Professional Documents
Culture Documents
Module No E16 Fire Alarm System
Module No E16 Fire Alarm System
ELECTRICAL
TITLE
:
MODULE NO :
OBJECTIVES:
Upon completion of this module, the electrical multitask technician will be able to:
1. Demonstrate knowledge and understanding on fire detection and alarm system, fire detection and
suppression system
2. Demonstrate understanding on the purpose and importance of fire alarm system
3. Demonstrate understanding on the types and operation of fire alarm system
4. Demonstrate understanding on the fire alarm system installation and circuitry
5. Describe the different components installed in a fire alarm system.
6. Demonstrate understanding and describe the different types of fire detection and alarm
devices
7. Demonstrate knowledge on suitable applications of fire detection devices
8. Describe the importance of maintenance, inspection and testing on fire alarm system
9. Demonstrate knowledge on isolation and de-isolation of fire alarm system
10. Demonstrate understanding and describe basic procedures in conducting periodic
inspection, repair, testing and re-commissioning
11. Perform routine preventive maintenance, inspection, and testing
12. Demonstrate understanding on fire detection and suppression system
13. Describe the major components of a fire detection and FM-200 fire suppression system
14. Describe the system of operation of a typical fire detection and suppression system
15. Demonstrate understanding on fire suppression system maintenance
16. Demonstrate knowledge and understanding on fire and gas detection system
17. Demonstrate knowledge and understanding on reading fire detection and suppression
system installation drawing
Page 2 of 62
TABLE OF CONTENTS
Section
Topic
Page
Page 3 of 62
4.2.4 Typical Application and Installation of Fire Detection and Suppression System ...................... 38
4.2.5 Typical Fire Detection and Suppression System Logic Diagram............................................... 39
5.0.0 SYSTEM COMPONENTS FOR AN AUTOMATIC FIXED FIRE SUPPRESSION SYSTEM .................... 40
5.1.0 FIRE INITIATION AND ANNUNCIATION DEVICES ......................................................... 40
5.1.1 Types of initiation and annunciation devices ......................................................................... 41
5.1.2 Heat/Thermal Detectors......................................................................................................... 41
5.1.3 Smoke Detector ...................................................................................................................... 42
5.1.4 Break glass and manual call points......................................................................................... 42
5.1.6 Abort Stations ......................................................................................................................... 43
5.1.7 Alarm Devices ........................................................................................................................ 44
5.2.0 EXTINGUISHING SYSTEMS .................................................................................................. 44
5.3.0 ELECTRICAL CONTROL EQUIPMENT (CONTROL PANEL) ....................................... 46
5.3.1 Network master control module ............................................................................................. 48
5.3.2 Secondary control module ...................................................................................................... 49
5.3.3 Single line diagram for Secondary Controller at each protected area .................................... 50
5.3.4 Power supply .......................................................................................................................... 51
5.3.5 Intelligent loop controller ....................................................................................................... 51
5.3.6 Zone releasing module (ZRM) and Fire suppression control panel (FSCP) ......................... 51
5.37 Event and status printer ........................................................................................................... 52
6.0.0 O P E R A T I O N
FIRE DETECTION
OF
AND
S U P P R E S S I O N S Y S T E M ............................... 54
FOR
FUNCTIONAL
TESTING OF
F I R E S U P P R E S S I O N S Y S T E M ............. 57
AND
G A S D E T E C T I O N S Y S T E M ................................................................................ 59
10.0.0 R EF E R E N C E S
AND
A T T A C H M E N T S ................................................................................. 62
Page 4 of 62
1.0.0 I NTRODUCTION
Fire is an observable event which occurs when a substance or material upon reaching an
uncertain temperature reacts chemically with oxygen, to produce heat, light, smoke, flame, water vapor,
carbon monoxide, carbon dioxide or other products and effects.
Three things must be present to have combustion, and they are FUEL, HEAT and AIR. These
three constitutes the so called triangle of fire. These three elements have to be put together in the
correct proportions in order for fire to occur. Once a fire has occurred, it becomes necessary to remove
one of the above components to extinguish it.
An electrical fire originates from an energized electrical equipment, wiring, fuses and
appliances. Its extinguishment calls for a non conductive dry powder, carbon dioxide or vaporizing
liquid.
An automatic fire detection, alarm and extinguishing system should be in-placed to detect the
presence of fire and initiate action.
In a big industrial complex the common fire fighting system installed are the following:
Fire alarm and detection system
Foam system
The majority of industrial and commercial premises require an alarm system, either for the
protection of life or for the protection of the goods, valuables, processes and machinery within the
premises.
In this module, two systems will be discussed namely, Fire Detection and Alarm System and
Fire Detection and Suppression System.
Page 5 of 62
AND
A LARM S YSTEM
Manual alarm systems, which consists of break glass units and alarm sounders connected to a
control panel, can only be operated and the alarm raised when activated by a individual having detected
a fire incident.
Automatic systems, which consist of smoke and heat detectors, in addition to break glass units
and alarm sounders connected to a control panel, are designed to raise the alarm whether or not
personnel are present at the time, thus giving early warning of a fire incident.
2.2.0 PURPOSE OF FIRE ALARM SYSTEM
Generally, a fire alarm system is installed with the intention to:
1. Minimize damage to the property and its contents
2. Enhance the safety of the occupants
Fire alarm systems can be designated as follows:
P-type systems - fire alarm system intended for the protection of property
L-type systems -fire alarm system intended for the protection of life
Fire alarm systems intended for the protection of property will automatically detect a fire at an
early stage, indicate its location and raise an effective alarm in time to summon the fire fighting forces.
Fire alarm system for the protection of life can be relied upon to sound a fire alarm while
sufficient time remains for the occupants to escape.
2.3.0 TYPES AND OPERATION OF FIRE DETECTION AND ALARM SYSTEM
Most fire detection systems fall into one of three main categories:
A) Conventional Systems
B) Addressable Systems
C) Analogue Addressable Systems
Page 6 of 62
condition of the detection devices throughout the whole system, with separate zones used to help to
pinpoint the location of the alarm. Zones are groups of initiating devices wired on a common circuit
Page 7 of 62
With conventional systems, when a detector is activated the zone (area) covered by the alarm
will be indicated on the control panel and a light emitting diode (LED) will indicate which detector is in
the alarm mode. Following activation of a device, the zone in which the device is located must be
searched to identify the precise location of the alarm. No other information about the zone can be
obtained at the control panel.
2.3.2 Addressable systems
Addressable system is a modern approach to fire alarm systems, which identifies the alarm
device that has actuated .It has an addressable fire alarm control panel or intelligent fire alarm control
panel which usually specify the number of detectors and modules that will be operated and this is the
same as the number of addressable devices. The panel identifies the call points, sensors, interface units,
sounders, repeat and mimic panels. In the addressable systems, detectors and call points are connected
by two-wire circuits in a loop arrangement.
Principle of Operation
Fire alarm devices and call points in the addressable systems are connected by two-wire circuits
in a loop arrangement. Devices on each loop are given a numerical address (typically from 1 to 126).
The two-wire circuits transmit power to the devices as well as convey
Page 8 of 62
information on the devices back to the control panel. Therefore, in addition to indicating the zone in
which the alarm has been raised, the panel may also be configured to display predefined messages to
identify the precise locations of the devices, thereby removing the need for a physical search of the
zone to identify the precise location of the alarm. Such information also enables the spread of fire to be
monitored from the control panel.
Addressable systems use conventional detectors but also allow the connection of other
input/output devices which may be used for signaling purposes or for interfacing with other devices.
2.3.3 Analogue addressable systems
The wiring of detectors and call-points is similar to that for addressable systems. However,
analogue addressable systems offer the advantage of being able to communicate continuously with the
control panel to provide information on the environmental conditions.
Analogue systems are able to monitor the environment for pre-alarm levels of heat or smoke and
environmental changes such as buildup of dust or dirt. When detectors become contaminated with dust
or dirt their sensitivity may be affected resulting in false alarms. Analogue addressable systems can
overcome this problem by automatically adjusting the pre-alarm and alarm levels to compensate for the
contamination.
Fire Alarm System - Module No E 16
Page 9 of 62
Page 10 of 62
smoke detectors
heat detectors
beam detectors
flame detectors
gas detectors
Page 11 of 62
Page 12 of 62
Typical main circuit board for Conventional Fire Alarm Control Panel (FACP)
Page 13 of 62
Page 14 of 62
Typical main circuit board for Addressable Fire Alarm Control Panel (FACP)
Page 15 of 62
Page 16 of 62
2. Heat detector- a device which detects abnormally high temperature or rate-of-temperature rise
point fixed heat detector
point rate of heat rise detectors
beam-type heat detectors
3. Beam detector- a device used in large open areas and very high ceilings where heat and
smoke detectors are ineffective.
4. Aspirating systems- a system consisting of extremely sensitive detector used to detect smoke
before the outbreak of flaming combustion.
5. Flame detector- a device which detects the infrared (IR) or ultraviolet (UV), or visible
radiation produced by a fire.
6. Fire-Gas detector- a device which detects gas or gases produced by a fire
2.4.3.1 Description of fire detection devices
1. Ionization Smoke detectors.
Ionization smoke detectors are particularly sensitive to small particle smoke. This type of
detector is ideal for detecting fast burning fires.
Air in the dual sensing chambers is irradiated to produce ions that travel to the positive and
negative electrodes, creating a current flow. As smoke enters the outer chamber, the flow drops and
voltage increases. The current is reduced by the presence of smoke. The device functions on the
principle of comparing two internally fitted chambers of which one is free to accept minute amounts of
visible and invisible particles of combustion while the other is hermetically sealed.
Smoke and other products of combustion entering the chamber attract charged air molecules
which envelope the invading pollution to form what is know as super ions. This reduces and impairs
the mobility of the ions causing a drop in current to occur. A second, but airtight chamber connected in
series formation with the sampling chamber allows minute change in current to flow to be interchanged
to measurable variation in voltage by means of an analogue amplification unit.
Once a predetermined response threshold has been reached, the detector transmits a signal from
the amplifier to a delay mechanism which in turn communicates with the fire alarm control panel. The
accepted signal automatically triggers the alarm sequence and activates the sounders. When triggered,
the detector will latch in electronically until manually reset by way of the control panel once smoke and
other products of combustion have been evacuated.
Page 17 of 62
Page 18 of 62
thermistor will increase rapidly, resulting in an imbalance of the thermistors and causing the detector to
change to the alarm state.
Fixed temperature heat detector responds to fast burning fires. This type of heat detector is a
simple device fitted with a fixed temperature element designed to activate the alarm circuit once a
predetermined temperature is reached. Usually a choice of two operational temperature is available,
60oC and 90oC. This type of detector is very suitable to monitor boiler rooms or kitchens where
fluctuations in ambient temperature are commonplace.
4. Rate of Heat rise detectors
The rate of rise heat detector responds to rises in air temperature. This type of heat detector is
fitted with a rate of rise element designed to operate in response to rapid rise in temperature. The rate of
heat rise detector type responds to rapid rise of temperature by sampling the temperature difference
between two heat-sensitive thermocouples or thermistor mounted in a single housing. If one
thermocouple increases in temperature relative to the other, an electrical potential is generated and the
detector will signal the alarm sounder circuit by way or the control panel.
Page 19 of 62
Ordinary
135 to 174
100
Intermediate
175 to 249
150
High
250 to 324
225
Extra High
325 to 399
300
400 to 499
375
Ultra High
500 to 575
475
5. Beam detectors
In buildings with large open areas and very high ceilings, point-type heat detectors and smoke
detectors are ineffective and detection may not occur until the fire is well established. In these
situations dedicated optical beam detectors are more suitable.
These detectors come in pairs, consisting of transmitter and receiver. The transmitter
propagates an infrared beam which travels across the protected area to the receiver. If the beam is
broken by smoke, the sensor is triggered.
In the event of a fire, the amount of infrared light that will be received by the receiver is reduced
due to the presence of smoke. Excess heat also affects the signal received and the receiver will indicate
whether an excess of smoke or heat has been detected.
These types of detectors are particularly suited to warehouses, aircraft hangars, historic buildings, art
galleries and loft spaces.
Fire Alarm System - Module No E 16
Page 20 of 62
6 Aspirating systems
In some premises where expensive equipment is housed, such as computer rooms and telephone
exchanges, it is important to detect smoke before the outbreak of flaming combustion. In such
situations an aspirating system should be used.
Aspirating systems generally consist of the following:
one or more pipes, drilled at regular intervals, installed throughout the area to be
protected and connected to the detector (the holes serve as individual smoke detectors)
a pump which draws air through the pipes to the detector where it is analyzed for the
presence of smoke
an optional filter to remove dust particles which may have been drawn into the pipes
appropriate electronic equipment to indicate the presence of smoke and control the
operation of output relays.
Unlike point detectors, which wait for smoke to reach them, air is drawn to the detector;
therefore they can be used in areas where smoke detection would otherwise prove difficult such as in
atria, stadia, gymnasia and large function rooms with high ceilings. They are also suitable for use in
dusty environments. Detection of this type may be more costly than a conventional fire detection
system and control system.
Page 21 of 62
7. Flame detectors
Flame detectors are used in areas that contain materials that are likely to produce rapidly
spreading flaming fires, such as flammable liquids.
There are two main type of flame detector
ultraviolet flame detectors which detect the ultraviolet radiation within a flame
infrared detectors which respond to the flickering component of the infrared radiation
from a fire.
Flame detectors are unable to detect smoke from smoldering fires and are therefore used to
supplement heat or smoke detectors. They are not used as general purpose detectors.
Page 22 of 62
Manual and automatic devices may be installed on the same system; however, it may be
advisable to install the manual call points on separate zones for speed of identification.
Page 23 of 62
In cases where persons to be alerted are in a very noisy areas, then a flashing beacons can be
wired into the sounder circuits.
2.4.6 Cables
The type of cable used in fire alarm systems can be divided into two main types:
those which need to continue to function during a fire condition (power supply cables,
links to sounders and remote communication centers).
those which can fail, having first served their purpose (cables to detectors, fail safe cables
to auxiliary devices such as door release devices)
Page 24 of 62
Fire alarm cables will be expected to resist fire for at least half an hour. Suitable cables include
FP 200 and MICC cable (mineral insulated copper sheathed cable). The minimum conductor size
should be 1mm2 if the cable is solid and 0.5mm2 if the cable is stranded.
Fire alarm cables should be segregated from cables used for other systems.
2.4.7 Applications for Smoke and Heat detectors
Location
Corridor
Ionization
Rate of rise
Suitable
Lift shaft
Optical
Notes
Fixed heat
Suitable
Suitable
Waiting room
Suitable
Suitable
Department store
Suitable
Suitable
Laboratory
Suitable
Factory workshop
Suitable
Suitable
Church
Suitable
Suitable
Suitable
Library
Suitable
Suitable
Naked flame
Smouldering
fire
Boiler room
Suitable
Rapid change
in room
temperature
Kitchen
Suitable
Suitable
Avoid placing
over ovens
Loading bay
Bedroom
Suitable
Suitable
Suitable
Page 25 of 62
Page 26 of 62
AND
T ESTING
OF
Page 27 of 62
removing the fusible element to determine that the detector contacts operate properly,
and then reinstalling the fusible element
2. Smoke Detectors
To assure that each smoke detector is operative, it shall be tested, in place, in accordance
with the manufacturers instruction. Normally, for ionization and optical type smoke
detectors, a nonflammable aerosol is used as smoke detector tester.
Smoke detector sensitivity shall be determined using either:
A calibrated test method, or
The manufacturers calibrated sensitivity instrument, or
Other calibrated sensitivity test method acceptable to the authority having jurisdiction.
Detectors found to be outside the approved range of sensitivity shall be replaced.
3. Flame Detectors, Fire-Gas Detectors and Other Fire Detectors.
Flame detectors, fire-gas detectors and other fire detectors shall be tested for operation in
accordance with instruction supplied by the manufacturer or other test methods acceptable to the
authority having jurisdiction.
4. Manual call points or break glass station
Older type of manual call points are triggered by undoing the from glass cover using a small
Allen screw while the modern one is activated by the use of a specially designed plastic key which
when fitted into a small opening at the base of the box, engages a cam which automatically moves the
glass and in turn closes the terminals. This will bring the system into an alarm mode. Reset the manual
call point by replacing back the glass cover or taking out the plastic key.
Page 28 of 62
Page 29 of 62
INSPECTION/TESTING
REMARKS
FREQUENCY
Fire Alarm Control Panel
Annually
Remote Annunciators
Annually
Annually
Detectors
Horns, Strobes, Bells,
Annually
Biannually
Testing
after installation
Semiannually
Semiannually
Page 30 of 62
Remarks
3
4
5
6
7
8
10
11
12
13
Page 31 of 62
INSPECTION/TESTING DATE:
FREQUENCY OF INSPECTION:
Monthly/Semiannually/Annually
INSPECTOR:
APPROVING AUTHORITY:
INSPECTION/TEST POINTS
REMARKS
Page 32 of 62
AND
S UPPRESSION S YSTEM
4.1.0 INTRODUCTION
The purpose of the Fire System is to monitor the control rooms, switch gear rooms, battery
rooms and other enclosed areas for incipient fire incidents. The system automatically and reliably alerts
personnel and operators to the existence and location of fire or smoke and initiates prescribed control
actions to reduce the threat and to shut down the interfacing equipment.
Upon detection of an alarm condition, suitable audible and visual alarms are registered in the
DCS, in the control room, and trigger annunciator beacons and horns. Visual alarms sent to the DCS
and matrix panels identify the type and location of the sensing device activated.
Both the inputs and outputs are self-monitoring and supervised type wherein the modules
supervise the field circuits, detecting faults that may effect the operation of the system. Detection of a
fault is alarmed at the DCS.
The signals from the fire detection are used to initiate operation of fire extinguishing system and
shutdown the interface equipment.
Fire Suppression using chemical agent or gas is one of several extinguishing method which
extinguish fire by reaction with the combustion process and by cooling of the atmosphere in the
enclosure. Fire Suppression is intended to prevent or extinguish fires in situations where conventional
extinguishing agents such as water, dry chemical, and carbon dioxide are unacceptable because they
may cause collateral damage, significantly interrupt business productivity, or present a safety risk.
These situations exist primarily where there is electrical or sensitive electronic equipment
servicing a critical operation, the loss of which would not only be the value of the equipment but also
the cost of business interruption.
4.2.0 FIRE SUPPRESSION SYSTEM
The most popularly used extinguishing gas for Fire Suppression System was Halon 1301. But
because of the ozone depleting effect of Halon 1301 it was phase out . Today, the suppression agent
that is most favored as halon replacement is the HFC-227 ear marketed under the name FM 200. HFC227 (FM 200) is chemically known as heptafluorocarbon or heptafluoropropane.
Page 33 of 62
The alternative agents fall into two categories based on their extinguishing method:
Chemical agent: these are primarily hydrofluorocarbon (HFC) and perfluorocarbon (PFC)
or HCFC blends which extinguish fire by reaction with the combustion process and by
cooling of the atmosphere in the enclosure.
Inert agents: these agents are permanent gas blends based on nitrogen which extinguish fire
by reducing the oxygen content of the atmosphere from 21% to below 15%.
The most commonly used chemical agent or halocarbon agent and has emerged as one of the
most favored halon replacements is a hydroflurocarbon marketed under the name FM 200.
HFC-227 (FM 200) is a pure hydrofluorocarbon and was the first environmentally acceptable
replacement for Halon 1301. FM-200 has zero ozone depleting potential, a low global warming
potential and a short atmospheric lifetime.
FM-200 is a colorless, liquefied compressed gas. It is stored as a liquid and dispensed into the
hazard as a colorless, electrically nonconductive vapor that is clear and does not obscure vision. It
leaves no residue and has acceptable toxicity for use in occupied spaces at design concentration. FM200 does not displace oxygen and therefore is safer for use in occupied spaces without fear of oxygen
deprivation.
Page 34 of 62
FM-200 extinguishing systems are employed to protect critical installation which includes the
following:
Data processing centers
Control rooms, flammable liquid hazards
Oil industry installation
Communications/Computer rooms
Power generation and electrical switch gear rooms
Telecommunications
Machinery, Gas turbines
Museums and Archives
4.2.2 General Description FM-200 Fire Suppression System
1. The FM-200 Fire Suppression System normally includes a detection and control system with
provision for both pre-alarm and automatic agent release.
2. Detection of products of combustion and fire is by approved devices and U.L. listed. The
detection employ photoelectric and ionization smoke detectors and heat detectors. A single
detector activated shall cause an alarm signal to be generated. A second detector activated
shall generate a pre-discharge signal and start the pre-discharge condition.
3. Alarm signals, system supervision, and agent releasing output is through a control panel
provided with a battery standby.
4. The suppression subsystem provide high speed release of FM-200 based on the concept of
total flooding fire protection for enclosed areas and with uniform extinguishing concentration
of 7% at 700F, or higher.
Page 35 of 62
5. FM-200 is discharged through the operation of a solenoid operated device which releases the
agent through a differential pressure valve. The system discharge is normally 10 seconds in
accordance with the NFPA Standard 2001.
6. FM-200 is stored in modular or central storage steel alloy storage containers complying with
the specifications and equipped with differential pressure valves. No replacement parts are
necessary to recharge the FM-200 containers.
Page 36 of 62
4.2.3 Single line diagram for Typical Fire Detection and Suppression System
Installation
Page 37 of 62
4.2.4 Typical Application and Installation of Fire Detection and Suppression System
Page 38 of 62
Page 39 of 62
Control Panel for alarm signals, system supervision, and agent releasing output
Page 40 of 62
Heat detector
Smoke detector
Abort stations
Heat Detector
Each detector is commonly provided with two (2) recessed LED indicators: one red and one
green. When the device is in normal condition, background supervision is indicated by a flashing green
LED. The red LED flashes in an alarm condition.
Commonly used brand are Kidde Fenwall, Edwards, Simplex.
Page 41 of 62
The detector has a flashing status indicating LEDs for visual supervision. When the device is in
normal condition, background supervision is indicated by a flashing green LED. The red LED flashes in
an alarm condition.
When the detector is actuated, the flashing LED will latch on steady and at full brilliance. The
detector may be reset by actuating the control panel. The detector head can be removed from its base
for cleaning, service, or replacement. Commonly used brand are Kidde Fenwall, Edwards, Simplex...
5.1.4 Break glass and manual call points
The breakage's call point is a device to enable personnel to raise the alarm, in the event of a fire,
by simply breaking a frangible element and thus activating the alarm system. Break glass call points
normally, should be located on exit routes and, in particular on the floor landings or staircases and at all
Page 42 of 62
exits to the open air. Location of break glass call points should be at a point where no person need
travel more than 30 meters from a y position within the premises to operate one.
Manual and automatic devices may be installed on the same system; however, it may be advisable
to install the manual call points on separate zones for speed of identification.
5.1.5 Manual Release Station
Manual release stations are located at major points of egress. The manual release station
provides a means of discharging the automatic fire extinguishing systems when used in conjunction
with the fire detection and suppression controller. The switch is specified as a dual action type to
prevent accidental operation and is to remain in the operated position until reset with a key.
Page 43 of 62
Upon entering an alarm mode, audible and visual indication are supplied via the controller to
both the DCS and local appliances in the form of a steady sounder and flashing light. Upon entering
the pre-discharge mode, the electronic sounder provides pulsed output. Upon system discharge, the
sounder provides a steady output and strobe light flashes rapidly. Both audible and visual alarms are
directly wired to the controller and fully supervised.
5.2.0 EXTINGUISHING SYSTEMS
The extinguishing system includes the following:
FM-200 container with valve, pressure switch, pressure gauge and FM-200 agent
Solenoid operated releasing device
Discharge nozzles
Page 44 of 62
FM 200 container
FM 200 agent is stored in the container as a liquid having natural vapor pressure of 66.4 psia at
77oF. The FM 200 discharge is activated by an output directly from the control panel which will
activate the solenoid in the releasing device. To aid release and distribution, the container is super
pressurized to 360 psig at 70oF with dry nitrogen.
FM-200 containers or storage cylinders are provided with safety rupture disc, pressure gauge,
low pressure switch and solenoid operated releasing device. A decrease in pressure will cause the
normally open contacts to close, indicating a trouble condition at the control panel.
FM-200 agent will be discharged through the operation of a solenoid operated device which releases the
agent through a differential pressure valves. The system discharge time is approximately 10 seconds in
accordance with NFPA Standard 2001.
Discharge nozzles are used to disperse the FM-200 agent. Discharge nozzle consists of orifice
and any associated horn, shield or baffle. The nozzles normally are of brass material with female
threads and come in two styles 1800 and 3600 dispersion patterns.
Page 45 of 62
Page 46 of 62
Page 47 of 62
The control panel has a common control board which provides common alarm and trouble
indications as well as alarm silence and reset switches. Major components in the control panel are the
following:
Network master control module or network controller
Secondary control module or slave controller
Power supply unit
Device interface card or intelligent loop controller card
Zone releasing module and Fire suppression control panel
System event and status printer
5.3.1 Network master control module
The network master control module contains the system database, coordinates all system
networking, printer reports and outputs, manual and override functions. The master control module
consists of motherboard with card slots, CPU card, serial communications card, front cover with
character display, common annunciation LEDs, common control switches, keypad for override control
and status reports. This common control board provides common alarm and trouble indications as well
as alarm silence and reset switches. Commonly used type of control panel is the Intelligent Response
Control (IRC) type.
Page 48 of 62
Page 49 of 62
5.3.3 Single line diagram for Secondary Controller at each protected area
Page 50 of 62
circuitry are integral part of the power supply. Battery standby power is on line so that batteries will
supply power system in the event of AC power loss without a power transfer relay. Batteries are sized
to provide a minimum 24 hours standby power and are supervised and provide a trouble signal upon
disconnect, open or shorted cell.
5.3.5 Intelligent loop controller
Device interface card or intelligent loop controller card (ZAS) is the intelligent interface
between signature series detectors and modules and controllers to form a fully digital, distributed
intelligent fire detection system. The loop controller card contains its own microprocessor used to
coordinate, process and interpret information received from and sent to signature devices. The card
provides LEDs that indicate trouble and alarm conditions, and data transmission.
5.3.6 Zone releasing module (ZRM) and Fire suppression control panel (FSCP)
The zone releasing module (ZRM) and fire suppression control panel (FSCP) are network
components for supervision and control of fire suppression system. The zone releasing module is
designed for use to release extinguishing agents. The ZRM utilizes network analog or traditional two
Page 51 of 62
wire smoke detectors located anywhere on the network to initiate the agent release sequence. Each
ZRM comes with two release solenoid circuits for connection to fire suppression equipment. The ZRM
has provision to hardwire Abort Switches, Manual Discharge Switches, Discharge Indicating
Appliances, first alarm and pre-discharge relays.
The FSCP Fire Suppression Control Panel is an optional remote user interface panel with the
ZRM Zone Release Module. The FSCP provides on board abort switch, manual release switch, digital
countdown timer, display timer, first alarm and pre-discharge relays. Discharge delay timing logic is
provided and the timer is field resettable from 0-60 seconds, in 10 second increments, by means of
switches to the exact time required in seconds. A key operated switch is provided to enable manual only
operation, even when an alarm is actively being processed.
5.37 Event and status printer
The event and status printer records system events and generates reports. Used on RS232, RS
485, fiber optic or 20 mA loop. The printer list the time, date, type and user defined message for each
event printed.
Page 52 of 62
Page 53 of 62
6.0.0 O PERATION
OF
F IRE D ETECTION
AND
S UPPRESSION S YSTEM
Normally, the system operates from an output voltage of 240 V AC, 50 Hz supplied to the
power charger module within the control panel. This voltage is transformed and rectified to 24 volt DC.
A 24 volt DC standby battery (minimum 8 hours) is provided in case of mains voltage failure. The
battery will automatically and instantaneously be switched into use as soon as the mains supply fails.
Battery is trickle charged during normal operations.
The space is protected by two or more combination heat and smoke detectors mounted on the
ceiling. During normal operation the FM-200 Clean Agent Halon Replacement total flooding system is
available to extinguish a fire which may occur in the protected area. This is signaled by a green light on
the Fire Suppression Panel and above each door of the protected area.
The system is normally initiated automatically upon activation of two or more of the fire detectors
installed within the enclosure by two out of three voting. This generates an alarm and closes the
ventilation dampers and releases the clean agent halon replacement, FM-200. A variable delay of at
least 20 seconds is incorporated into the release, which is proceeded by visual and audible alarms to
allow any personnel to evacuate the building before the agent is actually released.
The normal sequence of operation is as follows:
6.1.0 ACTUATION OF ANY ONE DETECTOR (PRE-ALARM CONDITION).
1. Steady alarm signal of the vibrating alarm bell
2. Annunciate to graphic annunciator panel to indicate location of detector in alarm
3. Annunciate to the monitoring equipment
4. Activate control functions such as for ventilation dampers, HVAC equipment shutdown
5. Shutdown all emergency generators from starting
6. Close all doors leading to the protected area.
6.2.0 ACTUATION OF A SECOND DETECTOR
1. The steady alarm bell silence and an electronic sounder will provide a pulsed signal
2. Annunciate to graphic annunciator panel to indicate location of detector in alarm
3. Actuate a time delay with illuminated display. Time delay shall delay release of the FM-200
agent. The FM-200 shall be released at the end of this time internal unless an abort switch is
operated. Upon release of the abort switch, the time delay cycle will resume unless the entire
system has been restored to normal by switching the reset switch on the FM-200 control
panel.
4. Actuation of any abort station will cause the audible signal to change, acknowledging proper
abort operation
Page 54 of 62
Page 55 of 62
Page 56 of 62
7.0.0 G UIDELINE
FOR
F UNCTIONAL
TESTING OF
For new installation, tests to be conducted shall demonstrate that the entire control system
functions as intended. All circuits shall be tested and shall include the following:
Automatic discharge
Manual discharge
Equipment shutdown
Alarm devices
Supervision of each circuit
For an active Fire Suppression Panel, normally a lockable maintenance override is provided.
This override inhibits the detection system and the FM-200 release to permit functional testing of the
system. In this override condition the visual evacuation alarm continues to be active and the status of
the system is indicated at the DCS operator station, Fire suppression panel and a status light above each
door of the enclosure.
For online testing purposes a supervised disconnect switch is provided to electrically isolate all
releasing devices from receiving a discharge signal. When the switch is in disconnected position it is
possible to simulate any alarm condition and observe proper operation of all detection and signaling
circuits without causing agent discharge.
Page 57 of 62
Page 58 of 62
9.0.0 F IRE
AND
G AS D ETECTION S YSTEM
Electrical centers or control rooms in the vicinity of potential large combustible vapor
releases
Inlets to ventilation and pressurization systems in classified areas and in the vicinity of
potentially large combustible vapor release
Around all potential hydrocarbon releases which could result in 40% LEL vapor cloud
within one minute of a release from a 1/4 orifice. At least four points of gas detection are
provided around the hazard
The location of the gas detectors takes into account the vapor density, wind rise analysis and the
potential for dead-air space.
9.2.0 GENERAL TYPES OF GAS DETECTORS
y
IR type detectors are used where immediate alarming without delay is required. They are
used at junction of all process areas and roads where vehicles may be exposed to hazardous
gas clouds.
Page 59 of 62
Alarm sirens and horns are provided for separate and distinctive alarming of fire or gas
detection.
The system is capable of generating six interchangeable alarm tones via tone generators and
explosion proof horns.
Alarm beacons are provided for a separate and distinctive alarming of fire or gas detection.
The beacons are illuminated on a block by block basis, with beacons located at block
boundaries at a maximum spacing of 100 m. The spacing has been reduced where adequate
line of sight cannot be maintained. Beacons are also provided on the exterior of each nonprocess building and inside high noise areas.
Three alarm tones are provided and are prioritized according to the nature of the emergency.
A higher priority tone shall override a tone of lower priority. The lower priority tone is
reactivated once a higher priority deactivated. The three alarm tones are MAJOR, MINOR
and ALL CLEAR.
Alarm tone will sound in all zones with AREA mode selected, while at ZONE mode
individual zone or combination of zones can be selected manually.
Page 60 of 62
Page 61 of 62
10.0.0 R EFERENCES
AND
A TTACHMENTS
References:
Fire Engineering, CIBSE Guide E
National Fire Protection Association NFPA 72E
GENT System 3400 Publications
Edwards Systems Technology IRC-3 Catalogue
Attachments:
1. System description and operating manual for GPP B Building Fire Detection and Alarm
System by Gent System 3400 Analogue Addressable Fire Alarm System
2. Fire Detection and Suppression System, IRC-3 Single Line Network Operations and
Troubleshooting Guide by Edwards System Technology Inc. (EST)
Page 62 of 62