIDA

RINFRA-KUMPP-NEE-220-R-0001-R00

13.03.2009

Page 1 of 6

KUMPP
(4000 MW)

DESIGN BASIS REPORT


FOR
CABLE TRAY

DOCUMENT CONTROL SHEET

PROJECT

: KRISHNAPATNAM ULTRA MEGA POWER PROJECT (4000 MW)

CLIENT

:COASTAL ANDHRA POWER LIMITED

DOCUMENT TITLE

:DESIGN BASIS REPORT FOR CABLE TRAY

DOCUMENT NO.

: RINFRA-KUMPP-NEE-220-R-0001-R00

REV. NO.

: 00

ENDORSEMENTS

0
Rev
No.

13
March
09
Date

Final
Description

SG/
AK
Prep
by

PSM
Mech

Civil

Elec

AG
C&I

Reviewed by
RINFRA

DG

SLK

PEM
Reviewed by
B&V

Head H ead
(Elec) (Engg)
Approved by
RINFRA

This document contains information provided to B&V by Reliance Infrastructure Limited.


B&V shall have no liability for defects attributable to B&V's reliance upon or use of data,
design criteria, drawings, specifications, or other information furnished by Reliance
Infrastructure Limited, or vendors retained by Reliance Infrastructure Limited.

RINFRA-KUMPP-NEE-220-R-0001-R00

13.03.2009

Page 2 of 6

DESIGN BASIS REPORT


FOR
CABLE TRAY

KUMPP
(4000 MW)

CONTENTS

1.00.00

FUNCTION..4

2.00.00

DESIGN CRITERIA...............4

3.00.00

SPECIFIC REQUIREMENTS4

4.00.00

CODES AND STANDARDS.....5

5.00.00

QUALITY ASSURANCE REQUIREMENTS..5

RINFRA-KUMPP-NEE-220-R-0001-R00

13.03.2009

Page 3 of 6

DESIGN BASIS REPORT


FOR
CABLE TRAY

1.00.00

KUMPP
(4000 MW)

FUNCTION

This document outlines the design philosophy of Cable Trays for 4000MW coal based Ultra Mega Thermal
Power Plant to be set up at Krishnapatnam in Nellore District, of Andhra Pradesh.

2.00.00

DESIGN CRITERIA

Cable tray system shall be used for laying of MV and LV power, control, instrumentation and special cables
in the Power Plant.
Cable trays shall be supported on cantilever brackets at specified interval. The trays shall be strong
enough to keep the deflection of the fully loaded tray within permissible limits.
In general, cable trays shall run in parallel to building walls and electrical panels.
Vertical distance between adjacent cable trays, measured from the bottom of upper tray to the bottom of
the lower tray, shall be at least 400 mm.
To avoid damage during cable laying, cable trays and accessories shall have no scales, abrasive, rough
surfaces or cutting edges.
Cables shall be clamped or tied with the tray rung generally at an interval of 1500 mm for horizontal run
and 900 mm for vertical run.
For corrosion prone areas viz. battery room etc. epoxy painted cable trays or fiberglass cable trays shall
be used. Trays used in chemical house shall be applied with acid resistant paint.
All metal section and components of the cable tray system shall be bonded together and effectively
grounded to provide a continuous circuit to ground for fault current.

3.00.00

SPECIFIC REQUIREMENTS

Cable trays shall be pre-fabricated / perforated ladder type made of hot dip galvanized sheet steel in
standard length of 2.5 meters. Alternatively cable trays shall be made up of Fibre Reinforced Plastic (FRP).
Cable trays shall be of standard width such as 300 mm, 450 mm and 600mm respectively.
Perforated cable trays shall be of standard width such as 100 mm, 150 mm, 300 mm and 600mm
respectively.
Two straight cable trays shall be coupled with a coupler plate made of 2 mm MS sheet.
Cable trays shall be complete with necessary hot dip galvanized sheet steel accessories such as coupler
plates, ground continuity connections, clamps, nuts, bolts, washers, hangers, clamps, horizontal / vertical
bends, horizontal / vertical Tee, elbows, reducers, horizontal cross-piece, covers etc. along with straight
runs in order to take care of cable tray alignments in different routes in the plant.
The minimum thickness of galvanization coating may be 75 micron or weight may be 610 gm/m2.
Cable trays and associated fittings shall be fabricated out of the MS sheets
galvanized.

(2 mm thick) and hot dip

Cable tray supports shall be fabricated from standard MS angles/channels/flats and depending upon site
conditions it shall be galvanized or painted. The trays shall be welded to the angle support.

RINFRA-KUMPP-NEE-220-R-0001-R00

13.03.2009

Page 4 of 6

DESIGN BASIS REPORT


FOR
CABLE TRAY

KUMPP
(4000 MW)

Cable Trays will have rung spacing of 250 mm and side runner of 100 mm.
Horizontally running cable trays shall be supported at an interval of 2000 mm without causing any
permanent deformation. Vertically running cable trays in cable riser/shaft shall be supported at an interval
of 1000 mm. In case cables are to be laid over the top of switchgear panels, a clearance of 300 mm shall
be maintained.
Cable trays will be bracket supported from walls or columns and hanger supported from overhead
structural members at intervals not exceeding 2.0 meters when measured along tray center lines between
supports.
Redundant circuits (standby drives) shall be spaced as far apart as possible and shall be laid in physically
segregated cable trays in separate route to the extent possible.
The highest voltage grade cables will be laid in the top-most tray and other voltage grade cables in the
lower trays in descending order.

4.00.00

CODES AND STANDARDS

The cable trays will be designed in accordance with the following codes and standards mentioned below:
No.
1
2
3
4

5.00.00

Work
Steel
Galvanizing

In Accordance With
IS-2062/1079
IS-2629/4759

Metal Cable Trays


Fiberglass Cable Trays

NEMA VE-1
NEMA FG-1

QUALITY ASSURANCE REQUIREMENTS

All the tests will be carried out at the manufacturer's work in the presence of the Purchaser's
representative. The manufacturer will submit the material fabrication quality plan for the cable trays and its
components, and it should be approved by the Purchaser before actual fabrication.
All cable tray and associated components furnished will be of uniformly high quality. In addition to
conforming to the referenced codes and standards, the following will also apply:
Finish will be uniform. On the galvanized steel tray, a durable, high quality, relatively smooth
coating is required. Straight members will be free of bends, flat members will be free from waves
and bellies, and curved members will curve uniformly.
Sharp corners and protrusions will be avoided and dimensional transitions will be gradual rather
than abrupt.
Welding fillets will be uniform in cross section, continuous where applicable, and free from voids,
porosity, or inclusions. Metal adjacent to welds will be free from burnouts or discoloration.
The interior of cable tray and cable tray components will be free of sharp edges or roughness.
All cable tray and associated components furnished will be such that the completed installation will
provide a neat and symmetrical appearance. Their construction and assembly will reflect careful
workmanship and rigid quality control in their manufacture. All tray and fittings will be uniform in
appearance and will be free of all markings except for piece designations, which will be on the
inside of the tray, and cable tray identification markers.

RINFRA-KUMPP-NEE-220-R-0001-R00

13.03.2009

Page 5 of 6

DESIGN BASIS REPORT


FOR
CABLE TRAY

KUMPP
(4000 MW)

Components used in trays of different depths and widths will be similar and uniform in material,
shape, appearance, and method of fabrication. It is preferred that trays of different depths and
widths will differ only in dimensions. Differences in construction or appearance that are excessive
in the opinion of the Engineer will be cause for rejection.
The method of joining tray sections, fittings, or tray sections and fittings will provide a smooth,
uniform junction of strength and rigidity equal to the tray side rail.

RINFRA-KUMPP-NEE-220-R-0001-R00

13.03.2009

Page 6 of 6