ATTACHMENT 1 SCOPE OF WORK

Biennial Testing and Calibration of Major Electrical Equipment


Santa Clara Valley Water District Treatment and Pumping Plants

Attachment 1 AS4603.Docx 1 of 6 September 22, 2014
SCOPE OF WORK
The project scope of work includes the following equipment to be tested and calibrated
in accordance with the Statement of Work.
Reference drawings for each facility are included in Attachment 2 for identification of
devices to be tested. Note that these drawings are compilation of as-built of past
projects. They shall be used as guidelines.

A. TREATED WATER FACILITIES
A.1 Santa Teresa Water Treatment Plant (STWTP)
See Attachment 2-S for reference Drawings
A.1.1 Service Entrance 21kV Medium Voltage Switchgear including,
a. MV circuit breaker, Mains (52-1) GE DEH-40368, Catalog # VB-27-16-1200
draw out type vacuum circuit breaker, 27kV, 1200A, 16kA, short circuit
current, 42kA close and latch, 125kV BIL, 3-pole, 120VAC charge and close
and 125VDC trip. One (1) SR750 feeder management relay GE Multilin
GEK-1062933
b. MV circuit breaker, Mains (52-2) GE DEH-40368, Catalog # VB-27-16-1200
draw out type vacuum circuit breaker, 27kV, 1200A, 16kA, short circuit
current, 42kA close and latch, 125kV BIL, 3-pole, 120VAC charge and close
and 125VDC trip. One (1) SR750 feeder management relay GE Multilin
GEK-1062933
c. MV circuit breaker, Mains (52-3) GE DEH-40368, Catalog # VB-27-16-1200
draw out type vacuum circuit breaker, 27kV, 1200A, 16kA, short circuit
current, 42kA close and latch, 125kV BIL, 3-pole, 120VAC charge and close
and 125VDC trip. One (1) SR750 feeder management relay GE Multilin
GEK-1062933
d. MV circuit breaker, Mains (52-4) GE DEH-40368, Catalog # VB-27-16-1200
draw out type vacuum circuit breaker, 27kV, 1200A, 16kA, short circuit
current, 42kA close and latch, 125kV BIL, 3-pole, 120VAC charge and close
and 125VDC trip. One (1) SR750 feeder management relay GE Multilin
GEK-1062933
A.1.2 Two (2), Power Transformers XFMR1 and XFMR2, ABB 1LUJ, Style
FZBE0115P75, 1000 KVA, 21kV-480/277V, 3-phase, mineral oil filled.
A.1.3 Distribution Switchboard DSB including nine (9) low-voltage, insulated case
circuit breakers, [Westinghouse, SPB100, draw out type main breaker (1) + fixed
type feeder breakers (8) with ground fault protection]
A.1.4 Distribution GSB including
a. Nine (9) low voltage, air circuit breakers, draw out type, Westinghouse, DS-
416, located in switchboard panel GSB, [one per generator (2)+ one per
transfer switch - to switchboard DSB (5) + MCC1G (1) + MCC2G (1)]
ATTACHMENT 1 SCOPE OF WORK

Biennial Testing and Calibration of Major Electrical Equipment
Santa Clara Valley Water District Treatment and Pumping Plants

Attachment 1 AS4603.Docx 2 of 6 September 22, 2014
b. MCC-15 Breaker (Draw out Type): Eaton Magnum DS, Eaton MDS608,
Catalog # MDS6083WEA 045GC CNNAX, 800 AF, 400AT, 600V, 3P, 65kA
c. MSB-A Breaker (Draw out Type): Eaton Magnum DS, Eaton MDS608,
Catalog # MDS6083WEA 045GC CNNAX, 800 AF, 250AT, 600V, 3P, 65kA
d. Two (2) reverse power relays [32], GE, Model12ICW51A3A, Type ICW,
located in switchboard panel GSB
e. Three (3) under-voltage relays [27], GE, Model 12IAV54E1A, Type IAV,
located in switchboard panel GSB (one per generator + mains)
f. Three (3) under-frequency relays [8IU], GE, Model 12IJF51B8A, Type IJT,
located in switchboard panel GSB (one per generator + mains)
A.1.5 MSB-A (Ozone Generation Building) including
a. Main breaker MSB-A, GE Power Breaker II Catalog # SSF20B220, 2000
AF, 1800 AT, 600V, 3P, 50kA @600VRating Plug TR20B, equipped with
ground fault protection
b. GSB source breaker GE Power Breaker II Catalog # 175038154100201, 800
AF, 250AT, 600V, 3P, 42kA @600V, Rating Plug TR20B, equipped with
ground fault protection
c. Generator Breaker MSB-E, GE Power Breaker II Catalog #
175038154100201, 800 AF, 200AT, 600V, 3P, 42kA @600V, Rating Plug
TR20B, equipped with ground fault protection
d. Transfer Switch ATS-11 (Normal, MSB-A), GE AV-Line Switchboard, Entelli
Switch 250
e. Transfer Switch ATS-12 (Emergency, MSB-B), GE AV-Line Switchboard,
Entelli Switch 250
A.1.6 Transfer Switches (Optional)
a. Six (6) transfer switches AT1 to ATS6, located in Transfer Switchboard Panel
board TSB, 400A and 600A, Russell Electric, Model 600C and 6003C, 480V,
3-phase, 3-wire
b. Two (2) transfer switches MTS1 and MTS2, located in Generator
Switchboard Panel GSB, ASCO 800A, 480Y/277 volts, 60 Hz, 3-phase,
catalog # F7ATSA3800N5.
A.2 Graystone Pumping Station
See Attachment 2-G for reference Drawings.
A.2.1 Motor Control Center MCC-A including
a. One (1) main breaker in MCC-A, 480V, 800A, 600A TU, Westinghouse
HMCG Catalog No. MMCG3800F, Style No. 1270C62G09.
b. Two (2) MCPs in MCC-A, 480V, 400A each, Westinghouse Catalog No.
MCP534000C, Style No. 673B019G2, Frame trip setting at 2000.
A.3 Rinconada Water Treatment Plant (RWTP)
See Attachment 2-R for reference Drawings.
A.3.1 Engine-Generator Unit (480V)
ATTACHMENT 1 SCOPE OF WORK

Biennial Testing and Calibration of Major Electrical Equipment
Santa Clara Valley Water District Treatment and Pumping Plants

Attachment 1 AS4603.Docx 3 of 6 September 22, 2014
a. One (1) 2500 A breaker, Merlin Gerin, Master Pact-MP25H2, Master-pact
with 2500 A sensor and 2500 A rating plug, Automatic Transfer Controller
b. One (1), Pad mounted transformer, T&R Electric, 1500 kVA, 3-phase, 60 Hz,
12,470-480Y/277 volt
c. Ground Fault Relay
A.3.2 Medium Voltage (2400V) Motors and MCC
a. Four (4) medium voltage Motors H-11, H-12, H-21 and H-22
b. Four (4) protection relays for these motors in MCC-HV, Multilin-239, Version
220, 250VAC, 10A.
A.3.3 Service Entrance 12kV Medium Voltage Switchgear (MSG) including,
a. MV circuit breaker, Mains (52-1), Cutler Hammer VCP-W, Type 150VCP-
W500, draw out type vacuum circuit breaker, 15kV, 1200A, 18kA, short
circuit current, 62kA close and latch, 955kV BIL, 3-pole, 120VAC charge and
close and 125VDC trip. One (1) Eaton Digitrip 3000 relay
b. MV circuit breaker, Generator (52-G) Cutler Hammer VCP-W, Type 150VCP-
W500, draw out type vacuum circuit breaker, 15kV, 1200A, 18kA, short
circuit current, 62kA close and latch, 955kV BIL, 3-pole, 120VAC charge and
close and 125VDC trip. One (1) Eaton Digitrip 3000 relay
c. Fusible disconnect for MCC-MAPS
A.3.4 12kV Medium Voltage Switchgear (SWGR-MAIN) including,
a. Nine (9) MV Circuit breakers 52-A, 52-A1, 52-A2, 52-A3, 52-T, 52-B, 52-
B1, 52-B2, 52-B3 Type GE POWERVAC, Style VB -15.0-25-4, 15kV, 1200A,
25kA
b. Eight (8) feeder protection relays, SEL 587
c. Eight (8) Lockout relays(86)
d. Two (2) digital over-current relays, SEL 551
e. 48VDC battery system
A.3.5 480V Switchgear (SWGR-1) including,
a. Two (2) Main Breakers, GE Enteliguard, Catalog # GN20N1BCP, 2000 AF,
1600 AT, equipped with ground fault
b. One (1) Generator Breaker, GE Enteliguard, Catalog # GN16N1BCP, 1600
AF, 1600 AT, equipped with ground fault
c. Seventeen (17) Feeder Breakers, GE Enteliguard, Catalog # GN08N1BCP,
800 AF, Various AT, including Spare, equipped with ground fault
A.3.6 Pad-mount Distribution Transformers
a. Two (2), Pad mounted transformers liquid filled (TR-2A & TR-2B), ABB,
Style-F6AX147LHR, 1500 kVA, 3-phase, 60 Hz, 12,470-2400/1385volt, BIL
95/45 kV HV/LV, --Y Class KNAN, oil sample only.
b. Two (2), Pad mounted transformers (TR-1A & TR-1B), ABB, Type VPE,
1000/1333 kVA, 3-phase, 60 Hz, 12,470-480Y/277 volt, --Y, BIL, 95/10 kV
HV/LV, Class AA/AF, mechanical/electrical inspection only.
ATTACHMENT 1 SCOPE OF WORK

Biennial Testing and Calibration of Major Electrical Equipment
Santa Clara Valley Water District Treatment and Pumping Plants

Attachment 1 AS4603.Docx 4 of 6 September 22, 2014
A.3.7 UPS System
a. Four (4), 50 kVA Mitsubishi UPS units and batteries

A.4 Penitencia Water Treatment Plant (PWTP)
See Attachment 2-P for reference Drawings.
A.4.1 Service Entrance Medium Voltage Switchgear SG1, including
a. Four (4) MV Circuit breakers 52M, 52G, 52BT, 52LC1 and 52 LC3, Type
GE POWERVAC, Style VB1-13.8-500-3, 15kV, 1200A, 18kA
b. Four (4) feeder protection relays, GE, Type SR-750/760 located in Sections
103A, 104A, 107A, and 108A for 52M, 52BT, 52LC4, 52LC1, and 52G)
c. Three (3) 50/51 digital over-current relays (in Section 103A), GE, Type
DIFCA5B
d. One (1) Sync-Check relay, (in Section 105B) Basler, Type BE1-25
A.4.2 Switchgear SB-1 including
a. Main circuit breaker (located in Utility building) - Westinghouse, PC
SELRRNC, 480V, 1600 AF, equipped with ground fault
A.4.3 Switchgear SB-3 including
a. Main Breaker, GE SS, SH Power Breaker II, Catalog # SSD16B216, 1600
AF, 1200 AT, Rating Plug TR16B1200, equipped with ground fault
b. Feeder MCC-PW, GE Spectra, Catalog # SKLL36BB0800, 600 AF, 600 AT,
Trip unit type SRPK800B, equipped with ground fault
A.4.4 Pad-mount Distribution Transformers
a. One (1), Pad mounted transformer ( LC1), GE PROLEC, (GEI-79025M),
750/840 kVA, 3-phase, 60 Hz, 12,470-480Y/277 volt, 55/65 C, --Y, BIL
95/30 kV HV/LV, Class KNAN, Type OA, Oil sample only.
b. Two (2), Pad mounted transformer ( LC2 - 3), PROLEC, (GEI-79025M),
1000/1120 kVA, 3-phase, 60 Hz, 12,470-480Y/277 volt, 55/65 C, --Y, BIL,
95/30 kV HV/LV, Class KNAN, Type OA, Oil sample only.
c. One (1) Pad mounted transformer (XFMR 101), GE PROLEC, 1500 kVA, 3-
phase, 60 Hz, 12,470 GNDY/7200 - 480 volt, 55/65 C, Y--, BIL 95 kV
HV, Type OA, Oil sample only.
A.4.5 MCC - PW Plant Water Pump Station including (Optional)
a. Main Breaker, GE Spectra, Catalog # SKLB36BD0800, 800 AF, 600 AT, Trip
unit type SRPK800B, equipped with ground fault
B. RAW WATER FACILILTIES
B.1 Anderson Hydro Facility
See Attachment 2-A for reference Drawings.
B.1.1 One (1) medium voltage, liquid-filled transformer, 20780-4160/2400 -Y,
1000/1120 KVA, oil sample only.
ATTACHMENT 1 SCOPE OF WORK

Biennial Testing and Calibration of Major Electrical Equipment
Santa Clara Valley Water District Treatment and Pumping Plants

Attachment 1 AS4603.Docx 5 of 6 September 22, 2014
B.1.2 Main Switchboard MS including:
a. Two (2) watt-hour meters, Westinghouse
b. One (1) under-voltage relay [27], Westinghouse, CVD
c. One (1) over-voltage relay [59], Westinghouse, SV
d. One (1) over/under voltage frequency delay [81 0/U], Basler, BE1
e. Four (4) reverse power relays [32], two located at/within Brown Boveri,
two located at Crompton equipment
f. Two (2) over-current relays [51V] with voltage restraint, Basler, BE1
/under-voltage relay [27]
g. Six (6) GE 369 Motor Management Relay

B.2 Coyote Pumping Plant (CPP), 4160 Volt Substation
See Attachment 2-CP for reference Drawings.
B.2.1 Medium Voltage Outdoor Switchyard Equipment including
a. Two (2) medium voltage, liquid-filled transformers KZ1A and KZ2A, Balteau
Standard, Inc., 500kVA, 4160-480/277 volt, oil test only
b. Six (6) very inverse time over-current relays, GE, model 121FC53B1A
c. Two (2) static frequency relays [81], GE, model 12FF31C1A
d. Two (2) phase sequencing under-voltage relays [47], GE, model
121CR51A1A
e. One (1) watt-hour meter, GE, cat. No. 701X4C569
f. Two (2) medium voltage circuit breakers, Siemens-Allis, Type MA-250B,
4160 volt (JZ1A and JZ2A)
B.2.2 ASD Gallery
a. Six (6) GE 369 Motor Management Relay
b. Two (2) DC Circuit Breakers (Unit 1 & 2); AEG, MEY-RAPID 1000, 1200A,
40kA, 1200V
B.3 Pacheco Pumping Plant (PPP), 4160 Volt Substation
See Attachment 2-PP for reference Drawings.
B.3.1 Medium Voltage Outdoor Switchyard Equipment including
a. Two (2) medium voltage, liquid-filled transformers KZ1A and KZ2A, Balteau
Standard, Inc., 500kVA, 4160-480/277 volt, oil test only
b. Three (3) medium voltage tie breaker (JZ1A, JZ2A, & Tie CB), Cutler
Hammer Type FA-VR-350, 4160 volt, 3000A
c. Two (2) Cutler Hammer Feeder Protection Relays Type FP-4000
B.3.2 Medium Voltage Outdoor Switchgear
a. Twelve (12) medium voltage breakers, Eaton/Cutler Hammer, 15kV, Type-
VacClad-W Vacuum Circuit Breaker, 1200AF, 400AT,
ATTACHMENT 1 SCOPE OF WORK

Biennial Testing and Calibration of Major Electrical Equipment
Santa Clara Valley Water District Treatment and Pumping Plants

Attachment 1 AS4603.Docx 6 of 6 September 22, 2014
b. Twelve (12) medium voltage breakers, Eaton DT-3000 Protective relays
c. InsulGard Meters (Optional)
B.3.3 Low Voltage (480V) Switchgear
a. Three (3) Main and Tie Circuit Breaker, 800 AF, 800 AT, equipped with
ground fault
b. One (1) ATS; 100A, 42KAIC
B.4 Vasona Pumping Station
See Attachment 2-VPP for reference Drawings
B.4.1 Motor Control Center, MCC, including following five (5) 480V feeder breakers
a. P-100 breaker, Model Westinghouse, NB, 800A, Thermal Magnetic
b. P200 breaker, Model Westinghouse, LAB, LA, 400A, Thermal Magnetic
c. P-300 breaker, Model Westinghouse, LAB, LA, 400A, Thermal Magnetic
d. P-500 breaker, Model Westinghouse, NB, 800A, Thermal Magnetic
e. Panel PN Switch, Westinghouse Type, LAB, 400A
B.4.2 Motors
a. Perform insulation resistance and polarization index tests on four (4), 480
volts, 3-phase Induction motors P-100 (400 hp), P-200 (200 hp), P-300 (200
hp), and P-500 (400 hp).
B.4.3 Panel PN main circuit breaker, Westinghouse Type, LAB, LA, 480V, 400A,
Thermal Magnetic (Optional)
B.4.4 Main Utility circuit breaker, 480V, 2000A, Cutler Hammer, Type SPB (Optional)