Professional Documents
Culture Documents
HVDC Protection
HVDC Protection
2, APRIL 2009
569
AbstractA novel hybrid protection algorithm, based on traveling wave protection principle and boundary protection principle
for a monopolar HVDC line is proposed. Stationary wavelet
transform (SWT) is adopted in the traveling wave protection
to process the dc signal and then wavelet modulus maxima are
used to further represent the useful traveling wave signal. The
boundary protection principle based on SWT is used jointly
with traveling wave protection to distinguish internal faults from
external faults. The effect of border distortion, noise, high ground
fault resistance, close-up faults, transients caused by lightning
strokes and different dc line terminations are considered in the
paper.
Index TermsBoundary protection, HVDC line protection,
lightning strokes, relay, stationary wavelet transform (SWT),
traveling waves.
I. INTRODUCTION
is found in the literature. It has been applied in ac line directional relay to extract traveling wave information [6], [7]. Reverse voltage traveling wave is used as an input to a wavelet
modulus maxima (WMM)-based edge detector for the HVDC
line [5]. Other applications in HVDC line protection can also
be found in [8][10]. The HVDC model for these papers is
single-wire ground return system with a Bergeron line model
and the termination is inductive.
A hybrid algorithm consisting of an impedance relay and
traveling wave relay, is shown to be effective in solving
close-up faults in ac transmission systems [2]. However, power
frequency-based distance protection cannot meet the requirement of HVDC transmission, because the steady state voltage
and current are largely influenced by the HVDC control strategies. So the hybrid algorithm might not work for HVDC line
protection. A new boundary protection concept is proposed and
successfully applied to ac line protection [11]. It is believed
that current transient signals, particularly in the high frequency
range, will be shunted to earth by busbar capacitance. By
applying this theory, boundary protection can distinguish internal faults from external faults based only on one-end high
frequency signals. A similar technique has also been applied
in HVDC line protection [10], [12]. The smoothing reactor in
the HVDC system can attenuate the sudden change caused by
external faults and, thus, forms a boundary.
In the literature, most studies regarding lightning strokes
are for insulation or overvoltage studies; few studies are about
the effect of lightning on transient-based protection algorithms
[13][15]. In these studies, a current source of positive polarity
is used. However, it is suggested that a current source of negative polarity should be used for lightning study [16][18] since
90% of strokes are negative [19]. Current magnitude and tower
structure are not adequately considered in the existing lightning
studies for protection purposes. It is also found that when
lightning strikes the tower without causing back-flashover,
transients can still be induced on the main line and will possibly
cause confusion to the protection algorithm too. It is thus
necessary to further study the influence of lightning strokes on
transient-based transmission line protection algorithms.
In this paper, a hybrid protection algorithm consisting of traveling wave distance protection and boundary protection is proposed for mono-polar metallic return HVDC line main protection. The method to distinguish lightning strokes, brief introduction of stationary wavelet transform (SWT), and discrete
wavelet transform (DWT), the method to deal with border distortion, the basics of WMM, the de-noising method, and the
protection principle used in this paper are given in Section II.
The simulation model is given in Section III. The detailed procedure of the algorithm is presented in Section IV. Simulation
570
are the rectifier-side line attenuation coefficient and terminal reis expressed as [22]
flection coefficient.
(2)
(1)
where
is the voltage change at distance 0 and time
is the initial wave from the fault point,
is a step input.
is the reflection coefficient of the fault location.
and
is the characteristic
where is the smoothing reactor and
impedance of line. At instant , the voltage change consists of
and
,
as shown near 0.5004 s in Fig. 1. Then, the voltage decays
according to the constant of the reflection coefficient . The
voltage remains much lower than the steady-state level until
instant (near 0.5013 s) when the reflected wave correthe
sponding to the third and fourth item in (1) causes a voltage
jump. For back-flashover, the behavior is similar to a high
impedance ground fault.
Next, a direct lightning hit on the dc line is shown in Fig. 3
and its lattice diagram is shown in Fig. 4. Since the width of
the lightning stroke is very narrow, it can be regarded as adding
an impulse input at the lightning location. The traveling wave
equation can be written as
(3)
are
where is the initial wave at the lightning point. and
the inverter-side terminal reflection coefficient and line attenuis the impulse input. Ideally, there should
ation coefficient.
be two spikes only. The lightning source, however, is not a pure
impulse and its width, together with the constant of reflection
coefficients, causes the decay. It is found in Fig. 3 that other
(close to 0.5004 s),
(close to 0.5022 s)
than at instant
and their corresponding decays, the voltage remains near steady
state. The lighting on tower with no back-flashover is similar to
the direct hit. An impulse is induced onto the line through the
insulation capacitor.
This difference in the behavior of the traveling wave can be
used to distinguish the fault from no fault conditions. The energy
LIU et al.: HYBRID TRAVELING WAVE/BOUNDARY PROTECTION FOR MONOPOLAR HVDC LINE
571
and
are highpass and lowpass filters at the th
signal.
level.
Due to its translation-invariance property, SWT has been
successfully applied in singularity detection in a noisy environment. The application of the wavelet transform in HVDC line
traveling wave protection is also a signal singularity detection
problem. Besides, the high sampling frequency of traveling
wave based algorithms will inevitably bring in noise. So the
SWT is used in the traveling wave protection in this paper.
The Haar wavelet is chosen as the mother wavelet since it
can detect sharp transients effectively. It only has two filter
coefficients and, thus, requires much less computation than any
other mother wavelet.
C. Wavelet Modulus Maxima and Denoising
572
is defined as
(8)
and
is the th detail coefficients of the th decomposition
level ( starts from 2 because the first level is dominated by
noise). is the maximum level of SWT decomposition and is
the total number of detail coefficients at each level. Four-level
SWT decomposition is found to be necessary to make a clear
distinction between internal and external faults.
F. Border Distortion
Due to the limited number of data in wavelet applications,
the border distortion can arise during the wavelet transform, but
users usually ignore it. For the fault location application, the position of spikes caused by traveling wave reflection is critical to
the fault distance calculation. For the boundary protection algorithm, border distortion can create extra energy and, thus, cause
wrong trip decision. The border extension [10] is a simple way
of dealing with border distortion; however, the default border
extension in the MATLAB wavelet toolbox uses too few extension samples and sometimes cannot solve the problem mentioned in this paper. Therefore, this problem is addressed here.
LIU et al.: HYBRID TRAVELING WAVE/BOUNDARY PROTECTION FOR MONOPOLAR HVDC LINE
573
574
LIU et al.: HYBRID TRAVELING WAVE/BOUNDARY PROTECTION FOR MONOPOLAR HVDC LINE
575
TABLE I
PERFORMANCE UNDER DC FAULTS
and, at the same time, the other end of the line is open. Since it
is a highly improbable coincidence, the main switching process
is only a ground fault on the transmission line [35]. For the dc
startup process, because of the control system, the voltage and
current increase mildly without much overshoot. So the disturbances for the dc line are mainly caused by line faults, lightning
stroke, and external faults.
A. Effect of Noise, Fault Resistance, and External Faults
(Inductive Termination)
Fig. 11. Removal of noise with SWT. (a) DC voltage with 30 dB noise. (b)
WMM before denoising. (c) WMM after denoising.
576
TABLE II
PERFORMANCE UNDER EXTERNAL FAULTS
TABLE IV
ENERGY RATIO UNDER DIFFERENT SITUATIONS
TABLE III
CLOSEUP FAULTS UNDER 30-dB NOISE (INDUCTIVE TERMINATION)
TABLE V
PERFORMANCE UNDER DC FAULTS
it does not affect the algorithm since external faults should not
trigger dc line protection anyway.
B. Performance Under Closeup Faults (Inductive Termination)
When the fault occurs extremely near the relay location, for
example 0.5 km away, the traveling wave algorithm may not
detect the fault [6]. Some closeup faults (with 30 dB noise) 0.5
km away from the relay location are shown in Table III. It can be
seen that the hybrid method can effectively detect these closeup
faults.
C. Effect of Lightning Strokes (Inductive Termination)
In order to distinguish transients caused by lightning strokes
from fault cases, the lightning energy ratio
is adopted. It can
be found that the ratio is below
for fault cases and above
the threshold for no fault cases as shown in Table IV. The ratio
is not influenced much by noise.
D. Performance Under Capacitive Termination
For a system with capacitive termination, the current signal
is used for the traveling wave protection part. All other settings
are basically the same. Some dc faults are shown in Table V. It
can be seen that all of these faults will generate the trip signal
are
including closeup faults. External faults and the energy
shown in Tables VI and VII, respectively. It is obvious that the
and, thus,
energy of all external faults is below the threshold
will not generate the trip signal. The lightning energy ratio
can distinguish fault cases from no fault cases.
VI. CONCLUSION
A novel hybrid HVDC line main protection algorithm consisting of traveling wave protection and boundary protection
is proposed. A revised denoising method is used to deal with
noise. Many factors that affect the performance of protection algorithms are considered, such as transients caused by lightning
strokes, border distortion, high ground fault resistance, external
faults, closeup faults, and line terminal configuration. The proposed algorithm shows satisfactory performance under various
conditions and does not require the knowledge of characteristic
impedance to calculate the traveling wave signal.
LIU et al.: HYBRID TRAVELING WAVE/BOUNDARY PROTECTION FOR MONOPOLAR HVDC LINE
TABLE VI
PERFORMANCE UNDER EXTERNAL FAULTS
TABLE VII
ENERGY RATIO UNDER DIFFERENT SITUATIONS
In some rare cases with high fault resistance and strong noise,
the influence of noise cannot be completely removed. Sometimes, noise can change the magnitude of the real spikes caused
by traveling wave reflection. Under these rare cases, the computed distance can be incorrect and/or the traveling wave protection may fail. However, the boundary protection can catch
the faults. There are two distance sets calculated from (5) and
(6). If the distance is wrong, the distance set that is not chosen
might be correct since it is based on a different principle and,
thus, is worth being considered.
The threshold of boundary protection is set assuming that
30 dB noise exists. However, in cases where the noise level is
known to be lower, the threshold can be set higher so that higher
fault resistance can be covered by the boundary protection.
REFERENCES
[1] P. M. Anderson, Power System Protection. New York: McGraw-Hill,
1999, pp. 915955.
[2] V. Pathirana, E. Dirks, and P. G. McLaren, Hardware and software
implementation of a travelling wave based protection relay, in Proc.
IEEE Power Eng. Soc. General Meeting, Jun. 2005, vol. 1, pp.
701706.
577
[3] P. F. Gale, P. V. Taylor, P. Naidoo, C. Hitchin, and D. Clowes, Travelling wave fault locator experience on ESKOMs transmission network, in Proc. Inst. Elect. Eng. 7th Int. Conf. Developments in Power
System Protection, Apr. 2001, pp. 327330.
[4] L. Al and W.-H. Chen, Discussion on line protection of HVDC transmission line, (in Chinese) Relay, vol. 32, no. 4, pp. 6163, Feb. 2004,
(indexed by INSPEC).
[5] L. Shang, G. Herold, J. Jaeger, R. Krebs, and A. Kumar, High-speed
fault identification and protection for HVDC line using wavelet technique, in Proc. IEEE Porto Power Tech Conf., Porto, Portugal, 2001,
vol. 3, pp. 15, pt. 3.
[6] W. Chen, O. P. Malik, X. Yin, D. Chen, and Z. Zhang, Study of
wavelet-based ultra high speed directional transmission line protection, IEEE Trans. Power Del., vol. 18, no. 4, pp. 11341139, Oct.
2003.
[7] X. Dong, Y. Ge, and J. He, Surge impedance relay, IEEE Trans.
Power Del., vol. 20, no. 2, pt. 2, pp. 12471256, Apr. 2005.
[8] K. Rajesh and N. Yadaiah, Fault identification using wavelet transform, in Proc. IEEE/Power Eng. Soc. Transmission Distribution Conf.
Exhibit.: Asia Pacific, 2005, pp. 16.
[9] X. Liu, A. H. Osman, and O. P. Malik, Stationary wavelet transform
based HVDC line protection, presented at the NAPS 2007, Las Cruces,
TX, Sep. 30, 2007.
[10] X. Liu, A. H. Osman, and O. P. Malik, Hybrid traveling
wave/boundary protection for HVDC line, presented at the Int.
Conf. Power System, Bangalore, India, Dec. 12, 2007.
[11] Z. Q. Bo, A new non-communication protection technique for transmission lines, IEEE Trans. Power Del., vol. 13, no. 4, pp. 10731078,
Oct. 1998.
[12] G. Wang, M. Wu, H. Li, and C. Hong, Transient based protection for
HVDC lines using wavelet-multiresolution signal decomposition, in
Proc. IEEE/Power Eng. Soc. Transmission Distribution Conf. Exhibit.:
Asia Pacific, 2005, pp. 14.
[13] H. X. Ha and B. H. Zhao, Study on identification of fault and lightning
strokes in boundary protection for EHV transmission lines, in Proc.
Int. Conf. Power System Technology, Oct. 2002, vol. 1, pp. 270274.
[14] H. Li, G. Wang, and Z. Liao, Distinguish between lightning strikes and
faults using wavelet multi-resolution signal decomposition, in Proc.
8th Inst. Elect. Eng. Int. Conf. Developments in Power System Protection, Apr. 2004, vol. 1, pp. 8083.
[15] J. Ren, J. Duan, B. Zhang, and P. Li, Identification of lightning disturbance in ultra-high-speed transmission line protection, in Proc. IEEE/
Power Eng. Soc. Transmission Distribution Conf. Exhibit.: Asia Pacific, 2005, pp. 15.
[16] Fast Front Transients Task Force of the IEEE Modeling and Analysis
of System Transients Working Group, Modeling guidelines for fast
front transients, IEEE Trans. Power Del., vol. 11, no. 1, pp. 493506,
Jan. 1996.
[17] L. A. Kraft, Modelling lightning performance of transmission systems
using PSpice, IEEE Trans. Power Syst., vol. 6, no. 2, pp. 573549, May
1991.
[18] T. Narita, T. Yamada, A. Mochizuki, E. Zaima, and M. Ishii, Observation of current waveshapes of lightning strokes on transmission
towers, IEEE Trans. Power Del., vol. 15, no. 1, pp. 429435, Jan.
2000.
[19] J. D. Glover and M. S. Sarma, Power system analysis and design,
Thomson Learning, p. 591, 2002.
[20] IEEE Guide for Improving the Lightning Performance of Transmission
Lines, IEEE Std. 1243-1997, Dec. 1997.
[21] E. W. Kimbark, Transient overvoltages caused by monopolar ground
fault on bipolar DC line: Theory and simulation, IEEE Trans. Power
App. Syst., vol. PAS-89, no. 4, pp. 584592, Apr. 1970.
[22] H. Li, F. Lin, J. He, Y. Lu, H. Ye, and Z. Zhang, Analysis and simulation of monopolar grounding fault in bipolar HVDC transmission
system, in Proc. IEEE Power Eng. Soc. General Meeting, Jun. 2007,
pp. 15.
[23] G. P. Nason and B. W. Silverman, The stationary wavelet transform
and some statistical applications, in Lecture Notes in Statistics, A.
Antoniadis and G. Oppenheim, Eds. Bristol, U.K.: Univ. Bristol,
1995, pp. 281300. [Online]. Available: www.maths.bris.ac.uk/
~magpn/Eliospub/reports/Wavelets/swtsa.ps.gz
[24] S. Mallat and W. L. Wang, Singularity detection and processing,
IEEE Trans. Inf. Theory, vol. 38, no. 2, pt. 2, pp. 617643, Mar. 1992,
Special issue.
[25] N. G. Hingorani, Transient overvoltage on a bipolar HVDC overhead
line caused by DC line faults, IEEE Trans. Power App. Syst., vol.
PAS-89, no. 4, pp. 592610, Apr. 1970.
578
[26] M. Ando, Fault location techniques for HVDC lines: analysis, development, simulation and field-data evaluation, Ph.D. dissertation,
Washington State University, Pullman, WA, 1984.
[27] M. Szechtman, T. Wess, and C. V. Thio, First benchmark model for
HVDC control studies, Electra, no. 135, pp. 5673, Apr. 1991.
[28] EMTDC Users Manual v3, Manitoba HVDC Research Center,
1988, pp. 2633, 239249.
[29] H. Elahi, R. W. Flugum, S. E. Wright, and D. R. Brown, Insulation coordination process for HVDC converter stations: Preliminary and final
designs, IEEE Trans. Power Del., vol. 4, no. 2, pp. 10371048, Apr.
1989.
[30] A. Maffucci and G. Miano, Irregular terms in the impulse response of
a multiconductor lossy transmission line, IEEE Trans. Circuits Syst.
I: Fundam. Theory Appl., vol. 46, no. 7, pp. 788805, Jul. 1999.
[31] J. Wang and X. Zhang, Double-exponential expression of lightning
current waveforms, in Proc. 4th Asia-Pacific Conf. Environmental
Electromagnetics, Aug. 2006, pp. 320323.
[32] S. J. Shelemy and D. R. Swatek, Monte Carlo simulation of lightning strikes to the Nelson river HVDC transmission lines, presented
at the Int. Conf. Power Systems Transients, Brazil, Jun. 2001. [Online].
Available: www.ipst.org/TechPapers/2001/IPST01Paper099.pdf.
[33] Electric Power Research Inc., Transmission Line Reference Book, 345
kV and Above, 2nd ed. Palo Alto, CA: Electric Power Research, 1987,
pp. 552575.
[34] J. L. Blackburn, Protective Relaying, Principles and Applications, 2nd
ed. New York: Marcel Dekker, 1998, p. 420.
[35] E. Uhlmann, Power Transmission by Direct Current. Berlin, Germany: Springer-Verlag, 1975, pp. 214215.
[36] K. G. Narendra, V. K. Sood, K. Khorasani, and R. Patel, Application
of a radial basis function (RBF) neural network for fault diagnosis in a
HVDC system, IEEE Trans. Power Syst., vol. 13, no. 1, pp. 177183,
Feb. 1998.
Xiaolei Liu (S07) received the B.Sc. degree from Qingdao University of Science and Technology, Qingdao, China, in 2005. He is currently pursuing the
Ph.D. degree at the University of Calgary, Calgary, AB, Canada.
His areas of interest include digital protection relaying, signal processing,
neural network, and HVDC systems.