Proposed Cooling Loads.

mit
03/Mar/2014
Contents: Project Summary System Comfort
Model Calc. data Weather

Loads

Energy Carbon Occupied Full day Peak hourly room

Project summary
Model data:
Project file
Building floor area1
Total volume
Building

Calculation data:
Results file
Calculated
Calc. Period:
Weather:
Climate file
#

run1

Total Heatin Coolin Fans/P Lights Equip.


g
g
umps

352

233

178

74

162

Proposed Cooling Loads.mit


42882.24 ft2
704695.13 ft3

"d:\..\princetel proposed1.aps"
03/Mar/2014 on 16:39
01/Jan - 31/Dec

PhiladelphiaTMY2.fwt

Note: The results in this report are generated by


the IES ApacheSim module. ApacheSim is a
rigorous building thermal simulation approach
that conforms to ANSI/ASHRAE Standard 140. If
you wish to know more about ApacheSim and
obtain a copy of the ANSI/ASHRAE 140 standard
report select the following link (will open new
window) www.iesve.com/apachesim
1. 'Building floor area' is the total area of all
rooms for which 'Include in building floor area' is
ticked in 'Room Data' (used for loads metrics in
this report)

History

Building systems energy


Month
A-Z

Summary

Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
Total

Heating
Cooling
Fans, pumps
(boilers etc.) (chillers etc.) and controls
Hi/Lo
Hi/Lo
Hi/Lo

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.5
0.6
4.6
20.6
72.9
137.2
192.7
174.8
127.7
47.2
21.8
0.9
801.7

Copyright 2009 Integrated Environmental Solutions Limited All rights reserved

27.2
25.3
29.9
34.5
52.6
75.3
95.7
88.5
72.0
43.6
34.9
28.6
608.1

Lights

Equip.

MBtu

Hi/Lo

Hi/Lo

22.0
19.8
21.9
20.6
19.8
20.1
20.4
20.4
20.6
20.7
21.7
23.6
251.9

45.5
42.4
48.1
46.2
45.5
46.2
47.0
46.6
46.2
45.5
46.2
48.1
553.7

The maximum value in each


column is highlighted in red.
The minimum value in each
column is highlighted in blue.
More than one value
may be highlighted
Total Yearly Energy
Consumption = 1,209.7MBtu
Total Yearly Energy
Consumption per Floor Area =
28.2kBTU/ft2

Carbon Dioxide
Month

Summary

Lights

Equip.

lbCO2

A-Z

System
(boilers, chillers,
fans,pumps)
Hi/Lo

Hi/Lo

Hi/Lo

Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
Total

-7,634.7
-13,759.7
-22,049.9
-22,291.9
-9,196.9
12,692.8
32,702.5
28,862.7
21,993.3
-747.4
-743.8
-4,515.2
15,311.9

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

The maximum value in each


column is highlighted in red.
The minimum value in each
column is highlighted in blue.
More than one value
may be highlighted

Copyright 2009 Integrated Environmental Solutions Limited All rights reserved

Total carbon dioxide


emissions = 15,311.9lbCO2

Comfort - Occupied
Temp
Room Name
A-Z

Relative
Humidity

Max
F

Min
F

Max
%

Min
%

Max
%

Min
%

Hi/Lo

Hi/Lo

Hi/Lo

Hi/Lo

Hi/Lo

Hi/Lo

4.8
4.7
4.6
4.8
4.7
4.8
4.6
4.8
4.8
4.8
4.8
4.8
4.7
4.6
4.6
4.7
4.7
4.7
4.7
5.1
5.1
5.1
4.7
4.9
4.9

15
8.6
8.6
8.6
7.2
8.6
7.8
8.6
7.2
8.6
6.9
7.2
8.1
8.7
8.6
8.6
8.6
8.1
8.6
8.6
8.2
8.0
8.0
8.6
8.6
8.5

Apply

Occupied

01-VESTIBULE
04-CONFERENCE
05-BARRY'S OFFICE
06-MENS TOILET
07-OPEN PLAN OFFICE
09-WOMENS TOILET
11-LUNCH ROOM
12-WOMENS BATHROOM
13-STOCK ROOM
15-MENS BATHROOM
16-INSPECTION
17-KITCHEN
18-NETWORK
19-LAB
20-PRODUCTION
21 22-RECEIVING MACHINE SHOP
23-ELECTRICAL ROOM
24-PRODUCTION 2
25-RECEIVING
26-WOMENS TOILET
27-MENS TOILET
28-COMPRESSOR ROOM
29-MACHINE SHOP
31-MEZZ 1
32-MEZZ 2

PPD

73.2
73.2
73.1
72.5
73.0
72.8
73.0
72.4
73.1
72.2
72.4
73.0
73.2
73.1
72.7
73.0
73.0
73.0
73.1
73.2
73.0
73.0
73.0
73.0
73.2

70.1
70.2
67.4
70.4
69.8
70.3
69.9
70.3
70.3
70.4
70.4
70.3
70.2
69.9
69.6
70.0
70.2
70.0
70.1
70.3
70.3
70.2
69.6
69.8
70.3

Copyright 2009 Integrated Environmental Solutions Limited All rights reserved

51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7
51.7

5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

PPD is the percentage of people


that will
find the room thermally
uncomfortable
Please alter the PPD max limit
value to
highlight rooms that are more
thermally uncomfortable
(US Only)ASHRAE 55 states
comfort
lies between 5 and 10% PPD

Comfort - Full Day


Temp
om Name
A-Z

Relative Humidity

Min
F

Max
%

Min
%

Max
%

Min
%

Hi/Lo

Hi/Lo

Hi/Lo

Hi/Lo

Hi/Lo

Hi/Lo

5.0
5.0

73.2
73.2

70.1
70.2

51.7
51.7

4.1
4.0

50
8.6
8.6

73.1

67.4

51.7

4.0

8.6

5.0

72.5

70.3

51.7

4.2

7.2

5.0

73.0

69.5

51.7

4.0

8.6

5.0

72.8

70.3

51.7

4.2

7.8

5.0

73.1

69.8

51.7

3.9

8.6

5.0

72.4

70.2

51.7

4.1

7.2

5.0

73.1

70.1

51.7

4.1

8.6

5.0

72.2

70.3

51.7

4.2

6.9

5.0

72.4
73.0
73.2
73.1
72.7

70.2
70.2
70.1
69.9
69.5

51.7
51.7
51.7
51.7
51.7

4.1
4.1
4.0
4.0
4.0

7.2
8.1
8.7
8.6
8.6

5.0
5.0
5.0
5.0
5.0

73.0

70.0

51.7

4.0

8.6

5.0

73.0

70.2

51.7

4.1

8.1

5.0

73.0
73.1

69.8
70.0

51.7
51.7

4.0
4.0

8.6
8.6

5.0
5.0

73.2

70.0

51.7

3.9

8.2

5.0

73.0

70.0

51.7

3.9

8.0

5.0

73.0

70.0

51.7

3.8

8.0

5.0

73.0
73.0
73.2

69.3
69.7
70.0

51.7
51.7
51.7

3.9
3.8
4.0

8.6
8.6
8.5

5.0
5.0
5.0

Apply

Full Day

01-VESTIBULE
04-CONFERENCE
05-BARRY'S
OFFICE
06-MENS TOILET
07-OPEN PLAN
OFFICE
09-WOMENS
TOILET
11-LUNCH ROOM
12-WOMENS
BATHROOM
13-STOCK ROOM
15-MENS
BATHROOM
16-INSPECTION
17-KITCHEN
18-NETWORK
19-LAB
20-PRODUCTION
21 22-RECEIVING
MACHINE SHOP
23-ELECTRICAL
ROOM
24-PRODUCTION 2
25-RECEIVING
26-WOMENS
TOILET
27-MENS TOILET
28-COMPRESSOR
ROOM
29-MACHINE SHOP
31-MEZZ 1
32-MEZZ 2

PPD

Max
F

Copyright 2009 Integrated Environmental Solutions Limited All rights reserved

PPD is the percentage of people


that will
find the room thermally
uncomfortable
Please alter the PPD max limit
value to
highlight rooms that are more
thermally uncomfortable
(US Only)ASHRAE 55 states
comfort
lies between 5 and 10% PPD

Peak Hourly Room Loads


Peak Room Conditioning Loads (Btu/h)
Room Name
A-Z

Sensible
Heating

Sensible
Cooling

Humidification

Dehumidification

Hi/Lo

Hi/Lo

Hi/Lo

Hi/Lo

Internal Gains
(Btu/h)

(Btu/hft2)

(cfm/ft2)

Hi/Lo

Hi/Lo

Hi/Lo

1.02

6784

11261

755

1956

6606

30
15.90

3135

3247

234

592

1813

14.78

0.95

3322

11206

176

469

1317

67.79

4.36

503

571

93

233

597

6.53

0.42

18950

46649

1758

4426

12335

28.25

1.82

468

525

84

210

541

6.63

0.43

8567

16987

552

1401

2767

32.72

2.11

1257

1449

237

594

1550

6.52

0.42

2681

4144

522

1270

4397

8.45

0.54

Apply

Peak Loads

01-VESTIBULE
04CONFERENCE
05-BARRY'S
OFFICE
06-MENS
TOILET
07-OPEN PLAN
OFFICE
09-WOMENS
TOILET
11-LUNCH
ROOM
12-WOMENS
BATHROOM
13-STOCK
ROOM
15-MENS
BATHROOM
16-INSPECTION
17-KITCHEN
18-NETWORK
19-LAB
20PRODUCTION
21 22RECEIVING
MACHINE SHOP
23-ELECTRICAL
ROOM
24PRODUCTION 2
25-RECEIVING
26-WOMENS
TOILET
27-MENS
TOILET
28COMPRESSOR
ROOM
29-MACHINE
SHOP
31-MEZZ 1
32-MEZZ 2

*Cooling Checks

753

845

140

351

863

6.44

0.41

1144
1041
2520
5791

1325
1209
3673
12970

217
192
156
467

545
478
397
1279

1506
1388
1369
3311

6.51
6.69
25.02
29.54

0.42
0.43
1.61
1.90

118116

183560

16290

42457

97161

12.00

0.77

14672

15110

1827

4602

11471

8.81

0.57

3140

1833

292

729

1937

6.68

0.43

66066

100398

10363

26619

76422

9.74

0.63

16860

20753

2255

5679

16719

10.26

0.66

246

693

62

207

1012

6.73

0.43

266

761

68

228

1118

6.70

0.43

620

1014

91

301

1177

6.67

0.43

52971

114181

5495

13989

40916

21.88

1.41

11257
3455

23228
5438

1328
554

3946
1438

16016
5427

12.75
8.94

0.82
0.58

Copyright 2009 Integrated Environmental Solutions Limited All rights reserved

Recommended strategies to
reduce the loads on these rooms
are:
- reorient the building
- move rooms with high internal
gain to avoid solar penetration
- increase u-values of
constructions
- improve solar performance of
the glazing