Preparing to synchronize a generator

to the grid
Post ed MAR 27 2013 by EDVARD i n ENERGY AND POWER wi t h 12 COMMENTS

Preparing to synchronize a generator to the grid (on photo: General Electric steam turbine generator)
Conditions
In order to synchronize a generator to the grid, four conditions must be met:
1. Phase Sequence
2. Voltage Magnitude
3. Frequency
4. Phase Angle

Figure 1 - Synchronizing a Generator to the Grid
1. Phase Sequence
The phase sequence (or phase rotation) of the three phases of the generator must
be the same as the phase sequence of the three phases of the electrical
system (Grid).
The only time that the phase sequence could be wrong is at initial installation or after
maintenance. There are two possible problem sources.
The generator or transformer power leads could actually be interchanged during
maintenance orthe potential transformer leads could be interchanged during
maintenance.


2. Voltage Magnitude
The magnitude of the sinusoidal voltage produced by the generator must be equal to
the magnitude of the sinusoidal voltage of the grid.
If all other conditions are met but the two voltages are not the same, that is there is a
voltage differential, closing of the AC generator output breaker will cause a potentially
large MVAR flow.
Recall that before a generator is synchronized to the grid, there is no current flow,
no armature reaction and therefore the internal voltage of the generator is the same as
the terminal voltage of the generator.
If the generator voltage is higher than the grid voltage, this means that the
internal voltage of the generator is higher than the grid voltage. When it is connected to
the grid the generator will be overexcited and it will put out MVAR.
If the generator voltage is less than the grid voltage, this means that the internal
voltage of the generator is lower than the grid voltage. When it is connected to the grid
the generator will be under-excited and it will absorb MVAR.


3. Frequency
The frequency of the sinusoidal voltage produced by the generator must be equal to
the frequency of the sinusoidal voltage produced by the grid.

Figure 2 - Generator Slower than Grid


In Figure 2 above the generator is slower than the grid.
The synchroscope would be rotating rapidly counter clockwise. If the generator breaker
were to be accidentally closed, the generator would be out of step with the external
electrical system. It would behave like motor and the grid would try to bring it up to
speed.
In doing so, the rotor and stator would be slipping poles and damage (possibly
destroy) the generator as described previously. The same problem would occur if
the generator were faster than the grid.
The grid would try to slow it down, again resulting in slipping of poles.

Figure 3 - Generator at Same Speed asGrid but not in Phase


Figure 3 shows the condition where the generator and grid have matching speed.
The high points and zero crossings of the sinusoidal voltages occur at the same rate of
speed.
However, if you notice in 2 with the grid and a phase angle exists between them. This
would appear as a non-rotating synchroscope (both generator and grid at same
frequency), where the pointer would appear stuck at about 9:00 oclock (generator
lagging grid).
If the generator breaker were to be closed at this time, the grid would pull the
generator into step.
However, this again would cause a large current in-rush to the generator and high
stresses on the rotor/stator with subsequent damage to the generator. If the
generator were leading the grid, it would try to immediately push power into the grid
with the same destructive forces as mentioned.
Hence the generator must be brought to a point where the grid voltage waveform
exactly matches what it is producing.


4. Phase Angle
As previously mentioned, the phase angle between the voltage produced by the
generator and the voltage produced by the grid must be zero.
The phase angle (0 to 360) can be readily observed by comparing the simultaneous
occurrence of the peaks or zero crossings of the sinusoidal waveforms.
If the generator breaker is closed when they match exactly, the connection will
appear smooth and seamless.
At that instance (Figure 4 below), the pointer on the synchroscope would indicate 12:00
oclock.
The worst case occurs if the generator is exactly out-of phase, with a phase angle of
180 and the synchroscope pointing at 6:00 oclock.

Figure 4 - Generator in Phase with Grid