SECTION 230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
This section specifies supports and anchors for non-vibration isolated equipment, tanks, ductwork, and piping systems. If this
section is used, always include Section 230545, Seismic Restraints for HVAC Piping and Equipment. If equipment requiring
vibration isolation is specified, include Section 230548, Vibration and Seismic Controls for HVAC Piping and Equipment.
PART 1 - GENERAL
SCHEDULE 0 - DESCRIPTION
PRODUCT DATA SHEET 0 - This section describes the following:
0.1 Hangers, supports, and anchors for equipment, tanks, ductwork, and piping systems.
0.2 Supplementary steel for support or attachment of tanks, equipments, ductwork, and
piping to general construction elements of the project.
SCHEDULE 1 - RELATED WORK SPECIFIED ELSEWHERE
PRODUCT DATA SHEET 0 - Section 230545, Seismic Restraints for HVAC Piping and Equipment
PRODUCT DATA SHEET 1 - Section 230518, Expansion Compensation
SCHEDULE 2 - REFERENCES
PRODUCT DATA SHEET 0 - ASHRAE: American Society of Heating, Refrigerating and AirConditioning Engineers
0.1 ASHRAE Chapter 41: Absorption, Cooling, Heating, and Refrigeration Equipment
PRODUCT DATA SHEET 1 - ASTM: American Society for Testing and Materials
1.1 ASTM A36: Standard Specification for Carbon Structural Steel
PRODUCT DATA SHEET 2 - IBC: International Building Code
PRODUCT DATA SHEET 3 - SMACNA: Sheet Metal and Air Conditioning Contractors National
Association
SCHEDULE 3 - SUBMITTALS
PRODUCT DATA SHEET 0 - Product Data: Submit product data for products specified herein.
PRODUCT DATA SHEET 1 - Shop Drawings:
1.1 Submit shop drawings of Contractor-fabricated piping support structures, pipe racks, and
anchors.
11/9/2014
/var/www/apps/conversion/tmp/scratch_1/250578933.doc
1.2
1.3
1.4
1.5
Suspended Piping and Ductwork: Submit shop drawings of piping and ductwork
indicating point loads and support locations, along with applicable details keyed to
layouts.
Support Frames, Piping, Tank, and Equipment Supports, and Anchorage: Submit shop
drawings indicating point loads and support locations, along with engineers calculations
and details keyed to the layouts pertaining to supports, support frames, and anchorages.
Supplementary Steel: Submit shop drawings showing details of fabrication and
installation. Indicate materials, thicknesses, gauges, sizes, dimensions, methods of
joining and fastening, welds, finishes, details of reinforcement and embedment,
attachments, anchorages, miscellaneous metal items incidental to basic fabrication
shown, provisions for work of other trades, and other pertinent information. Submit
structural calculations for necessary supplementary steel for supports, anchors, and
attachment of equipment, pipes, and ducts to general construction. Calculations shall be
prepared and stamped by a registered professional structural engineer licensed in the state
of Oregon.
As-Constructed Drawings and Data: Submit as-constructed data and as-constructed
drawings.
11/9/2014
/var/www/apps/conversion/tmp/scratch_1/250578933.doc
1.2
1.3
Support frames, such as pipe racks or stanchions, for piping and equipment which
provide support from below.
Tank, equipment and piping support frame anchorage to supporting slab or structure.
PRODUCT DATA SHEET 1 - Fabricate support members from welded standard structural shapes,
pipe, and plate. Carry the necessary rollers, hangers, and accessories as required. Piping less
than 4-inch pipe size may be supported from or by prefabricated roll-formed channels as
specified in this section with necessary accessories to adequately support piping system.
PRODUCT DATA SHEET 2 - Supports and Accessories: Preformed roll-formed channels and
accessories with matching compatible accessories as shown, as specified, and as required.
PRODUCT DATA SHEET 3 - Dissimilar Metal Protection: Cush-a-Strip, Hydra-Zorb cushions, or
equal.
PRODUCT DATA SHEET 4 - Attachments to roof and floor decks are not allowed.
SCHEDULE 2 - PIPE ATTACHMENTS
PRODUCT DATA SHEET 0 - Acceptable Manufacturers: B-Line Systems, Elcen, Anvil, Michigan
Hanger, Superstrut, Telco, or equal.
PRODUCT DATA SHEET 1 - Clamps: Superstrut Series 700 through 702.
PRODUCT DATA SHEET 2 - Insulated Horizontal Steel Piping:
2.1 Chilled Water, 2 Inches and Under: Anvil 65 with Fig. 167 shield.
2.2 Chilled, Over 2 Inches: Anvil Fig. 260 with Fig. 167 shield.
2.3 Other, 2 Inches and Under: Anvil Fig. 65 with Fig. 167 shield.
2.4 Other, Over 2 Inches: Anvil Fig. 260 with Fig. 167 shield.
PRODUCT DATA SHEET 3 - Uninsulated Horizontal Steel Piping:
3.1 2 Inches and Under: Anvil Fig. 65.
3.2 Over 2 Inches: Anvil Fig. 260.
PRODUCT DATA SHEET 4 - Insulated Horizontal Copper Piping:
4.1 Chilled Water, 2 Inches and Under: Anvil Fig. 65 with Fig. 167 shield.
4.2 Chilled Water, Over 2 Inches: Anvil 260 with Fig. 167 shield.
PRODUCT DATA SHEET 5 - Uninsulated Horizontal Copper Piping:
5.1 2 Inches and Under: Anvil Fig. CT65, CT69.
5.2 Over 2 Inches: Anvil Fig. CT65.
PRODUCT DATA SHEET 6 - Riser Clamps, Steel and Cast Iron Pipe: 3/4-inch to 20-inch, Anvil Fig.
261.
11/9/2014
/var/www/apps/conversion/tmp/scratch_1/250578933.doc
PRODUCT DATA SHEET 7 - Riser Clamps, Copper Pipe: Anvil Fig. CT-121.
SCHEDULE 3 - PIPE ROLLERS
PRODUCT DATA SHEET 0 - Supported: Anvil Fig. 274, pipe roll chair, adjustable; or equivalent
product by B-Line Systems, Elcen, Superstrut, Telco, or equal.
PRODUCT DATA SHEET 1 - Supported: Superstrut C728H, pipe roller, aluminum wheels, steel
brackets, or equivalent product by B-Line Systems, Elcen, Anvil, Telco, or equal.
PRODUCT DATA SHEET 2 - Suspended: Anvil Fig. 171 or Fig. 177 adjustable pipe roller; or
equivalent product by B-Line Systems, Elcen, Superstrut, Telco, or equal.
SCHEDULE 4 - PIPE RACKS
PRODUCT DATA SHEET 0 - Acceptable Manufacturers: Kin-Line, Superstrut, Uni-Strut, or equal.
PRODUCT DATA SHEET 1 - Supports and Accessories: Preformed roll-formed channels and
accessories with electrochromate or equal finish and matching compatible accessories as shown,
as specified, and as required.
SCHEDULE 5 - PROTECTION SHIELDS
PRODUCT DATA SHEET 0 - Select protection shields based on actual outside diameter of pipe plus
insulation. Protection shields shall be used at hanger or roller assemblies on chilled or cold
water piping, where hangers are installed around insulation, and on both sides of clamps or Ubolts where installed around insulation. Use Anvil Fig. 167, or equal.
SCHEDULE 6 - BUILDING ATTACHMENTS
PRODUCT DATA SHEET 0 - Acceptable Manufacturers: B-Line Systems, Elcen, Anvil, Superstrut,
Telco, or equal.
PRODUCT DATA SHEET 1 - Beam Hangers Beam Clamps: Anvil Fig. 218, adjustable malleable
iron beam clamp, or Fig. 228, adjustable forged steel beam clamp.
PRODUCT DATA SHEET 2 - Beam Hangers C-Type Clamps: Anvil Fig. 93. Sized for required rod
to support load being carried.
PRODUCT DATA SHEET 3 - Beam Hangers Welded: Anvil Fig. 66. Sized for required rod to
support load being carried.
PRODUCT DATA SHEET 4 - Inserts:
4.1 Malleable iron or steel inserts, Superstrut M-732CB or S. Inserts sized for required rod
to support load being carried.
4.2 Malleable iron or steel inserts, Grinnell, Fig. 152. Inserts sized for required rod to
support load being carried.
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
230529-4
11/9/2014
/var/www/apps/conversion/tmp/scratch_1/250578933.doc
PRODUCT DATA SHEET 5 - Expansion Plugs: Similar and equal to Phillips red-head self-drilling
flush shell, selected for safety factor of 4.
PRODUCT DATA SHEET 6 - Powder-actuated fasteners with silencers as approved by the Port.
SCHEDULE 7 - PIPE ANCHORS
PRODUCT DATA SHEET 0 - Fabricate from steel plate as detailed (steam, condensate, pumped
condensate, and hot water).
PRODUCT DATA SHEET 1 - Insulated Pipe Anchors (Chilled Water):
1.1 Acceptable Manufacturers: Pipe Shields Inc., Rilco, or pre-bid approved equal.
1.2 Insulated pipe anchors shall maintain vapor barrier and a positive axial, lateral, and
vertical stop.
A.
Steel Inner Thrust Plates: Welded attachments, material shall be compatible with
pipe, shipped loose.
B.
Structural Inserts: High-density calcium silicate, compressive strength 600 psi
minimum. Asbestos-free treated with water repellant.
C.
Jackets: Galvanized steel.
D.
Steel Straps Base and Outer Thrust Plates: Carbon steel.
E.
Fasteners: Cadmium plated.
1.3 The anchor shall bear the piping system design load. Pipe Shields models C4000 through
C4300.
PART 3 - EXECUTION
SCHEDULE 0 - HANGERS AND SUPPORTS
PRODUCT DATA SHEET 0 - General:
0.1 Install all support systems as detailed and in accordance with manufacturers
recommendations. Provide pipe racks, pipe stands, trapeze hangers, etc., as required and
as detailed on the drawings.
0.2 Provide adjustable hangers complete with inserts, adjusters, bolts, nuts, swivels, allthread rods, etc., for all pipes, except where specified otherwise.
0.3 Size hangers to clear insulation for piping services conveying liquids less than 70F.
0.4 Support fire protection piping independently of other piping.
0.5 Prevent electrolysis in support of copper tubing by use of hangers and supports which are
copper plated, or by other recognized industry methods. Do not use tape for isolation.
0.6 Arrange for grouping of parallel runs of horizontal piping to be supported together on
trapeze type hangers where possible. Where piping of various sizes is to be supported
together by trapeze hangers, space hangers for smallest pipe size or install intermediate
supports for smaller diameter pipe. Do not use wire or perforated metal to support
piping, and do not support piping from other piping.
0.7 Except as otherwise indicated for exposed continuous pipe runs, install hangers and
supports of same type and style as installed for adjacent similar piping.
0.8 Install piping systems in accordance with SMACNA standards.
11/9/2014
/var/www/apps/conversion/tmp/scratch_1/250578933.doc
Max. Span
Steel
7 feet
8 feet
11 feet
14 feet
17 feet
19 feet
20 feet
20 feet
20 feet
20 feet
20 feet
20 feet
20 feet
Max. Span
Copper
5 feet
8 feet
9 feet
10 feet
12 feet
14 feet
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Rod Size
3/8"
3/8"
1/2"
1/2"
5/8"
7/8"
7/8"
7/8"
1"
1"
1 1/4"
1 1/4"
1 1/2"
Maximum Rod Load: Below are maximum loads for hanger rods based on Chapter 41 of
ASHRAE Guide and as follows for ASTM A36, with a safety factor of 5.
Nominal Rod Diameter
3/8"
1/2"
5/8"
3/4"
7/8"
Load
610 pounds
1,130 pounds
1,810 pounds
2,710 pounds
3,770 pounds
11/9/2014
/var/www/apps/conversion/tmp/scratch_1/250578933.doc
Load
4,960 pounds
8,000 pounds
11,630 pounds
11/9/2014
/var/www/apps/conversion/tmp/scratch_1/250578933.doc