Professional Documents
Culture Documents
Working Manual Complete Version 2014
Working Manual Complete Version 2014
Working Manual Complete Version 2014
For
JABATAN KESIHATAN NEGERI SARAWAK
ENERGY MANAGEMENT SYSTEM
Doc num: JKNSSEMS/WM 1
Revision num: 00
Page 2
Content
1. Operational guide
1.1 Objectives
1.2 Scope of guide
1.3 Standard and reference document
1.4 Normal working procedures to control energy consumption
Page
3
3
4
5
8
10
13
13
13
5. Revision Record
6. Lampiran
a. Memo Perlantikan Sebagai Ahli Jawatankuasa Tenaga (Energy
Committee)
b. Memo Polisi Tenaga Jabatan Kesihatan Negeri Sarawak
21
Revision num: 00
Page 3
Revision num: 00
Page 4
Revision num: 00
Page 5
Revision num: 00
Page 6
CHILLER RUN
YES
BREAKDOWN / TRIP /
EMERGENCY SHUTDOWN
/ ANY UNFAMILLIAR
VIBRATION OR SOUND
NO
12.45 PM CHILLER STOP (TOUCH
SCREEN ONLY) CHANGE THE
CHILLER SELECTOR TO 0
SEVERE
REFER TO
MANUFACTURER
ENGINEERING
ASSESS SEVERITY
OF PROBLEM
NOT SEVERE
AUTOMATIC CHILLER
STOP ON 4.30 PM.
AHU SHALL STOP AT
LEAST 15 MINUTES
AFTER CHILLER.
Revision num: 00
Page 7
Building Envelope
Install Replacement Windows
Install Window Sun Shades
Install/Increase Attic Insulation
Install Roof Insulation
Install Wall Insulation
Control Air Leakage
Space Cooling
Condenser water temperature reset
Chilled water temperature reset
Appication of Variable Speed Drive
Improve chiller efficiency through regular maintenance
More efficient fan/blower/ cooling tower
More efficient pump
Eliminate flow control valve and bypass control
Start stop control of pump
Impeller trimming
Lighting
Replace Incandescent Lighting with Compact Fluorescent Lamps in Dwelling Units
Replace Incandescent Lighting with Fluorescent Lighting in Common Areas
Replace Standard Fluorescent Lamps with Energy-Saving Lamps and Install Electronic Ballasts in
Common Areas
Install Lighting Controls in Common Areas
Convert Exterior Lighting Fixtures
Install Photo-Controls for Exterior Lighting
Revision num: 00
Page 9
Miscellaneous ECMs
Replace Older Refrigerators with High-Efficiency Units
Convert Water Supply Pumps
Install Checkmetering or Individual Metering
Install Water-Saving Toilets
Ref:
http://portal.hud.gov/hudportal/HUD?src=/program_offices/public_indian_housing/programs/ph/ph
ecc/strat_list
Zone Scheduling
Permits defined sections of a building to have HVAC and lighting reduced or shut down on a
schedule. Zone scheduling means that a whole building does not need to run at a 100% comfort
setting if on only a few occupants are in the facility.
Night/Unoccupied Setback
Changes the comfort settings (setpoints) of HVAC so that space temperature decreases in
winter and increases in summer, thereby reducing demand for heating and cooling during
unoccupied hours. This feature can also be done using a programmable thermostat, but with only a
few schedules and no flexibility to more aggressively change setback temperatures.
After-Hours Override
Allows temporary changes to comfort settings after-hours. This eliminates the need to modify
schedules, which can sometimes become permanent by accident. This also avoids having the entire
building run in occupied mode to meet the needs of a small group.
Occupancy Sensors
Detect motion or infrared signatures in the space, and trigger lights or HVAC accordingly. The BAS
also enables scheduled overrides or triggers based on card access to an area of the building.
Holiday Scheduling
A calendar defines HVAC and lighting control for an entire calendar year, saving staff time
implementing special schedules and ensuring holiday weekdays do not run in occupied mode
Chiller Optimization
The chilled water loop temperature can be raised as the cooling requirements for the building are
reduced, increasing chiller efficiency. A technique known as load reset raises the chilled water
temperature setpoint until one of the chilled water valves is 100% open.
Cooling Tower Optimization
The condenser water supply to the chiller can be decreased to a minimum setpoint, as defined by
the manufacturer. Then an optimal water supply setpoint can be calculated using a combination of
the outside air wet-bulb temperature and the cooling tower approach temperature. The reduced
water temperature improves the chillers partial load efficiency and also optimizes the cooling
towers operation.
Hot Water Reset
Hot water system temperatures can be reset based on outside air temperature, decreasing heat
losses in supply piping. This saves energy and also makes the office space more comfortable because
it reduces localized heating caused by excessively hot pipes.
Ref:
http://www.schneiderelectric.com.my/documents/buildings/office_building_energy_efficiency.pdf
Revision num: 00
Page 13
Revision num: 00
Page 14
Power (socket)
Lighting
100
Powering appliances
and compliance to
item 1.4 .4
Lighting set to right
brightness and
compliance to item
1.4.1
Revision num: 00
Page 15
EAC: EAC 4
Baseline EEI :
Sub EEI :
No Energy Input
kWh
%
1
kWh/working days
Process Detail
Diagram
Chiller
Output
Cold water
Operating hours
100
Revision num: 00
Page 16
100
kWh/working days
Process Detail
Diagram
Common area
lighting
Output
Lighting set to right
brightness and
compliance to item
1.4
Process or
Machine/Equipment
Cooling-AHU/CWFCU/ACSU
Lighting
Control
Value
24-26C
300 lux
Inspection
Frequency
Monthly
Monthly
Monthly
Inspector
EAC 1
EAC 1
EAC 1
Inspection
Items
Refer 1.4 .2
Refer 1.4 .1
Refer 1.4 .4
Ir Imran
Engr Asmee
Engr Lailatul
spot-checks
EAC 2
EAC 2
EAC 2
Refer 1.4 .2
Refer 1.4 .1
Refer 1.4 .4
24-26C
300 lux
Monthly
Monthly
Monthly
Engr Khairul
Engr Azhar
A.Engr Sani
spot-checks
Refer 1.4 .2
Refer 1.4 .1
Refer 1.4 .4
24-26C
300 lux
EAC 3
EAC 3
EAC 3
Monthly
Monthly
Monthly
Engr Yusuf
A.Engr Zulhairi
Engr James
spot-checks
Cooling -Chiller
Lighting
Lift
EAC 4
EAC 5
EAC 2
Refer 1.4 .2
Refer 1.4 .1
Refer 1.4.3
4-6 C
300 lux
Monthly
Monthly
Monthly
Engr Khairrul
A.Engr Zulhairi
Engr Yusuf
spot-checks
Cooling-AHU/CWFCU/ACSU
Lighting
Power for electrical appliances
Cooling-AHU/CWFCU/ACSU
Lighting
Location
Revision num: 00
Page 17
Recommendation Remark
Revision num: 00
Page 18
ref:
EAC:
Item
Process
Machine/Equipment
Inspection Items
Inspector: .
Control
Value
Inspection
Date
Normal
X
Abnormal
Problem
Correction
Remark
Revision num: 00
Page 19
ref:
LS/JKNS/EAC
2/2014
Imran
Inspector: .
Process
Machine/Equipment
Example:
AHU BII/G1
AHU BII/G2
AHU BII/F1
4
5
6
7
8
9
10
11
AHU BII/F2
AHU BII/S1
AHU BII/S2
AHU BII/S3
AHU BII/T1
AHU BII/T2
Lighting BII/G
Lighting BII/F
Inspection Items
Control
Value
Inspection
Date
Normal
24-26C
24-26C
24-26C
9/4/2014
9/4/2014
9/4/2014
24-26C
24-26C
24-26C
24-26C
24-26C
24-26C
300 lux
300 lux
9/4/2014
9/4/2014
9/4/2014
9/4/2014
9/4/2014
9/4/2014
9/4/2014
9/4/2014
X
Abnormal
20C
Problem
Correction
nil
nil
overcooling
nil
nil
Thermostat
damage
nil
nil
nil
nil
nil
nil
nil
nil
nil
nil
nil
nil
nil
nil
nil
nil
Remark
Further Inspection
and repair by
others
Revision num: 00
Page 20
12
Lighting BII/S
300 lux
9/4/2014
900
13
Lighting BII/T
300 lux
9/4/2014
700
14
9/4/2014
Curtain
completely
closed with all
lamps switch on
Curtain
completely
closed with all
lamps switch on
Photocopier not
on save mode
lamps partially
switched on
and slide open
curtain
lamps partially
switched on
and slide open
curtain
Set to save
mode/off
Revision No
Page
Revision num: 00
Page 21
Detail
Revision Record
Effective Date
Note
LAMPIRAN