2 Port Solenoid Valve

For Dust Collector

Series VXF
2 port solenoid valve for dust collector
Series VXF

VX2

Working principle (VXFA)


In this L-shaped 2 port valve, the bag filter is cleaned by high speed air jet and shock
Fluid from the IN side goes through the
wave to materialize high speed response and control of instantaneous large flow rate. De-energized
supply orifice and fills the pressure action

VXZ

VXD

chamber. The main valve is kept closed


by the force pushing down the valve and
the reaction force of the valve spring.
The supply port to the pressure
action chamber is installed in the
body and the diaphragm free from
stress concentration has a long life
span.

VXP

Valve spring
Pressure action
chamber

The pressure action


chamber capacity is
reduced.
High speed main valve
opening & closing/min.
pulse 50 ms

VXE

Supply orifice

VXR
VXH

Right after energized

VXF
Armature

When power is supplied to the solenoid


valve, the armature begins to be retracted,
and the pilot orifice opens. The fluid filled
in the pressure action chamber flows
through the pilot orifice to the OUT side.

VX3
VXA

Pressure action chamber

VCH

The main valve made of polyacetal


is free from sticking and strong
against produced shock waves.

Model
2150
VXF
2160
VXFA
2280

Port size
34

1
11 2

Energized

VDW
Since the bleeding lowers the pressure inside
the pressure action chamber, the valve pressing-down force becomes weaker than the valve
pressing-up force and the valve is opened.

Cv
9.5
18
45

VQ
LVM

Pressure action chamber

VCA
VCB

Controller dedicated for operation


Series VXFC

2 port solenoid valve for


dust collector (VXF)
Blow tube Nozzle

Dedicated
controller

VCL

Clean air outlet

VCS

Bag filter

VCW

Dust exhaust port

0.01 0.99

Two-time hitting can be set to improve the sweeping effect by


the bag filter. Two-time hitting is available by turning ON the
DIP SW (one-time by turning OFF).

O
F
F

OUT1 OUT2 IN1 IN2


8

SW2
2

0 0 0

OFF

0 0

456

78

901

SW1

ON
SW8

O
F
F

Dust including
air inlet
23

The valve controller turns ON/OFF


many valves for the dust controller.
Power voltage: 100 VAC to 220 VAC
24 VDC, 12 VDC
Output points: 6 points, 10 points
 Two-time hitting function

sec

0 299

sec

LED LED
11
12
OUT CAS

LED LED
13
14
IN POW

140

LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10

 Connection of multiple circuit boards is possible

Number of output points can be increased (16/20/26/30 points)


by connecting boards.

ON

 Wide ranging time setting

1A

ON-time (output to the valve): 0.01 to 0.99 sec.


OFF-time (adjournment to next output): 0 to 299 sec.

 Interrupt operation function


Interrupting an operation from an external switch is possible
using input signals.

OFF

SV2
SV1

SV4
SV3

SV6
SV5

SV8
SV7

SV10
SV9

COM

AC1 AC2 FG

5
140

4 x 4.5

169

Series VXF
How to Order
Solenoid type
Normally closed

VXF 2150

06

Air operated type

VXFA 2150

06

1 G

Option
Standard
S
With silencer
Refer to the table (2) below for availability.
Nil

Table (2) Option/Silencer


Model Noise reduction Effective area
2504-002 19 dB or more
33.9 mm
2

Electrical option
Nil

Model Port size


2150
2160
2280

06
10
14

S
L

Rc 3/4
Rc 1
Rc 1 1 2

Refer to the table (1) given below for availability.

Rated voltage
1
2
3
4
5
6
7
8
9

None
With surge voltage suppressor
With indicator light
With light/
surge voltage suppressor

Electrical entry

100 VAC 50/60 Hz


200 VAC 50/60 Hz
110 VAC 50/60 Hz
220 VAC 50/60 Hz
24 VDC
12 VDC
240 VAC 50/60 Hz
48 VAC 50/60 Hz
Other (Contact us for inquiry)
Refer to the table (1) given
below for availability.
Refer to page 173 for ordering coil only.

G
Grommet
C
Conduit
D
DIN terminal
T
Conduit terminal
Refer to the table (1) given below for availability.

Caution
Table (1)
Rated Voltage-Electrical Entry-Electrical Option
Insulation type
Class B
Electrical entry
G
C
D, T
S
L, Z

Electrical option
S Note)
1 (100 V)

2 (200 V)

3 (110 V)

AC
4 (220 V)

7 (240 V)

8 (48 V)

5 (24 V)

DC

6 (12 V)

Note) Surge voltage suppressor is attached in the middle of a lead wire.

170

Selection
When selecting the air operated type VXFA, select 2 port solenoid
valves (with orifice dia. of 3 or more and effective area of 6 mm2 or
more) in order to maintain the pilot valve performance.

2 Port Solenoid Valve for Dust Collector

Series VXF

Model/Valve Specifications
Port Orifice
dia.
size (mm)

20

34

27

Solenoid type
40

11 2

Model

Min.
Flow
Max. operating pressure
operating
Ambient
Fluid
characteristics Withstand
differential (MPa)
pressure
pressure temperature temperature
Air
differential Solenoid
Air
(MPa)
(C) Note 1)
(C)
operated
2
(MPa)
valve
valve Effective area (mm )

AC 1.0

VXF2150
VXFA2150

1.0

0.03

170

2.0

10
to 60

DC 0.7
AC 1.0

VXF2160
VXFA2160

0.03

VXF2280
VXFA2280

0.03

1.0

330

2.0

10
to 60

1.0

810

2.0

10
to 60

DC 0.7
AC 1.0
DC 0.7

Mass
(g)

AC 5to 60 VXF
2150 530
VXFA
DC 5to 40 2150 350
VXF
AC 5to 60 2160 580
VXFA
DC 5to 40 2160 400
VXF
AC 5to 60 2280 1500
VXFA
DC 5to 40 2280 1300

Note 1) Dew point shall be 10C or less. No condensation allowed.

Model

VXF
2150
VXF
2160
VXF
2280

Power Frequency
(Hz)
source
AC
DC
AC
DC
AC
DC

50
60

50
60

50
60

VXD
VXZ
VXE
VXP
VXR

Solenoid Specifications
Air operated type

VX2

Apparent
power (VA)

Pilot exhaust
Power
Temperature
Voltage
noise (dB)
consumptions
rise (C)
fluctuation
(W)
(Rated
Without With
(%)
Inrush Holding
(Holding)
voltage)
silencer silencer
45
Rated
20
11
4.5
value
35
104
83
10

55
6
45
Rated
20
11
4.5
value
35
105
85
10

55
6
60
Rated
40
18
7.5
value
50
108
85
10

8
60

VXH
VXF
VX3
VXA
VCH
VDW
VQ
LVM
VCA
VCB
VCL
VCS
VCW

171

Series VXF
Model Selection (In the case of using as a bag filter)
Model selection
The deterrioration of VXF/VXFA properties due to the tube length from data B (response time/idle time) and data C (start-up speed), can be measured.
Refer to this data to set energization time. Use data A (flow rate characteristics) to calculate the flow rate for each loading time separately in relation to the
nozzle dia./qty., pressure, and tube. The data does not correspond to the actual bag filter operation. (In the data: Without tube and Tube length = VXF)

How to calculate

How to read the data

Pilot valve
(I.D. 6, 10)

How to calculate
Provide the pressure from the air resource to the air
tank. Close the stop valve, set the nozzle dia. and
qty., and then energize the solenoid valve as well as
the pilot valve of the air operation valve in accordance
with the prescription. (Change the tube length.)

Stop valve

Energization
time
Electric signal
Air tank inside pressure PA
Ultimate pressure

Air
tank

Nozzle
Amplifier

Data (B) Response Time/Idle Time

VXF2150/VXFA2150

Tank 20l
Pressure 0.7 MPa
MP
6 x 6 pcs.
PM: Raised up to 0.41 MPa
MP

6 x 10 pcs.

6 x 10 pcs.

Tube
2,000
mm

66 x 8 pcs.
pcs
6 x 6 pcs.

VXF2160
VXFA2160
Tank 41l
6 x 10 pcs.
Pressure 0.7 MPa
MP
PM: Raised up to 0.43 MPa
MP

VXF2280
VXFA2280
Tank 70l
Pressure
0.7 MPa
10 x 8 pcs.

500 mm

6 x 6 pcs.
Without tube
(VXF2150)

A=0.5 MPa
MP
PA=0.5
6 x 6 pcs.

Time T1, T2 (ms)

Flow rate Q (Nl)

VXF2150
VXFA2150

Air tank 20l


PA=0.7 MPa
6 x 6 pcs.

Air tank 41l


PA=0.7 MPa

6 x 8 pcs.

Start-up time

Idle time T1
Response time T2

Solenoid oscillograph

Data (A) Flow Characteristics


Air tank 20l
A=0.7 MPa
MP
PA=0.7

Nozzle inside pressure

PM x 0.9

I.D. x qty.

PM: Raised up
to 0.48 MPa

T2 (Response time)
Energization time T (ms)
T1 (Idle time)

VXF2160/VXFA2160
Air tank 70l
A=0.7 MPa
MP
PA=0.7

Air tank 41l


A=0.7 MPa
MP
PA=0.7

Tube length L (mm)

How to read the graph

6 x 10 pcs.
66 x 14 pcs.
pcs

The longer the tube length, the longer the response time and wasted time. If
longer than the length in the diagram, the valve might not open due to the tube
resistance.

6 x 12 pcs.

66 x 12 pcs.
pcs

500 mm

Data (C) Start-up Speed

2,000
mm
Without tube
(VXF2160)

6 x 10 pcs.
A=0.5 MPa
MP
PA=0.5
6 x 10 pcs.

Energization time T (ms)

VXF2280/VXFA2280
Air tank 70l
A=0.7 MPa
MP
PA=0.7

Air tank 70l


A=0.7 MPa
MP
PA=0.7

Air tank 70l


A=0.7 MPa
MP
PA=0.7
10 x 8 pcs.

Flow rate Q (Nl)

10 x 12 pcs.
10
10 x 12 pcs.
pcs

10 x 10 pcs.
10
10 x 8 pcs.
pcs

10
10 x 8 pcs.
pcs
10
10 x 10 pcs.
pcs

Without tube
(VXF2280)

VXF(A)2150
Tank 20l
6 x 6 pcs.

VXF(A)2160
Tank 41l
10pcs.
pcs.
6 x 6

VXF(A)2280
Tank 70l
10 x 8 pcs.

100 mm
Tube length L (mm)
500 mm

A=0.5 MPa
MP
PA=0.5
10 x 8 pcs.
Energization time T (ms)

How to read the graph


Even if the energizing time is constant, a greater amount of air flows when the PA
is at 0.7 MPa than at 0.5 MPa. Moreover, the greater the air tank capacity, the
greater the amount of airflow. Furthermore, the greater the nozzle's total cross
sectional area, the greater the amount of airflow. While the flow volume changes
according to the length of the tube, be aware that a wasted flow volume is
involved during a return.

172

Inlet pressure: 0.7 MPa


MP

Start-up speed (MPa/ms)

Flow rate Q (Nl)

6 x 14 pcs.

Air tank 41l


PA=0.7 MPa
6 x 10 pcs.

How to read the graph


The start-up speed stands for the degree of the nozzle
inside pressure rise per the unit of time. The greater it is,
the stronger the shock wave from the nozzle becomes.
It also means that the closing speed increases and
consumption of air can be used effectively.
Start-up speed = PM x 0.9
t
MPa/ms

2 Port Solenoid Valve for Dust Collector

Series VXF

Construction
Solenoid type

Air operated type

VX2
VXD
VXZ
VXE
VXP
VXR
VXH
VXF
VX3
VXA

Component Parts
No.

1
2
3
4
5
6

Description
Body
Bonnet
Diaphragm assembly
Spring
Hexagonal bolt
Operated valve for dust collector

VCH

Material
Aluminum
Aluminum
NBR, POM
Stainless steel
Stainless steel

VDW
VQ
LVM
VCA

Operated Valve for Dust Collector Part No.

VCB
VCL

VXF 2150 00 1 G
Model Port size
2150
2160
2280

VCS
Electrical option

Rc 3/4
Rc 1
Rc 1 1/2

Nil

S
L
Z

VCW

None
With surge voltage suppressor
With indicator light
With light/surge voltage suppressor

Rated voltage
1
2
3
4
5
6
7
8
9

100 VAC (50/60 Hz)


200 VAC (50/60 Hz)
110 VAC (50/60 Hz)
220 VAC (50/60 Hz)
24 VDC
12 VDC
240 VAC (50/60 Hz)
48 VAC (50/60 Hz)
Other

Electrical entry
G
C
D
T

Grommet (G, GS)


Conduit (C)
DIN terminal (D, DS, DL, DZ)
Conduit terminal (T, TS, TL, TZ)

173

Series VXF
Dimensions
VXF2165 0: Solenoid type
Grommet: G

2xM

VXF2280: Solenoid type


Grommet: G

2xM

Model
VXF2150
VXF2160
VXF2280

174

M
Port size
Rc
34

1
11 2

40
48
77

25
33.5
48.5

66
74
110

36
45
63

35.5
40
57

32.5
38
49

20
20
23

30
30
35

23
23
25

113
127
162

103
118
152

33
37
28

2 Port Solenoid Valve for Dust Collector

Conduit: C

Series VXF

Conduit

VXF2150/2160

VXF2280

K
39
39
41

Model
VXF2150
VXF2160
VXF2280

N
96
110
144.5

VX2
VXD
VXZ
VXE
VXP
VXR
VXH

DIN Terminal
DIN terminal: D
VXF2150/2160

VXF2280
Hexagon width across flats 22

Model
VXF2150
VXF2160
VXF2280

K
59
59
60

N
96
110
144.5

Q
45
45
48

Hexagon width across flats 22


Cable 6 to 12

Cable 6 to 12

VXF
VX3
VXA
VCH
VDW
VQ
LVM
VCA
VCB
VCL
VCS

Conduit terminal: T
VXF2150/2160

VCW

Conduit Terminal
VXF2280

Model
VXF2150
VXF2160
VXF2280

K
92
92
95

N
96
110
144.5

Q
59
59
62

175

Series VXF
Dimensions
VXFA2150/2160: Air operated type

Exhaust port

2xM

VXFA2280: Air operated type

Exhaust port

2xM

Model
VXFA2150
VXFA2160
VXFA2280

176

M
Port size
Rc
34

1
11 2

40
48
77

25
33.5
48.5

66
74
110

36
45
63

35.5
40
57

32.5
38
49

20
20
23

30
30
35

23
23
25

72
86
114

33
37
55

Series VXF

2 Port Solenoid Valve for Dust Collector

Controller Specifications: Series VXFC

How to Order Controller

Specifications
Model
Input voltage
Output voltage
ON time
Time setting OFF time
Time accuracy
Number of output points
Operating ambient temperature
Operating ambient humidity
Ouput current
Power supply fuse

VXFC 06 D
Number of
output points
06
10

Voltage
D 24 to 48 VDC
D-6
12 VDC
A 85 to 220 VAC

6
10

VXFC 06
10 A
85 to 220 VAC

VXFC 06
10 D
24 to 48 VDC
Same as input voltage
0.01 to 0.99
0 to 299
2%
6 to 10 points
0 to 50C (No condensation)
45 to 80% (No condensation)
0.3 A or less
0.3 A or less
3A
1A

VXFC 06
10 D-6
12 VDC

VX2
VXD
VXZ
0.3 A or less
1A

VXE
VXP

Two-time Hitting Function

Interrupt operation Function

A two-time hitting function is adopted to improve the bag filter dusting


efficiency. Turn ON the dip switch for two-time hitting (OFF for one-time
hitting).
(Effective up to the number of setting channels)

Interrupting an operation from an external switch is possible using


input signals.

Operation sequence diagram

4 output points
Two-time hitting only for CH2
For
ON for 1 sec.
OFF for 2 sec.

2 sec.

1 sec.

OFF t

CH2

VXA

OFF t

OFF t

1 sec.

VDW

Dimensions

VQ

1 sec.
Power SW OFF (Output stop)

Controller
No.n
(Slave)
Slave
setting

901

Terminal block
for power supply

VCB

0 0 0

SW8

VCA

OUT1 OUT2 IN1 IN2

SW2
1
2
3
4
5
6
7
8
9
0

0 0

SW1
1
2

OFF

O
F
F

ON

0.01 to 0.99 sec

0 to 299 sec

LED LED LED LED


14
13
12
11
OUT CAS IN POW

VCL
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10

Output display LED

SV2
SV1

SV4
SV3

SV6
SV5

SV8
SV7

SV10
SV9

COM

AC1 AC2 FG

13

9
5

OFF

9.5 9.5

4 x 4.5
5
18.75

9.5

Output terminal block


Common terminal
block for output

1 cycle
No.1 output

30.5 13
52.5
14

No.2 output

9 9
47
140

No.3 output

VCS
Power switch

ON
1A

Operation sequence diagram

45.5
66.5
61

34 or less

26

Start
output

output

output

output

output

10 or less

output

38 or less

No.n output

Operation

LVM

Terminal block for cascade connection

140

Controller
No.3
(Slave)
Slave
setting

Rotary SW for setting the


number of output points
23

VXFC10-1: One board allows outputs at merely 10 output points max.


But the points can be increased to 20 and 30 output points by
connecting cascades.
Controller
No.2
(Slave)
Slave
setting

Two-time hitting setting DIP SW

ON time setting SW

5
11.5

Cascade Connection
(Multiple-board connection)

Cascade setting DIP SW

OFF time setting SW

78

Power SW ON (Output start)

O
F
F

2 sec.

VCH

tA

tA

2 sec.

1 sec.

1 sec.
2 sec.
1 sec.
Two-time hitting

Controller
No.1
(Master)
Master
setting

VX3

ON t

CH1

CH4

1 sec.
2 sec.

2 sec.

1 sec.

Connection

Stop signal

VXH
VXF

456

2 sec.

Operation sequence diagram

CH3

ON time

Power supply

VXR

(VXFC10)
177

VCW

VXF
Specific Product Precaution
Series

Be sure to read before handling. Refer to front matters 42 and 43 for Safety Instructions,
and pages 17 to 19 for 2 Port Solenoid Valves for Fluid Control Precautions.

2 Port Solenoid Valve for


Dust Collector: Series VXF
Silencer

Caution
1. The silencer's response properties do not change in the initial
stage, but will change due to the blockage after long use. Replace it after using about 500,000 times. This number is subject
to change based on fluid quality and energization time.
2. When using a silencer, make space for silencer replacement.

Selection

Caution
1. The response performance and start-up speed deterriorate in
case of air operated type (VXFA) as compared with a solenoid
type (VXF) case. Refer to the data for pilot piping.
2. Note that for DC units, idle time and return time increase if the
voltage is lowered. If a surge voltage suppressor is installed,
the return speed decreases.

Dedicated Controller for


Operation: Series VXFC
Wiring

Warning
1. The controller starts its output the moment the power switch is
turned ON. Be aware that even if the power switch is turned
OFF, power is connected to the terminal board.

Caution
1. Make sure that the voltage of the power to be input matches
the voltage in the controller's specifications. The voltage of the
power that has been input becomes the voltage that is output
to the solenoid valves.
2. Connect a ground that is rated Class 3 or greater to the power
supply terminal board.
3. If the power source is DC, use caution to its polarity. If the polarity is incorrect, it may result in a malfunction or damage.
4. Refer to the separate operation manual for further details.

Environment

Caution
1. Operate under conditions that are free of vibration and impact.
2. Operate in an ambient temperature range between 0C and
50C.
3. Operate in an ambient humidity range between 45% to 85%
(with no condensation). For further details, refer to the instruction manual in which it is explained separately.