This document serves as a cover sheet for Process Industry Practice (PIP) STC01015 - Structural Design Criteria with applicable additions, deletions, modifications, and clarifications listed with associated addendum. Replace: "000.220.ARC01015" - Architectural and Building Utilities Design Criteria - "000.210.CVC01017" - Building Data Sheets.
This document serves as a cover sheet for Process Industry Practice (PIP) STC01015 - Structural Design Criteria with applicable additions, deletions, modifications, and clarifications listed with associated addendum. Replace: "000.220.ARC01015" - Architectural and Building Utilities Design Criteria - "000.210.CVC01017" - Building Data Sheets.
This document serves as a cover sheet for Process Industry Practice (PIP) STC01015 - Structural Design Criteria with applicable additions, deletions, modifications, and clarifications listed with associated addendum. Replace: "000.220.ARC01015" - Architectural and Building Utilities Design Criteria - "000.210.CVC01017" - Building Data Sheets.
Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 2 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Record of Revisions Rev. No. Date Description 0 20Feb2014 Issue for Construction
Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 3 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering 1 INTRODUCTION 1.1. Purpose This document serves as a cover sheet for Process Industry Practice (PIP) STC01015 Structural Design Criteria with applicable additions, deletions, modifications, and clarifications listed with associated addendum. 1.2. Scope This document, along with PIP STC01015, provides general guidance and minimum requirements for structural design. More specific and comprehensive criteria may need to be developed for specific project needs. 2 ADDENDUM The following requirements are defined as additions, deletions, and revisions to PIP STC01015 Section Description Section 1.2 Scope Replace: PIP ARC01015, PIP ARC01016, PIP CVC01015, PIP CVC01017, and PIP CVC01018
With: project specifications 000.220.ARC01015, 000.220.ARC01016, 000.210.CVC01015, 000.210.CVC01017, and 000.210.CVC01018 Section 2.1 Replace Process Industry Practices (PIP) With Project Specifications & Process Industry Practices (PIP) Replace Process Industry Practices (PIP) with: 000.220.ARC01015 Architectural and Building Utilities Design Criteria 000.220.ARC01016 Building Data Sheets 000.210.CVC01015 Civil Design Criteria 000.210.CVC01017 Plant Site Data Sheet 000.210.CVC01018 Project Data Sheet PIP PCCWE001 Weighing Systems Criteria PIP PCEWE001 Weighing Systems Guidelines PIP REIE686/API 686 Recommended Practices for Machinery Installation and Installation Design 000.215.STC01018 Blast Resistant Building Design Criteria 000.215.STE05121 Anchor Bolt Design Guide 000.215.STE03360 Heat Exchanger and Horizontal Vessel Foundation Design Guide Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 4 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Section Description A6RF-000-15-SP-012 Application of ACI 336.1-01, Specification for the Construction of Drilled Piers Section 2.2 Industry Codes and Standards Add: American Concrete Institute (ACI) ACI 301 Specification for Structural Concrete
Add: American Institute of Steel Construction (AISC) AISC 341 Seismic Provisions for Structural Steel Buildings, including Supplement No. 1 AISC 360 Specification for Structural Steel Buildings
Delete: American Institute of Steel Construction (AISC) AISC Steel Construction Manual Allowable Stress Design (ASD) and Load Resistance Factor Design (LRFD) Specification for Structural Joints Using ASTM A325 or A490 Bolts
Replace: American Society of Civil Engineers (ASCE) ASCE/SEI 7-05 Minimum Design Loads for Buildings and Other Structures with ASCE/SEI 7-10 Minimum Design Loads for Buildings and Other Structures
Add: ASTM International (ASTM) ASTM A53/A53M Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless ASTM A123/A123M Standard Specification for Zinc (Hot-Dip) on Iron and Steel Hardware ASTM A153/A153M Standard Specification for Zinc (Hot-Dip) on Iron and Steel Hardware ASTM A500/A500M Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes ASTM A563 Rev A Standard Specification for Carbons and Alloy Steel Nuts ASTM A572/A572M Standard Specification for High-Strength Low-Alloy Columbrium-Vanadium Structural Steel ASTM A786/A786M Standard Specification for Hot-Rolled Carbon, Low-Alloy, High-Strength Low-Alloy, and Alloy Steel Floor Plates ASTM A1011/A1011M Standard Specification for Steel, Sheet and Strip, Hot- Rolled, Carbon, Structural, High-Strength Low-Allow, High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength ASTM F436 Standard Specification for Hardened Steel Washers ASTM F1852 Standard Specification for Twist-Off Type Tension Control Structural Bolt/Nut/Washer Assemblies, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 5 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Section Description ASTM F2280 Standard Specification for Twist-Off Type Tension Control Structural Bolt/Nut/Washer Assemblies, Steel, Heat Treated, 150 ksi Minimum Tensile Strength
Add: American Society of Mechanical Engineers (ASME) ASME STS-1 Steel Stacks
Add: Research Council on Structural Connections (RCSC) Specification for Structural Joints Using ASTM A325 or A490 Bolts
Add: Local Building Code 2012 International Building Code (IBC)
Add: Project Geotechnical Report Subsurface Exploration and Geotechnical Engineering Report, Ryckman Creek Compressor Station, by Inberg-Miller Engineers, Report No 15040-GX, dated August 30, 2010.
Add Project Standards and Specifications Document No. A6RF-000-15-SP-002 Structural Data for Mechanical Equipment Specification Adaptation A6RF-000-15-SP-006 Specification Adaptation Fabrication of Structural and Miscellaneous Steel Specification Specification Adaptation A6RF-000-15-SP-007 Specification Adaptation Erection of Structural and Miscellaneous Steel Specification Specification Adaptation A6RF-000-15-SP-003 Specification Adaptation Plain and Reinforced Concrete Specification Section 3.0 DEFINITIONS Replace engineer of record with registered design professional in responsible charge. Section 4.1.1 Design Loads 4.1.1.1 Replace ASCE/SEI 7 with IBC. Replace: PIP CVC01017 and CVC01018 with project specifications 000.210.CVC01017 and 000.210.CVC02018
4.1.1.5 Replace PIP STE03360 with 000.215.STE03360
4.1.1.6 Replace ASCE/SEI 7-05 with ASCE/SEI 7-10.
Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 6 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Section Description Section 4.1.1 4.1.1.6 Replace See ASCE/SEI 7-05, Section 1.5.2 and Table 1-1 with See ASCE/SEI 7-10 Section 1.5.3 and Table 1.5-1 Section 4.1.3 Live Loads (L) 4.1.3.3 Replace ASCE/SEI 7 with "IBC Section 1607
4.1.3.5 Replace ASCE/SEI 7 with IBC Section 1607.4
4.1.3.7 Replace ASCE/SEI 7 with IBC Section 1607.10
4.1.3.8 Replace ASCE/SEI 7 with IBC Section 1607.10
4.1.3.10 Replace in accordance with the building code with in accordance with IBC Section 1607.8. Section 4.1.4 Wind Loads (W) 4.1.4.1 Replace ASCE/SEI 7 with IBC Section 1609
4.1.4.2 Replace PIP CVC01017 with project specification 000.210.CVC01017
4.1.4.2 Add the following: Every buildings, structure, equipment, component, and cladding shall be designed to resist wind effects according to IBC Section 1609, with the following parameters. a. Basic wind speed shall be 120 mph based on a 3-second gust at 33 feet above ground b. Exposure Category =C c. Topographic Factor, K zt shall be equal to 1.0 d. Wind Directionality Factor K d shall be determined by ASCE 7 Table 26.6-1 e. Gust Effect Factor, G =0.85 for rigid structures
4.1.4.5 Replace second sentence with, The design wind speed for test and erection periods shall be taken at 75% of the basic wind speed (0.75 x 120 mph = 90 mph).
Add the following paragraphs:
4.1.4.7 For the purpose of calculating wind gust factors, assume 1 percent critical damping ratio for steel structures and 2 percent for concrete structures per ASCE 7 Section C26.9, paragraph Structural Damping.
4.1.4.8 No reduction shall be made for the shielding effect of vessels or structures adjacent to the equipment being designed. Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 7 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Section Description 4.1.4.9 In applying the wind pressure as a lateral force on the projected areas of a vessel, the insulation thickness, if any, shall be added to the vessel diameter.
4.1.4.10 Wind loads shall be separately computed for all supported equipment, platforms, ladders, and stairs except for vessels when projected area increase factors have already account for them.
4.1.4.11 Slender vertical pressure vessels shall be checked for wind inducted vibration in accordance with ASME STS-1.
4.1.4.12 Wind forces on flexible wind sensitive structures shall be determined according to ASCE 7. Gust effect factors for flexible wind sensitive structures shall be determined by a rational analysis procedure that incorporates the dynamic properties of the main wind force resisting system. Section 4.1.5 Earthquake Loads (E) 4.1.5.1 Replace ASCE/SEI 7 with IBC Section 1613.
4.1.5.2 Replace PIP CVC01017 with project specification 000.210.CVC01017
4.1.5.2 Add the following: All buildings, structures and equipment shall be designed for earthquake forces according to IBC Section 1613 and the following parameters. a. Site Class =D (ASCE 7 Table 20.3-1) b. 0.2 Sec Spectral Response Acceleration S s =0.531g (IBC Section 1613.3.1) c. 1.0 Sec Spectral Response Acceleration S 1 =0.136g (IBC Section 1613.3.1) d. Short-Period Site Coefficient, F a =1.38 (IBC Section 1613.3.1(1)) e. Long-Period Site Coefficient, F v = 2.08 (IBC Section 1613.3.1(2)) f. Short Period Spectral Design Response Acceleration, S DS =0.487g (IBC Section 1613.3.4) g. 1-Second Period Spectral Design Response Acceleration, S D1 =0.249g (IBC Section 1613.3.4) h. Seismic Design Category =D (IBC Tables 1613.3.5(1) and 1613.3.5(2)) i. Long-Period Transition Period, TL =6 seconds (ASCE/SEI 7 Figure 22-12) j. Seismic Importance Factors: I =1.25, I p =1.50 for Risk Category III structures 4.1.5.3 Replace first sentence with: Earthquake loading for nonbuilding structures shall be determined using IBC and ASCE/SEI 7 Chapter 15. Section 4.1.6 Impact Loads 4.1.6.1 Replace ASCE/SEI 7 with IBC Section 1607.9. Section 4.1.10 Blast Loads 4.1.10.3 Replace PIP STC01018 with project specification 000.215.STC01018 Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 8 of 13 Revision 0
4.1.12.2 Replace with the following: a. Ground Snow Load, P g =40 psf (ASCE 7 Figure 7-1 and Table 7-1) b. Exposure Factor, C e =0.9 (ASCE/SEI 7 Table 7-2) c. Thermal Factor, C t =1.2 Heated Structures (ASCE/SEI 7 Table 7-3) d. Thermal Factor, C t =1.0 Unheated Structures (ASCE/SEI 7 Table 7-3) e. Importance Factor, I s =1.10 (ASCE/SEI 7 Tables 1.5-2 and 7-4) Section 4.1.13 (Add) Vibration Loads (V) 4.1.13.1 Vibration loads are defined as those forces that are induced by reciprocating machinery such as compressors, or rotating unbalanced forces from equipment such as pumps, blowers, fans, turbine-generators and compressors. Included with this definition are surge and slugging forces. Load factors for surge, slugging, and vibration forces shall be the same as for live loads. Section 4.1.14 (Add) Construction Loads (C) Construction/Erection Loads are temporary forces caused by erection of structures or equipment. 4.1.14.1 Construction/Erection Loads shall have the same load factor as live loads. Section 4.1.15 (Add) Rain Loads (R) For the effect of ponding due to rain loads on buildings and enclosed structures, refer to IBC Section 1611 Load factors shall be the same as for roof live load. Section 4.1.16 (Add) Other Loads 4.1.16.1 Additional loads such as wind-blown sand build-up, and hydrostatic and earth pressures shall be considered when applicable.
4.1.16.2 Maintenance loads are temporary forces caused by the dismantling, repair, or painting of equipment. When applicable, they shall be considered in load combinations as live loads. Section 4.2.1 Load Combination General 4.2.1.a Replace ASCE/SEI 7 with IBC Section 1605. Section 4.2.2 Typical Load Combinations (for Structures and Foundations) 4.2.2.1.a (Comment) Replace ASCE/SEI 7-05, Section 2 with IBC Section 1605.3.
4.2.2.2 Replace ASCE/SEI 7-05, Section 2 with IBC Section 1605.
4.2.2.3.a Replace ASCE/SEI 7-05, Section 1.5 and Table 1-1 with IBC Section 1604.5 and Table 1604.5 in both Table 3 and Table 4.
4.2.2.6 Replace ASCE/SEI 7 with IBC Section 1605. Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 9 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Section Description Section 4.2.3 Test Combinations Add the following: 4.2.3.7 When there is more than one vessel to be tested in a structure they may be tested concurrently or non-concurrently. Structural design shall be based on the worst case. This requirement may be waived if testing more than one vessel causes a severe structural penalty and if Project Management, Construction, and the Client all agree. Such exceptions shall be documented in the test procedures for vessels, on the structural drawings, and in a letter to the Client. Section 4.3.1 Steel (Add) Structural steel design, fabrication, and erection shall be according to IBC Chapter 22 and the following AISC manuals and specifications, materials, and general requirements.
4.3.1.1 (Add) Steel Design Specifications a. AISC 360 b. Specification for Structural Joints Using ASTM A325 or A490 Bolts c. AISC 341 d. A6RF-000-15-00-006 e. A6RF-000-15-00-007
4.3.1.5 (Add) The minimum weld size shall be of an inch.
4.3.1.7 Delete the word plates from the paragraph.
Add the following paragraphs:
4.3.1.14 Materials a. Structural Steel (W and WT): ASTM A992 b. Structural Steel (All other): ASTM A36 c. Plate (Including gusset and column base plates): ASTM A572, Grade 50 d. Structural Pipe: ASTM A53 Type E or S, Grade B e. Structural Tubing: ASTM A500, Grade B f. All High Strength bolts shall be in accordance with the AISC Specification for Structural J oints Using ASTM A325 or A490 Bolts. High Strength Bolts shall be either Heavy Hex Head structural bolts or Tension Control (Twist- Off) Bolts. Tension Control Bolts are the preferred bolting system. g. High Strength Tension Control (Twist-Off) Bolts: ASTM F1852 (A325 material) ASTM F2280 (A490 material) h. Heavy Hex Head High Strength Bolts and Nuts: Bolts ASTM A325, Type 1 Nuts ASTM A563, Grade DH Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 10 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Section Description i. Heavy Hex Head Common Bolts and Nuts: Bolts ASTM A307, Grade A Nuts ASTM A563, Grade A j. Welding Electrodes: Low hydrogen AWS D1.1, with minimum yield strength of 58 ksi and minimum tensile strength of 70 ksi k. Steel Grating: ASTM A1011 l. Steel Floor Plate: ASTM A786
4.3.1.15 For connections subjected to fatigue, significant load reversal (other than seismic), crane supports, and oversized holes, slip critical connections according to AISC shall be used.
4.3.1.16 All welding design shall be in accordance with IBC Chapter 22, AISC 360, AISC 341, and AWS D1.1, D1.2, D1.3, D1.4 and D1.6.
4.3.1.17 Platforms and walkways shall be covered with 1-1/4 inch by 3/16 inch galvanized serrated grating unless otherwise noted. The weight of removable flooring sections shall not exceed 150 pounds.
4.3.1.18 Where checkered plate is required, use inch thick, field seal welded to supporting steel.
4.3.1.19 Guardrails shall conform to IBC, and OSHA.
4.3.1.20 Unless otherwise noted, all steel embedded items and grating shall be hot-dipped galvanized per ASTM A132 or A153 as applicable.
4.3.1.21 Metal deck for roof, floors, and siding shall be selected and approved by the Lead Structural Engineer.
4.3.1.22 Structural design and detailing for the support of overhead cranes shall be in accordance with CMAA Specification #70 and #74. Section 4.3.3 Masonry (Add) IBC 2012 Chapter 21. Section 4.3.2 Concrete (Add) Concrete design and construction shall be according to IBC Chapter 19 and the following codes and ACI specifications, materials, and general requirements.
4.3.2.1 (Add) Concrete design shall also be in accordance with ACI 301 and project specification A6RF-000-15-SP-00-003.
(Add) 4.3.2.7 Materials The minimum design compressive strength, f c , shall be as follows: Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 11 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Section Description a. Aboveground and Underground Structures: 4000 psi Foundations: 4000 psi b. Liquid Retaining Structures: 5000 psi c. Fireproofing: 3000 psi d. Paving and Sidewalks: 3000 psi e. Electrical Duct Banks: 2000 psi f. Manholes, Catch Basins, Ditch Lining, End walls, Curbs: 3000 psi Section 4.3.4 Elevator Supports Add after ASME A17.1, and IBC Chapter 30. Section 4.3.6 Allowable Drift Limits (Add) 4.3.6.8 The maximum amplified inelastic seismic drift for pipe racks, M , shall not exceed 0.025H (where H =overall total pipe rack height) Section 4.3.7 Foundations 4.3.7.1 (Add) General foundation requirements are defined in A6RF-000-15-SP-00-003. Foundations shall be designed to conform to Chapter 18 of the IBC.
4.3.7.2 Replace ASCE/SEI 7-05, Section 2 with IBC Section 1605. Replace ASCE/SEI 7 with IBC.
4.3.7.3 Replace ASCE/SEI 7-05, Section 2 with IBC Section 1605. Replace ASCE/SEI 7 with IBC.
4.3.7.4 Replace ASCE/SEI 7-05, Section 1.5 and Table 1-1 with IBC Section 1604.5 and Table 1604.5.
4.3.7.5 Replace ASCE/SEI 7-05, Section 12.8.5 with IBC Section 1808.3.1. Replace ASCE/SEI 7-05, Section 12.13.4 with ASCE/SEI 7-10, Section 12.13.4.
Add the following paragraphs:
4.3.7.12 Foundations shall be sized in increments of 2 inches or efficient utilization of adjustable formwork.
4.3.7.13 Galvanized steel slide plate shall be provided at all sliding surfaces except where equipment saddles bear directly against structural steel supporting members.
4.3.7.14 Teflon Slide Plates shall be specified at all horizontal exchangers and vessels where the equipment weight on the sliding support exceeds 25 kips. Stainless steel slide plate shall be specified for corrosive service and where temperatures at the support exceed 500 degrees Fahrenheit or the temperature limits specified by the Teflon slide plate supplier. Section 4.3.8 Supports for Vibrating Machinery 4.3.8.4 Add before centrifugal machinery the words grade mounted. Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 12 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Section Description Section 4.3.8 4.3.8.5 Add before reciprocating machinery the words grade mounted. (Add) Foundations for reciprocating compressors greater than 200 brake horsepower (150 kilowatts) shall be designed for the expected dynamic forces using dynamic analysis procedures.
Add the following paragraphs:
4.3.8.9 All table-top mounted machinery shall be designed for the expected dynamic forces using dynamic analysis procedures.
4.3.8.10 Dynamic soil and pile properties used in the foundation vibration analysis shall be in accordance with the Geotechnical Report. Section 4.3.9 Anchor Bolts 4.3.9.3 Replace PIP STE05121 with project specification A6RF-000-15-SP-008 Section 4.3.10 Wood (Replace) Wood design shall be in accordance with Chapter 23 of the IBC. Section 4.3.12 Design of Driven Piles 4.3.12.1 Replace PIP STS02360 with project specification 000.215.STS02360 Section 4.3.14 (Add) Deflection and Camber Criteria 4.3.14.1 Deflection limitations for structures shall conform to IBC Section 1604.3 and 1613, and as specified herein.
4.3.14.2 Total vertical deflection of each individual beam shall not exceed l/240 of the span.
4.3.14.3 For beams supporting closely interconnected equipment, total deflection shall not exceed l/360 of the span.
4.3.14.4 Maximum live load deflection of grating and floor plate shall not exceed 1/4 inch.
4.3.14.5 Camber requirements to ensure proper roof drainage and to control deflection of large span trussed and girders shall conform to IBC Section 1611.3 and AISC 360 Chapter L2. Ryckman Creek Resources Specification Adaptation A6RF-000-15-SP-001 NRU Restoration Project Date: 20 Feb 2014 Fluor Contract No. A6RF Page 13 of 13 Revision 0
STRUCTURAL DESIGN CRITERIA A6RF-000-15-SP-001_Rev0.doc Structural Engineering Section Description Section 4.3.15 (Add) Clearances 4.3.15.1 Minimum headroom over platforms, walkways and stairways shall be 7-6 to the lowest point of any overhead obstruction
4.3.15.2 In providing for minimum clearances, allowances shall be made for fireproofing, piping, heating and ventilating ducts, insulation and structural member size, wherever applicable.
4.3.15.3 Minimum unobstructed width of walkways shall be 3-0 clear.
4.3.15.4 Stairs and ladders shall be in accordance with OSHA, and IBC code requirements.
TECHNICAL CORRECTION September 2007
Process Industry Practices Structural PIP STC01015 Structural Design Criteria
PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES
In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice. This Practice is subject to revision at any time. Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP member companies and subscribers may copy this Practice for their internal use. Changes, overlays, addenda, or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. PRINTING HISTORY December 1998 Issued August 2004 Complete Revision February 2002 Technical Revision February 2006 Technical Correction April 2002 Editorial Revision September 2007 Technical Correction Not printed with State funds TECHNICAL CORRECTION September 2007 Process Industry Practices Page 1 of 30
Process Industry Practices Structural PIP STC01015 Structural Design Criteria Table of Contents 1. Introduction................................. 2 1.1 Purpose............................................ 2 1.2 Scope............................................... 2 2. References .................................. 2 2.1 Process Industry Practices .............. 2 2.2 Industry Codes and Standards ........ 2 2.3 Government Regulations................. 4 3. Definitions ................................... 5 4. Requirements.............................. 5 4.1 Design Loads................................... 5 4.2 Load Combinations........................ 14 4.3 Structural Design........................... 23 4.4 Existing Structures......................... 30
PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 2 of 30 Process Industry Practices 1. Introduction 1.1 Purpose This Practice provides structural engineering design criteria for the process industries. 1.2 Scope This Practice describes the minimum requirements for the structural design of process industry facilities at onshore U.S. sites. This Practice is intended to be used in conjunction with PIP ARC01015, PIP ARC01016, PIP CVC01015, PIP CVC01017, and PIP CVC01018, as applicable. 2. References Applicable parts of the following Practices, industry codes and standards, and references shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles will be used herein where appropriate. 2.1 Process Industry Practices (PIP) PIP ARC01015 - Architectural and Building Utilities Design Criteria PIP ARC01016 - Building Data Sheets PIP CVC01015 - Civil Design Criteria PIP CVC01017 - Plant Site Data Sheet PIP CVC01018 - Project Data Sheet PIP PCCWE001 - Weighing Systems Criteria PIP PCEWE001 - Weighing Systems Guidelines PIP REIE686/API 686 - Recommended Practices for Machinery Installation and Installation Design PIP STC01018 - Blast Resistant Building Design Criteria PIP STE05121 - Anchor Bolt Design Guide PIP STE03360 - Heat Exchanger and Horizontal Vessel Foundation Design Guide PIP STS02360 - Driven Piles Specification 2.2 Industry Codes and Standards American Association of State Highway and Transportation Officials (AASHTO) AASHTO Standard Specifications for Highway Bridges American Concrete Institute (ACI) ACI 318/318R - Building Code Requirements for Structural Concrete and Commentary TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 3 of 30 ACI 350/350R Code Requirements for Environmental Engineering Concrete Structures and Commentary ACI 530/ASCE 5/TMS 402 - Building Code Requirements for Masonry Structures American Institute of Steel Construction (AISC) AISC Steel Construction Manual - Allowable Stress Design (ASD) and Load and Resistance Factor Design (LRFD) Specification for Structural Joints Using ASTM A325 or A490 Bolts American Iron and Steel Institute (AISI) AISI SG 673, Part I - Specification for the Design for Cold-Formed Steel Structural Members AISI SG 673, Part II - Commentary on the Specification for the Design for Cold-Formed Steel Structural Members AISI SG 913, Part I - Load and Resistance Factor Design Specification for Cold-Formed Steel Structural Members AISI SG 913, Part II - Commentary on the Load and Resistance Factor Design Specification for Cold-Formed Steel Structural Members American Petroleum Institute (API) API Standard 650 - Welded Steel Tanks for Oil Storage American Society of Civil Engineers (ASCE) ASCE/SEI 7-05 - Minimum Design Loads for Buildings and Other Structures SEI/ASCE 37-02 - Design Loads on Structures During Construction ASCE Guidelines for Seismic Evaluation and Design of Petrochemical Facilities ASCE Guidelines for Wind Loads and Anchor Bolt Design for Petrochemical Facilities ASCE Design of Blast Resistant Buildings in Petrochemical Facilities American Society of Mechanical Engineers (ASME) ASME A17.1 - Safety Code for Elevators and Escalators ASTM International (ASTM) ASTM A36/A36M - Standard Specification for Carbon Structural Steel ASTM A82/A82M - Standard Specification for Steel Wire, Plain, for Concrete Reinforcement ASTM A185/A185M - Standard Specification for Steel Welded Wire Reinforcement, Plain, for Concrete ASTM A193/A193M - Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for High Temperature or High Pressure Service and Other Special Purpose Applications PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 4 of 30 Process Industry Practices ASTM A307 - Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength ASTM A325 - Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength ASTM A354 - Standard Specification for Quenched and Tempered Alloy Steel Bolts, Studs, and Other Externally Threaded Fasteners ASTM A490 - Standard Specification for Structural Bolts, Alloy Steel, Heat Treated,150 ksi Minimum Tensile Strength ASTM A615/A615M - Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement ASTM A706/A706M - Standard Specification for Low-Alloy Steel Deformed and Plain Bars for Concrete Reinforcement ASTM A992/A992M - Standard Specification for Structural Steel Shapes ASTM F1554 - Standard Specification for Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength American Welding Society (AWS) AWS D1.1/D1.1M - Structural Welding Code - Steel American Forest and Paper Association National Design Specification for Wood Construction (NDS) NDS Supplement - Design Values for Wood Construction Crane Manufacturers Association of America (CMAA) CMAA No. 70 - Specifications for Top Running Bridge and Gantry Type Multiple Girder Overhead Electric Traveling Cranes CMAA No. 74 - Specifications for Top Running and Under Running Single Girder Overhead Electric Traveling Cranes Utilizing Under Running Trolley Hoist Precast/Prestressed Concrete Institute (PCI) PCI MNL 120 - Design Handbook - Precast and Prestressed Concrete Steel J oist Institute (SJ I) SJI Standard Specifications, Load Tables and Weight Tables for Steel Joists and Joist Girders 2.3 Government Regulations Federal Standards and Instructions of the Occupational Safety and Health Administration (OSHA), including any additional requirements by state or local agencies that have jurisdiction in the state where the project is to be constructed, shall apply. U.S. Department of Labor, Occupational Safety and Health Administration (OSHA) OSHA 29 CFR 1910 - Occupational Safety and Health Standards OSHA 29 CFR 1926 - Safety and Health Regulations for Construction TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 5 of 30 3. Definitions engineer of record: Purchasers authorized representative with overall authority and responsibility for the engineering design, quality, and performance of the civil works, structure, foundations, materials, and appurtenances described in the contract documents. The engineer of record shall be licensed as defined by the laws of the locality in which the work is to be constructed, and be qualified to practice in the specialty discipline required for the work described in the contract documents. owner: The party who has authority through ownership, lease, or other legal agreement over the structures to be designed 4. Requirements 4.1 Design Loads 4.1.1 General 4.1.1.1 New facilities, buildings, and other structures, including floor slabs and foundations, shall be designed to resist the minimum loads defined in ASCE/SEI 7, local building codes, this section and the loads defined in PIP CVC01017 and CVC01018. 4.1.1.2 In addition to the loads in this section, other loads shall be considered as appropriate. These loads shall include, but are not limited to, snow, ice, rain, hydrostatic, dynamic, upset conditions, earth pressure, vehicles, buoyancy, and erection. 4.1.1.3 Future loads shall be considered if specified by the owner. 4.1.1.4 For existing facilities, actual loads may be used in lieu of the minimum specified loads. 4.1.1.5 Eccentric loads (piping, platforms, etc.), particularly on horizontal and vertical vessels and exchangers, shall be considered. For additional information regarding eccentric loads on horizontal vessels and exchangers, see PIP STE03360. 4.1.1.6 The owner shall be consulted to determine the classification of Occupancy Categories for buildings and other structures for the purpose of applying wind, earthquake, snow, and ice load provisions in accordance with Section 1.5 of ASCE/SEI 7-05. Comment: For process industry facilities, ASCE/SEI 7 Category III is the most likely classification because of the presence of toxic or explosive substances. Category II may be used if the owner can demonstrate that release of the toxic or explosive substances does not pose a threat to the public. See ASCE/SEI 7-05, Section 1.5.2 and Table 1-1, for specific details. In some cases, it may be appropriate to select Category IV. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 6 of 30 Process Industry Practices 4.1.2 Dead Loads (D) 4.1.2.1 Dead loads are the actual weight of materials forming the building, structure, foundation, and all permanently attached appurtenances. 4.1.2.2 Weights of fixed process equipment and machinery, piping, valves, electrical cable trays, and the contents of these items shall be considered as dead loads. 4.1.2.3 For this Practice, dead loads are designated by the following nomenclature: D s , D f , D e , D o , and D t , where D s = Structure dead load is the weight of materials forming the structure (not the empty weight of process equipment, vessels, tanks, piping, nor cable trays), foundation, soil above the foundation resisting uplift, and all permanently attached appurtenances (e.g., lighting, instrumentation, HVAC, sprinkler and deluge systems, fireproofing, and insulation, etc.). D f = Erection dead load is the fabricated weight of process equipment or vessels (as further defined in Section 4.1.2.4). D e = Empty dead load is the empty weight of process equipment, vessels, tanks, piping, and cable trays (as further defined in Sections 4.1.2.4 through 4.1.2.6). D o = Operating dead load is the empty weight of process equipment, vessels, tanks, piping, and cable trays plus the maximum weight of contents (fluid load) during normal operation (as further defined in Sections 4.1.2.4 through 4.1.2.7). D t = Test dead load is the empty weight of process equipment, vessels, tanks, and/or piping plus the weight of the test medium contained in the system (as further defined in Section 4.1.2.4). 4.1.2.4 Process Equipment and Vessel Dead Loads 1. Erection dead load (D f ) for process equipment and vessels is normally the fabricated weight of the equipment or vessel and is generally taken from the certified equipment or vessel drawing. 2. Empty dead load (D e ) for process equipment and vessels is the empty weight of the equipment or vessels, including all attachments, trays, internals, insulation, fireproofing, agitators, piping, ladders, platforms, etc. Empty dead load also includes weight of machinery (e.g., pumps, compressors, turbines, and packaged units). 3. Operating dead load (D o ) for process equipment and vessels is the empty dead load plus the maximum weight of contents (including packing/catalyst) during normal operation. TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 7 of 30 4. Test dead load (D t ) for process equipment and vessels is the empty dead load plus the weight of test medium contained in the system. The test medium shall be as specified in the contract documents or as specified by the owner. Unless otherwise specified, a minimum specific gravity of 1.0 shall be used for the test medium. Equipment and pipes that may be simultaneously tested shall be included. Cleaning load shall be used for test dead load if the cleaning fluid is heavier than the test medium. 4.1.2.5 Pipe Rack Piping Loads 1. Dead loads for piping on pipe racks shall be estimated as follows, unless actual load information is available and requires otherwise: a. Operating dead load (D o ): A uniformly distributed load of 40 psf (1.9 kPa) for piping, product, and insulation Comment: This is equivalent to 8-inch (203-mm) diameter, Schedule 40 pipes, full of water, at 15-inch (381-mm) spacing. b. Empty dead load (D e ): For checking uplift and components controlled by minimum loading, 60% of the estimated piping operating loads shall be used if combined with wind or earthquake unless the actual conditions require a different percentage. c. Test dead load (D t ) is the empty weight of the pipe plus the weight of test medium contained in a set of simultaneously tested piping systems. The test medium shall be as specified in the contract documents or as specified by the owner. Unless otherwise specified, a minimum specific gravity of 1.0 shall be used for the test medium. 2. For any pipe larger than 12-inch (304-mm) nominal diameter, a concentrated load, including the weight of piping, product, valves, fittings, and insulation shall be used in lieu of the 40 psf (1.9 kPa). This load shall be uniformly distributed over the pipes associated area. 3. Pipe racks and their foundations shall be designed to support loads associated with full utilization of the available rack space and any specified future expansion. 4.1.2.6 Pipe Rack Cable Tray Loads Dead loads for cable trays on pipe racks shall be estimated as follows, unless actual load information is available and requires otherwise: a. Operating dead load (D o ): A uniformly distributed dead load of 20 psf (1.0 kPa) for a single level of cable trays and 40 psf (1.9 kPa) for a double level of cable trays. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 8 of 30 Process Industry Practices Comment: These values estimate the full (maximum) level of cables in the trays. b. Empty dead load (D e ): For checking uplift and components controlled by minimum loading, a reduced level of cable tray load (i.e., the actual configuration) should be considered as the empty dead load. Engineering judgement shall be exercised in defining the dead load for uplift conditions. 4.1.2.7 Ground-Supported Storage Tank Loads Dead loads for ground-supported storage tanks are shown in Table 9 with the same nomenclature as other dead loads in this Practice for consistency. The individual load components making up the dead loads may have to be separated for actual use in design, discussed as follows: a. Operating dead load (D o ): Operating dead load for a ground- supported storage tank is made up of the metal load from the tank shell and roof, vertically applied through the wall of the tank, in addition to the fluid load from the stored product. The fluid load acts through the bottom of the tank and does not act vertically through the wall of the tank. Therefore, the metal dead load and the fluid load must be used separately in design. b. Empty dead load (D e ): For checking uplift and components controlled by minimum loading, the corroded metal weight (if a corrosion allowance is specified) should be considered as the empty dead load. c. Test dead load (D t ): Test dead load for a ground-supported storage tank is made up of the metal load from the tank shell and roof, vertically applied through the wall of the tank, in addition to the fluid load from the test medium. The fluid load acts through the bottom of the tank and does not act vertically through the wall of the tank. Therefore, the metal dead load and the fluid load must be used separately in design. The test medium shall be as specified in the contract documents or as specified by the owner. Unless otherwise specified, a minimum specific gravity of 1.0 shall be used for the test medium. 4.1.3 Live Loads (L) 4.1.3.1 Live loads are gravity loads produced by the use and occupancy of the building or structure. These include the weight of all movable loads, such as personnel, tools, miscellaneous equipment, movable partitions, wheel loads, parts of dismantled equipment, stored material, etc. 4.1.3.2 Areas specified for maintenance (e.g., heat exchanger tube bundle servicing) shall be designed to support the live loads. 4.1.3.3 Minimum live loads shall be in accordance with ASCE/SEI 7, applicable codes and standards, and, unless otherwise specified, in Table 1: TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 9 of 30 TABLE 1. MINIMUM LIVE LOADS Uniform** Concentrated** Stairs and Exitways 100 psf (4.8 kN/m 2 ) 1,000 lb (4.5 kN) Operating, Access Platforms, and Walkways 75 psf (3.6 kN/m 2 ) 1,000 lb (4.5 kN) Control, I/O, HVAC Room Floors 100 psf (4.8 kN/m 2 ) 1,000 lb (4.5 kN) Manufacturing Floors and Storage Areas: Light
125 psf (6.0 kN/m 2 )
2,000 lb (9.0 kN) Heavy 250 psf (12.0 kN/m 2 )* 3,000 lb (13.5 kN) Ground-Supported Storage Tank Roof 25 psf (1.2 kN/m 2 ) NA *This 250 psf (12.0 kN/m 2 ) live load includes small equipment. **The loads provided in this table are to be used unless noted otherwise on the owners data sheet.
4.1.3.4 Uniform and concentrated live loads listed in Table 1 shall not be applied simultaneously. 4.1.3.5 According to ASCE/SEI 7, concentrated loads equal to or greater than 1,000 lb (4.5 kN) may be assumed to be uniformly distributed over an area of 2.5 ft (750 mm) by 2.5 ft (750 mm) and shall be located to produce the maximum load effects in the structural members. 4.1.3.6 Stair treads shall be designed according to OSHA regulations or building code as applicable. 4.1.3.7 Live load reductions shall be in accordance with ASCE/SEI 7. 4.1.3.8 For manufacturing floor areas not used for storage, the live load reduction specified by ASCE/SEI 7 for lower live loads may be used. 4.1.3.9 The loadings on handrails and guardrails for process equipment structures shall be in accordance with OSHA 1910. 4.1.3.10 The loadings on handrails and guardrails for buildings and structures under the jurisdiction of a building code shall be in accordance with the building code. 4.1.4 Wind Loads (W) 4.1.4.1 Unless otherwise specified, wind loads shall be computed and applied in accordance with ASCE/SEI 7 and the recommended guidelines for open frame structures, pressure vessels, and pipe racks in ASCE Guidelines for Wind Loads and Anchor Bolt Design for Petrochemical Facilities. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 10 of 30 Process Industry Practices 4.1.4.2 Site specific design parameters shall be in accordance with PIP CVC01017. 4.1.4.3 The full design wind load shall be used when calculating wind drift (see Section 4.3.6). 4.1.4.4 A solid width of 1.5 ft (450 mm) shall be assumed when calculating the wind load on ladder cages. 4.1.4.5 Partial wind load (W P ) shall be based on the requirements of SEI/ASCE 37-02, Section 6.2.1, for the specified test or erection duration. The design wind speed shall be 68 mph (109 kph) (which is 0.75 x 90 mph [145 kph] according to SEI/ASCE 37 for test or erection periods of less than 6 weeks). 4.1.4.6 For test or erection periods of 6 weeks or more or if the test or erection is in a hurricane-prone area and is planned during the peak hurricane season (from August 1 to October 31 in the U.S.A), see SEI/ASCE 37-02, Section 6.2.1. 4.1.5 Earthquake Loads (E) 4.1.5.1 Except for API Standard 650 ground-supported storage tanks, earthquake loads shall be computed and applied in accordance with ASCE/SEI 7, unless otherwise specified. Comment: The earthquake loads in ASCE/SEI 7 are limit state earthquake loads, and this should be taken into account if using allowable stress design methods or applying load factors from other codes. Earthquake loads for API Standard 650 storage tanks are allowable stress design loads. 4.1.5.2 Site specific design parameters shall conform to PIP CVC01017. 4.1.5.3 ASCE Guidelines for Seismic Evaluation and Design of Petrochemical Facilities may also be used as a general reference for earthquake design. 4.1.5.4 Earthquake loading shall be determined using ASCE/SEI 7-05, Chapter 15, if ASCE/SEI 7 is used for the earthquake design of nonbuilding structures as defined in ASCE/SEI 7-05, Section 15.1.1 and Tables 15.4-1 and 15.4-2. Comment: Nonbuilding structures include but are not limited to elevated tanks or vessels, stacks, pipe racks, and cooling towers. 4.1.5.5 The importance factor I for nonbuilding structures shall be determined from ASCE/SEI 7-05, Section 15.4.1.1. TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 11 of 30 Comment: In general, for nonbuilding structures in petrochemical process units, use an importance factor I of 1.25 in conjunction with Occupancy Category III; however, in some cases, it may be appropriate to use an importance factor I of 1.0 or 1.5 in conjunction with Occupancy Category II or IV respectively. 4.1.5.6 For the load combinations in Section 4.2, the following designations are used: E o = Earthquake load considering the unfactored operating dead load and the applicable portion of the unfactored structure dead load E e = Earthquake load considering the unfactored empty dead load and the applicable portion of the unfactored structure dead load 4.1.6 Impact Loads 4.1.6.1 Impact loads shall be in accordance with ASCE/SEI 7. 4.1.6.2 Impact loads for davits shall be the same as those for monorail cranes (powered). 4.1.6.3 Lifting lugs or pad eyes and internal members (included both end connections) framing into the joint where the lifting lug or pad eye is located shall be designed for 100% impact. 4.1.6.4 All other structural members transmitting lifting forces shall be designed for 15% impact. 4.1.6.5 Allowable stresses shall not be increased when combining impact with dead load. 4.1.7 Thermal Loads 4.1.7.1 For this Practice, thermal loads are designated by the following nomenclature: T p , T, A f , and F f , where T p = Forces on vertical vessels, horizontal vessels, or heat exchangers caused by the thermal expansion of the pipe attached to the vessel T = Self-straining thermal forces caused by the restrained expansion of horizontal vessels, heat exchangers, and structural members in pipe racks or in structures A f = Pipe anchor and guide forces F f = Pipe rack friction forces caused by the sliding of pipes or friction forces caused by the sliding of horizontal vessels or heat exchangers on their supports, in response to thermal expansion PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 12 of 30 Process Industry Practices 4.1.7.2 All support structures and elements thereof shall be designed to accommodate the loads or effects produced by thermal expansion and contraction of equipment and piping. 4.1.7.3 Thermal loads shall be included with operating loads in the appropriate load combinations. Thermal load shall have the same load factor as dead load. 4.1.7.4 Thermal loads and displacements shall be calculated on the basis of the difference between ambient or equipment design temperature and installed temperature. To account for the significant increase in temperatures of steel exposed to sunlight, 35 o F (20 o C) shall be added to the maximum ambient temperature. 4.1.7.5 Friction loads caused by thermal expansion shall be determined using the appropriate static coefficient of friction. Coefficients of friction shall be in accordance with Table 2:
TABLE 2. COEFFICIENTS OF FRICTION Steel to Steel 0.4 Steel to Concrete 0.6 Proprietary Sliding Surfaces or Coatings (e.g., Teflon) According to Manufacturers Instructions
4.1.7.6 Friction loads shall be considered temporary and shall not be combined with wind or earthquake loads. However, anchor and guide loads (excluding their friction component) shall be combined with wind or earthquake loads. 4.1.7.7 For pipe racks supporting multiple pipes, 10% of the total piping weight shall be used as an estimated horizontal friction load applied only to local supporting beams. However, an estimated friction load equal to 5% of the total piping weight shall be accumulated and carried into pipe rack struts, columns, braced anchor frames, and foundations. Comment: Under normal loading conditions with multiple pipes, torsional effects on the local beam need not be considered because the pipes supported by the beam limit the rotation of the beam to the extent that the torsional stresses are minimal. Under certain circumstances, engineering judgement shall be applied to determine whether a higher friction load and/or torsional effects should be used. 4.1.7.8 Pipe anchor and guide loads shall have the same load factor as dead loads. 4.1.7.9 Internal pressure and surge shall be considered for pipe anchor and guide loads. TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 13 of 30 4.1.7.10 Beams, struts, columns, braced anchor frames, and foundations shall be designed to resist actual pipe anchor and guide loads. 4.1.7.11 For local beam design, only the top flange shall be considered effective for horizontal bending unless the pipe anchor engages both flanges of the beam. 4.1.8 Bundle Pull Load (Bp) 4.1.8.1 Structures and foundations supporting heat exchangers subject to bundle pulling shall be designed for a horizontal load equal to 1.0 times the weight of the removable tube bundle but not less than 2,000 lb (9.0 kN). If the total weight of the exchanger is less than 2,000 lb (9.0 kN), the bundle pull design load need not exceed the total weight of the exchanger. 4.1.8.2 Bundle pull load shall be applied at the center of the bundle. Comment: If it can be assured that the bundles will be removed strictly by the use of a bundle extractor attaching directly to the exchanger (such that the bundle pull force is not transferred to the structure or foundation), the structure or foundation need not be designed for the bundle pull force. Such assurance would typically require the addition of a sign posted on the exchanger to indicate bundle removal by an extractor only. 4.1.8.3 The portion of the bundle pull load at the sliding end support shall equal the friction force or half the total bundle pull load, whichever is less. The remainder of the bundle pull load shall be resisted at the anchor end support. 4.1.9 Traffic Loads 4.1.9.1 Buildings, trenches, and underground installations accessible to truck loading shall be designed to withstand HS20 load as defined by AASHTO Standard Specifications for Highway Bridges. 4.1.9.2 Maintenance or construction crane loads shall also be considered where applicable. 4.1.9.3 Truck or crane loads shall have the same load factor as live load. 4.1.10 Blast Load 4.1.10.1 Blast load is the load on a structure caused by overpressure resulting from the ignition and explosion of flammable material or by overpressure resulting from a vessel burst. 4.1.10.2 Control houses or other buildings housing personnel and control equipment near processing plants may need to be designed for blast resistance. 4.1.10.3 Blast load shall be computed and applied in accordance with PIP STC01018 and the ASCE Design of Blast Resistant Buildings in Petrochemical Facilities. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 14 of 30 Process Industry Practices 4.1.11 Pressure Loads (Ground-Supported Tanks Only) For this Practice, pressure loads for ground-supported tanks are designated by the following nomenclature: P i , P e , and P t , where P i = design internal pressure P e = external pressure P t = test internal pressure 4.1.12 Snow Loads (S) 4.1.12.1 Unless otherwise specified, snow loads shall be computed and applied in accordance with ASCE/SEI 7. 4.1.12.2 Site specific design parameters shall be in accordance with PIP CVC01017. 4.2 Load Combinations 4.2.1 General Buildings, structures, equipment, vessels, tanks, and foundations shall be designed for the following: a. Appropriate load combinations from ASCE/SEI 7 except as otherwise specified in this Practice b. Local building codes c. Any other applicable design codes and standards d. Any other probable and realistic combination of loads 4.2.2 Typical Load Combinations (for Structures and Foundations) 4.2.2.1 General Load combinations are provided in Sections 4.2.2.2 through 4.2.2.6 for specific types of structures in both allowable stress design (ASD) and strength design format. a. Allowable Stress Design 1. The noncomprehensive list of typical load combinations for each type of structure provided in Sections 4.2.2.2 through 4.2.2.6 shall be considered and used as applicable. Comment: The dead load factor used for the earthquake uplift ASD load combinations is generally taken as 0.9. This factor is greater than the 0.6 dead load factor used in the ASD load combinations of ASCE/SEI 7-05, Section 2, because the dead loads of nonbuilding structures are known to a higher degree of accuracy than are the corresponding dead loads of buildings. A dead load factor of 0.9 instead of 1.0 is used to TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 15 of 30 account for the effect of vertical seismic forces. The use of this reduction is necessary because foundations sized using ASD loads, except for foundations for ground-supported storage tanks, are generally not required to consider the effect of vertical seismic uplift forces if a dead load factor of 0.6 is used. A dead load factor of 1.0 is used for the wind uplift ASD load combinations because of the higher accuracy of dead loads of nonbuilding structures 2. Engineering judgment shall be used in establishing all appropriate load combinations. 3. The use of a one-third stress increase for load combinations including wind or earthquake loads shall not be allowed for designs using AISC ASD. b. Strength Design 1. The noncomprehensive list of typical factored load combinations for each type of structure provided in Sections 4.2.2.2 through 4.2.2.6 shall be considered and used as applicable. 2. Engineering judgment shall be used in establishing all appropriate load combinations. 3. The following load combinations are appropriate for use with the strength design provisions of either AISC LRFD (third edition or later) or ACI 318 (2002 edition or later). 4.2.2.2 General Plant Structures Load combinations for buildings and open frame structures shall be in accordance with ASCE/SEI 7-05, Section 2. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 16 of 30 Process Industry Practices 4.2.2.3 Vertical Vessels TABLE 3. LOADING COMBINATIONS - ALLOWABLE STRESS DESIGN (SERVICE LOADS) Load Comb. No.
Load Combination Allowable Stress Multiplier
Description 1 D s +D o +L 1.00 Operating Weight + Live Load 2 D s +D o + (W or 0.7 E o a ) 1.00 Operating Weight + Wind or Earthquake 3 D s +D e +W 1.00 Empty Weight + Wind (Wind Uplift Case) 4a 0.9 (D s +D o ) +0.7 E o a 1.00 Operating Weight + Earthquake (Earthquake Uplift Case) 4b 0.9 (D s +D e ) +0.7 E e a 1.00 Empty Weight + Earthquake (Earthquake Uplift Case) 5 D s +D f +W p 1.00 Erection Weight + Partial Wind b (Wind Uplift Case) 6 D s +D t +W p 1.20 Test Weight + Partial Wind Notes: a. For skirt-supported vertical vessels and skirt-supported elevated tanks classified as Occupancy Category IV in accordance with ASCE/SEI 7-05, Section 1.5 and Table 1-1, the critical earthquake provisions and implied load combination of ASCE/SEI 7-05, Section 15.7.10.5, shall be followed. b. Erection weight +partial wind is required only if the erection weight of the vessel is significantly less than the empty weight of the vessel. c. Thrust forces caused by thermal expansion of piping shall be included in the calculations for operating load combinations, if deemed advisable. The pipe stress engineer shall be consulted for any thermal loads that are to be considered. TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 17 of 30 TABLE 4. LOADING COMBINATIONS AND LOAD FACTORS STRENGTH DESIGN Load Comb. No.
Load Combination
Description 1 1.4 (D s +D o ) Operating Weight 2 1.2 (D s +D o ) +1.6 L Operating Weight +Live Load 3 1.2 (D s +D o ) + (1.6 W or 1.0 E o a ) Operating Weight +Wind or Earthquake 4 0.9 (D s +D e ) +1.6 W Empty Weight +Wind (Wind Uplift Case) 5a 0.9 (D s +D o ) +1.0 E o a Operating Weight +Earthquake (Earthquake Uplift Case) 5b 0.9 (D s +D e ) +1.0 E e a Empty Weight +Earthquake (Earthquake Uplift Case) 6 0.9 (D s +D f ) +1.6 W p Erection Weight +Partial Wind b (Wind Uplift Case) 7 1.4 (D s +D t ) Test Weight 8 1.2 (D s +D t ) +1.6 W p Test Weight +Partial Wind Notes: a. For skirt-supported vertical vessels and skirt-supported elevated tanks classified as Occupancy Category IV in accordance with ASCE/SEI 7-05, Section 1.5 and Table 1-1, the critical earthquake provisions and implied load combination of ASCE/SEI 7-05, Section 15.7.10.5, shall be followed. b. Erection weight +partial wind is required only if the erection weight of the vessel is significantly less than the empty weight of the vessel. c. Thrust forces caused by thermal expansion of piping shall be included in the calculations for operating load combinations, if deemed advisable. The pipe stress engineer shall be consulted for any thermal loads that are to be considered. The same load factor as used for dead load shall be used. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 18 of 30 Process Industry Practices 4.2.2.4 Horizontal Vessels and Heat Exchangers TABLE 5. LOADING COMBINATIONS - ALLOWABLE STRESS DESIGN (SERVICE LOADS) Load Comb. No.
Load Combination Allowable Stress Multiplier
Description 1 D s +D o + (T or F f ) b 1.00 Operating Weight + Thermal Expansion or Friction Force 2 D s +D o +L + (T or F f ) b
1.00 Operating Weight + Live Load + Thermal Expansion or Friction Force 3 D s +D o + (W or 0.7 E o ) 1.00 Operating Weight + Wind or Earthquake 4 D s +D e +W 1.00 Empty Weight +Wind (Wind Uplift Case) 5a 0.9 (D s +D o ) + 0.7 E o
1.00 Operating Weight + Earthquake (Earthquake Uplift Case) 5b 0.9 (D s +D e ) + 0.7 E e
1.00 Empty Weight + Earthquake (Earthquake Uplift Case) 6 D s +D f +W p 1.00 Erection Weight + Partial Wind c (Wind Uplift Case) 7 D s +D t +W p 1.20 Test Weight + Partial Wind (For Horizontal Vessels Only) 8 D s +D e d +Bp 1.00 Empty Weight + Bundle Pull (For Heat Exchangers Only) Notes: a. Wind and earthquake forces shall be applied in both transverse and longitudinal directions, but shall not necessarily be applied simultaneously. b. The design thermal force for horizontal vessels and heat exchangers shall be the lesser of T or F f . c. Erection weight +partial wind is required only if the erection weight of the vessel or exchanger is significantly less than the empty weight of the vessel or exchanger. d. Heat exchanger empty dead load will be reduced during bundle pull because of the removal of the exchanger head. e. Sustained thermal loads not relieved by sliding caused by vessel or exchanger expansion shall be considered in operating load combinations with wind or earthquake. TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 19 of 30 f. Thrust forces caused by thermal expansion of piping shall be included in the calculations for operating load combinations if deemed advisable. The pipe stress engineer shall be consulted for any thermal loads that are to be considered.
Description 1 1.4 (D s +D o ) +1.4 (T or F f ) b Operating Weight + Thermal Expansion or Friction Force 2 1.2 (D s +D o ) +1.6 L + 1.2 (T or F f ) b
Operating Weight +Live Load + Thermal Expansion or Friction Force 3 1.2 (D s +D o ) + (1.6 W or 1.0 E o ) Operating Weight + Wind or Earthquake 4 0.9 (D s +D e ) +1.6 W Empty Weight +Wind (Wind Uplift Case) 5a 0.9 (D s +D o ) +1.0 E o Operating Weight +Earthquake (Earthquake Uplift Case) 5b 0.9 (D s +D e ) +1.0 E e Empty Weight +Earthquake (Earthquake Uplift Case) 6 0.9 (D s +D f ) +1.6 W p Erection Weight +Partial Wind c (Wind Uplift Case) 7 1.4 (D s +D t ) Test Weight (For Horizontal Vessels Only) 8 1.2 (D s +D t ) +1.6 W p Test Weight +Partial Wind (For Horizontal Vessels Only) 9 1.2 (D s +D e d ) +1.6 Bp Empty Weight +Bundle Pull (For Heat Exchangers Only) 10 0.9 (D s +D e d ) +1.6 Bp Empty Weight +Bundle Pull (For Heat Exchangers Only) (Bundle Pull Uplift Case) Notes: a. Wind and earthquake forces shall be applied in both transverse and longitudinal directions, but shall not necessarily be applied simultaneously. b. The design thermal force for horizontal vessels and heat exchangers shall be the lesser of T or Ff. c. Erection weight +partial wind is required only if the erection weight of the vessel or exchanger is significantly less than the empty weight of the vessel or exchanger. d. Heat exchanger empty dead load will be reduced during bundle pull because of the removal of the exchanger head. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 20 of 30 Process Industry Practices e. Sustained thermal loads not relieved by sliding from vessel or exchanger expansion shall be considered in operating load combinations with wind or earthquake. f. Thrust forces caused by thermal expansion of piping shall be included in the calculations for operating load combinations, if deemed advisable. The pipe stress engineer shall be consulted for any thermal loads that are to be considered. The same load factor as used for dead load shall be used. 4.2.2.5 Pipe Rack and Pipe Bridge Design
Description 1 D s +D o +F f +T +A f 1.00 Operating Weight + Friction Force + Thermal Expansion + Anchor Force 2 D s +D o +A f + (W or 0.7 E o ) 1.00 Operating Weight + Anchor +Wind or Earthquake 3 D s +D e c +W 1.00 Empty Weight +Wind (Wind Uplift Case) 4a 0.9 (D s ) +0.6 (D o ) + A f +0.7 E o d 1.00 Operating Weight + Earthquake (Earthquake Uplift Case) 4b 0.9 (D s +D e c ) + 0.7 E e
1.00 Empty Weight + Earthquake (Earthquake Uplift Case) 5 D s +D t +W p 1.20 Test Weight + Partial Wind e
Notes: a. Considerations of wind forces are normally not necessary in the longitudinal direction because friction and anchor loads will normally govern. b. Earthquake forces shall be applied in both transverse and longitudinal directions, but shall not necessarily be applied simultaneously. c. 0.6D o is used as a close approximation of the empty pipe condition D e . d. Full D s +D o value shall be used for the calculation of E o in load combination 4a. e. Test weight +partial wind normally is required only for local member design because test is not typically performed on all pipes simultaneously.
TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 21 of 30 TABLE 8. LOADING COMBINATIONS AND LOAD FACTORS STRENGTH DESIGN Load Comb. No.
Load Combination
Description 1 1.4 (D s +D o +F f +T
+A f ) Operating Weight + Friction Force + Thermal Expansion + Anchor 2 1.2 (D s +D o +A f ) + (1.6 W or 1.0 E o ) Operating Weight + Anchor +Wind or Earthquake 3 0.9 (D s +D e c ) +1.6 W Empty Weight +Wind (Wind Uplift Case) 4a 0.9 (D s +D o ) +1.2 (A f ) + 1.0 E o
Operating Weight + Earthquake (Earthquake Uplift Case) 4b 0.9 (D s + D e c ) +1.0 E e Empty Weight +Earthquake (Earthquake Uplift Case) 5 1.4 (D s +D t ) Test Weight 6 1.2 (D s +D t ) +1.6 W p Test Weight +Partial Wind d
Notes: a. Considerations of wind forces are normally not necessary in the longitudinal direction because friction and anchor loads will normally govern. b. Earthquake forces shall be applied in both transverse and longitudinal directions, but shall not necessarily be applied simultaneously. c. 0.6D o is used as a close approximation of the empty pipe condition D e . d. Test weight +partial wind normally is required only for local member design because test is not typically performed on all pipes simultaneously. 4.2.2.6 Ground-Supported Storage Tank Load Combinations Load combinations for ground-supported storage tanks shall be taken from API Standard 650. Load combinations from API Standard 650 and modified for use with ASCE/SEI 7 loads and PIP nomenclature are shown in Table 9. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 22 of 30 Process Industry Practices TABLE 9. LOADING COMBINATIONS - ALLOWABLE STRESS DESIGN (SERVICE LOADS) Load Comb. No.
Load Combination
Description 1 D s +D o +P i Operating Weight + Internal Pressure a
2 D s +D t +P t Test Weight + Test Pressure 3 D s +(D e or D o ) +W +0.4 P i b Empty or Operating Weight +Wind + Internal Pressure a
4 D s +(D e or D o ) +W +0.4 P e b Empty or Operating Weight +Wind + External Pressure 5 D s +D o +(L or S) +0.4 P e b Operating Weight + Live or Snow + External Pressure 6 D s +(D e or D o ) +0.4 (L or S) +P e Empty or Operating Weight + Live or Snow + External Pressure 7 D s +D o +0.1 S +E o c +0.4 P i b Operating Weight + Snow +Earthquake + Internal Pressure a (Earthquake Uplift Case) 8 D s +D o +0.1 S +E o c Operating Weight + Snow +Earthquake Notes: a. For internal pressures sufficient to lift the tank shell according to the rules of API Standard 650, tank, anchor bolts, and foundation shall be designed to the additional requirements of API Standard 650 Appendix F.7. b. If the ratio of operating pressure to design pressure exceeds 0.4, the owner shall consider specifying a higher factor on design pressure in load combinations 3, 4, 5, and 7 of Table 9. c. Earthquake loads for API Standard 650 tanks taken from ASCE/SEI 7 bridging equations or from API Standard 650 already include the 0.7 ASD seismic load factor. 4.2.2.7 Load Combinations for Static Machinery, Skid and Modular Equipment, Filters, and Other Equipment Load combinations for static machinery, skid and modular equipment, filters, etc., shall be similar to the load combinations for vertical vessels. TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 23 of 30 4.2.3 Test Combinations 4.2.3.1 Engineering judgment shall be used in establishing the appropriate application of test load combinations to adequately address actual test conditions in accordance with project and code requirements while avoiding overly conservative design. 4.2.3.2 Consideration shall be given to the sequence and combination of testing for various equipment, vessels, tanks, and/or piping systems supported on common structures, pipe racks, or foundations. 4.2.3.3 Full wind and earthquake loads are typically not combined with test loads unless an unusually long test duration is planned (i.e., if a significant probability exists that the partial wind velocity will be exceeded or an earthquake event may occur). 4.2.3.4 Additional loading shall be included with test if specified in the contract documents. 4.2.3.5 For allowable stress design, a 20% allowable stress increase shall be permitted for any test load combination. 4.2.3.6 For ultimate strength/limit states design, no load factor reduction shall be permitted for any test load combination. 4.3 Structural Design 4.3.1 Steel 4.3.1.1 Steel design shall be in accordance with AISC ASD or AISC LRFD specifications. 4.3.1.2 For cold-formed shapes, design shall be in accordance with AISI specifications. 4.3.1.3 Steel joists shall be designed in accordance with SJ I standards. Comment: Supplement number 1 to the AISC ASD specification deleted the one-third stress increase for use with load combinations including wind or earthquake loads. Because of the deletion of the one-third stress increase, designs made to the AISC LRFD specifications should be considered for economy. 4.3.1.4 Steel design, including steel joists and metal decking, shall be designed in accordance with OSHA 29 CFR 1926, Subpart R, to provide structural stability during erection and to protect employees from the hazards associated with steel erection activities. Comment: Common requirements that affect steel design areas follow (this is not an all inclusive list): a. All column base plates shall be designed with a minimum of four anchor bolts. Posts (which weigh less than 300 lb [136 kg]) are distinguished from columns and are excluded from the four- anchor bolt requirement. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 24 of 30 Process Industry Practices b. Columns, column base plates, and their foundations shall be designed to resist a minimum eccentric gravity load of 300 lb (136 kg) located 18 inches (450 mm) from the extreme outer face of the column in each direction at the top of the column shaft. Column splices shall be designed to meet the same load- resisting characteristics as those of the columns. c. Double connections through column webs or at beams that frame over the tops of columns shall be designed so that at least one installed bolt remains in place to support the first beam while the second beam is being erected. The fabricator may also supply a seat or equivalent device with a means of positive attachment to support the first beam while the second beam is being erected. d. Perimeter columns shall extend 48 inches (1,200 mm) above the finished floor (unless constructability does not allow) to allow the installation of perimeter safety cables. Provision shall be made for the attachment of safety cables. e. Structural members of framed metal deck openings shall be turned down to allow continuous decking, except where not allowed by design constraints or constructability. The openings in the metal deck shall not be cut until the hole is needed. f. Shear stud connectors that will project vertically from or horizontally across the top flange of the member shall not be attached to the top flanges of beams, joists, or beam attachments until after the metal decking or other walking/working surface has been installed. 4.3.1.5 All welded structural connections shall use weld filler material conforming to AWS D1.1/D1.1M, Section 3.3 (including Table 3.1), and have an electrode strength of 58 ksi (400 MPa) minimum yield strength and 70 ksi (480 MPa) tensile strength, unless otherwise required. 4.3.1.6 Structural steel wide-flange shapes, including WT shapes, shall be in accordance with ASTM A992/A992M, unless otherwise specified. 4.3.1.7 All other structural shapes, plates, and bars shall be in accordance with ASTM A36/A36M, unless otherwise specified. 4.3.1.8 Preference in design shall be given to shop-welded, field-bolted connections. 4.3.1.9 Compression flanges of floor beams, not supporting equipment, may be considered braced by decking (concrete or floor plate) if positively connected thereto. 4.3.1.10 Grating shall not be considered as lateral bracing for support beams. 4.3.1.11 Except as specified in Section 4.3.1.12 or if slip-critical connections are required by the AISC Specification for Structural Joints Using ASTM A325 or A490 Bolts, all bolts 3/4 inches (19 mm) and larger TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 25 of 30 (except anchor bolts) shall be type-N (bearing-type with threads included in the shear plane) high-strength ASTM A325 bolts. 4.3.1.12 Bolt size shall be as follows: a. Structural members - 3/4 inch (19 mm) minimum b. Railings, ladders, purlins, and girts - 5/8 inch, (16 mm) ASTM A307 4.3.1.13 Minimum thickness of bracing gusset plates shall be 3/8 inch (10 mm). 4.3.2 Concrete 4.3.2.1 Concrete design shall be in accordance with ACI 318/318R. 4.3.2.2 Concrete design for liquid-containing structures shall also be designed in accordance with ACI 350/350R. 4.3.2.3 Unless otherwise specified, all reinforcing steel shall be in accordance with ASTM A615/A615M Grade 60 deformed. 4.3.2.4 ASTM A615/A615M Grade 60 plain wire conforming to ASTM A82/A82M may be used for spiral reinforcement. 4.3.2.5 Welded wire fabric shall conform to ASTM A185/A185M. 4.3.2.6 Reinforcement designed to resist earthquake-induced flexural and axial forces in frame members and in wall boundary elements shall be in accordance with ASTM A706/A706M. ASTM A615/A615M Grade 60 reinforcement is acceptable for these members under the following conditions: a. The actual yield strength based on mill tests does not exceed the specified yield strength by more than 18,000 psi (124 MPa). Retests shall not exceed this value by more than an additional 3,000 psi (20.7 MPa). b. The ratio of the actual ultimate tensile strength to the actual tensile yield strength is not less than 1.25. 4.3.2.7 Precast and prestressed concrete shall be in accordance with the PCI Design Handbook. 4.3.3 Masonry Masonry design shall be in accordance with ACI 530/ASCE 5/TMS 402. 4.3.4 Elevator Supports Elevator support design shall be in accordance with ASME A17.1. 4.3.5 Crane Supports 4.3.5.1 Vertical deflection of support runway girders shall not exceed the following limits given in Table 10 if loaded with the maximum wheel load(s), without impact (where L =the span length). PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 26 of 30 Process Industry Practices TABLE 10. MAXIMUM ALLOWABLE GIRDER DEFLECTIONS Top-Running CMAA Class A, B, and C Cranes L/600 Top-Running CMAA Class D Cranes L/800 Top-Running CMAA Class E and F Cranes L/1000 Under-Running CMAA Class A, B, and C Cranes L/450 Monorails L/450
4.3.5.2 Vertical deflection of jib crane support beams shall not exceed L/225 (where L =the maximum distance from the support column to load location along the length of the jib beam) if loaded with the maximum lifted plus hoist load(s), without impact. 4.3.5.3 Lateral deflection of support runway girders for cranes with lateral moving trolleys shall not exceed L/400 (where L =the span length) if loaded with a total crane lateral force not less than 20% of the sum of the weights of the lifted load (without impact) and the crane trolley. The lateral force shall be distributed to each runway girder with consideration for the lateral stiffness of the runway girders and the structure supporting the runway girders. 4.3.5.4 Crane stops shall be designed in accordance with the crane manufacturers requirements or, if not specified, for the following load: F =W V 2 /(2gTn) where: F = Design force on crane stop, kips (kN) W = 50% of bridge weight +90% of trolley weight, excluding the lifted load, kips (kN) V = Rated crane speed, ft/sec (m/sec) g = Acceleration of gravity, 32.2 ft/sec 2 (9.8 m/sec 2 ) T = Length of travel (ft) of spring or plunger required to stop crane, from crane manufacturer, typically 0.15 ft (0.05 m) n = Bumper efficiency factor (0.5 for helical springs. Consult crane manufacturer for hydraulic plunger.)
4.3.6 Allowable Drift Limits 4.3.6.1 Allowable wind drift limits for pipe racks shall not exceed H/100 (where H =pipe rack height). 4.3.6.2 Except as indicated in the following subsections, the allowable wind story drift limits for occupied buildings shall not exceed H/200 (where H =story height). TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 27 of 30 4.3.6.3 Allowable wind drift limits for pre-engineered metal buildings shall not exceed H/80 (where H =building height). 4.3.6.4 Allowable wind drift limits for a building with a bridge crane that is required to be in service even during hurricanes shall not exceed H/400 or 2 inches (50 mm), whichever is less (where H =the height from the base of the crane support structure to the top of the runway girder). 4.3.6.5 Allowable wind drift limits for buildings with bridge cranes that will not be in service during hurricanes shall not exceed H/140 or 2 inches (50 mm), whichever is less (see Section 4.3.6.4 for definition of H). 4.3.6.6 Allowable wind drift limits for process structures and personnel access platforms shall not exceed H/200 (where H =structure height at elevation of drift consideration). 4.3.6.7 Allowable seismic drift limits shall be in accordance with ASCE/SEI 7. 4.3.7 Foundations 4.3.7.1 Foundation design shall be based on the results of a geotechnical engineering investigation. 4.3.7.2 The minimum overturning stability ratio for service loads other than earthquake shall be 1.5 (see Section 4.3.7.4 for the minimum overturning stability ratio for earthquake loads). For foundation design of buildings and open frame structures, if the dead load factor is 0.6 in accordance with ASCE/SEI 7-05, Section 2, the minimum overturning stability ratio shall be 1.0. Comment: This requirement is consistent with ASCE/SEI 7 provisions, in which the factor of safety is built into the 0.6 dead load factor in the load combinations. 4.3.7.3 The minimum factor of safety against sliding for service loads other than earthquake shall be 1.5 (see Section 4.3.7.4 for the minimum sliding factor of safety for earthquake loads). For foundation design of buildings and open frame structures, if the dead load factor is 0.6 in accordance with ASCE/SEI 7-05, Section 2, the minimum factor of safety against sliding shall be 1.0. Comment: This requirement is consistent with ASCE/SEI 7 provisions, in which the factor of safety is built into the 0.6 dead load factor in the load combinations. 4.3.7.4 Overturning and sliding caused by earthquake loads shall be checked in accordance with ASCE/SEI 7-05, Chapter 12. The minimum overturning stability ratio and the minimum factor of safety against sliding for earthquake service loads shall be 1.0. In addition, the minimum overturning stability ratio for the anchorage and PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 28 of 30 Process Industry Practices foundations of skirt-supported vertical vessels and skirt-supported elevated tanks classified as Occupancy Category IV in accordance with ASCE/SEI 7-05, Section 1.5 and Table 1-1, shall be 1.2 for the critical earthquake loads specified in ASCE/SEI 7-05, Section 15.7.10.5. 4.3.7.5 For earthquake loads calculated by the Equivalent Lateral Force Procedure in ASCE/SEI 7, additional stability checks shall be performed in accordance with ASCE/SEI 7-05, Section 12.8.5, Overturning. For foundations designed using seismic load combinations from Tables 3, 5, and 7 of this Practice, the reduction in overturning effects at the soil-foundation interface permitted in ASCE/SEI 7-05, Section 12.13.4, shall not be used. 4.3.7.6 The minimum factor of safety against buoyancy shall be 1.2 if using actual unfactored service loads. 4.3.7.7 Long-term and differential settlement shall be considered if designing foundations supporting interconnected, settlement- sensitive equipment or piping systems. 4.3.7.8 Because OSHA requires shoring or the equivalent for excavations 5 ft (1,525 mm) deep or greater and because it is costly to shore excavations, minimizing the depth of spread footings shall be considered in the design. 4.3.7.9 Unless otherwise specified, the top of grout (bottom of base plate) of pedestals and ringwalls shall be 1 ft (300 mm) above the high point of finished grade. 4.3.7.10 Except for foundations supporting ground-supported storage tanks, uplift load combinations containing earthquake loads do not need to include the vertical components of the seismic load effect, E, if used to size foundations. 4.3.7.11 Foundations for ground-supported storage tanks that have sufficient internal pressure to lift the shell shall be designed for the requirements of API Standard 650 Appendix F.7.5. 4.3.8 Supports for Vibrating Machinery 4.3.8.1 Machinery foundations shall be designed in accordance with PIP REIE686, Chapter 4, equipment manufacturers recommendations, and published design procedures and criteria for dynamic analysis. 4.3.8.2 If equipment manufacturers vibration criteria are not available, the maximum velocity of movement during steady-state normal operation shall be limited to 0.12 inch (3.0 mm) per second for centrifugal machines and to 0.15 inch (3.8 mm) per second for reciprocating machines. 4.3.8.3 Support structures or foundations for centrifugal machinery greater than 500 horsepower shall be designed for the expected dynamic forces using dynamic analysis procedures. TECHNICAL CORRECTION PIP STC01015 September 2007 Structural Design Criteria Process Industry Practices Page 29 of 30 4.3.8.4 For centrifugal machinery less than 500 horsepower, in the absence of a detailed dynamic analysis, the foundation weight shall be designed to be at least three times the total machinery weight, unless specified otherwise by the equipment manufacturer. 4.3.8.5 For reciprocating machinery less than 200 horsepower, in the absence of a detailed dynamic analysis, the foundation weight shall be designed to be at least five times the total machinery weight, unless specified otherwise by the manufacturer. 4.3.8.6 The allowable soil-bearing or allowable pile capacity for foundations for equipment designed for dynamic loads shall be a maximum of half of the normal allowable for static loads. 4.3.8.7 The maximum eccentricity between the center of gravity of the combined weight of the foundation and machinery and the bearing surface shall be 5% in each direction. 4.3.8.8 Structures and foundations that support vibrating equipment shall have a natural frequency that is outside the range of 0.80 to 1.20 times the exciting frequency. 4.3.9 Anchor Bolts 4.3.9.1 Anchor bolts shall be headed type or threaded rods with compatible nuts using ASTM A36/A36M, A307, F1554 Grade 36, F1554 Grade 55, F1554 Grade 105, A193/A193M Grade B7, A354 Grade BC, or A354 Grade BD material. 4.3.9.2 All ASTM A36/A36M, A307, and F1554 Grade 36 anchor bolts shall be hot dip galvanized. 4.3.9.3 Anchor bolt design shall be in accordance with PIP STE05121. 4.3.10 Wood Wood design shall be in accordance with the American Forest and Paper Association National Design Specification for Wood Construction and with the NDS Supplement - Design Values for Wood Construction. 4.3.11 Design of Drilled Shafts 4.3.11.1 Minimum vertical reinforcement shall be 0.50% of the pier gross area or as required to resist axial loads and bending moments. 4.3.11.2 The minimum clear spacing of vertical bars shall not be less than three times the maximum coarse aggregate size nor less than three times the bar diameter. 4.3.11.3 Reinforcing steel shall allow a minimum of 3 inches (75 mm) of concrete cover on piers without casing and 4 inches (100 mm) of concrete cover on piers in which the casing will be withdrawn. 4.3.12 Design of Driven Piles 4.3.12.1 Unless otherwise specified or approved, the pile types specified in PIP STS02360 shall be used. PIP STC01015 TECHNICAL CORRECTION Structural Design Criteria September 2007 Page 30 of 30 Process Industry Practices 4.3.12.2 In addition to in-place conditions, piles shall be designed to resist handling, transportation, and installation stresses. 4.3.12.3 Unless otherwise specified, the exposure condition shall be evaluated to establish the corrosion allowances for steel piles. 4.3.12.4 The top of piles shall penetrate a minimum of 4 inches (100 mm) into the pile cap. 4.3.13 Vessel Load Cell Supports Supports for vessel load cells shall be designed in accordance with PIP PCCWE001 and PIP PCEWE001. 4.4 Existing Structures If the owner and the engineer of record agree that the integrity of the existing structure is 100% of the original capacity based on the design code in effect at the time of original design, structural designs shall be performed in accordance with the following: 4.4.1 If additions or alterations to an existing structure do not increase the force in any structural element or connection by more than 5%, no further analysis is required. 4.4.2 If the increased forces on the element or connection are greater than 5%, the element or connection shall be analyzed to show that it is in compliance with the applicable design code for new construction. 4.4.3 The strength of any structural element or connection shall not be decreased to less than that required by the applicable design code or standard for new construction for the structure in question.