7-DAY RF THERMOSTAT
Installation warning:
This programmer can be used either as a
central heating ON/OFF thermostat and
as boiler remote control (only with
selected Beretta boilers), therefore is
mandatory to determinate the correct
working mode (denominated TYPE)
before installation and setting.
Type
crt
rEc
crS
Description
Room thermostat working with
ON/OFF command to the boiler.
Connect the 2 right wires (highlighted
with T.A.) to room thermostat
connection on the boiler. Maximum
switching load of 2A at 30VDC or
0,25A at 230VAC.
Boiler remote control using a bus
protocol to communicate with the
boiler. Connect the 2 right wires
(highlighted with OT+.) to remote
control connection on the boiler.
To be used only when boiler is set in
a continuous pump running mode.
Room thermostat working with
ON/OFF command to the boiler.
Connect the 2 right wires (highlighted
with T.A.) to room thermostat
connection on the boiler. Maximum
switching load of 2A at 30VDC or
0,25A at 230VAC.
Programming
button
Fast room
temperature
adjusting
buttons
Fast DHW
adjusting
buttons
(rEc only)
Heating
mode button
Adjusting
buttons
Display
Heating
mode button
Temperature
sensor
Battery flap
INSTALLATION OF TRANSMITTER
Before installing the transmitter check the
encoding functionality while the receiver
and the transmitter are still very near. The
encoding between the transmitter and the
receiver is already factory set therefore
12
OPERATING INSTRUCTIONS
The programmer is factory set as room
thermostat type (crt). Most of the
parameters are already set, at the start
up it is necessary to set the time and the
day (please note no summer time is precharged inside therefore if during the year
there is time modification it must be
adjusted).
The following operation must done at
start up
END USER MENU (MAIN MENU)
Enter inside the end user menu pressing
the
button once. Use the
button
to escape at any time. Scroll inside the
end user menu pressing any of the
triangle buttons and press again the
button to enter inside the single setting,
14
icon
Description
Factory set
T1 = 21C
T2 = 16C
Unset
Unset
Unset
15
Use the
and
to switch between
the values (see the table at page 2 for
details).
PL Enter inside the technical menu.
16
with the
Battery low
When the controller feels that the battery
CLIMATIC CURVES
Below the climatic curves of the
programmer. Curves from 0,2 to 0,8 are
used when the boiler is set for low
temperature (i.e. floor heating).
Curves from 1 to 3 are used when the
boiler is used for high temperature (i.e.
radiator heating),
Selection of the climatic curve can be
made inside the technical menu only.
The climatic curve function is active only
if an external sensor if fitted to the boiler.
If there is not external sensor fitted, the
programmer make an automatically
regulation using the room sensor.
18
External temperature
The
icon means that there is a heat
request from the room to the boiler. The
boiler will switch ON.
The
central heating symbol and bar
is a proportional indication of the set-point
of the desired temperature in the room.
Each bar represents to 2C. They will
disappear when the central heating is
turned OFF.
The
icon means that the device is set
as a wireless device, and that the
communication is effective
19
The
temperature
display
indicates
the
actual
temperature
measured inside the room
The
day icon and the night icon
indicate whether the current set point for
the current time is night or day.
The
time display indicates the
actual time
The
day icon indicates the
actual day of the week
The
party icon is lit up when the
party mode is selected. In this mode the
central heating fascia bar will be
completely lit up at T1 together with the
day icon. After midnight, the display will
turn back to the pre-set working fascia.
The
central heating fascia bar is a
permanent display of the functioning
fascia set for the central heating set point
setting. If a bar is completely blank, the
set-point is the anti-frost level (central
heating OFF). If only the lower part of a
bar is black, the set point is the economy
(T2). If the whole bar is black, the set
point is the comfort (T1). They will
disappear when the central heating is
turned OFF.
The
holiday icon is lit up when the
holiday mode is selected. In this mode
the central heating fascia bar will be lit up
at T2 together with the night icon. After
the holiday counter is over, the display
will turn back to the pre-set working
fascia.
20
When the
icon appears, the controller
is working as to keep the anti-frost
temperature.
The
icon means that the device is set
as a wireless device, and that the
communication is effective
The
icon means that there is a heat
request from the room to the boiler. The
boiler is ON with flame present.
The
central heating symbol and bar
is a proportional indication of the set-point
of the desired temperature in the room.
Each bar represents to 2C.They will
disappear when the central heating is
turned OFF. In case of external sensor
fitted, the bar is moved up and down
according the room comfort level chosen.
21
The
temperature
display
indicates
the
actual
temperature
measured inside the room
The
house icon around the
temperature display, indicates that the
controller is set as a Remote Control
(rEc) and appears only in this mode of
functioning.
The
day icon and the night icon
indicate whether the current set point for
the current time is night or day.
The
display on the right side of the
house indicates the external temperature
reading, and it appears only when the
outdoor sensor is correctly connected.
The
domestic hot water symbol and
bar is a proportional indication of the setpoint of the desired temperature when the
boiler works in domestic hot water mode.
Each bar represents 1C.
The
central heating fascia bar is a
permanent display of the functioning
22
The
party icon is lit up when the
party mode is selected. In this mode the
central heating fascia bar will be
completely lit up at T1 together with the
day icon. After midnight, the display will
turn back to the pre-set working
fascia.The
holiday icon is lit up when
the holiday mode is selected. In this
mode the central heating fascia bar will
be lit up at T2 together with the night icon.
After the holiday counter is over, the
display will turn back to the pre-set
working fascia.
When the
icon appears, the controller
is working as to keep the anti-frost
temperature.
TECHNICAL MENU
The device has the possibility to set a
series of parameters to better adapt the
23
Par.
Ref.
Descr.
Factory
set value
Type
Operation
Display shows the wireless channel and the address. Use
the
01
Encoding
procedure
codified
Type
rEc
and crt
08
Max set
point
heating
85C
(30C
85C)
Type
rEc
only
Use the
button to decrease and the
button to
increase the temperature value. The value is automatically
memorized when moving to the next parameter. This
parameter put a high limit on the maximum temperature
value communicated to the boiler.
09
Min set
point
heating
30C
(30C
85C)
Type
rEc
only
Use the
button to decrease and the
button to
increase the temperature value. The value is automatically
memorized when moving to the next parameter. This
parameter put a low limit on the minimum temperature
value communicated to the boiler.
24
Par.
Ref.
Descr.
10
Climatic
curve
selection
11
Influence
of
temperatur
e sensor
Factory
set value
1.2
(see
climatic
curves)
Type
Operation
Type
rEc
only
Use the
button to decrease and the
button to
increase the climatic curve value (see below the climatic
curves). The value is automatically memorized when
moving to the next parameter.
10
(020)
Type
rEc
only
Use the
button to decrease and the
button to
increase the influence of room sensor on the calculation of
the boiler flow temperature. 10 is the standard, higher
values is good for pour insulation houses. The value is
automatically memorized when moving to the next
parameter.
13
Calibration
of the
room
sensor
Actual
Type
rEc
and crt
Use the
button to decrease and the
button to
increase the reference room temperature. Use this
parameter in case of not proper installation of the device.
The value is automatically memorized when moving to the
next parameter.
14
Programm
er reset
Type
rEc
and crt
Use the
25
Par.
Ref.
Descr.
Factory
set value
Type
Operation
Actual
Type
rEc
and crt
Type
rEc
and crt
16
Software
release
17
Choice
C or F
18
Hysteresis
OFF
0.1C
(0.02.0)
Type
rEc
and crt
Use the
button to decrease and the
button to
increase the hysteresis OFF of the device. The value is
automatically memorized when moving to the next
parameter
19
Hysteresis
ON
0.5C
(0.02.0)
Type
rEc
and crt
Use the
button to decrease and the
button to
increase the hysteresis ON of the device. The value is
automatically memorized when moving to the next
parameter
20
Frost
protection
temp.
5C
(3C
10C)
Type
rEc
and crt
Use the
button to decrease and the
button to
increase the frost protection temperature limit. The value is
automatically memorized when moving to the next par.
26
Par.
Ref.
Descr.
Factory
set value
21
Alarms
history
Actual
22
Boiler TSP
reading
Actual
23
AntiLegionella
function
OFF
24
Clock on
DHW
OFF
Type
Type
rEc
only
Type
rEc
only
Type
rEc
only
Type
rEc
only
Operation
Use the
and the
button to scroll last 9 alarms code
memorized on the device.
Unused
Use the
and the
button to switch ON or OFF the
legionella function (function active only with boiler
connected to a tank with sensor control).
Use the
and the
button to switch ON or OFF the
programming time on the DHW production via a tank with
sensor. (function active only with boiler connected to a
tank with sensor control). If selected ON, on the end user
menu will appear a dedicated programming fascia to be
set (programmable daily fascia only)
27
TRANSMITTER
Linked with receiver via RF: frequency
868 MHz
Power rating: 2 x 1,5AA - Alkaline
batteries
TECHNICAL SPECIFICATIONS
LIMIT OF SETTING OF THE TEMPERATURES:
Anti-frost temperature: 3C 10C
T2: anti-frost temperature 35C
T1: T2 35C
DHW (if applicable): 37C 60C
Room temperature: 5C 30C
READING LIMITS
Outdoor sensor: -10C 40C
Room sensor: -10C 40C
RECEIVER
Linked with transmitter via RF:
frequency 868 MHz
Power rating: 230 VAC 10%, 50 Hz
T.A. Switching capacity (crt only):
Min 1mA,
Max 2A at 30 VDC
Max 0,25A at 230 VAC
OT+ contact: for bus protocol only.
Never supply with 230V this contact.