Professional Documents
Culture Documents
Droop Control in LV Grids
Droop Control in LV Grids
Droop Control in LV Grids
I. I NTRODUCTION
the idle voltage, the slopes of the droops and basic commands.
This way expensive control bus systems are replaced by using
the grid quantities voltage and frequency for the co-ordination
of the components. Such approach results in the following
features:
simple expansion of the system
increased redundancy, as the system does not rely on a
vulnerable bus system
for optimisation a simple bus system is sufficient
a simplified supervisory control
more complex control tasks in the components.
Additional redundancy in grids can be achieved by using
voltage source inverters (VSI) in parallel. This approach avoids
the master/slave operation. In fact, all VSIs form the grid.
The inverters are coupled via the inductances resulting from
their filters for the pulse suppression and of decoupling chokes
(s. Fig. 2). But the configuration in Fig. 2 is difficult to handle
as will be shown. The active power P and the reactive power
Q of the voltage sources can be calculated as follows:
Pinv
Qinv
Uinv Ugrid
sin
N L
2
Uinv Ugrid
Uinv
cos
N L
N L
u0
f0
The authors would like to express their thanks to the European Commission
for their support in the MicroGrids-project ENK5-CT-2002-00610.
A. Engler is with the ISET e. V., Konigstor 59, 34119 Kassel, Germany.
N. Soultanis is with the ICCS/NTUA, Athens, Greece.
(2)
(1)
Df
-1
Fig. 1.
Du -4%
-1%
1P
PN
-1
Ugrid
Uinv
equivalent circuit
Fig. 2.
1Q
QN
d
Ugrid
Uinv
phasor diagram
P
Tmech
st1
st'1
u ref
300
U/V, Itotal*10/A
u0
u
Q
Texcit e
st2
200
IuI
100
0
I
100
200
300
Fig. 3.
decoupling
droops
voltage
reference
Firstly this control approach, named selfsyncTM , was implemented into the battery inverter SunnyIsland TM for rural
electrification (s. Fig. 4). For an experiment [5] three of these
inverters programmed with this scheme were connected on
a single phase to an ohmic load, each via a thin low voltage
cable. The frequency droop of the inverters denoted by L1 , L2
in Fig. 5 was set to 1 Hz/rated power. The inverter denoted
with L3 was set to 2 Hz/rated power. It is evident that this
method allows L3 to supply a smaller proportion of power.
The load sharing corresponds to the settings. L1 , L2 are equal,
L3 half of it. Noticeable is the phase shift of L3 to L1 , L2
which is due to the different loading of the cables, causing a
slight voltage difference between the inverters, which results
in reactive power flow.
The compatibility of selfsyncTM with rotating generators has
been shown in [6] and the compatibility with the grid in [7].
III. I MPLICATIONS OF LINE PARAMETERS
A. Boundaries of power transmission
Table I shows the typical line parameters R0 , X 0 and
the typical rated current for the high-, medium- and low
voltage lines. Assuming inductive coupled voltages sources for
representing the droop controlled inverters and the distribution
system would be only correct for the high voltage level. A
medium voltage line has mixed parameters and the low voltage
line is even predominantly resistive.
Basically the boundaries of power transmission as a function
of line parameters can be derived from following inequality:
2
2
P
Q
+
Ssc
Ssc
2
Q
1
P
cos z +
sin z
Ssc
Ssc
2
(3)
5.01
5.02
5.03
5.04
t/s
5.05
5.06
5.07
5.08
5.05
5.06
5.07
5.08
IL1, L2
6
4
IL1, IL2, IL3/A
power
acquisition
IL3
2
0
2
4
6
5
5.01
5.02
5.03
5.04
t/s
R
/km
0.642
0.161
0.06
X
/km
0.083
0.190
0.191
IN
A
142
396
580
R0
X0
7.7
0.85
0.31
0.5
Qinv
Pinv
Qpu
0.25
Uinv Ugrid
sin
Rline
2
Uinv Ugrid
Uinv
cos .
Rline
Rline
(4)
(5)
0.25
0.5
1
1
Fig. 6.
0.5
0.25
0
Ppu
0.25
0.5
Ugrid
Rline
Uinv
d
Ugrid
Uinv
Fig. 9.
phasor diagram
0.5
Qpu
0.25
0.25
0.5
1
1
Fig. 7.
0.5
0.25
0
Ppu
0.25
0.5
Eq. 5 reveals that the active power flow and the voltage is
linked in the low voltage grid. A phase difference between
the voltage sources causes reactive power flow (s. Eq. 4).
This fact suggests to use active power/voltage and reactive
power/frequency droops - hereinafter called opposite droops
- in the low voltage grid instead of reactive power/voltage and
active power/frequency droops - hereinafter called conventional droops.
0.5
Qpu
0.25
0.25
0.5
1
1
Fig. 8.
0.5
0.25
0
Ppu
0.25
0.5
TABLE II
C OMPARISON OF DROOP CONCEPTS FOR THE LOW VOLTAGE LEVEL
conventional droop
yes
yes
no
yes
opposite droop
no
no
yes
no
As one can see from the Table II the only advantage of using
the inverse droops is the direct voltage control. But if one
would control the voltage this way, no power dispatch would
be possible. Each load would be fully supplied by the nearest
generator. As this generally is not possible, voltage deviations
would remain in the grid. Using conventional droops results
in connectivity to the high voltage level, allows power sharing
also with rotating generators and a precise power dispatch. The
voltage deviations within the grid depend on the grid layout,
which is todays standard.
+ Pinv R .
(6)
2
4
These both have to be taken into account for describing the
process. Uinv1 is a voltage close to the grid voltage and Uinv2
is a slightly negative voltage. This implies a 180 phase shift.
Therefore in Eq. 7 the factor k is introduced with k1 = 1 for
the first solution and k2 = 1 for the negative solution. The
factor k is an approximation of the cos-function in Eq. 5:
Uinv1,2 Ugrid
Uinv1,2 k1,2 .
(7)
R
The inverter power Pinv is adjusted by changing the inverter
voltage Uinv with the reactive power:
Pinv =
(8)
(11)
2
pdroop qdroop k1,2 Ugrid Uinv1,2
, (12)
2
R
|
{z
}
=C
which describes a first order lag with the solution:
Pinv = Pset (1 eC t ) .
(13)
(14)
case
1
2
3
4
description
inverse conv.
conv.
pdroop
pos.
neg.
pos.
neg.
qdroop
pos.
neg.
neg.
pos.
k
1
1
1
1
comment
allowed
allowed
not allowed
not allowed
u0
f0
Df
-1
u0
f0
+1%
Du +4%
1P
PN
-1
Df
-1
1Q
QN
1P
PN
Du -4%
-1%
-1
1Q
QN
400
400
Uinv
Uinv
Ugrid
200
Ugrid
200
Uline
0
200
200
400
0.5
0.505
0.51
0.515
0.52
0.525
0.53
0.535
400
0.5
0.54
Uline
0.505
0.51
0.515
0.52
0.525
Fig. 11.
0.54
u0
f0
Df
C. Choice of droops
-1
+1%
Du -4%
-1
1P
PN
1Q
QN
Uline
Ugrid
Uinv
200
0.535
u0inv (t)
0.53
200
400
0.5
(15)
In Fig. 14 resulting voltages with approximately total compensation are depicted. 10 kW is injected requiring almost
no reactive power . Accordingly there is almost no phase shift
between the inverter- and grid voltage (compare with Fig. 11).
One should be careful with line compensation as overcompensation becomes unstable. An approach could be the
compensation of 90% - unknown resistivity and sensor errors
- of the line up to the next knot. As lower currents circulate
in the grid problems concerning voltages are reduced.
VI. C ONCLUSION
It has been shown that the droops, used in the interconnected
grid, can be used effectively on the low voltage level due
to their indirect operation. So far, this effect has not been
0.505
0.51
0.515
0.52
0.525
0.53
0.535
0.54
u0
f0
Df
-1
Du +4%
-1%
-1
1P
PN
1Q
QN
Ugrid
200
Uline
Uinv
200
400
0.5
0.505
0.51
0.515
0.52
0.525
0.53
0.535
0.54
400
Uinv
Ugrid
200
Uline
200
400
0.5
Fig. 14.
0.505
0.51
0.515
0.52
0.525
0.53
0.535
0.54
R EFERENCES
[1] J. Lynch, MicroGrid power networks, Cogeneration & On-Site Power
Production, James & James, London, May-June 2004.
[2] A. Engler, Regelung von Batteriestromrichtern in modularen und erweiterbaren Inselnetzen, Dissertation.de, Berlin, May 2002, ISBN 3-89825439-9.
[3] A. Engler, Control of Parallel Operating Battery Inverters, 1st PV Hybrid
Power Systems Conference, Aix-en-Provence, September 2000.
[4] A. Engler, Vorrichtung zum gleichberechtigten Parallelbetrieb von einoder dreiphasigen Spannungsquellen, German patent No. 101 40 783.1
(pending), European patent No. 02 018 526.26 (pending), US Patent No.
US 6,693,809 B2, Feb. 17, 2004 (granted), Japanese patent No. 2002240991 (pending).
[5] A. Arulampalam, M. Barnes, A. Engler, A. Goodwin, N. Jenkins, Control
of Power Electronic Interfaces in Distributed Generation, International
Journal of Electronics, London, 2004.
[6] A. Engler, C. Hardt, Ph. Strauss and M. Vandenbergh, Parallel Operation
of Generators for Stand-Alone Single Phase Hybrid Systems, EPVSEC,
Munich, October 2001.
[7] S. Papathanassiou, D. Georgakis, N Hatziargyriou, A. Engler, Ch.
Hardt, Operation of a prototype Micro-grid system based on microsources equipped with fast-acting power electronic interfaces, 31th PESC,
Aachen, June 2004.
[8] Klaus Heuk, Klaus-Dieter Dettmann, Elektrische Energieversorgung,
Vieweg, 3rd edition.