GEA MPower-Geko Fan Coil Unit

Sizes .......................................................................................................... 1.2


Fan Coil Unit Components ......................................................................... 2
Unit Selection ............................................................................................... 3
Unit Description ........................................................................................... 4
Recirculating Air Unit Cooling and Heating .............................................. 6
Accessories/Valves .............................................................................................. 7

Recirculating Air Unit Cooling and Heating .............................................. 8


Accessories/Valves .............................................................................................. 9

Recirculating Air Unit Heating .................................................................. 10


Accessories/Valves ............................................................................................ 11

Recirculating Air Unit Heating .................................................................. 12


Accessories/Valves ............................................................................................ 13

Pressure Drop in Heat Exchanger, Warm and Chilled Water ................ 14


Power and Current Consumption ............................................................. 15
Capacity Overview for Different Operating Points Size 1....................... 16
Overview of Acoustic Data for Different Operating Points, Size 1 ...................... 17

Capacity Overview for Different Operating Points Size 2....................... 18


Overview of Acoustic Data for Different Operating Points, Size 2 ...................... 19

Capacity Overview for Different Operating Points Size 3....................... 20


Overview of Acoustic Data for Different Operating Points, Size 3 ...................... 21

Capacity Overview for Different Operating Points Size 4 ...................... 22


Overview of Acoustic Data for Different Operating Points, Size 4 ...................... 23

Samples for Capacity Definition .............................................................. 24


Installation Samples .................................................................................. 28
Dimensions of Basic Units ....................................................................... 29
Dimensions of Accessories ...................................................................... 31
Overview of Valves
Selection Tables.................................................................................................. 33
Valve Actuators .................................................................................................. 34
Valve Bodies ...................................................................................................... 35
Shut-off Valves ................................................................................................... 36
Ball Traps ........................................................................................................... 37

Control via Thermostat / Speed Switches / Control by Others ............. 38


Control System GEA MATRIX .................................................................. 40
Product Type Code .................................................................................... 51
Copyright note
Disclosing, copying, distributing or taking any action in reliance on the contents of this
document is strictly prohibited without express prior consent. Violations entail liability
for any damages or other liability arising. All rights in relation to patents, utility patents
or design patents are reserved.
2
1.1

PR-2009-0139-GB Subject to modifications Status 10/2009

Fan Coil Unit Components

GEA MPower-Geko Fan Coil Unit

Size

Width

Air volume flow

Sound power level 1)

Heating capacity QH

Cooling capacity QK
[m3/h]

[mm]

1
2
3
4

975

515-1215

1275

1575

1775

[dB(A)]
29-48

685-1555

805-2020

1000-2460

32-53

27-47

30-51

[kW]
5,4-17,3
2,0-4,1
7,1-22,3
3,0-5,9
9,3-29,7
3,0-7,0
10,9-35,5
4,0-8,5

1)

Sound level measured at unit casing, modular unit, capacity stage 1, filter class G2, without external pressure, without accessories. For other
acoustic data refer to Sample for capacity definition, page 24 to page 27.

2)

Capacity data apply for the following input parameters: WWP 82/71C, tL1 = +20 C; CWP 6/12 C, tL1 = 23 C, 50 % r.h.
For other input parameters - please contact your GEA office!

1
1.2

PR-2009-0139-GB Subject to modifications Status 10/2009

Fan Coil Unit Components

Fig. 1:

GEA MPower-Geko Fan Coil Unit

Unit components (depending on unit model)

Pos. 1: Basic casing

Pos. 7: Service panel

Pos. 2: Fixing bracket

Pos. 8: Filter cover

Pos. 3: Heat exchanger

Pos. 9: Filter element

Pos. 4: Fan

Pos. 10: Electric switch box

Pos. 5: Condensate tray

Pos. 11: Contact protection

Pos. 6: Condensate pump


GEA participates in the EUROVENT certification programme.
The certified products are accordingly listed by the EUROVENT.

PR-2009-0139-GB Subject to modifications Status 10/2009

Unit Selection

GEA MPower-Geko Fan Coil Unit

Recirculating air

Cooling and
Heating

Cooling or
Heating

Unit Description

4-Pipe Chilled and Warm Water

2-Pipe Chilled or Warm Water

Heating

2-Pipe Warm Water

10

Cooling

2-Pipe Chilled Warm Water

12

Technical Data, Dimensions and Specification of


Accessories

14

Valves

33

GEA MATRIX Control System/Thermostat Switches

38

Druckverluste im Wrmetauscher

4 Rohrreihen Khlen, 2-Leiter-System


1

25

20
6

DruckverlustDp [kPa]

15

10
9,0
8,0
7,0
6,0
5,0
4,5
4,0
3,5
3,0

30

2,5
2,0
1,5

1500

600
700
800
900
1000

2000

250
300
350
400
450
500

200

50
60
70
80
90
100

0,5

150

1,0
0,9
0,8
0,7
0,6

Wasservolumenstrom VW [l/h]
Abb. 25.3
GEA Top-Geko nderungen vorbehalten Stand 08/00 (D)

25

PR-2009-0139-GB Subject to modifications Status 10/2009

Unit Description

GEA MPower-Geko Fan Coil Unit

Basic units as modular and


compact models
Heating/cooling/filtering/
with 2/4-pipe system. Ceiling
mounting, single skin panel
construction made of galvanized
sheet steel with internal acoustic
and thermal insulation (electrical
and valve equipment depending
on functions and requirements).

Basic unit

Fig. 2
Basic unit + sound attenuator + intake plenum

Compact basic unit with air


intake sound attenuator and
air intake box, acoustic and
thermal insulation of inner
panels

Fig. 3
Thermoelectric valves

Modulating valves

Valves
2 and 3-way valves with
actuators for
2-point, 230/24 V~ 50/60 Hz
3-point, 230/24 V~ 50/60 Hz
continuous 24 V~,
control signal 0-10 V
mounted and wired by factory

Fig. 4
Electric equipment
Terminal box
Steel sheet electrical control box
(depending on unit model,
function and requirements)

Electric equipment

Fig. 5
Speed and thermostat switches

MATRIX Control System

Control systems
according to unit model, valves,
internal and external electronic
components

Fig. 6
4

PR-2009-0139-GB Subject to modifications Status 10/2009

Unit Description

GEA MPower-Geko Fan Coil Unit

Heat exchanger
for warm/chilled water
(2-pipe system)

Heat exchanger
for warm/chilled water
(4-pipe system)

Copper pipes with drawn


aluminium fins, supplied with "
connection, internal thread, air
vent and drain screws
max. inlet temperature 90 C
max. operating pressure 16 bar

Fig. 7
Centrifugal fan with low noise
maintenance-free sleeve
bearings, high pressure
stability, protection type IP00,
insulation class B

Centrifugal fan 230 V~ 50/60 Hz

Type and fan number depend


on unit size and selection

Fig. 8
Condensate pump (optional)

Filter

As an option, forming
condensate can be drained using
a condensate pump. High
operational safety through
contact-free sensors.
Regenerative filter hose on
clip-on frame, filter quality G2
(EN 779) or G3 (EN 779)

Fig. 9
Fixing and connecting bracket

Fixing and connecting bracket


provides different possibilities
for ceiling mounting and
connecting the unit and its
add-on modules.

Fig. 10

PR-2009-0139-GB Subject to modifications Status 10/2009

Recirculating Air Unit Heating and Cooling

515

2,1

9,0

4,5*

12,7

2,0

3,3

5,4*

16,6

40

41

29

685

2,6

12,7

5,1*

12,7

2,4

4,7

6,3*

16,6

44

46

34

915

3,1

17,9

5,7*

12,7

2,9

6,7

7,1*

16,6

52

54

41

1080

3,4

21,0

6,1*

12,7

3,2

8,0

7,5*

16,6

56

58

45

1215

3,6

23,9

6,4*

12,7

3,4

9,1

7,9*

16,7

58

62

48

685

3,0

22,1

6,0*

17,0

3,0

9,1

7,1*

22,4

42

45

32

930

3,7

32,7

6,9*

17,0

3,7

13,4

8,2*

22,5

50

53

40

1115

4,2

40,1

7,4*

17,1

4,1

16,4

8,8*

22,5

54

58

44

1295

4,6

47,6

7,8*

17,1

4,6

19,7

9,4*

22,5

58

62

48

Pressure drop

Pressure drop

Pressure drop

Pressure drop

pK

pH
kPa

Sound power air


discharge**

pH

Filter
Size

Sound power air intake**

kPa

QH
kW

Heating capacity

kPa

QK
kW

pK

Cooling capacity

Cooling capacity

kPa

QH
kW

Heating capacity

Air flow rate**


[m3/h]

QK
kW

Speed stages

Design
Modular (G)
Compact (M)

Capacity stage 2

Sound power casing**

Sizes 1 to 4
Capacity stage 1

GEA MPower-Geko Fan Coil Unit

CWP 6/12 C WWP 82/71 C


tL1 = +23 C
tL1 = +20 C
1 = 50 % r.h.

4-Pipe Chilled and Warm Water

G3 mat filter

dB(A) dB(A) dB(A)

Terminal box (select sheet steel electric


switch box with GEA MATRIX)

1555

5,0*

53,8

8,4*

17,1

5,0

23,6

10,1*

22,6

63

67

53

815

3,6

13,1

7,2*

21,4

3,1

1,9

9,4*

24,6

38

38

27

1-2-3

1150

4,6

20,6

8,4*

21,5

4,1

3,3

11,3*

24,6

44

45

33

2-3-4

1380

5,2

25,4

9,0*

21,5

4,7

4,2

12,3*

24,6

48

49

37

3-4-5

1670

5,9

31,7

9,6*

21,5

5,3

5,3

13,3*

24,7

52

54

42

1-3-5

Speed combination

1-2-3-4-5

2020

6,5

38,6

10,2*

21,6

6,0

6,5

14,4*

24,7

57

60

47

1000

4,4

20,2

8,2*

23,6

4,0

3,4

10,9*

26,1

40

43

30

1380

5,5

30,6

9,4*

23,7

5,1

5,2

12,8*

26,1

47

50

37

1730

6,3

39,4

10,3*

23,8

5,9

6,8

14,2*

26,1

52

55

42

2065

7,1

48,1

10,9*

23,8

6,6

8,4

15,2*

26,1

57

60

47

2460

7,6*

51,6

11,5*

23,8

7,2

10,0

16,3*

26,2

62

64

51

515

2,1

9,0

4,5*

12,7

2,0

3,3

5,4*

16,6

40

41

29

680

2,5

12,6

5,1*

12,7

2,4

4,7

6,3*

16,6

44

46

34

905

3,1

17,6

5,7*

12,7

2,9

6,6

7,0*

16,6

52

54

41

1065

3,3

20,7

6,1*

12,7

3,2

7,8

7,5*

16,6

56

58

45

1190

3,6

23,3

6,3*

12,7

3,4

8,9

7,8*

16,7

58

62

48

685

3,0

22,1

6,0*

17,0

3,0

9,1

7,1*

22,4

42

45

32

925

3,7

32,5

6,8*

17,0

2,8

7,8

8,2*

22,5

50

53

40

1105

4,1

39,7

7,3*

17,1

4,1

16,2

8,8*

22,5

54

58

44

1-2-3

1275

4,5

46,8

7,8*

17,1

4,5

19,2

9,4*

22,5

58

62

48

2-3-4
3-4-5

4
Sheet steel electric switch box with
terminal strip or for integrated control

Speed combination
2

1515

4,9*

53,8

8,3*

17,1

5,0

23,0

10,0*

22,6

63

67

53

805

3,6

12,9

7,2*

21,4

3,0

1,9

9,3*

24,6

38

38

27

1-3-5

1135

4,6

20,3

8,4*

21,5

4,0

3,2

11,2*

24,6

44

45

33

1-2-3-4-5

1360

5,1

25,0

8,9*

21,5

4,6

4,1

12,2*

24,6

48

49

37

1635

5,8

31,0

9,5*

21,5

5,3

5,2

13,2*

24,7

52

54

42

1965

6,5

38,1

10,1*

21,6

5,9

6,3

14,3*

24,7

57

60

47

1000

4,4

20,2

8,2*

23,6

4,0

3,3

10,9*

26,1

40

43

30

1365

5,5

30,2

9,4*

23,7

5,0

5,1

12,6*

26,1

47

50

37

1700

6,2

38,6

10,2*

23,8

5,8

6,6

14,1*

26,1

52

55

42

2015

6,9

46,8

10,8*

23,8

6,5

8,1

15,1*

26,1

57

60

47

2375

7,5*

51,6

11,4*

23,8

7,1

9,8

16,1*

26,1

62

64

51

G2 mat filter

Motor thermal contact


5-speed
motor

Integrated
TC

External TC

2
Capacity stage

Medium connection - front connection


side, facing discharge

Condensate line

Ceiling

left

right

with drainage

with condensate pump ***

Data apply to basic units with filter class G2, without accessories and external
pressure. Refer to table on page 24 for other operating points.
* Capacity at max. allowed medium flow rate
** Air flow rates and sound data for capacity stage 1
*** sheet steel electrical control box necessary

Order
code

PR-2009-0139-GB Subject to modifications Status 10/2009

Accessories/Valves

GEA MPower-Geko Fan Coil Unit

Recirculating Air Unit Heating and Cooling


4-Pipe Chilled and Warm Water, Sizes 1 to 4

Accessories

Spare filter hoses


Filter class G2

Filter class G3

Air intake

Air discharge**

Air intake

Air discharge

Box with round


connector

Flexible discharge connector

Sound attenuation module

Cover cap for round connector DN200


(irrespective of size) *

Contact protection

Air intake

Suspension rail
(irrespective of
size) *

Air intake

Air discharge**

Air intake

Air discharge**

950 mm

1550 mm

2150 mm

Sizes 1 to 4
* 0, if irrespective of size
** Only for basic units in
modular configuration

Order code

Valves

MATRIX 500

MATRIX 2000

MATRIX 3000/4000

Terminal box

Connection/shut-off

Actuator

Inlet/outlet with external thread


Inlet/outlet with solder fitting
Inlet/outlet + ball trap with external thread
Inlet/outlet + ball trap with solder fitting
Inlet + ball trap/outlet + shut-off valve with external
thread
Inlet + ball trap/outlet + shut-off valve with solder
fitting

Operating voltage/circuit

2-point
open/
close
3-point
open/
stop/
close
continuous

230 V AC

2)

24 V AC1), 2)
230 V AC
24 V AC1)

230 V AC + 2 contacts

0/2 ... 10 V = 24 V

R
N

AC1)

Heating
circuit

0.25
0.40

Cooling
circuit

1.00
1,602)
2.50

24 V-transformer to be provided by
others

2)

kvs-values for open/close actuators


(T,Q) only kvs 1,6 and 4,0 possible

Order code

PR-2009-0139-GB Subject to modifications Status 10/2009

4
5

kvs-values
Cooling/Heating

0.63

1)

Medium connection
L
left
R
right

0
1
2
3

4,002)

03
04
06
10
16
25
40

Cooling circuit

Heating circuit

Recirculating Air Unit Heating or Cooling

GEA MPower-Geko Fan Coil Unit

Compact (M)

Sound power air intake**

515

2,0

3,3

8,2

12,5

2,1

2,3

8,9

8,5

40

41

29

685

2,4

4,7

10,2

18,9

2,7

3,5

11,3

13,3

44

46

34

915

2,9

6,8

12,5

27,7

3,4

5,2

14,1

20,2

52

54

41

1080

3,2

8,1

14,0*

31,7

3,8

6,3

15,8

25,0

56

58

45

1215

3,5

9,3

14,9*

31,7

4,1

7,3

17,3

29,6

58

62

48

685

3,0

9,1

11,1

27,6

3,3

6,4

12,0

18,7

42

45

32

930

3,7

13,5

14,1*

39,1

4,1

9,7

15,5

29,8

50

53

40

1115

4,2

16,6

16,0*

39,1

4,8

12,6

18,1*

39,0

54

58

44

1295

4,6

19,9

17,4*

39,1

5,3

15,2

20,1*

39,1

58

62

48

pK

Pressure drop

Pressure drop

Pressure drop

Pressure drop

pH

pH
kPa

Sound power air


discharge**

kPa

QH
kW

Heating capacity

kPa

QK
kW

Heating capacity

Cooling capacity

kPa

QH
kW

Speed stages

[m3/h]

QK
kW

pK

Cooling capacity

Capacity stage 2

Air flow rate**

Modular (G)

Design

Capacity stage 1

Filter
Size

Sizes 1 to 4

Sound power casing**

CWP 6/12 C WWP 82/71 C


tL1 = +23 C
tL1 = +20 C
1 = 50 % r.h.

2-Pipe Chilled or Warm Water

G3 mat filter

dB(A) dB(A) dB(A)

Terminal box (select sheet steel electric


switch box with GEA MATRIX)

1555

5,1

24,1

19,3*

39,2

5,9

18,7

22,3*

39,1

63

67

53

815

3,1

2,0

13,6

8,1

3,2

1,2

14,3

5,2

38

38

27

1-2-3

1150

4,1

3,3

17,8

13,4

4,6

2,4

19,3

9,2

44

45

33

2-3-4

1380

4,7

4,2

20,3

17,2

5,3

3,1

22,3

12,0

48

49

37

3-4-5

1670

5,4

5,4

23,2

22,0

6,2

4,1

26,0

16,0

52

54

42

1-3-5

Speed combination

1-2-3-4-5

2020

6,0

6,6

26,2

27,7

7,0

5,1

29,7

20,5

57

60

47

1000

4,0

3,4

16,2

12,1

4,4

2,3

17,6

8,2

40

43

30

1380

5,1

5,3

20,9

19,3

5,7

3,8

23,0

13,6

47

50

37

1730

5,9

6,9

24,8

26,6

6,7

5,2

27,3

18,6

52

55

42

2065

6,6

8,5

27,8*

30,9

7,6

6,5

31,4

24,1

57

60

47

2460

7,3

10,2

30,8*

30,9

8,5

7,9

35,5

30,4

62

64

51

515

2,0

3,3

8,2

12,5

2,1

2,3

8,9

8,5

40

41

29

680

2,4

4,7

10,1

18,7

2,7

3,5

11,3

13,3

44

46

34

905

2,9

6,7

12,4

27,3

3,4

5,1

14,0

19,9

52

54

41

1065

3,2

8,0

13,9*

31,7

3,7

6,2

15,6

24,5

56

58

45

1190

3,4

9,1

14,7*

31,7

4,0

7,1

17,1

28,9

58

62

48

685

3,0

9,1

11,1

27,6

3,3

6,4

12,0

18,7

42

45

32

925

3,7

13,4

14,1*

39,1

4,1

9,6

15,6

30,1

50

53

40

1105

4,1

16,4

15,9*

39,1

4,7

12,5

17,8

38,5

54

58

44

1-2-3

1275

4,5

19,5

17,2*

39,1

5,2

14,8

19,8*

39,0

58

62

48

2-3-4
3-4-5

4
Sheet steel electric switch box with
terminal strip or for integrated control

Speed combination
2

1515

5,0

23,4

19,0*

39,2

5,9

18,4

21,9*

39,1

63

67

53

805

3,1

1,9

13,3

7,8

3,2

1,2

14,1

5,1

38

38

27

1-3-5

1135

4,1

3,2

17,6

13,2

4,5

2,3

19,1

9,0

44

45

33

1-2-3-4-5

1360

4,7

4,1

20,1

16,8

5,2

3,0

21,9

11,6

48

49

37

1635

5,3

5,2

22,9

21,5

6,1

4,0

25,7

15,6

52

54

42

1965

5,9

6,4

25,8

26,8

6,8

4,9

29,1

19,7

57

60

47

1000

4,0

3,4

16,2

12,1

4,3

2,3

17,5

8,2

40

43

30

1365

5,1

5,2

20,7

19,0

5,7

3,8

22,6

13,1

47

50

37

1700

5,8

6,7

24,5

26,0

6,6

5,0

26,9

18,1

52

55

42

2015

6,5

8,3

27,4*

30,9

7,5

6,3

30,9

23,4

57

60

47

2375

7,2

10,0

30,3*

30,9

8,4

7,7

34,6

28,9

62

64

51

G2 mat filter

Motor thermal contact


5-speed
motor

Integrated
TC

External TC

2
Capacity stage

Medium connection - front connection


side, facing discharge

Condensate line

Ceiling

left

right

with drainage

with condensate pump ***

Data apply to basic units with filter class G2, without accessories and external
pressure. Refer to table on page 24 for other operating points.
* Capacity at max. allowed medium flow rate
** Air flow rates and sound data for capacity stage 1
*** Sheet steel electrical control box necessary

Order
code

. U

PR-2009-0139-GB Subject to modifications Status 10/2009

Accessories/Valves

GEA MPower-Geko Fan Coil Unit

Recirculating Air Unit Heating or Cooling


2-Pipe Chilled or Warm Water, sizes 1 to 4

Accessories

Spare filter hoses


Filter class G2

Filter class G3

Air intake

Air discharge**

Air intake

Air discharge

Box with round


connector

Flexible discharge connector

Sound attenuation module

Cover cap for round connector DN200


(irrespective of size) *

Contact protection

Air intake

Suspension rail
(irrespective of
size) *

Air intake

Air discharge**

Air intake

Air discharge**

950 mm

1550 mm

2150 mm

Sizes 1 to 4
* 0, if irrespective of size
** Only for basic units in
modular configuration

Order code

Valves
Medium connection

MATRIX 500

MATRIX 2000

MATRIX 3000/4000

Terminal box

Connection/shut-off

Actuator

Operating voltage/circuit

2-point
open/
close
3-point
open/
stop/
close
continuous

230 V AC

2)

24 V AC1), 2)

230 V AC
24 V AC1)

R
N

230 V AC + 2 contacts

0/2 ... 10 V = 24 V AC1)

Inlet/outlet with external thread


Inlet/outlet with solder fitting
Inlet/outlet + ball trap with external thread
Inlet/outlet + ball trap with solder fitting
Inlet + ball trap/outlet + shut-off valve with external
thread
Inlet + ball trap/outlet + shut-off valve with solder
fitting

0
1
2
3

kvs-values
Cooling/Heating
Cooling/
heating circuit

0.25
0.40
1.00
1,602)

2,50
4.002)

24 V-transformer to be provided by
others

Order code

L
R

0.63

1)

left
right

03
04
06
10
16
25
40

Cooling/heating circuit

2) kvs-values for open/close actuators


(T,Q) only kvs 1,6 and 4 possible

PR-2009-0139-GB Subject to modifications Status 10/2009

Recirculating Air Unit Heating

8,2

12,5

8,9

8,5

40

41

29

685

10,2

18,9

11,3

13,3

44

46

34

915

12,5

27,7

14,1

20,2

52

54

41

1080

14,0*

31,7

15,8

25,0

56

58

45

1215

14,9*

31,7

17,3

29,6

58

62

48

685

11,1

27,6

12,0

18,7

42

45

32

930

14,1*

39,1

15,5

29,8

50

53

40

1115

16,0*

39,1

18,1*

39,0

54

58

44

1295

17,4*

39,1

20,1*

39,1

58

62

48

pH
kPa

Pressure drop

Pressure drop

Pressure drop

Sound power air


discharge**

515

pK

Filter
Size

Sound power air intake**

pH

Pressure drop

kPa

QH
kW

Heating capacity

kPa

QK
kW

Heating capacity

Cooling capacity

kPa

QH
kW

Speed stages

[m3/h]

QK
kW

pK

Cooling capacity

Capacity stage 2

Air flow rate**

Modular (G)

Design

Capacity stage 1

Sound power casing**

Sizes 1 to 4

Compact (M)

GEA MPower-Geko Fan Coil Unit

WWP 82/71 C
tL1 = +20 C

2-Pipe Warm Water

G3 mat filter

dB(A) dB(A) dB(A)

Terminal box (select sheet steel electric


switch box with GEA MATRIX)

1555

19,3*

39,2

22,3*

39,1

63

67

53

815

13,6

8,1

14,3

5,2

38

38

27

1-2-3

1150

17,8

13,4

19,3

9,2

44

45

33

2-3-4

1380

20,3

17,2

22,3

12,0

48

49

37

3-4-5

1670

23,2

22,0

26,0

16,0

52

54

42

1-3-5

Speed combination

1-2-3-4-5

2020

26,2

27,7

29,7

20,5

57

60

47

1000

16,2

12,1

17,6

8,2

40

43

30

1380

20,9

19,3

23,0

13,6

47

50

37

1730

24,8

26,6

27,3

18,6

52

55

42

2065

27,8*

30,9

31,4

24,1

57

60

47

2460

30,8*

30,9

35,5

30,4

62

64

51

515

8,2

12,5

8,9

8,5

40

41

29

680

10,1

18,7

11,3

13,3

44

46

34

905

12,4

27,3

14,0

19,9

52

54

41

1065

13,9*

31,7

15,6

24,5

56

58

45

1190

14,7*

31,7

17,1

28,9

58

62

48

685

11,1

27,6

12,0

18,7

42

45

32

925

14,1*

39,1

15,6

30,1

50

53

40

1105

15,9*

39,1

17,8

38,5

54

58

44

1-2-3

1275

17,2*

39,1

19,8*

39,0

58

62

48

2-3-4
3-4-5

4
Sheet steel electric switch box with
terminal strip or for integrated control

Speed combination
2

1515

19,0*

39,2

21,9*

39,1

63

67

53

805

13,3

7,8

14,1

5,1

38

38

27

1-3-5

1135

17,6

13,2

19,1

9,0

44

45

33

1-2-3-4-5

1360

20,1

16,8

21,9

11,6

48

49

37

1635

22,9

21,5

25,7

15,6

52

54

42

1965

25,8

26,8

29,1

19,7

57

60

47

1000

16,2

12,1

17,5

8,2

40

43

30

1365

20,7

19,0

22,6

13,1

47

50

37

1700

24,5

26,0

26,9

18,1

52

55

42

2015

27,4*

30,9

30,9

23,4

57

60

47

2375

30,3*

30,9

34,6

28,9

62

64

51

G2 mat filter

Motor thermal contact


5-speed
motor

Integrated
TC

External TC

2
Capacity stage

Medium connection - front connection


side, facing discharge

Ceiling

left

right

Data apply to basic units with filter class G2, without accessories and external
pressure. Refer to table on page 24 for other operating points.
* Capacity at max. allowed medium flow rate
** Air flow rates and sound data for capacity stage 1

10

Order
code

. U

PR-2009-0139-GB Subject to modifications Status 10/2009

Accessories/Valves

GEA MPower-Geko Fan Coil Unit

Recirculating Air Unit Heating


2-Pipe Warm Water, Sizes 1 to 4

Accessories

Spare filter hoses


Filter class G2

Filter class G3

Air intake

Air discharge**

Air intake

Air discharge

Box with round


connector

Flexible discharge connector

Sound attenuation module

Cover cap for round connector DN200


(irrespective of size) *

Contact protection

Air intake

Suspension rail
(irrespective of
size) *

Air intake

Air discharge**

Air intake

Air discharge**

950 mm

1550 mm

2150 mm

Sizes 1 to 4
* 0, if irrespective of size
** Only for basic units in
modular configuration

Order code

Connection/shut-off
Terminal box

MATRIX 3000/4000

MATRIX 2000

MATRIX 500

Valves

Actuator

Operating voltage/circuit

2-point
open/
close
3-point
open/
stop/
close
continuous

230 V AC2)

24 V
230 V AC
24 V AC1)

230 V AC + 2 contacts

0/2 ... 10 V = 24 V AC1)

AC1), 2)

Inlet/outlet with external thread


Inlet/outlet with solder fitting
Inlet/outlet + ball trap with external thread
Inlet/outlet + ball trap with solder fitting
Inlet + ball trap/outlet + shut-off valve with external
thread
Inlet + ball trap/outlet + shut-off valve with solder
fitting

R
N
Heating circuit

0.25
0.40
1.00

1,602)
2.50
4,002)

24 V-transformer to be provided by
others

2)

kvs-values for open/close actuators


(T,Q) only kvs 1,6 and 4,0 possible

PR-2009-0139-GB Subject to modifications Status 10/2009

Order code

4
5

kvs-values
Cooling/Heating

0.63

1)

Medium connection
L
left
R
right

0
1
2
3

03
04
06
10
16
25
40

Heating circuit

11

Recirculating Air Unit Cooling

515

2,0

3,3

2,1

2,3

40

41

29

685

2,4

4,7

2,7

3,5

44

46

34

915

2,9

6,8

3,4

5,2

52

54

41

1080

3,2

8,1

3,8

6,3

56

58

45

1215

3,5

9,3

4,1

7,3

58

62

48

685

3,0

9,1

3,3

6,4

42

45

32

930

3,7

13,5

4,1

9,7

50

53

40

1115

4,2

16,6

4,8

12,6

54

58

44

1295

4,6

19,9

5,3

15,2

58

62

48

Pressure drop

Pressure drop

Pressure drop

Pressure drop

pK

pH
kPa

Sound power air


discharge**

pH

Filter
Size

Sound power air intake**

kPa

QH
kW

Heating capacity

kPa

QK
kW

Heating capacity

Cooling capacity

kPa

QH
kW

Speed stages

[m3/h]

QK
kW

pK

Cooling capacity

Capacity stage 2

Air flow rate**

Modular (G)

Design

Capacity stage 1

Sound power casing**

Sizes 1 to 4

Compact (M)

GEA MPower-Geko Fan Coil Unit

CWP 6/12 C
tL1 = +23 C
1 = 50 % r.h.

2-Pipe Chilled Water

G3 mat filter

dB(A) dB(A) dB(A)

Terminal box (select sheet steel electric


switch box with GEA MATRIX)

1555

5,1

24,1

5,9

18,7

63

67

53

815

3,1

2,0

3,2

1,2

38

38

27

1-2-3

1150

4,1

3,3

4,6

2,4

44

45

33

2-3-4

1380

4,7

4,2

5,3

3,1

48

49

37

3-4-5

1670

5,4

5,4

6,2

4,1

52

54

42

1-3-5

Speed combination

1-2-3-4-5

2020

6,0

6,6

7,0

5,1

57

60

47

1000

4,0

3,4

4,4

2,3

40

43

30

1380

5,1

5,3

5,7

3,8

47

50

37

1730

5,9

6,9

6,7

5,2

52

55

42

2065

6,6

8,5

7,6

6,5

57

60

47

2460

7,3

10,2

8,5

7,9

62

64

51

515

2,0

3,3

2,1

2,3

40

41

29

680

2,4

4,7

2,7

3,5

44

46

34

905

2,9

6,7

3,4

5,1

52

54

41

1065

3,2

8,0

3,7

6,2

56

58

45

1190

3,4

9,1

4,0

7,1

58

62

48

685

3,0

9,1

3,3

6,4

42

45

32

925

3,7

13,4

4,1

9,6

50

53

40

1105

4,1

16,4

4,7

12,5

54

58

44

1-2-3

1275

4,5

19,5

5,2

14,8

58

62

48

2-3-4
3-4-5

4
Sheet steel electric switch box with terminal
strip or for integrated control

Speed combination
2

1515

5,0

23,4

5,9

18,4

63

67

53

805

3,1

1,9

3,2

1,2

38

38

27

1-3-5

1135

4,1

3,2

4,5

2,3

44

45

33

1-2-3-4-5

1360

4,7

4,1

5,2

3,0

48

49

37

1635

5,3

5,2

6,1

4,0

52

54

42

1965

5,9

6,4

6,8

4,9

57

60

47

1000

4,0

3,4

4,3

2,3

40

43

30

1365

5,1

5,2

5,7

3,8

47

50

37

1700

5,8

6,7

6,6

5,0

52

55

42

2015

6,5

8,3

7,5

6,3

57

60

47

2375

7,2

10,0

8,4

7,7

62

64

51

G2 mat filter

Motor thermal contact


5-speed
motor

Integrated
TC

External TC

2
Capacity stage

Medium connection - front connection


side, facing discharge

Condensate line

Ceiling

left

right

with drainage

with condensate pump ***

Data apply to basic units with filter class G2, without accessories and external
pressure. Refer to table on page 24 for other operating points.
* Capacity at max. allowed medium flow rate
** Air flow rates and sound data for capacity stage 1
*** sheet steel electrical control box necessary

12

Order
code

. U

PR-2009-0139-GB Subject to modifications Status 10/2009

Accessories/Valves

GEA MPower-Geko Fan Coil Unit

Recirculating Air Unit Cooling


2-Pipe Chilled Water, Sizes 1 to 4

Accessories

Spare filter hoses


Filter class G2

Filter class G3

Air
0
disharge**

Air intake

Box with round


connector

Flexible discharge connector

Sound attenuation module

Cover cap for round connector DN200


(irrespective of size) *
Air intake

Air discharge

Contact protection

Air intake

Suspension rail
(irrespective of
size) *

Air intake

Air discharge**

Air intake

Air discharge**

950 mm

1550 mm

2150 mm

Sizes 1 to 4
* 0, if irrespective of size
** Only for basic units in
modular configuration

Order code

Valves

MATRIX 500

MATRIX 2000

MATRIX 3000/4000

Terminal box

Connection/shut-off

Actuator

Operating voltage/circuit

2-point
open/
close
3-point
open/
stop/
close
continuous

230 V AC

2)

24 V AC1), 2)
230 V AC
24 V AC1)

230 V AC + 2 contacts

0/2 ... 10 V = 24 V AC1)

Inlet/outlet with external thread


Inlet/outlet with solder fitting
Inlet/outlet + ball trap with external thread
Inlet/outlet + ball trap with solder fitting
Inlet + ball trap/outlet + shut-off valve with external
thread
Inlet + ball trap/outlet + shut-off valve with solder
fitting

R
N

0.25
Cooling circuit

0.40
0.63

1,602)
2.50
4,002)

24 V-transformer to be provided by
others

2)

kvs-values for open/close actuators


(T,Q) only kvs 1,6 and 4,0 possible

PR-2009-0139-GB Subject to modifications Status 10/2009

Order code

4
5

kvs-values
Cooling/Heating

1.00

1)

Medium connection
L
left
R
right

0
1
2
3

03
04
06
10
16
25
40

Cooling circuit

13

Pressure Drop in Heat Exchanger, Warm and Chilled Water

GEA MPower-Geko Fan Coil Unit

Cooling in 2-pipe system

Heating in 2-pipe system

25

25

20

BG/LG*

2/1

20

4/1

1/1

2/1

3/1

15

5,0
4,5
4,0
3,5

2000

1500

2000

0,5

2000

0,6

0,5

50

0,6
600
700
800
900
1000

1,0
0,9
0,8
0,7

300
350
400
450
500

1,0
0,9
0,8
0,7

250

1,5

200

1,5

150

2,0

60
70
80
90
100

2,0

50

2,5

1500

3,0

2,5

1500

3,0

4/2
3/2

6,0

600
700
800
900
1000

5,0
4,5
4,0
3,5

300
350
400
450
500

6,0

2/2
1/2

250

3/2

200

1/2

10
9,0
8,0
7,0

150

4/2

60
70
80
90
100

2/2

Pressure drop [kPa]

10
9,0
8,0
7,0

Water flow rate Vw [l/h]

Water flow rate Vw [l/h]

Cooling in 4-pipe system

Heating in 4-pipe system


25

20

BG/LG*

2/1
1/1

20

4/1

BG/LG*
4/1

3/1

15

3/1

15

1/2
2/2

2/1

3/2
4/2

1/1

2,5

5,0
4,5
4,0
3,5
3,0
2,5

Water flow rate Vw [l/h]

2000

0,5
1500

0,6

0,5
600
700
800
900
1000

0,6
300
350
400
450
500

1,0
0,9
0,8
0,7

250

1,0
0,9
0,8
0,7

200

1,5

150

1,5

60
70
80
90
100

2,0

50

2,0

300
350
400
450
500

3,0

6,0

250

5,0
4,5
4,0
3,5

200

6,0

10
9,0
8,0
7,0

150

3/2

Pressure drop [kPa]

1/2

4/2

60
70
80
90
100

2/2

50

10
9,0
8,0
7,0

600
700
800
900
1000

25

Pressure drop [kPa]

4/1

1/1

15

Pressure drop [kPa]

BG/LG*

3/1

Water flow rate Vw [l/h]

* Size = Size, CS = Capacity stage

14

PR-2009-0139-GB Subject to modifications Status 10/2009

Power and Current Consumption

GEA MPower-Geko Fan Coil Unit

Maximum power and current consumption


Size

Speed

Motor

Air flow rate [m3/h]


Capacity [W]

Current [A]

515

100

0.66

685

131

0.74

915

184

0.86

1080

197

0.91

1215

212

0.98

685

131

0.75

930

194

0.90

1115

212

0.98

1295

233

1.07

1555

278

1.32

815

133

0.78

1150

184

0.85

1380

221

1.02

1670

264

1.22

2020

300

1.38

1000

163

0.85

1380

225

1.04

1730

264

1.21

2065

303

1.38

2460

358

1.64

Note: the current table applies for modular units, capacity stage 1 and filter class G2. Power and current consumption
decreases in other units variants and/or in case of mounted air side accessories and additional external static pressure
drop.

PR-2009-0139-GB Subject to modifications Status 10/2009

15

Capacity Overview for Different Operating Points

GEA MPower-Geko Fan Coil Unit

CWP 6/12 C
tL1 = +23 C
L1 = 50 % r.h.

Size 1

WWP 82/71 C
tL1 = +20 C

180
1: Compact basic unit (0 cap), basic unit
CS2, air intake sound attenuator, contact
protection, discharge plenum (0 cap)
2: Compact basic unit (1 cap), air intake
plenum (0 cap), discharge plenum
(1 cap)
3: Discharge sound attenuator
4: Basic unit filter class G3
5: Air intake box (1 cap)
6: Compact basic unit (2 caps), discharge
plenum (2 caps)
7: Air intake box (2 cap)

160
140
Speed 5
Static pressure [Pa]

120

Speed 4

Speed 3

100

Speed 2

80

Speed 1

60

g
f
e
d
c

40
20
0
0

200

400

600

800

1000

1200

1400

Air flow rate [m/h]

4-pipe system

2-pipe system

System

Air flow
rate

Capacity stage 1
Cooling
capacity

Pressure
drop

Heating
capacity

Q
K

pK

[m /h]

[kW]

1200

3,5

1150
1100

Capacity stage 2
Pressure
drop

Cooling
capacity

Pressure
drop

QH

Heating
capacity

Pressure
drop

pH

QK

pK

QH

pH

[kPa]

9,2

[kW]

[kPa]

[kW]

[kPa]

[kW]

[kPa]

14,8*

31,7

4,1

7,3

17,4

3,4

8,7

29,9

14,5*

31,7

4,0

7,0

16,9

3,3

28,4

8,3

14,2*

31,7

3,8

6,6

16,2

26,3

1050

3,2

7,9

13,8*

31,7

3,7

6,2

15,7

24,6

1000

3,1

7,6

13,2

30,8

3,6

5,9

15,1

22,9

950

3,0

7,1

12,8

28,9

3,5

5,5

14,5

21,3

900

2,9

6,7

12,4

27,1

3,4

5,2

14,0

20,1

850

2,8

6,2

11,9

25,3

3,2

4,8

13,5

18,6

800

2,7

5,8

11,5

23,5

3,1

4,4

12,7

16,7

750

2,6

5,3

11,0

21,7

2,9

4,0

12,2

15,4

700

2,5

4,9

10,4

19,5

2,8

3,6

11,4

13,6

650

2,3

4,4

9,8

17,5

2,6

3,3

10,8

12,2

600

2,2

4,0

9,3

15,8

2,5

2,9

10,2

11,0

550

2,1

3,6

8,7

14,0

2,3

2,5

9,4

9,5

500

1,9

3,1

8,0

12,0

2,1

2,2

8,7

8,1

450

1,8

2,7

7,3

10,2

1,9

1,8

7,9

6,9

400

1,6

2,2

6,7

8,5

1,7

1,5

7,1

5,6

1200

3,6

23,5

6,4*

12,7

3,5

9,2

7,9*

16,7

1150

3,5

22,5

6,3*

12,7

3,4

8,7

7,8*

16,7

1100

3,4

21,5

6,1*

12,7

3,3

8,3

7,6*

16,7

1050

3,3

20,4

6,0*

12,7

3,2

7,9

7,5*

16,6

1000

3,2

19,4

5,9*

12,7

3,1

7,6

7,4*

16,6

950

3,1

18,3

5,8*

12,7

3,0

7,1

7,2*

16,6

900

3,0

17,5

5,7*

12,7

2,9

6,7

7,1*

16,6

850

2,9

16,4

5,6*

12,7

2,8

6,2

6,9*

16,6

800

2,8

15,3

5,4*

12,7

2,7

5,8

6,7*

16,6

750

2,7

14,1

5,3*

12,7

2,6

5,3

6,5*

16,6

700

2,6

13,0

5,2*

12,7

2,5

4,9

6,3*

16,6

650

2,5

11,9

5,0*

12,7

2,3

4,4

6,1*

16,6

600

2,4

11,0

4,8*

12,7

2,2

4,0

5,9*

16,6

550

2,2

9,8

4,6*

12,7

2,1

3,6

5,6*

16,6

500

2,1

8,6

4,4*

12,7

1,9

3,1

5,3*

16,6

450

1,9

7,6

4,2

11,5

1,8

2,7

5,0*

16,6

400

1,8

6,4

3,9

10,2

1,6

2,2

4,7*

16,5

* Capacity at max. allowed medium flow rate

16

PR-2009-0139-GB Subject to modifications Status 10/2009

Overview of Acoustic Data for Different Operating Points

GEA MPower-Geko Fan Coil Unit

Size 1

Sound power level free air intake and discharge


(Modular configuration, capacity size 1, filter class G2)
Speed

Measure point

Sound power level LW [dB]


Octave centre frequency [Hz]

not rated

rated

63

125

250

500

1000

2000

4000

8000

[dB]

[dB(A)]

Air intake

42

43

44

39

30

21

48

40

Air discharge

42

45

43

39

36

26

49

41

Casing

34

36

34

25

18

40

29

Air intake

47

48

48

44

36

29

19

53

44

Air discharge

46

49

48

45

41

34

28

53

46

Casing

38

40

39

30

24

16

10

44

33

Air intake

53

55

56

52

44

39

33

27

60

52

Air discharge

52

55

56

52

50

43

39

31

61

54

Casing

45

47

47

38

32

26

22

12

51

41

Air intake

56

59

59

55

48

43

38

34

64

56

Air discharge

54

59

59

56

54

48

44

36

64

58

Casing

47

51

50

42

36

30

27

18

55

45

Air intake

59

61

62

58

51

46

42

38

66

58

Air discharge

58

61

62

59

58

51

48

42

67

61

Casing

50

53

53

44

39

33

31

23

57

48

Sound power level with other operating points


Sum level LW
[dB(A)]

Air flow rate


[m/h]
1200

Air intake

Air discharge

58

Casing

61

48

1150

58

61

47

1100

58

61

47

1050

56

58

58

61

45

47

1000

56

58

58

60

45

47

950

56

57

58

60

45

46

900

52

56

57

54

58

60

41

45

46

850

53

56

57

55

58

60

42

45

46

800

53

56

57

55

58

59

42

45

46

750

53

56

57

55

58

59

42

45

45

700

54

56

57

55

58

59

42

45

45

650

47

54

56

56

49

56

58

59

36

43

44

45

600

50

55

56

53

56

57

39

43

44

550

53

55

56

56

43

43

500

42

56

43

60

31

46

450

47

49

37

400

53

55

43

Speed

Acoustic insulation of sound attenuator (accessories)


Octave centre frequency [Hz]

Acoustic insulation [dB]

Sum level

63

125

250

500

1000

2000

4000

8000

16

21

25

17

13

PR-2009-0139-GB Subject to modifications Status 10/2009

approx. LW
[dB]

Intake

10

Air discharge

12

17

Capacity Overview for Different Operating Points


Size 2

GEA MPower-Geko Fan Coil Unit

CWP 6/12 C
tL1 = +23 C
L1 = 50 % r.h.

WWP 82/71 C
tL1 = +20 C

1:
2:
3:
4:

Contact protection
Basic unit CS2
Air intake sound attenuator
Compact basic unit (0 caps),
discharge plenum (0 caps)
5: Air intake box (0 caps)
6: Discharge sound attenuator
7: Compact basic unit (1 cap), discharge
plenum (1 cap)
8: Basic unit filter class G3
9: Air intake box (1 cap)
10: Compact basic unit (2 caps),
discharge plenum (2 caps)
11: Air intake box (2 caps)

Speed 5

Static pressure [Pa]

Speed 4
Speed 3
Speed 2

Speed 1

e
d
c

Air flow rate [m/h]

4-pipe system

2-pipe system

System

Air flow
rate

Capacity stage 1

Capacity stage 2

Cooling
capacity

Pressure
drop

Heating
capacity

Pressure
drop

Cooling
capacity

Pressure
drop

Heating
capacity

Pressure
drop

QK

pK

QH

pH

QK

pK

QH

pH

[m /h]

[kW]

[kPa]

[kW]

[kPa]

[kW]

[kPa]

[kW]

[kPa]

1550

5,1

24,0

19,3*

39,2

6,0

19,0

22,5*

39,1

1500

5,0

23,1

18,9*

39,2

5,9

18,6

22,0*

39,1

1440

4,9

22,5

18,5*

39,2

5,7

17,6

21,4*

39,1

1380

4,8

21,4

18,1*

39,2

5,6

16,7

20,8*

39,1

1320

4,6

20,3

17,6*

39,1

5,4

15,8

20,4*

39,1

1260

4,5

19,2

17,1*

39,1

5,2

14,8

19,8*

39,0

1200

4,4

18,1

16,7*

39,1

5,0

13,9

18,9*

39,0

1140

4,2

17,1

16,2*

39,1

4,8

13,0

18,3*

39,0

1080

4,1

16,0

15,7*

39,1

4,7

12,2

17,6

37,6

1020

3,9

14,9

15,1*

39,1

4,5

11,2

17,0

35,3

960

3,8

14,1

14,5*

39,1

4,3

10,3

16,0

31,6

900

3,6

12,9

13,8*

39,1

4,0

9,3

15,3

29,1

840

3,4

11,8

13,2

38,0

3,8

8,4

14,3

25,8

780

3,3

10,7

12,4

33,6

3,6

7,7

13,5

23,0

720

3,1

9,6

11,7

30,4

3,4

6,9

12,6

20,4

660

2,9

8,6

10,9

26,7

3,2

6,0

11,6

17,6

600

2,7

7,4

10,1

23,0

2,9

5,2

10,7

15,0

1550

5,0*

53,8

8,3*

17,1

5,1

24,0

10,2*

22,6

1500

4,9*

53,8

8,3*

17,1

5,0

23,1

10,0*

22,6

1440

4,8*

53,8

8,1*

17,1

4,9

22,5

9,9*

22,6

1380

4,8

51,2

8,0*

17,1

4,8

21,4

9,7*

22,6

1320

4,6

48,7

7,9*

17,1

4,6

20,3

9,5*

22,5

1260

4,5

46,2

7,7*

17,1

4,5

19,2

9,4*

22,5

1200

4,4

43,7

7,6*

17,1

4,4

18,1

9,3*

22,5

1140

4,2

41,2

7,4*

17,1

4,2

17,1

9,0*

22,5

1080

4,1

38,7

7,3*

17,1

4,1

16,0

8,8*

22,5

1020

4,0

36,7

7,1*

17,1

3,9

14,9

8,6*

22,5

960

3,8

34,1

6,9*

17,1

3,8

14,1

8,3*

22,5

900

3,6

31,4

6,7*

17,0

3,6

12,9

8,1*

22,4

840

3,5

28,8

6,6*

17,0

3,4

11,8

7,9*

22,4

780

3,3

26,7

6,3*

17,0

3,3

10,7

7,6*

22,4

720

3,1

23,8

6,1*

17,0

3,1

9,6

7,3*

22,4

660

2,9

21,0

5,9*

17,0

2,9

8,6

7,0*

22,4

600

2,7

18,7

5,6*

17,0

2,7

7,4

6,7*

22,4

* Capacity at max. allowed medium flow rate

18

PR-2009-0139-GB Subject to modifications Status 10/2009

Overview of Acoustic Data for Different Operating Points

GEA MPower-Geko Fan Coil Unit

Size 2

Sound power level free air intake and discharge


(Modular configuration, capacity size 1, filter class G2)
Speed

Measure point

Sound power level LW [dB]


Octave centre frequency [Hz]

not rated

rated

63

125

250

500

1000

2000

4000

8000

[dB]

[dB(A)]

Air intake

45

48

46

40

35

32

23

51

43

Air discharge

44

48

47

44

39

33

25

52

45

Casing

36

40

37

28

22

17

43

32

Air intake

53

56

53

48

43

38

34

26

59

50

Air discharge

51

56

55

52

48

43

39

31

60

53

Casing

44

48

45

36

30

25

22

12

51

40

Air intake

63

60

58

52

47

43

39

35

66

54

Air discharge

57

60

60

56

53

47

45

39

65

58

Casing

53

52

50

40

35

30

28

20

57

44

Air intake

58

63

61

55

52

47

43

40

67

58

Air discharge

59

64

64

59

57

51

49

44

69

62

Casing

51

56

54

44

39

34

32

25

59

48

Air intake

63

68

65

59

57

52

49

46

71

62

Air discharge

62

67

69

64

62

56

54

49

73

67

Casing

54

60

58

48

44

38

37

31

63

53

Sound power level with other operating points


Sum level LW
[dB(A)]

Air flow rate


[m/h]
1550

Air intake

Air discharge

62

Casing

67

53

1500

62

66

52

1440

62

66

52

1380

61

65

51

1320

61

64

51

1260

58

60

62

64

48

50

1200

58

60

61

63

48

50

1140

57

60

61

63

47

49

1080

54

57

59

58

60

62

44

47

48

1020

55

57

59

58

60

61

44

47

48

960

55

57

58

58

60

61

44

46

47

900

50

55

57

58

54

57

59

60

40

44

46

47

840

51

55

57

54

57

59

41

44

46

780

52

55

54

57

41

44

720

53

55

55

57

42

44

660

46

54

48

55

35

42

600

53

54

42

Speed

Acoustic insulation of sound attenuator (accessories)


Octave centre frequency [Hz]

Acoustic insulation [dB]

Sum level

63

125

250

500

1000

2000

4000

8000

16

21

25

17

13

PR-2009-0139-GB Subject to modifications Status 10/2009

approx. LW
[dB]

Intake

10

Air discharge

12

19

Capacity Overview for Different Operating Points


Size 3

GEA MPower-Geko Fan Coil Unit

CWP 6/12 C
tL1 = +23 C
1 = 50 % r.h.

WWP 82/71 C
tL1 = +20 C

160
1:
2:
3:

140

Static pressure [Pa]

120

Speed 5
Speed 4

100

Speed 3
80

Speed 2

60

Contact protection
Basic unit CS2 intake sound attenuator
Compact basic unit (0 caps), discharge
plenum (0 caps)
4: Air intake box (0 caps)
5: Compact basic unit (1 cap), discharge
plenum (1 cap), discharge sound
attenuator
6: Basic unit filter class G3
7: Air intake box (1 cap)
8: Compact basic unit (2 caps), discharge
plenum (2 caps)
9: Air intake box (2 caps)
10: Compact basic unit (3 caps), discharge
plenum (3 caps)
11: Air intake box (3 cap)

Speed 1

40

20
0
0

500

1000

1500

e
d
c

2000

2500

Air flow rate [m/h]

4-pipe system

2-pipe system

System

Air flow
rate

Capacity stage 1
Cooling
capacity

Pressure
drop

Heating
capacity

QK

pK

[m /h]

[kW]

2000

6,0

1900
1800

Capacity stage 2
Pressure
drop

Cooling
capacity

Pressure
drop

QH

Heating
capacity

Pressure
drop

pH

QK

pK

QH

pH

[kPa]

6,5

[kW]

[kPa]

[kW]

[kPa]

[kW]

[kPa]

26,1

27,4

7,0

5,1

29,9

5,8

6,2

20,7

25,2

25,8

6,8

4,8

28,7

5,7

5,9

19,2

24,3

24,1

6,5

4,5

27,5

17,7

1700

5,4

5,5

23,5

22,5

6,3

4,2

26,6

16,7

1600

5,2

5,1

22,6

20,9

6,0

3,9

25,5

15,3

1500

5,0

4,7

21,6

19,4

5,7

3,5

23,9

13,7

1400

4,8

4,3

20,7

17,8

5,4

3,2

22,7

12,4

1300

4,5

3,9

19,4

15,8

5,1

2,9

21,5

11,3

1200

4,3

3,5

18,2

14,0

4,8

2,5

20,0

9,8

1100

4,0

3,1

17,2

12,6

4,4

2,2

18,8

8,7

1000

3,7

2,7

15,8

10,8

4,1

1,9

17,2

7,4

900

3,4

2,3

14,7

9,4

3,6

1,5

15,7

6,3

800

3,0

1,9

13,2

7,7

3,2

1,2

14,1

5,1

700

2,7

1,5

11,8

6,3

2,9

1,1

12,6

4,1

600

2,3

1,2

10,4

5,0

2,7

0,9

10,9

3,2

500

2,1

0,9

8,8

3,7

2,4

0,7

9,2

2,3

2000

6,5

38,2

10,2*

21,6

6,0

6,5

14,5*

24,7

1900

6,4

36,7

10,0*

21,6

5,8

6,2

14,2*

24,7

1800

6,1

34,5

9,8*

21,5

5,7

5,9

13,9*

24,7

1700

5,9

32,4

9,7*

21,5

5,4

5,5

13,5*

24,7

1600

5,7

30,2

9,5*

21,5

5,2

5,1

13,1*

24,7

1500

5,5

28,0

9,2*

21,5

5,0

4,7

12,9*

24,7

1400

5,2

25,9

9,0*

21,5

4,8

4,3

12,5*

24,6

1300

5,0

24,1

8,8*

21,5

4,5

3,9

12,0*

24,6

1200

4,8

21,8

8,6*

21,5

4,3

3,5

11,5*

24,6

1100

4,5

19,5

8,2*

21,4

4,0

3,1

11,0*

24,6

1000

4,2

17,3

7,9*

21,4

3,7

2,7

10,5*

24,6

900

3,9

15,1

7,5*

21,4

3,4

2,3

9,9*

24,6

800

3,6

12,7

7,1*

21,4

3,0

1,9

9,3*

24,6

700

3,2

10,8

6,7*

21,4

2,7

1,5

8,5

23,4

600

2,9

8,7

6,2*

21,3

2,3

1,2

7,7

19,3

500

2,5

6,7

5,6*

21,3

2,1

0,9

6,8

15,3

* Capacity at max. allowed medium flow rate


= for values in sample calculation refer to pages 24 - 27

20

PR-2009-0139-GB Subject to modifications Status 10/2009

Overview of Acoustic Data for Different Operating Points

GEA MPower-Geko Fan Coil Unit

Size 3

Sound power level free air intake and discharge


(Modular configuration, capacity size 1, filter class G2)
Speed

Measure point

Sound power level LW [dB]


Octave centre frequency [Hz]

not rated

rated

63

125

250

500

1000

2000

4000

8000

[dB]

[dB(A)]

Air intake

42

43

42

36

29

47

38

Air discharge

42

42

42

36

33

19

47

38

Casing

34

34

33

22

16

39

27

Air intake

47

49

48

42

36

27

53

44

Air discharge

47

48

47

43

40

33

23

53

45

Casing

39

41

39

29

22

15

44

33

Air intake

50

53

52

46

40

33

25

57

48

Air discharge

50

52

52

47

44

38

30

57

49

Casing

42

44

43

33

26

20

13

48

37

Air intake

54

57

57

51

45

38

33

25

61

52

Air discharge

55

57

56

52

49

43

38

29

62

54

Casing

47

49

48

38

31

26

21

10

53

42

Air intake

60

62

61

55

50

44

40

35

66

57

Air discharge

61

62

61

57

54

49

45

38

67

60

Casing

52

54

52

43

37

31

28

20

58

47

Sound power level with other operating points


Air flow rate

Sum level LW [dB(A)]

[m/h]
2000

Air intake

Air discharge

57

Casing

60

47

1900

57

59

47

1800

57

59

46

1700

57

59

46

1600

53

57

59

42

46

1500

53

57

55

59

43

46

1400

54

57

56

59

43

46

1300

49

54

57

50

56

59

38

44

46

1200

50

55

57

52

57

59

39

44

46

1100

45

51

55

57

46

53

57

59

34

41

45

46

1000

46

53

56

57

48

54

58

59

36

42

45

46

900

48

54

56

57

50

55

58

59

37

43

46

46

800

38

50

55

57

39

52

57

59

27

39

44

46

700

43

52

57

43

54

58

32

41

46

600

47

54

58

48

56

59

37

43

47

500

52

56

53

58

41

45

Speed

= for values in sample calculation refer to pages 24 - 27

Acoustic insulation of sound attenuator (accessories)


Octave centre frequency [Hz]

Acoustic insulation [dB]

Sum level

63

125

250

500

1000

2000

4000

8000

16

21

25

17

13

PR-2009-0139-GB Subject to modifications Status 10/2009

approx. LW
[dB]

Intake

10

Air discharge

12

21

Capacity Overview for Different Operating Points


Size 4

GEA MPower-Geko Fan Coil Unit

CWP 6/12 C
tL1 = +23 C
1 = 50 % r.h.

WWP 82/71 C
tL1 = +20 C

160
1:
2:
3:
4:

140
120

Speed 5

Static pressure [Pa]

Speed 4

100

Speed 3

80

Speed 2

Speed 1

60

Contact protection
Basic unit CS2, intake sound attenuator
Air intake box (0 caps)
Compact basic unit (0 cap), basic unit
filter class G3, air intake plenum (1 cap),
air discharge plenum (0 cap)
5: Discharge sound attenuator
6: Compact basic unit (1 cap), discharge
plenum (1 cap)
7: Air intake box (2 caps)
8: Compact basic unit (2 caps), discharge
plenum (2 caps)
9: Air intake box (3 cap)
10: Compact basic unit (3 caps), discharge
plenum (3 caps)

40

20
0
0

500

1000

1500

2000

e
d
c
2500

Air volume flow [m/h]

System

Air flow
rate

Cooling
capacity

2-pipe system

Pressure
drop

Cooling
capacity

Capacity stage 2
Pressure
Heating
drop
capacity

Pressure
drop

pK

QH

pH

QK

pK

QH

[m3/h]

[kW]

[kPa]

[kW]

[kPa]

[kW]

[kPa]

[kW]

[kPa]

2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700

7,2
7,1
6,9
6,7
6,5
6,3
6,1
5,8
5,6
5,4
5,1
4,9
4,6
4,3
4,0
3,7
3,3
2,9
7,5*
7,4*
7,2*
7,1
6,9
6,7
6,5
6,2
6,0
5,8
5,6
5,3
5,0
4,7
4,4
4,0
3,7
3,4

9,9
9,6
9,1
8,7
8,2
7,7
7,2
6,7
6,2
5,8
5,4
4,9
4,4
3,9
3,4
2,9
2,4
1,9
51,6
51,6
51,6
49,0
46,4
43,8
41,2
38,6
36,0
33,9
31,1
28,4
25,7
23,2
20,2
17,4
15,2
12,6

30,4*
29,8*
29,1*
28,4*
27,3*
26,3
25,4
24,5
23,6
22,3
21,1
20,1
18,9
17,5
16,2
14,9
13,6
12,1
11,4*
11,3*
11,1*
10,9*
10,8*
10,6*
10,4*
10,2*
10,0*
9,7*
9,5*
9,2*
8,9*
8,5*
8,2*
7,8*
7,4*
6,9*

30,9
30,9
30,9
30,9
30,9
29,7
27,9
26,0
24,2
21,8
19,7
18,0
16,1
13,9
12,1
10,3
8,8
7,0
23,8
23,8
23,8
23,8
23,8
23,8
23,8
23,8
23,7
23,7
23,7
23,7
23,7
23,6
23,6
23,6
23,6
23,5

8,5
8,3
8,1
7,8
7,5
7,3
7,0
6,7
6,4
6,1
5,8
5,5
5,1
4,8
4,4
4,0
3,5
3,1
7,2
7,1
6,9
6,7
6,5
6,3
6,1
5,8
5,6
5,4
5,1
4,9
4,6
4,3
4,0
3,7
3,3
2,9

7,9
7,6
7,2
6,8
6,4
5,9
5,5
5,1
4,7
4,3
3,9
3,5
3,1
2,7
2,3
2,0
1,6
1,2
9,9
9,6
9,1
8,7
8,2
7,7
7,2
6,7
6,2
5,8
5,4
4,9
4,4
3,9
3,4
2,9
2,4
1,9

35,3
34,2
33,1
31,9
31,0
29,9
28,7
27,1
26,1
24,8
23,4
22,0
20,5
19,0
17,6
15,9
14,3
12,7
16,3*
16,0*
15,8*
15,4*
15,1*
14,8*
14,3*
14,2*
13,8*
13,4*
12,9*
12,4*
12,0*
11,5*
10,9*
10,3*
9,7*
9,0*

30,1
28,4
26,6
24,8
23,6
22,0
20,4
18,4
17,2
15,5
14,0
12,5
10,9
9,5
8,2
6,9
5,6
4,5
26,2
26,1
26,1
26,1
26,1
26,1
26,1
26,1
26,1
26,1
26,1
26,1
26,1
26,1
26,1
26,0
26,0
26,0

QK

4-pipe system

Capacity stage 1
Pressure
Heating
drop
capacity

pH

* Capacity at max. allowed medium flow rate

22

PR-2009-0139-GB Subject to modifications Status 10/2009

Overview of Acoustic Data for Different Operating Points

GEA MPower-Geko Fan Coil Unit

Size 4

Sound power level free air intake and discharge


(Modular configuration, capacity size 1, filter class G2)
Speed

Measure point

Sound power level LW [dB]


Octave centre frequency [Hz]

not rated

rated

63

125

250

500

1000

2000

4000

8000

[dB]

[dB(A)]

Air intake

46

47

45

37

32

22

51

40

Air discharge

46

49

45

41

36

28

18

52

43

Casing

38

40

36

26

19

10

43

31

Air intake

51

54

52

45

39

33

27

58

47

Air discharge

49

54

52

48

44

37

32

58

50

Casing

43

46

43

33

26

20

15

49

37

Air intake

56

59

57

50

44

39

35

26

62

52

Air discharge

56

59

57

53

49

43

39

30

63

55

Casing

48

51

48

38

31

26

22

12

54

42

Air intake

60

64

61

55

49

44

41

36

67

57

Air discharge

60

64

62

58

54

49

46

39

68

60

Casing

52

56

53

42

36

31

29

21

59

47

Air intake

63

68

66

59

54

49

46

43

71

62

Air discharge

64

67

67

62

59

54

51

45

72

64

Casing

56

60

57

46

41

36

34

27

63

51

Sound power level with other operating points


Sum level LW
[dB(A)]

Air flow rate


[m/h]
2400

Air intake

Air discharge

62

Casing

64

51

2300

61

64

51

2200

61

63

50

2100

61

63

50

2000

60

62

50

1900

57

60

60

62

47

49

1800

57

60

60

62

47

49

1700

52

57

59

55

59

61

42

47

48

1600

53

57

59

55

59

61

43

47

48

1500

54

57

59

56

59

60

43

47

48

1400

54

57

56

59

44

47

1300

48

55

57

51

56

59

38

44

47

1200

50

56

52

57

40

45

1100

51

56

53

57

41

45

1000

40

53

57

43

54

58

31

42

46

900

45

54

47

55

35

43

800

49

55

51

57

39

45

700

54

55

43

Speed

Acoustic insulation of sound attenuator (accessories)


Octave centre frequency [Hz]

Acoustic insulation [dB]

Sum level

63

125

250

500

1000

2000

4000

8000

16

21

25

17

13

PR-2009-0139-GB Subject to modifications Status 10/2009

approx. LW
[dB]

Intake

10

Air discharge

12

23

Samples for Capacity Definition

GEA MPower-Geko Fan Coil Unit

The tables with capacity data on pages 6 to 12 indicated cooling and heating capacity
as well as sound power level of the GEA MPower-Geko of modular configuration with
a G2 filter and without mounted air side accessories and/or additional external static
pressure.
A different unit configuration and using air side accessories like air intake and discharge plenums or sound attenuation modules change internal and external air side
resistance. Air ducts and discharges connected by others can increase air side static
pressure drop that must be covered by the GEA MPower-Geko. In such a way the air
flow rate of the unit decreases which results in reduced cooling and/or heating capacity. The sound level emitted in air ducts by others and via unit casing is also influenced
by the size of air side resistance.
The diagrams and tables given on pages 14 to 23 make it possible to calculate performance data for such operating conditions that are different from "a least complicated
situation".

Example
Cooling load:
Max. sound pressure level:
Accessories:

Filter class:
External static pressure
drop:
1. Pre-selection of unit size

Air flow rate:


Cooling capacity:
Sound power level:

The following sample demonstrates the basic procedure:


1: Pre-selection of unit size
2: Determination of unit characteristics curve and actual operating point.
3: Calculation of actual cooling and/or heating capacity
4: If necessary - conversion of calorific output in other air/medium units
5: Determination of actual sound power level
6: Calculation of expected indoor sound pressure level
In an open plan office with a suspended ceiling of size 20 x 10 x 4 m 2 GEA MPowerGekos in compact configuration are to be installed:
8 kW at air intake 23C/50 % r.h. and chilled water 6/12 C (total indoor cooling load)
45 dB(A) as of VDI 2081
2 discharge cover caps DN200 (only 3 out of 5 connectors should be used)
Air intake sound attenuator
Intake flexible connection
G3
35 Pa at 1000 m/h (per unit)
Based on the projected air flow rate of around 1000 m/h and max. allowed sound level
unit size 3 in capacity stage 2 and speed 2 is selected. The following preliminary capacity is calculated:
1000 m/h at app. 40 Pa static pressure (refer to unit curve speed 2, page 20)
4,1 kW (refer to table Overview of capacity for different operating points size 3
page 20)
48 dB(A) (refer to table Sound power level with other operating points on page 21)*
*) Note: In this case only discharge related sound level is considered, because a sound attenuator is provided on the intake side.

2. Determination of unit
curve
Example

In characteristics curve field on page 20 the curve of external static pressure drop is
entered. The points of the curve can be calculated using the formula
dp2 = dp1 * (V2/V1).
dp1 = 35 Pa
V1 = 1000 m/h
V2 = 1500 m/h
dp2 = 35 Pa * (1500/1000) = 78,8 Pa
Characteristics curves of additional unit internal pressure drops (capacity stage 2 and
filter class G3) and pressure drops of air side accessories (air intake sound attenuator,
compact basic unit with 2 caps) are added up to unit characteristics curve which is a
sum of all additional external and internal pressure drops.

24

PR-2009-0139-GB Subject to modifications Status 10/2009

Samples for Capacity Definition

GEA MPower-Geko Fan Coil Unit

Example

The task is to arrive at the sum of individual pressure losses at V = 1500 m/h
dp Capacity stage 2 = 5,0 Pa (as indicated on curve)
dp Intake sound attenuator = 5,0 Pa (as indicated on curve)
dp Filter class G3 = 12,5 Pa (as indicated on curve)
dp Compact basic unit 2 caps = 19,5 Pa (as indicated on curve)
dp External = 78,8 Pa (based on previous sample calculation)
dp unit = (5,0 + 5,0 + 12,5 + 19,5 + 78,8) Pa = 120,8 Pa
The intersection point of this unit curve with the unit curve of speed 2 is identical to the
actual operating point of unit at speed 2.
This results in air flow rate of around 980 m/h (refer to Fig. 11).

160
140

Unit characteristics curve

120

External static pressure drop

Static pressure [Pa]

100

Speed 2

80
60
40

Compact basic unit with 2 caps

Filter class G3

20

Air intake attenuator


Capacity stage 2

0
0

500

980

1000

1500

2000

2500

Air flow rate [m/h]

Fig. 11: Size 3 - curve field

3. Determination of actual
cooling capacity

The actual cooling capacity can be interpolated from table data on page 20. This
results in cooling capacity of around 4,0 kW.

4. Determination of actual
sound power level of unit.

Using tables Sound power level with different operating points (refer to page 21) the
sound power level of the basic unit can be interpolated on air intake, discharge side
and acoustic emission of casing. Air flow rate of 980 m/h at speed 2 results in the
following values:
LW intake: approx. 47 dB(A)
LW discharge: approx. 49 dB(A)
LW casing: approx. 36 dB(A)
Because a sound attenuator is mounted on the intake side, the acoustic insulation of
sound attenuator (LW = ca. 10 dB intake side, refer to table Acoustic insulation of
sound attenuator - sum level, page 21) must be deducted from the previously calculated value:
LW air intake (sound attenuator): approx 37 dB(A)

5. Calculation of expected
indoor sound pressure
level

Tables on pages 6 to 13 (unit selection) and 16 to 23 (Overview of capacity) present


sound power level of basic units on air intake and discharge sides as well as unit casing
acoustic emission. These data correspond to unit acoustic emission energy. In order

PR-2009-0139-GB Subject to modifications Status 10/2009

25

Samples for Capacity Definition

GEA MPower-Geko Fan Coil Unit

to determine actual sound level perceived by human ear at a certain point indoors,
different factors need to be considered.
Sound energy emitted in the air ductwork by others is usually absorbed (= reduced)
thanks to absorption and reflection process. The manufacturer usually provides information on certain components, e.g. acoustic insulation of a sound attenuator. Other
influencing factors can be e.g. material and form of air ducts, form and number of cross
section changes, duct ramifications, etc. As a rule, these can be estimated based on
the empirical data of the manufacturer.
Sound energy emitted by unit casing in room direction is usually reduced only by the
suspended ceiling. In this case material type and ceiling thickness as well as possibly
used addition insulating material of suspended ceiling play a key role (e.g. mineral wool
coating).
Supply and exhaust air flow entering and leaving the room through air ducts generates
flow noise, that to a great extent depends on the used product (refer to manufacturer
specifications). If the difference between sound level before the air duct opening and
specific sound level of duct opening amounts to more than 10 dB, the increase of the
total level is to be neglected. If the difference is smaller - the level with a higher figure
must be increased by the level difference which is calculated according to the following
formula:

L = 10 * log (1+10^(L1-L2)/10)
In our example it is assumed that only one duct opening is used for each unit and the
specific sound level difference exceeds 10 dB.
In order to define the anticipated indoor sound pressure level - the previously calculated A-rated sound power level is used in connection with a conversion
diagram Fig. 12.
Conversion of sound power level in sound pressure level
FFac
abtro
ikr-y

aimnmd

10

RWeo
shi

ndre

10
12
15

20

20
50
HKo
rs
ap

0,4

30

800 m 3

25

8
4
2

Fig. 12

4 5 6

8 10

15 20

Distance
from
sound source
Abstand
von der
Schallquelle
[ m ] [m]

30 40

60 70

50
Direction
coefficient
Richtungsfaktor

Unit tis
the middle
Ger
istmounted
frei in derfree
Mitteineiner
Fl che of a surface

200
500
1000
2000
5000

Unit
twoRaumfl
indoor surfaces
Gerborders
t grenztwith
anzwei
chen

100

el

35

0,5

Lggarroor
geee
K
chircu
amred
hrecn
rs,, k
CoK
hes
slemin
nofne
aellK
freeren
cirhchu
nczer
e
rnch
ruomo
es
em
, Tsh
, etaht
De
eear t
paar
K
r es
ufthm
euns t
ersto
CoM
res
nucse
ikrztim
hm
alelsr

nkitea
nlzw
im

2
2 Sabin
Absorbtionsflsurface
che [ m[m
]
Absorption
Sabin]

hsaw
lleinm
min
a=
SScc
gp
0,03
ulro
nutmia hho
ool
l
ucm
el, a
s
l
a
e
B
s
rerao
sro
=0
LReesad
s
s,, Ho
om
,05
es ing
o
s
ftfeiclz
le, ro
eim
Ferom
s,mhe
=
nses,
or te
hstTV
0
,
1
l
udios
stud
=
ios
RRa
0,1
ud
5
ndiof
us
=
ntkusd
tuido
0,2
ss
io
5

Ger borders
t grenzt with
an drei
Raumfl
chen
Unit
three
indoor
surfaces

26

u.hSa
cllhsw

eeif
FFr e

Sound
level difference L=LW
L=LW- LP
- LP
[dB]
Schallpegeldifferenz
[dB]

100

200

500

1000 2000

5000 10000

30000

Raumvolumen
m 33]]
Room volume[ [m

Absorption factor
A wall surface that absorbs all sound waves that hit it has an absorption
factor of a = 1. The above am values represent the relationship between the
actual and ideal absorption performance of a wall. They represent mean
values.
Absorption surface m2 (Sabin)
This is the surface that completely absorbs all sound waves that hit it. It is
not identical to the entire room surface.

PR-2009-0139-GB Subject to modifications Status 10/2009

Samples for Capacity Definition

GEA MPower-Geko Fan Coil Unit

1. Based on the room volume (800 m3), an absorption surface of approx. 100 m2 Sabin
is estimated in accordance with the diagram Fig. 12Homes, offices, hotel rooms, conference rooms.

2. The mean distance to the duct opening is assumed to be approx. 3 m and the direction coefficient to be 2, Fig. 13. The intersection of the dotted sample lines in the diagram Fig. 12 mounts to the sound level difference: L~12 dB.

Direction coefficient 2
(hemispherical radiation): unit is mounted free in the middle of a surface
Direction coefficient 4
(quarter-spherical radiation): unit borders with two room surfaces
Direction coefficient 8
(eight-spherical radiation): unit borders with three room surfaces

Sound level increase in dB

Fig. 13: Direction coefficient

3. The anticipated A-rated sound pressure


level LP for a unit is thus:
LP = LW L = 49 dB(A) 12 dB = 37 dB(A)

10
9
8
7
6
5
4
3
2
1
1

Sound level in case of 2 discharge openings increases according to the


diagram Fig. 14, by approx. 3 dB.

5 6

8 10

Number of units

Fig. 14: Sound level increase (dB)

Thus, the anticipated sound pressure level in the room amounts to:
LPges. = LP + 3 dB = 37 dB(A) + 3 dB = 40 dB(A)
The approximate value for increased requirements (large office 45 dB (A) in table Fig.
15) is thus fulfilled.
Table A-sound pressure level LP1 as approximate value according to VDI 2081
Room type
Apartment
(Hotel room) night
Residential rooms day
Auditoriums
TV studio
Concert halls
Operas
Theatre
Cinema
Lecture halls
Reading rooms
Seminar rooms
Classrooms
Offices
Conference rooms
Leisure rooms
Break rooms
Small offices
Large offices
Church
Museums
Service halls
IT/Telecommunication room
Laboratories
Restaurants
Kitchens
Sales rooms

A-sound level [dB(A)]

Mean reverberation time [s]

*
35/30
35

**
30/25
30

0.5
0.5

30
30
30
35
40
40
40
40
40

25
25
25
30
30
35
35
35
35

1.5
2.0
1.5
1.0
1.0
1.0
1.0
1.0
1.0

40
40
40
40
50
35
40
45
55
45
40
45
45

35
35
35
35
45
25
35
40
40
40
552
602
602

1.0
0.5
0.5
0.5
0.5
3.0
1.5
1.5
1.5
2.0
1.0
1.5
1.0

to
to
to

Fig. 15
* = Mimimum requirements
** = Increased requirements
1
2

Also refer to applicable building regulations, DIN standards and VDI guidelines (e.g. DIN 4109, DIN 1946, VDI 2058)
Depending on application

PR-2009-0139-GB Subject to modifications Status 10/2009

27

Installation Samples

GEA MPower-Geko Fan Coil Unit

On-Demand Mounting of Intake and Discharge Side Accessories

Modular Version

Compact Version

Fig. 16: Modular basic unit without accessories

Fig. 17: Compact basic unit without accessories

Fig. 18: Modular unit with air discharge box

Fig. 19: Compact unit with air intake box

Fig. 20: Air intake and discharge box

Fig. 21: Air intake flexible connection + air intake sound


attenuator

Fig. 22: Intake flexible connection + discharge sound attenuator


+ discharge box

Fig. 23: Air intake box + air intake sound attenuator

Fig. 24: Air intake box + air intake sound attenuator + air discharge sound attenuator + discharge box
28

PR-2009-0139-GB Subject to modifications Status 10/2009

Dimensions of Basic Units

GEA MPower-Geko Fan Coil Unit

Fig. 25: Dimensions modular unit type


Recommended service opening for maintenance work on
the basic unit

1: Condensate tray
2: Service panel
3: Filter behind cover strip
*) Dimensions of basic unit and service opening
Fig. 26

Fig. 27: Dimensions compact unit type

Dimensions
Size

b
[mm]

bmax
[mm]

B
[mm]

682

1060

1260

982

1360

1560

1282

1660

1860

1432

1810

2010

PR-2009-0139-GB Subject to modifications Status 10/2009

Please consider that possibly further or larger openings


must be provided if accessories are mounted.

29

Dimensions of Basic Units

GEA MPower-Geko Fan Coil Unit

Minimum mounting clearances

Fig. 28
Medium connections (warm/chilled water)

Medium connections (warm/chilled water)

2
1
2-pipe system heat
exchanger CS1 and CS2

Size

Capacity stage
1

Connections: 1/2" internal


thread

190

165

Fig. 29

4-pipe system heat


exchanger with heating
and cooling circuit

Size

Connections: 1/2" internal


thread

Capacity stage
1

215

215

190

165

30

30

Pos. 1: cooling

80

55

Pos. 2: heating

205

230

255

255

Fig. 30

Unit weight and water charge of heat exchanger


Weight1)
[kg]

Water charge [l]

Size
Modular type

1) Max.

30

4-pipe

Compact
type

2-pipe
Cooling circuit

Heating circuit

CS 1

CS 2

CS 1

CS 2

CS 1

CS 2

37

46

1.64

2.10

1.32

1.64

0.32

0.43

45

54

2.26

3.01

1.82

2.26

0.44

0.60

55

66

2.88

3.84

2.31

2.88

0.57

0.76

61

76

3.19

4.25

2.56

3.19

0.63

0.85

basic unit weight without accessories


PR-2009-0139-GB Subject to modifications Status 10/2009

Accessory Sizes

GEA MPower-Geko Fan Coil Unit

Spare filter hoses (1 set = 5 pieces)


Quality class G2, G3 (EN 779); regenerative filter
medium
Size
1
2
3
4

Fig. 31

Order-Nr. Filter quality


G2
G3
ZGM.1A823
ZGM.1A833
ZGM.2A823
ZGM.2A833
ZGM.3A823
ZGM.3A833
ZGM.4A823
ZGM.4A833

Filter length
L
approx. 700
approx. 1000
approx. 1300
approx. 1450

Air intake flexible connector (material class B1)


Size
1
2
3
4

Order-Nr.
ZGM.1A111
ZGM.2A111
ZGM.3A111
ZGM.4A111

Weight [kg]
2.9
3.7
4.5
5.4

Air discharge flexible connector(material class B1)


Size
1
2
3
4

Fig. 32

Order-Nr.
ZGM.1A112
ZGM.2A112
ZGM.3A112
ZGM.4A112

Weight [kg]
2.9
3.7
4.5
5.4

Air intake box with round connector,


insulated (galvanized steel)
Size
1
2
3
4

Size 1

Order-Nr.
ZGM.1A041
ZGM.2A041
ZGM.3A041
ZGM.4A041

Weight [kg]
5.8
7.8
9.9
10.9

Size 2
Air discharge box with round connector,
insulated (galvanized steel)
Size
1
2
3
4

Size 3

Order-Nr.
ZGM.1A042
ZGM.2A042
ZGM.3A042
ZGM.4A042

Weight [kg]
5.8
7.8
9.9
10.9

Cover cap for all sizes


(galvanized sheet steel, not insulated)

Size 4

Size
1-4

Fig. 33

Order-Nr.
Air intake
Air discharge
ZGM.0A711
ZGM.0A712

Weight
[kg]
0.3

Air intake sound attenuator (galvanized sheet steel


with internal acoustic and thermal insulation)
Size
1
2
3
4

Order-Nr.
ZGM.1A211
ZGM.2A211
ZGM.3A211
ZGM.4A211

Weight [kg]
16.2
21.6
26.9
30.2

Air discharge sound attenuator (galvanized sheet


steel with internal acoustic and thermal insulation))
Size
1
2
3
4

Fig. 34
Size
b [mm]

682

982

1282

1482

Octave centre frequency [Hz]


Acoustic insulation [dB]

Sum level

63

125

250

500

1000

2000

4000

8000

8.0

16

21

25

17

13

PR-2009-0139-GB Subject to modifications Status 10/2009

Order-Nr.
ZGM.1A212
ZGM.2A212
ZGM.3A212
ZGM.4A212

Weight [kg]
16.2
21.6
26.9
30.2

approx. LW [dB]

Air intake side

10

Air discharge side

12

31

Accessory Sizes

GEA MPower-Geko Fan Coil Unit

Installation sample:
Suspension rail with threaded
rods M8+minor parts
Mounting
length
[mm]
950
1550
2150

Order-Nr.

Weight
[kg]

ZGM.0A613
ZGM.0A623
ZGM.0A633

2.4
4.0
5.5

Mounting with suspension rail


and mounting adapter on one
side and threaded rods on the
other side.

Fig. 35
Suspension rail 950 mm

Cross section of suspension rail


and mounting adapter

Rail length enough for a


maximum 1 basic unit and 1 air
intake and discharge box.

Fig. 36
Suspension rail 1550 mm

Rail length enough for a maximum 1 basic unit, 1 sound attenuator and 1 air intake and
discharge box.

Fig. 37
Suspension rail 2150 mm

Rail length enough for a maximum 1 basic unit, 1 intake and


discharge sound attenuator, 2
sound attenuators and 1 air intake
and discharge box.

Fig. 38

In order to minimize the remaining structure borne sound it recommended to use standard spring elements.

32

PR-2009-0139-GB Subject to modifications Status 10/2009

Overview of Valves

GEA MPower-Geko Fan Coil Unit

Selection Table
!

The following selection table presents all available valves


models with main features and compatible control equipment.

The following symbols are used:


y = Valve type compatible with the corresponding control
panel or electric equipment.
= Valve type not compatible with the corresponding control
panel or electrical equipment.

Valve type

Function
type

Control
type

Voltage

3 point
(modulating)

230 V~

AB
B

Compatible control equipment

Controls by
others

MATRIX
500

MATRIX
2000

MATRIX
3000

MATRIX
4000

Thermostat
switch

(only 2-pipe
system;
transformer
by others
necessary)

(Transformer by
others necessary)

(Transformer by
others necessary)

(only 2-pipe
system)
N
A

AB
B

C
A

AB
B

3 point
(modulating)

24 V~

3 point
(modulating)

230 V~

(2 floating
auxiliary
switches)
T

2 point
(modulating)

230 V~

2 point
(modulating)

24 V~

(Transformer
by others
necessary)

(Transformer by
others necessary)

(Transformer by
others necessary)

AB
B

AB

(only 2-pipe
system)

S
A

AB
B

continuous

24 V~
(analoguesignal
0..10 V)

PR-2009-0139-GB Subject to modifications Status 10/2009

33

Overview of Valve Actuators

GEA MPower-Geko Fan Coil Unit

Modulating Actuator 230 V AC / 3-point Operation / opt. 2 Floating Auxiliary Switches /

Modulating Actuator 24 V AC and 0-10 V/24 V AC / Thermoelectric Actuator 230 V AC and 24 V AC


Continuous virtually continuous actuators
Plastic motor casing
Floating auxiliary switch:
Switch S1
(valve signal 100% open)
Switch S2
(valve signal setting settable 0..100%)
B

Technical data:
Function

Fig. 39: For dimensions of continuous and virtually continuous valve


actuators refer to table

Control mode

3-point

3-point

3-point

continuous

Order-Nr. actuator (loose)

308 173

312 370

311 947

311 948

230 V AC
50/60 Hz

230 V AC
50/60 Hz

24 V AC
50/60 Hz

0-10 V/24 V AC
50/60Hz

Power
consumption

7 VA

7 VA

0.7 VA

1.4 VA

Protection

IP43

IP43

IP43

IP43

Operating
voltage

Run time

120 s/50 Hz 150 s/50 Hz 120 s/50 Hz

120s/50 Hz

Operating
force [N]

180

180

180

180

Control
stroke [mm]

6.5

6.5

6.5

6.5

Max. allowed
ambient
temp.

60 C

60 C

60 C

60 C

Cable [m]

2.7

2.7

2.7

2.7

Load
capacity
Auxiliary
switch

max. 5 (1) A/
250 V
max. 100 mA/
24 V

Rated dimensions [mm]


A

100

109

100

100

61

85

61

61

49

49

49

49

Thermoelectric valve actuators


Plastic actuator casing
Technical data:
Function

2-point

2-point

Order-Nr. actuator

240 5072

240 5073

Operating voltage

230 V AC
50/60 Hz

24 V AC
50/60 Hz

0.6

0.7

Rated current [A]

0.014

0.1

Protection type

IP44

IP44

2.5

Operating force [N]

90 N

90 N

Control stroke [mm]

Max. ambient temp.

50 C

50 C

Control mode

Power consumption [W]


Heat up current [A]

Run time (approx.) [min]

Fig. 40: Dimensions of thermoelectric valve actuators in mm

Connecting cable [m]

34

PR-2009-0139-GB Subject to modifications Status 10/2009

Overview of Valve Bodies

GEA MPower-Geko Fan Coil Unit

Two and Three-Way

Two and three-way valves

Brass or red brass valve body

Stainless steel spindle and cone

Technical data:
Rated pressure

16 bar

max. medium temperature

120 C

max. glycol concentration

50 %
a

Stroke 2,5
mm

G 1/2" A
G 3/4" A

56
66

40
40

34.5
36.6

5
5

Stroke 6,5
mm

G 1/2" A
G 3/4" A

56
66

40
40

32
34

18
18

Rated dimensions

[mm]

Three-way valves
Valve body with spindle stroke 2,5 mm:
Fig. 41: Dimensions of two and three-way valves
DN

kVS A-AB
[m3/h]

kVS B-AB
[m3/h]

Valve external
thread

Dpmax
[kPa]

Order-Nr.
(loose)

15

1.6

1.0

G 1/2" A

200

240 5070

20

4.0

2.5

G 3/4" A

100

240 5078

For suitable thermoelectric valve actuator refer to page 34

Pressure drop p [kPa]

Valve body with spindle stroke 6,5 mm:


DN

kVS A-AB
[m3/h]

kVS B-AB
[m3/h]

Valve external
thread

Dpmax
[kPa]

Order-Nr.
(loose)

15

0.25

0.16

G 1/2" A

600

240 5061

15

0.40

0.25

G 1/2" A

600

240 5062

15

0.63

0.40

G 1/2" A

600

240 5063

15

1.00

0.63

G 1/2" A

600

240 5064

20

1.60

1.00

G 1/2" A

300

240 5065

20

2.50

1.60

G 3/4" A

150

240 5066

20

4.00

2.50

G 3/4" A

50

240 5067

For suitable virtually continuous/continuous valve actuators refer to


page 34

Water flow rate V [l/h]

Fig. 42: kVS-values for valves with spindle hub 6,5 mm

Two-way valves
Valve body with spindle stroke 2,5 mm:
DN

kVS A-AB
[m3/h]

Valve external thread

Dpmax
[kPa]

Order-Nr.
(loose)

15

1.6

G 1/2" A

300

240 5068

20

4.0

G 3/4" A

100

240 5141

Pressure drop p [kPa]

For suitable thermoelectric valve actuator refer to page 34

Valve body with spindle stroke 6,5 mm:

Water flow rate V [l/h]

Fig. 43: kVS-values for valves with spindle stroke 2,5 mm


PR-2009-0139-GB Subject to modifications Status 10/2009

DN

kVS A-AB
[m3/h]

Valve external thread

Dpmax
[kPa]

Order-Nr.
(loose)

15
15

0.25

G 1/2" A

600

240 5054

0.40

G 1/2" A

600

240 5055

15

0.63

G 1/2" A

600

240 5056

15

1.00

G 1/2" A

600

240 5057

20

1.60

G 1/2" A

300

240 5058

20

2.50

G 3/4" A

150

240 5059

20

4.00

G 3/4" A

50

240 5060

For suitable virtually continuous/continuous valve actuators refer to


page 34

35

Overview of Valves

GEA MPower-Geko Fan Coil Unit

Shut-off Valves

kvs-value 1,45

All GEA valves can be optionally supplied with


shut-off valves at the outlet.

SW19

32

These valves are used for shutting-off the cooling


or heating medium as well as for adjusting and
equalizing medium flow rate.

3/4"

MNG

3/4"

Depending on rated size of the control valve, shutoff valves are used with kvs-value of 1,45 or kvsvalue 2,20.

51

Technical data:
Rated pressure:
Max. water inlet temperature:
pH-value:

kvs-value 2,20
SW24

33

As medium water with a max. 50% glycol rate is


allowed.

3/4"

3/4"

Depending on the valve equipment the shut-off


valves are supplied with outer thread connection
(designation number 4 in on page 51) or with
connecting nut and solder fitting (designation
number 5, refer to Product type code on
page 51).

66

Connection
15

3/4"

10 bar
130 C
8 - 9,5

Control valve

18

Shut-off valve

kvs-values

Connection
thread

kvs-values

Connection
Solder fitthread
ting Cu pipe

0.25-1,60

G 1/2" A

1.45

G 3/4" A

15

2.50-4,00

G 3/4" A

2.20

G 3/4" A

15

Fig. 44

The setting of the necessary medium flow rate is carried out on the basis of the following diagrams. The pre-setting
corresponds to the number of rotations to the left of the setting/adjustment screw starting from the right stop position
(valve closed).
kvs-value 1,45

kvs-value 2,20

Pre-setting
 

 

  

  







 

 







1/2

1 1/2











Water flow rate mW [kg/h]












Water flow rate mW [kg/h]

Pre-setting

1/4

kv-values

0.07 0.13 0.22 0.32 0.43 0.65 0.85 1.10 1.25 1.40 1.45

36

 

Pressure drop p [kPa]

Pressure drop p [kPa]

Pre-setting
 

Pre-setting

1/2

1 1/2

2 1/2

kv-values

0.2

0.4

0.6

1.0

1.5

1.7

2.0

2.2

PR-2009-0139-GB Subject to modifications Status 10/2009

Overview of Valves

GEA MPower-Geko Fan Coil Unit

Ball Traps

27

All GEA valves can be optionally supplied with ball


traps.

36

These are necessary to shut-off cooling or heating


medium.
SW 27

3/4

3/4

26

Materials:
Valve casing:
Ball:
Gasket:

Brass
Brass, ground
Rubber

Technical data:
Rated pressure:
Max. water inlet temperature:
kvs-value

63

10 bar
110 C
6,70 m/h

Depending on the valve equipment ball traps are


supplied with outer thread connection (designations 2 and 4, see Product Type Code on page 51)
or with connecting nut and solder fitting (designations 3 and 5, see Product Type Code on
page 51).

15

3/4

As a medium water and water/glycol is allowed.

Ball trap

18
kvs-value

Connection thread

Solder fitting for Cu


pipe

6.70

G 3/4" A

15

Fig. 45

The servicing of the ball cock is performed via a flat-bladed screwdriver.


20
15

10
9,0
8,0
7,0

Pressure drop p [kPa]

6,0
5,0
4,5
4,0
3,5
3,0
2,5
2,0
1,5

1,0
0,9
0,8
0,7
0,6

3000

2500

1500

1600
1700
1800
1900
2000

1400

1300

1200

1100

1000

900

800

700

600

500

0,5

Water flow rate mW [kg/h]

PR-2009-0139-GB Subject to modifications Status 10/2009

37

Control via Thermostat / Speed Switches, Controls by Others

GEA MPower-Geko Fan Coil Unit

Terminal box with connections for Geko units


Order code basic unit
Terminal box

Sheet steel electric


switch box

In order to carry out connection to the control system all components


like fan(s) and valve(s) are wired in the terminal box.

GMxx.xxxx.Axxxx
GMxx.xxxx.Bxxxx
GMxx.xxxx.Cxxxx
GMxx.xxxx.Exxxx
GMxx.xxxx.Hxxxx

Depending on the selected unit configuration and valve equipment, the


terminal box is either made of plastic or sheet steel. The selection is
performed using the product type code, as illustrated.

GMxx.xxxx.Kxxxx
GMxx.xxxx.Lxxxx
GMxx.xxxx.Mxxxx
GMxx.xxxx.Oxxxx
GMxx.xxxx.Rxxxx

Using thermostat and speed switches of series C easy control is provided for fan coil units. Switches are supplied loose.
Unit mounting is not possible.
The switches can be used with:
Cooling
and
Heating
Cooling
or
Heating

Valve type

Switch type

Return air
sensor

CMT (= 983 861)

4-pipe system chilled


and warm water

0
5

1
6

0
5

CMS (= 983 860)

CMT

0
5

without
with

CET (= MCR2000)

CMT with flow thermostat (flow


thermostat to be ordered separately
using order number 902 035)
CET with flow sensor (flow sensor without
included in package)
with

2-pipe system chilled or


warm water

CMT
Heating

2-pipe system warm


water

Cooling

without
with

CET

2-pipe system chilled


water

without
with

CET

Order symbol

CMS

Alternatively to a return air sensor, a room temperature sensor can be connected to a CET type switch. If a return air
sensor is used, the fan mustbe operating in a continuous mode.

Please consider:
In connection with thermostat / speed switches only on/off valve actuators can be used (T).

Relay kit
is necessary if up to four fan coil units are
switched in parallel. The mixing of different
Geko types and sizes is allowed - refer to
note!

Slave unit with relay kit

With kit

Without
kit

Order code

Order code

0 2

1 Z

NOTE!
Only one unit with CMT/CMS switch may be operated without a relay kit. Units
that are operated with CET switch must be equipped with a relay kit.

38

PR-2009-0139-GB Subject to modifications Status 10/2009

Control via Thermostat / Speed Switches, Controls by Others

GEA MPower-Geko Fan Coil Unit

Operation of thermostat and speed switches


Switch type

Functions

CMS

On/off switch
Fan speed selection switch 1-2-3

CMT

On/off switch
Fan speed selection switch 1-2-3
Setpoint setting indoor temperature 5 ... 35 C (mechanical setting limitation)
Thermostat with neutral zone

CET

On/standby switch
Fan speed selection switch 1-2-3
Setpoint setting indoor temperature 5 ... 35 C (mechanical setting limitation)
Thermostat with settable neutral zone
Enable input via potential free floating contact by others
Room frost protection
Connection possibilities for external room or return air sensor and flow sensor
Integrated indoor temperature sensor

Sensors

Functions

Indoor temperature
sensor
903 414

Thermistor sensor for on-wall mounting


NTC-sensor element; resistance coefficient at 25 C = 10 k
Plastic casing: white, similar to RAL 9010
Protection class IP 20; dimensions in mm (W x H x D): 84 x 84 x 22

Flow sensor
903 434

Thermistor sensor with tightening strap for mounting at inlet line


NTC-sensor element; resistance coefficient at 25 C = 10 k
Max. ambient temperature 100 C
Protection class 2; cable length 2 m

Return air sensor


903 474

Thermistor sensor for mounting in unit


NTC-sensor element; resistance coefficient at 25 C = 10 k
Protection class IP 43; casing dimensions (D x L): 6 x 100 mm; cable length 1,5 m
Max. ambient temperature 100 C

Flow thermostat
902 035

Flow thermostat for change-over between heating or cooling mode


Capillary length 1000 mm; switching points 19 C/25 C 1 K
Operating voltage 250 VAC 50/60 Hz
Dimensions in mm (W x H x D): 85 x 53 x 65
Flow thermostat in enclosed casing for wall mounting, the measuring capillaries are
mounted on the water inlet.

Additional sensors which are supplied loose and wired on-site by others should be ordered optionally (not in connection with the above-mentioned
switch types CMT and CMS).

NOTE!
Flow and return air sensor are integrated in the relevant controls packages and do
not have to be selected separately if ordered using the package number.

PR-2009-0139-GB Subject to modifications Status 10/2009

39

GEA MPower-Geko Fan Coil Unit

Control System GEA MATRIX


Recirculating Air Unit, Sizes 1-4
GEA MATRIX 500/2000
System features:

Assigning of temperature 10... 30 C


Assigning of fan speed
Limitable setting range
Change-over between normal / economy mode on control
panel
Room temperature measurement via control panel
External room temperature sensor can be connected*
Valve control (2-point)
Temperature control via fan on/off and/or valve(s)
Status signals via LED
Group control
Group switch-off in event of malfunction

MATRIX OP4C
Control panel for MATRIX 500 control system
Pure white casing, IP20 protection type
Setpoint temperature setting
Fan speed selection switch 0 - A (continuous) - 1-2-3
Economy mode switch
LEDs for operation / malfunction / ext. control
Integrated room temperature sensor

MATRIX OP5C

Control panel for MATRIX 500,


like OP4C, but with:
Economy mode button

MATRIX OP20C
Additional features with MATRIX 2000:

Extended temperature setpoint assignment.: 7...40 C


(default 10..30 C)
Temperature control via fan speed switch and valves
Network capability

Control panel for MATRIX 2000,


like OP5C, but with:
Fan speed selection switch 0-A (Auto)-1-2-3

MATRIX OP21C
* if required with add-on module

GEA MATRIX 3000

MATRIX OP30C

System features:

Control panel for MATRIX 3000/4000 control system


Pure white casing, IP20 protection type
Setpoint temperature setting
Fan speed selection switch 0 - A (auto) - 1-2-3
LEDs for operation / malfunction / ext. control
Integrated room temperature sensor

Assigning of temp. 7 ... 40 C (default 10... 30 C)


Assigning of fan speed
Limitable setting range
Change-over between normal / economy mode on control
panel
Input for change-over between normal / economy mode or
unit OFF with frost protection
Room temperature measurement via control panel
External room temperature sensor can be connected
Valve control (2-point)
Temperature control via fan and/or valve(s)
Room frost protection function
Status signals via LED
Operating and error messaging via
potential free change-over contacts
Stand alone unit or group control
Stand alone unit switch-off in event of malfunction
Network capability

Control panel for MATRIX 2000,


like OP20C, but with:
Economy mode button

MATRIX OP31C
C

As OP30C control panel, but also includes:


Normal / economy mode switch

MATRIX OP44C

As OP31C control panel, but also includes switches for:


Change-over between heating / cooling / automatic
operation
Change over between recirculating and mixed air mode

MATRIX OP50C

Control panel for MATRIX 3000/4000 control system


Pure white casing, IP20 protection type
Menu-assisted operation via rotating switch
LCD display with plain text display
Status messages via pictograms
Integrated room temperature sensor

MATRIX OP51C
As OP50C control panel, but also includes:
Integrated weekly clock timer with programme for
holiday and special switching days

MATRIX.IR
Infrared remote control for MATRIX 3000/4000
control system
Black casing, similar to RAL 9004
LCD display approx. 45x30mm
Functions such as OP44C (without operation,
malfunction and ext. control messaging, no integr. room
temperature sensor)
Max. range 20m

40

off

on
func

send

PR-2009-0139-GB Subject to modifications Status 10/2009

GEA MPower-Geko Fan Coil Unit

Control System GEA MATRIX


Recirculating Air Unit, Sizes 1-4

Master
unit

Slave
units:

With controller type:


D0 = 7x2x0,8 J-Y(ST)Y
D2 = max. 5x2x0,8 J-Y(ST)Y

MATRIX 500: 1-3


MATRIX 2000: 1-15

With controller type:


D0 = 7x2x0,8 J-Y(ST)Y
D2 = max. 5x2x0,8 J-Y(ST)Y

3x1,5 mm2 NYM

3x1,5 mm2 NYM

3x1,5 mm2 NYM


Flow sensor (only with HoC units)
with connecting cable

230 V ~
50 Hz

MATRIX
500 HoC

MATRIX 2000
Cooling
Heating
Heating or cooling
Heating and cooling

K
H
HoK
HuK

w/o return sensor *


with return sensor *

1
2

Cooling/heating medium

MATRIX 500 H,
C, HaC/
MATRIX 2000
0
5

1
6

Control panel

Order code MATRIX 500

0 5

0 5

1 Z

Order code MATRIX 2000

1 Z

Master
unit

Slave units
1-15

With controller type:


D2 = 4x2x0,8 J-Y(ST)Y
D3/4 = e. g. 1x2x0,5 Helukabel

e. g. 2x2x0,5 Helukabel

3x1,5 mm2 NYM

Cooling

Cooling/heating medium

Connection for
external sensor

Silent
valve control

up to
5speed

Supply air temp.


limitation

Input unit OFF with


room frost protection

Input economy
mode contact

Group control
with operation and
error messaging

Individual unit control


with operation- and
error messaging

Speeds

Contact cooling and


heating request

Flow sensor (only with HoC units)


with connecting cable

230 V ~
50 Hz

up to
3speed

3x1,5 mm2 NYM

3x1,5 mm2 NYM


2x2x0,8

1
1
1

Heating
Cooling or heating

Cooling and heating

w/o return sensor *

with return sensor *

Control panel

Order code

* Alternative room temperature sensor (refer to page 46) / with MATRIX.IR return or indoor sensor absolutely necessary!

PR-2009-0139-GB Subject to modifications Status 10/2009

41

GEA MATRIX Control System

GEA MPower-Geko Fan Coil Unit

System Description
Overview

Valve actuator type


2 point (modulating)

LEDs for
operation/
fault/
ext.control

Speed stage
selection switch

MATRIX 500 control system supports all basic functions (heating/cooling) of recirculating air fan coil unit. The controller can be used in the following unit types:
2-pipe units only heating
2-pipe units only cooling
2-pipe units cooing or heating (change over)
4-pipe unit cooling and heating
The speed can be set manually and the unit switched off via the control panel. Valves
with on/off or modulating control behaviour and a supply voltage of 230 V AC can be
activated to control the heating and/or cooling capacity. Additionally, the MATRIX 500
enables monitoring of the fan motor via thermal contacts with external leads as well
as the condensate water level for cooling units with a condensate pump. The connected sensors are monitored as well.

Normal/
economy mode
buttons

MATRIX 500

Setpoint
temperature

The OP4/OP5 control panel enables the setpoint values to be set quickly and easily
without extensive prior experience. Mechanical limit stops can be used to limit the setting range for the setpoint temperature and speed stage. Room temperature is measured via a sensor integrated in the control panel. If the control panel is positioned in
an unfavourable location (such as by the door), an external temperature sensor or return air sensor can be connected (not possible on changeover systems). System
faults are signalled centrally via the red malfunction LED and output using a changeover contact. If economy mode is activated, it is displayed via the yellow LED integrated into the button. In addition to protection type IP20 (OP4 C/OP5 C), an IP54 control
panel model (OP5 I) is available for moist areas.
The connection in the unit is made via plug-in cage clamps. Electronics, fans and
valves (230V) are fused separately via two backup fuses on the power supply. A fuse
of B 10A type must be supplied to provide the necessary circuit protection.
The MATRIX 500 can be used for controlling individual circulating air units and recirculating air unit groups as well.

MATRIX 2000

Valve actuator
type
2 point
(modulating)

3 point
(modulating)

42

The MATRIX 2000 control system is based on features incorporated in the MATRIX
500 system but also provides additional functions that can be summarized as follows:
Along with manual speed selection the fan control can be also carried out in a 3
speed mode based on the deviation of actual temperature from the setpoint.
With 2-pipe units 3-point modulating valve actuators can be controlled as well.
Besides, the control of valve actuators using 24V AC supply voltage is also
possible (transformer by others).
The direct connection of an external room temperature sensor is not possible with
change over units, but can be performed via a Global Module. A fault message can
also be received using a Global Module. Direct tapping is not possible.

PR-2009-0139-GB Subject to modifications Status 10/2009

GEA MATRIX Control System

GEA MPower-Geko Fan Coil Unit

System Description

LEDs for
operation/
fault/
ext.control

Normal/
economy mode
buttons
Speed stage
selection switch

Setpoint
temperature
switch

The OP20/OP21 control panel enables the setpoint values to be set quickly and easily
without extensive prior experience. Mechanical limit stops can be used to limit the setting range for the setpoint temperature and speed stage. Room temperature is measured via a sensor integrated in the control panel. If the control panel is positioned in an
unfavourable location (such as by the door), an external temperature sensor or return
air sensor can be connected (not possible on change over systems please use a Global Module). System faults are signalled centrally via the red malfunction LED. If
economy mode is activated, it is displayed via the yellow LED integrated into the
button.
In addition to protection type IP20 (OP20 C/OP21 C), an IP54 control panel model
(OP21 I) is available for moist areas.
The connection in the unit is made via plug-in cage clamps. Electronics, fans and
valves (230V) are fused separately via two microfuses on the power supply. A backup
fuse B 10A must be supplied to provide the necessary circuit protection.
The MATRIX 2000 can be used for controlling individual recirculation air units and also
recirculation air unit groups. The integrated MATRIX.Net bus system enables integration of up to 16 several groups to one network. The combination with MATRIX 3000
controllers and connection of Global Modules and communication interfaces is also
possible.

Valve actuator
type
2 point
(modulating)

3 point
(modulating)

MATRIX 3000
The Matrix 3000 control system is based on the MATRIX 2000 system and provides
additional functions that can summarized are as follows:
3-point valves with modulating control behaviour can be applied on 4-pipe systems.
Mixed operation is also possible (2-point cooling valve / modulating heating valve or
modulating cooling valve / 2-point heating valve).
Operation and fault signals are output via two change-over contacts on the unit. The
maximum load on the contacts at 230 V AC is 4 A ohmic / 2 A inductive.
The supply air temperature can be limited for heating and cooling. Fixed and sliding
limits can be defined.
An external temperature sensor or return air sensor can be connected to all system
types.
An additional control input enables the following operating modes that can be set
externally:

Normal/economy operation or
Unit OFF with frost protection

Various types of control panels are available. The range varies from a simple variant
with setpoint temperature and fan operating mode selection using infrared remote
control to a control panel with display. The display unit can also be supplied with an
integrated weekly timer.

MATRIX 4000
The Matrix 4000 control system is based on the MATRIX 2000/3000 system and provides additional functions that can summarized are as follows:
5

In order to provide improved selection of heating/cooling capacity a five speed fan


control is enabled.
For applications with highest comfort requirements electronic control elements provide absolutely silent valve control.
Four additional control inputs enable external assignment of the following operating
modes:
Normal mode
Economy mode
Free mode
Unit OFF with frost protection
Compulsory setting of a fan speed
A connection possibility for an outdoor sensor makes it possible to activate summer
compensation. Outdoor air temperature value is automatically transmitted to all units
connected within the MATRIX.Net.

PR-2009-0139-GB Subject to modifications Status 10/2009

43

GEA MATRIX Control System

GEA MPower-Geko Fan Coil Unit

Overview of Features

Description of features
Unit type

Fan mode

Valve control

MATRIX
500

MATRIX
2000

MATRIX
3000

MATRIX
4000
9

2-pipe systems: only heating, only cooling; heating or cooling

4-pipe system heating and cooling

up to 3 speeds

up to 5 speeds

Temperature related fan speed switching

Minimum speed 1

Motor monitoring with external thermal contacts

2 and 4-pipe system: on/off actuators

2-pipe system: 3-point modulating actuator


4-pipe system: 3-point modulating actuators

9
9

Silent control (semiconductor relay)


External heating valve with cooling unit with fan switch off
Electric heating

1-speed

Room frost protection

9
9*

Min/Max limitation heating

9*

Min/Max limitation cooling

Summer/winter compensation

Control inputs

Measuring outdoor temperature

9
9

Unit frost protection

Supply air temperature limitation

9
9

2-speed
Frost protection

Economy mode
Economy mode or door or window contact

9*

Economy mode and door or window contact and unit OFF and free operating mode

9*

9*

via local sensor connection


using MATRIX.AI

Measuring inlet temperature

via local sensor connection

Measuring return air temperature

via local sensor connection

9**

Measuring supply air tempera- via local sensor connection


ture
Messages/signals

Alarm condensate level too high with unit switch off

Heating and/or cooling request


Status signal via change-over contact
Fault signal via change-over contact

9*

9*

9*

9*

Mixed air damper control

Open/close or continuous

Exhaust fan control

1 speed via relay output

9
9

via power unit / exhaust air controller


Chiller control

up to 2 speeds via MATRIX.RF module

Control modes

Indoor temperature control

9
9

Supply air temperature control

MATRIX.DI

MATRIX.AI

MATRIX.DO

MATRIX.Net bus system


can be extended by:

MATRIX.RF
9

MATRIX.Clock

9
9

MATRIX.EM
MATRIX.LON

Service tools

MATRIX.PDA

Control panels

MATRIX OP4C/MATRIX OP5x

MATRIX OP30x

MATRIX OP31x

MATRIX OP44x

MATRIX OP50x/51x

MATRIX.PC

MATRIX OP20C/MATRIX OP21x

44

9
9

with additional module only**not with heating or cooling units

PR-2009-0139-GB Subject to modifications Status 10/2009

GEA MATRIX Control System

GEA MPower-Geko Fan Coil Unit

Mounting Control Panels

As the control panel is split into two units, the control panel cover only needs to be
snapped on the mounting plate during commissioning. This provides optimum
protection against dirt and damage for the control panels during the construction
phase.

The cable connection is established via cage clamps. This enables quick and easy use
of solid and flexible cores.

To mount the control panel in a standard in-wall socket, corresponding drill holes need
to be provided in the mounting plate.

The control panel can also be fitted directly on the wall (cable laid under plaster or in
cavity wall).

IP54 control panels for moisture proof applications are available on request.

To prevent dirt accumulation or accidental operation, control panel covers are


available as accessories (refer to Fig. 49 on page 46).

PR-2009-0139-GB Subject to modifications Status 10/2009

45

GEA MATRIX Control System

GEA MPower-Geko Fan Coil Unit

Sensors/Accessories
Indoor sensor, order-Nr. 903.414
Thermistor sensor for on-wall mounting

NTC sensor element


Plastic casing: white, similar to RAL 9010
Resistance coefficient at 25 C = 10 k
Protection type IP20
Dimensions in mm (W x H x D): 84 x 84 x 22

The 903.414 indoor sensor replaces indoor sensor in the


MATRIX OP XXC control panels. The additional sensor
must be fitted if the control panel is mounted in a location
that is unsuitable for accurate temperature
measurement.
Fig. 46
External sensor order-nr. 903.454
Thermistor sensor for measuring ambient temperature
e.g. for summer/winter compensation (according to DIN
1946 part 2/3)

NTC sensor element


Impact resistant white plastic casing
for outdoor wall mounting
PG bolts
Resistance coefficient at 25 C = 10 k
Protection type IP 54
Dimensions in mm (W x H x D): 65 x 50 x 37.5

Fig. 47
Flow sensor order-nr. 903.434
Thermistor sensor for mounting at inlet line

NTC sensor element


Sensor on basic plate; white plastic casing;
RAL 9010
Mounted with tightening strap at inlet line
Max. ambient temperature 100 C
Dimensions in mm (W x H x D): 85 x 53 x 65
Resistance coefficient at 25 C = 10 k
Protection type IP 43

Fig. 48
Unit cap
white

order nr. OPD.C

(for OP21C / OP30C / OP31C / OP44C)


Light grey

order-nr. OPD.I

(for OP21I / OP30I / OP31I / OP44I)


For covering operating elements of control panel
The control panel cover is hung into the guide slots of the
control panel and protects the control panel from dirt
accumulation and accidental operation.
Fig. 49

46

PR-2009-0139-GB Subject to modifications Status 10/2009

Controls System GEA MATRIX

GEA MPower-Geko Fan Coil Unit

Global Modules
The global modules of the MATRIX control system are designated for input and output
of MATRIX system signals. The global modules enable the transmission of messages
and operation statuses to external units as well as control via these external units. The
modules can be integrated at any location within the MATRIX network. The network
may contain and simultaneously operate a maximum of 2 MATRIX modules of the
same type (DI,DO,AI) or 16 modules (LON).
The modules are supplied with the default factory configuration. Configurations with
other settings can be adjusted using the MATRIX.PC software.
.

Technical data:
Power supply
Protection type
Operation temperature
Fusing
Mounting
MATRIX.DI max. current consumption
MATRIX.DI dimensions
MATRIX.DO max. current consumption
MATRIX.DO contact assignment
MATRIX.DO dimensions
MATRIX.AI nominal current consumption
MATRIX.AI dimensions
MATRIX.LON nominal current
consumption
MATRIX.LON dimensions

24 V DC 15 %
IP 20
0 up to +45 C
10 A T
Mounting rail
0,1 A
106 mm x 90 mm x 58 mm
0,14 A
250 V/5 A (ohmic); 2 A (inductive)
160 mm x 90 mm x 58 mm
0,03 A
160 mm x 90 mm x 58 mm
0,045 A
106 mm x 90 mm x 58 mm

Digital input module MATRIX.DI


The digital input module MATRIX.DI is used to receive 8 independent digital control
signals.
Factory configuration:
Input

valid for

Closed contact results in

1
2
3
4
5
6
7
8

all groups
all groups
all groups
all groups
Group 0
Group 0
Group 0
Group 0

HVAC Heating Mode


HVAC Cooling Mode
Normal mode
Economy mode
Fan in speed 3
Secondary air damper close
Secondary air damper open
Mixed air operation 100 %

Digital output module MATRIX.DO


The module has 8 digital outputs with potential free change over contacts.
Factory configuration:
Output

valid for

Energized relay signals

1
2
3
4
5
6
7
8

all groups
Group 0
Group 0
Group 1
Group 1
Group 2
Group 2
all groups

Operation
Fault message
Frost message
Fault message
Frost message
Fault message
Frost message
Fault message

PR-2009-0139-GB Subject to modifications Status 10/2009

47

Controls System GEA MATRIX

GEA MPower-Geko Fan Coil Unit

Analogue input module MATRIX.AI


The module has 8 analogue inputs that are controlled using 010 V/2..10 V signals or
can be supplied with NTC sensors (10 k Ohm/25 C).
Factory configuration:
Input

valid for

Parameter

Type

Filter
value

Measurement
range

all groups

NTC

2
3
4
5
6
7
8

all groups
Group 0
Group 1
Group 2
Group 1
Group 2
Group 3

Outside
temperature
Inlet temperature
Room setpoint
Room setpoint
Room setpoint
Outside air ratio
Outside air ratio
Outside air ratio

NTC
0 ... 10 V
0 ... 10 V
0 ... 10 V
0 ... 10 V
0 ... 10 V
0 ... 10 V

0
0
0
0
0
0
0

10 30 C
10 30 C
10 30 C
0 ... 100 %
0 ... 100 %
0 ... 100 %

MATRIX.LON module
The MATRIX.LON communication module is part of the global modules of the GEA
MATRIX control system and is used for connecting the MATRIX control system to a
network structure in accordance with the LON WORKS standard. It enables the connection of air treatment components to a building management system or other facility
management systems. It also enables external systems such as dampers or lighting
systems to be controlled via the MATRIX OP50/51 control panel. The module can be
integrated into the MATRIX network at any point.
Gruppe 2

Gruppe 3

Gruppe 4

Gruppe 16

Gruppe 1

MATRIX.Clock timer module


The MATRIX.Clock timer module is intended for use as a central weekly timer. The
module can be integrated into the MATRIX network at any point and supports up to 16
groups in a network. The groups can be assigned individually to six weekly
programmes, special switching days and the holiday programme. In each weekly
programme, up to four switching times (2 x on / 2 x off) can be defined. Additionally, up
to six special switching days with up to four switching times (2 x on / 2 x off) per special
switching day can be defined. Holiday periods can be defined via the holiday days that
can be programmed for the whole calendar year. Input is carried out via a
straightforward push&turn control. Ease of user navigation is ensured by means of
structured menus, plain text messages and pictograms. The current status of the
individual programmes is displayed via a menu.
The timer module can be toggled between six different languages online. The switch
between summer and winter time is done automatically. If required, a blocking
protection e.g. for pumps can be activated (once a week). Additionally, the time format
can be selected between 12 and 24 hour display.
Power to the clock timer is supplied via the MATRIX controllers power unit..
There are two different variants available:

48

MATRIX.Clock C with IP 20 protection type; colour white (similar to RAL 9016)


MATRIX.Clock I with IP 54 protection type; colour light grey (similar to RAL 7035)

PR-2009-0139-GB Subject to modifications Status 10/2009

Controls System GEA MATRIX

GEA MPower-Geko Fan Coil Unit

MATRIX.OP71 control panel for all groups


The MATRIX.OP71 control panel is designed to be operated from one central point. It
can integrated at any location within the MATRIX network and can simultaneously
serve up to 16 groups.
Up to 16 unit groups can be assigned to one cluster:
One unit group per each cluster
Each cluster with up to 16 unit groups.
Clear text menus and "push&turn" function enable easy handling during operation or
configuration. A maximum of 16 unit groups can be induvidually grouped to clusters.
Using the control panel the wanted setpoints for temperature, fan speed, etc. can be
assigned for each cluster. Thanks to control panel features comprising all groups, the
necessary room or return air sensors are located in the respective groups (group
locations).
Local control panels (OP2xx, OP3xx, OP4xx, OP5x) can be additionally integrated in
individual groups. Their functional scope can be defined and adjusted using the control
panel for all groups. Thus, a relative daily setpoint can be entered via a local control
panel, whereas the OP71C setpoint is assigned as standard.
The integrated clock timer enables to assign 8 weekly programmes to clusters at any
sequence. Each weekly programme enables to enter four switching times per day
(2 x On/2 x Off), that can also be set to be valid for the whole day. Besides, it is possible
to set 8 special switching days with up to four switching times (2 x On/2 x Off) per
special switching day. Holidays / bank holidays can be set using the calendar annual
programme.
During holidays the unit can be set to operate in "unit off" or economy mode.
The summer / winter time switch over is performed automatically.
The control unit is currently supplied with 7 selectable languages:
German
English
French
Polish
Czech and
Hungarian.
Two different variants are available:

MATRIX.OP71C with IP 20 protection type; colour white (similar to RAL 9016)


MATRIXOP71I with IP 54 protection type; colour light grey (similar to RAL 7035)

PR-2009-0139-GB Subject to modifications Status 10/2009

49

Controls System GEA MATRIX

GEA MPower-Geko Fan Coil Unit

Service tools
MATRIX.PDA
The MATRIX.PDA service tool is used for setting parameters of the MATRIX control
system and makes the commissioning and maintenance of systems considerably
easier. The service tool can be connected via the service interface that is integrated
into all control panels, controllers, global modules, the clock timer and the
communication modules. Input is carried out via a straightforward push&turn control.
The following main functions are available:

Automatic network scanning with display of detected users


Plain text error display
Modification of parameters such as temperature limits, times or control type
Display of actual values
Display of current unit status such as HVAC mode or valve position
Manual control of actuators such as fans and valves
Reading out, saving and writing of configuration data

The service tool can be toggled between six different languages online. The unit is protected from damage during transit and use via a rubber guard.

Service software MATRIX.PC


Based on the functions of the MATRIX.PDA service tool, the MATRIX.PC service
software provides further comprehensive functions in the field of parameterization,
commissioning and data recording of the GEA MATRIX controller system.
The service software can be connected via the service interface that is integrated into
all control panels, controllers, global modules, the timer and the communication
modules. A USB interface is required on the PC. The enclosed adaptor establishes the
necessary connection between the PC and the service interface.
In addition to the functions of the MATRIX.PDA, the following main functions are also
available:

Online display of module, status and network data


Recording and saving of temperature developments and switching states of the
actuators with adjustable sample rate
Offline parameterization
Programming of inputs and outputs provided for this purpose
(controllers, global modules)
Output of messages and network data
Parameterisation of controller and control panel functions
Input of sensor correction factors

PC system requirements:

PC with 233 MHz clock speed or higher


20 MB of free hard drive space
Minimum screen resolution of 800x600 pixels
USB interface for CAN adaptor

The software can be run on the following operating systems:


Windows 98 Second Edition; Windows 2000; Windows XP
In addition to the program CD, the installation instructions and interface module for
connection to the USB port of the PC are also provided.

50

PR-2009-0139-GB Subject to modifications Status 10/2009

Product Type Code

GEA MPower-Geko Fan Coil Unit

Unit type code


G

1 . U

Controls package
0

3 . A

2 . 0

1 . B

Valve code
A

M . R

Cooling/heating

Size

Controller type

1
2
3
4

0 = Terminal box/
Matrix 500
2 = MATRIX 2000
3 = MATRIX 3000
4 = MATRIX 4000

= Size 1
= Size 2
= Size 3
= Size 4

Capacity stage
1 = Capacity stage 1
2 = Capacity stage 2
Air flow function
U = Circulating air
Medium related function
Heating only
0W
= Warm water pump
Cooling only
W0
= Chilled water pump
Cooling or heating
WC = WWP - CWP
Cooling and heating
War = WWP - CWP
m
waMedium
connection *
ter
Ceiling
3 = left
4 = right
Speed stages
Terminal box with terminal strip
A = Speed 1, 2, 3
B = Speed 2, 3, 4
C = Speed 3, 4, 5
E = Speed 1, 3, 5
H = Speed 1, 2, 3, 4, 5
Sheet steel electric switch box with terminal
strip or for integrated controls
K = Speed 1, 2, 3
L = Speed 2, 3, 4
M = Speed 3, 4, 5
O = Speed 1, 3, 5
R = Speed 1, 2, 3, 4, 5

Valve body

control panel

2
3

=
=
=
=
=
=
=
=
=
=
=
=
=
=

MATRIX OP21C
MATRIX OP30C
MATRIX OP31C
MATRIX OP44C
MATRIX OP50C
MATRIX OP51C
MATRIX.IR
CMS = 983 860
CMT = 983 861
CET = MCR 2000
MATRIX OP4C
MATRIX OP5C
MATRIX OP20C
without control panel

Unit type
Master unit, control panel
A = Single/master unit, control
panel supplied
C = Master unit without control
panel
D = Slave unit without control
panel

5 . 1

Heating circuit

Function type
R = 3-point 230 V
T = 2-point 230 V
N = 3-point 24 V
Q = 2-point 24 V
S = 0-10 V, 24 V
C = 3-point 230 V + 2 contacts

Controls package Nr.

A
B
C
D
E
F
N
P
Q
R
S
T
U
Z

=
=

2-way
3-way

Kvs-value
03 = Kvs 0,25
04 = Kvs 0,40
06 = Kvs 0,63
10 = Kvs 1,0
16 = Kvs 0,40
25 = Kvs 2,5
40 = Kvs 4,0

(R, N, S, C)
(R, N, S, C)
(R, N, S, C)
(R, N, S, C)
(R, N, S, C, T, Q)
(R, N, S, C)
(R, N, S, C, T, Q)

Connection/shut-off
0
1
2
3
4

=
=
=
=
=

Inlet/outlet with external thread


Inlet/outlet with solder fitting
Inlet/outlet + ball trap with external thread
Inlet/outlet + ball trap with solder fitting
Inlet + ball trap/outlet + shut-off valve with external
thread
5 = Inlet + ball trap/outlet + shut-off valve with solder fitting
Medium connection
L = left
R = right

Thermal contact
0 = with integrated thermal contacts
1 = with external (led out) thermal contacts
Condensate pump
0 = with condensate drain
1 = with condensate pump **
Design
G = Basic unit for modular design
M = Compact unit with integrated discharge connector
Filter
2 = G2 mat filter
3 = G3 mat filter

*
**

Front connection side, facing discharge


Steel sheet electrical switch box necessary

PR-2009-0139-GB Subject to modifications Status 10/2009

51

Customer proximity, sales structures

Reachable always and everywhere!


A

BG

GEA Klimatechnik
GmbH & Co KG
A-4673 Gaspoltshofen
Tel. +43 / 7735 / 8000-0
GEA Happel Belgium N. V.
B-1130 Brussels
Tel. +32 / 2 / 2406161
EVISS Ltd.
BG-7000 Rousse
Tel . +359 / 82 / 81000

BIH GEA Klimatechnik


GmbH & Co KG
RS-11070 Novi Beograd
Tel. +381 / 11 / 3193955
BY

GEA Klimatechnik UAB


LT-01141 Vilnius
Tel. +370 / 5 / 2106060

DK

CH ATC Klimatec Schweiz AG


CH-3065 Bolligen-Station
Tel. +41 / 31 / 9171919
CZ

GEA LVZ, a.s.


CZ-46312 Liberec
Tel. +420 / 48 / 5225-111

CZ

GEA Klimatizace spol. s r.o.


CZ-46312 Liberec
Tel. +420 / 48 / 5225-303

GEA Happel
Klimatechnik GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-00

GEA Happel
Wieland GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-754

GEA Deichmann
Umwelttechnik GmbH
D-36179 Bebra
Tel. +49 / 6622 / 504-0
GEA Delbag
Lufttechnik GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-700
GEA Delbag-Luftlter
Vertriebsgesellschaft mbH
D-10709 Berlin
Tel. +49 / 30 / 43592-3
GEA Klimateknik ApS
DK-2610 Rdovre
Tel . +45 / 38 / 887070
GEA Air Treatment
Marketing Services Int.
GmbH ocina Espaa
E-28036 Madrid
Tel. +34 / 91 / 3837701

EST GEA Klimatechnik UAB


LT-01141 Vilnius
Tel. +370 / 5 / 2106060
F

GEA Delbag
Filtration de lair
F-77450 Montry
Tel. +33 / 1 / 60043355
GEA Happel France sarl
F-59436 Roncq Cedex
Tel. +33 / 3 / 20689020

FIN OY TEKNOCALOR AB
FIN-01300 Vantaa
Tel. + 358 / 10 / 8201100

GB

GEA Denco Ltd.


UK-HR4 8DS Hereford
Tel. +44 / 1432 / 277 277

GEA Klimatechnika Kft


H-1037 Budapest
Tel. +36 / 1 / 4393200

PL

HR GEA Klima-rashladna
tehnika d.o.o.
HR-10000 Zagreb
Tel. +385 / 1 / 6064900
IE

Aspect Environmental Ltd.


Ardee, Co. Louth Ireland
Tel. +353 / 41 / 6858983

IS

Rafn Jensson
IS-110 Reykjavik
Tel. +354 / 56 / 780-30

GEA Happel Luxembourg


L-4940 Bascharage
Tel. +352 / 26 / 502970

LT

GEA Klimatechnik UAB


LT-01141 Vilnius
Tel. +370 / 5 / 2106060

LV

GEA Klimatechnik UAB


LT-01141 Vilnius
Tel. +370 / 5 / 2106060

MWE GEA Klimatechnik


GmbH & Co KG
RS-110 70 Novi Beograd
Tel. +381 / 11 / 3193955
N

GEA Klimaprodukter AS
N-0484 Oslo
Tel. +47 / 220 / 27990

NL

GEA Happel Nederland B.V.


NL-2909 LL

GEA Klimatyzacja Sp. z o.o.


PL-54610 Wroclaw
Tel. +48 / 71 / 3737952

RO

GEA Klimatechnik s.r.l.


RO-300222 Timisoara
Tel. +40 / 356 / 423703

RUS GEA Klimatechnik


GmbH & Co KG
RU-105094 Moskva
Tel. +7 / 495 / 9566674
S

SK

GEA EXOS Ventilation AB


S-74528 Enkping
Tel. +46 / 171 / 85530
GEA Klimatizcia s.r.o.
SK-83104 Bratislava
Tel. +421 / 7 / 44457917

SLO GEA Klimatizacijska


Tehnika d.o.o.
SI-1000 Ljubljana
Tel. +386 / 1 / 2573850
SRB GEA Klimatechnik
GmbH & Co KG
RS-11070 Novi Beograd
Tel. +381 / 11 / 3193955
TR

GEA ISISAN
TR-80700
Balmumcu Istanbul
Tel. +90 / 212 / 2757171

UA

GEA Ukraina t.o.v.


UA-01135 Kyiv
Tel. +38 / 044 / 4619356

UAE GEA Air Treatment


Middle East
UAE-Dubai
Tel. +971 / 4 / 887 3881
moJOMMVJMNPVJd_=y=p==~
xx/xxxx PR-xxxx-xxxx-xxx
p~=NMLOMMV=y=`=db^=^=q~
3UBJECTTOMODIFICATIONs#OPYRIGHT'%!,UFTTECHNIK

Capelle a/d Ijssel


Tel. +31 / 10 / 2350606

Nnio, Lda.
P-1269-090 Lisboa
Tel. +351 / 21 / 3826160

The complete addresses are available on the


Internet under: www.gea-air-eco2nomy.com.

www.gea-air-eco2nomy.com

You might also like