City Government of Addis Ababa


Cleansing Management Agency
N

Food Description

Physi

Qty

w Unit

Unit price

With vat

Remar

with Vat

total

price
1

60 KVA Generator

Pce

with Accessories
10 KVA Generator

Pce

10

with Accessories

Tender Name ____________________


Date ____________________
Signature_________________
2. List of Related Service and Completion Schedule
Service

Description of Service

Qty

Physi

Place where

Final

cal

service

completio

Unit
Installation

The supplier shall install

11

n date (s)
At the final

of service
Within one

destination

week

At the final

Within two

destination

days

Perso

At the final

Within one

destination

week after

Pcs

the Generators at the final


destination and adapt with
internal distribution
Test and

system
Test and commissioning

Commissio

shall be carried out by the

ning

purchasers nominated

Training

agent after installation


The supplier shall train
personnel assigned to

11

Pcs

operate the Generator


installation
N.B. The final destination is at city government of Addis Ababa Cleansing
Management Agency

SCHEDULE OF GUARANTEED CHARACTERISTICS


The following list contains the technical characteristics guaranteed by the
bidder. The bidder shall complete the column headed Guaranteed Value
Omission of one or more of guaranteed values may result in rejection of the

offer. Phrases such as refer to catalogue etc are not acceptable. The
guaranteed value should be supported by catalogues and submittal of
catalogues which describes each item is mandatory. If the guaranteed value is
not supported by catalogues the offer will be rejected.

A. 60 KVA Diesel Generator Guaranteed Value


Description
Generating set Manufacturer
Generating Set Model
Rated site output
Engine Manufacturer
Country of Origin
Engine Model
Cylinder arrangement
Injection
Aspiration and cooling
Alternator Manufacturer
Alternator Model
Rated Voltage
Rated frequency
Power factor
Number of Phase
Alternator Connection
Excitation
Insulation class for stator and rotor
Operating condition:- Altitude
Climate temperature

Guaranteed Value
Required
Bidder
Required
Required
60KVA
Required
Required
Required
In line
Direct
Turbocharged
Required
Required
400/230V
50 Hz
0.8
3
Star/Y
Self exciter
H type
2500m a.s.l
250C

B. 10 KVA Diesel Generator Guaranteed Value


Description

Guaranteed Value
Required
Bidder

Generating set Manufacturer


Generating Set Model
Rated site output
Engine Manufacturer
Country of Origin
Engine Model
Cylinder arrangement
Injection
Aspiration and cooling
Alternator Manufacturer
Alternator Model
Rated Voltage
Rated frequency
Power factor
Number of Phase
Alternator Connection
Excitation
Insulation class for stator and rotor
Operating condition:- Altitude
Climate temperature

Required
Required
10KVA
Required
Required
Required
In line
Direct
Natural
Required
Required
400/230V
50 Hz
0.8
3/1
Star/Y
Self exciter
H type
2500m a.s.l
250C

Technical Specification for 60 KVA and 10KVA Full


Automatic Diesel Generating Set
The intent of this specification is to describe Generator with accessories
to be used by city Government of Addis Ababa Cleansing Management
Agency. The generator shall be constructed, assembled and equipped as
per standard and current.
The following technical specification is the minimum acceptable range to
describe the generator. Thus bidders can supply a product which exceeds
the minimum acceptable range.

Therefore the technical offer of the bidders shall be evaluated as per the
following

1. General

El generador sera automatic y canopiado/insonoro con error de red


automatic y conmutacin automatic. El ofertante garantizar la
provision de piezas de repuesto y servicio post-venta (generadores sin
pre-calentador y cargador de bateras automatic NO sirven como
generador diesel automatic)

2. Engine

El motor sera de cuatro tiempos, distribucin de cilindros en lnea e


inyeccin directa,con silencioso residencial.
2.1. Cooling system
Refrigerado por agua por medio de proceso cerrado presurizado
de enfriamiento de agua motado sobre radiador con ventilador
de

tipo

turbina

condiciones
2.2.

de

debe

ser

seguridad

adaptado
en

la

para

manterer

temperatura

las

ambiente

especificada.
Exhaust System
El conjunto de escape sera dimensionado para cumplir con los
requerimientos de motor del fabricante en cuanto a cada de la
presin.

2.3.

Starting System
El motor estar equipado a 12 or 24v D.C y arranque electric
con con conjunto de arranque-parada automtica y manual. El
cargador de bacteria incluir control de carga y proteccin de

2.4.

sobrecarga.
Speed Governing

2.5.

El gobernador de velocidad ser mecnico o elctrico


Sistema de combustible
Depsito de combustible de tamao adecuado para funcionar

2.6.

durante 8 horas al 75% de carga.


Proteccin del motor
La proteccin del motor asegurar el cierre automatic para
proteger el motor de dao debido a condiciones fuera de lon

normal:
Baja presin del aceite lubricante
Elevada temperatura de agua refrigerante
Sobrevelocidad del motor con manivela
2.7. Engine Mounting
El motor diesel se montar sobre bancada de acero y sobre base
antivibracin. El chasis tundra la Resistencia suficiente para
cumplir lo siguiente:
Resistir la fuerza

hecha

durante

su

manipulacin

transporte.
Limitar la torsion y movimientos de flexin
Prevenir la vibracin en el rango dado,

3. Alternator
3/single phase sncrono, de rodamiento individual. It shall be
brushless, revolving field type screen protected. Its rated site output
shall not be less than the required capacity at the rated speed and P.F
at the given site condition. The insulation class of alternator, exciter,
and auxiliary windings shall be H type. Provisto de sistema de
excitacin que pueda funcionar sobre las siguientes condiciones:

3.1.

Voltage Regulation
El sistema de regulacin automatic del voltaje mantendr la
corriente al +- 1% del voltaje diseado,para cualquier carga de
cero a cien a cualquier factor de potencia. Tambin sera capaz
de restablecer el voltaje en cualquier situacin en un mximo de
2 segundosIt shall also re-establish the voltage at rated value,
with in maximum of 2 seconds of a sudden load change form no
load to full load or vice versa.
Instruments and Relays
All instruments shall be tropicalized and their accuracy class

3.2.

shall be not greater than 1.5. Each really shall be clearly


marked with a device number at the front or backside in case of
application of solid-0state protective relays.

The panel shall include but not be limited to the following


equipment:-

3.3.

Automatic, Test and manual start/stop controls.


Battery charger
One D.C voltmeter
One A.C voltmeter
Voltmeter selector switch, six position and off.
Frequency meter.
Ammeter and selector switch, three position and OFF.
One push button for emergency stop of Diesel Generating set
Hours run meter
Energy meter
Oil pressure indicator
Water temperature indicator
Engine alarm/stop lights
Current transformer for metering and relays
Generator Circuit Breaker

The circuit breaker in the generator panel shall be of the


molded case circuit breaker (MCCB) type, rated for the
generator output. The breaker shall be installed as a load circuit
interrupting and protection device. It shall operate both
manually for normal switching functions and automatically
during over load and short circuit conditions. The generator
shall be capable of withstanding a minimum 30-second 3 phase
short circuit at its terminal when operating at full load and
3.4.

rated power factor.


Automatic Transfer Switch (ATS)
The ATS component shall be standard and comply with

3.5.

generator rated capacity


Over Speed
The generator shall be constructed that in and emergency it will
withstand and over speed minimum of 25% without mechanical
failure.

4. Operating Site Condition & Main Technical Data


4.1.

The generating sets are to be operated outdoor. De-rating from


the standard curves (Calculations) shall be enclosed with

4.2.

the offer for both engines and alternators.


- Altitude 2500 m a.s.l, and
- Climate temperature 300C
Main Technical Data of the Generating Set
Rated site output
: 60/10 KVA
Cylinder arrangement
: In-Line
Rated voltage
: 400/230 volt
Rated frequency
: 50Hz
Rated speed
: 1500 RPM

Power factor
: 0.8
Phase
: 3/1
Alternator connection
: Start/Y
Excitation
: Self excited
Insulation class for stator and rotor
:H
5. Control Board
The control Panel of generating sets shall incorporate all
instrumentations relays mentioned above.
6. Loose Items
Lead acid battery with connecting cable
7. Other
o Operation and maintenance manuals.
o Wiring diagrams.
o Spare part catalogue.
o Factory test certificate should be submitted with the generator
o ISO certificate should be submitted with the bid
o Manufacturer standard tools
8. Specific fuel consumption of the engine in L/Kwhr at 100, 75, and
50% of rated load should be stated.
9. De rating factor for (alternator and Engine) showing the maximum
power at different altitude and temperatures should be attached
10. List of recommended spare parts for 3000hrs operation shall be
prepared and filling out price of each item.
11. Manufacturer broachers and other supporting documents relevant
for the purpose should be attached.
12. Cost of installation and installation material should be included in
the quotation.
13. Bidders should produce documentary evidence which justify past
performance and capable of similar assignment.
14. Bidders should submit the manufacturers authorization to
demonstrate that it has been duly authorized by the manufacturer to
supply these goods in the purchasers country.
15. All pages of the bid shall be signed by the bidder or a person duly
authorized.

N.B. The rated site output shall be analyzed taking into account the
continuous prime power.
16. Inspection and Tests
Inspection and testes shall be carried out by the purchasers
nominated agent at its receiving point.

Technical Evaluation Criteria


A. Technical Mandatory Criteria
1. Guaranteed characteristics should be as per the tender.
2. Bidder should submit the manufacturers Authorization

to

demonstrate that it has been duly authorized by the manufacturer to


supply these goods in the purchasers country
3. ISO Certificate should be submitted with the bid
4. The engine protection system shall ensure automatic shut down to
protect the engine from damage due to the following abnormal
conditions:
Low lubricating oil pressure
High cooling water temperature
Over speed
Engine over crank
5. The generator set should be full automatic and canopy (sound
attenuated) type with automatic mains failure (AMF) and automatic
transfer switch (ATS). The bidder shall guarantee the provision of
spare parts and after sale service. (Diesel generator without pre heater
and automatic battery charger could not serve as a full automatic
diesel generator.)
6. All pages of the bid shall be signed by the bidder or a person duly
authorized
Note: - Bids that fail to meet any of the mandatory criteria will be
considered non responsive.

B. Technical Rated Criteria

Only bids that meet mandatory criteria will be subjected to point rating
as applicable.
1. Technical Specification. (Point 50%)
2. Previous similar Experience (Number of contracts performed). (Point
20%)
3. Delivery time. (Point 10%)
4. Warranty period. (Point 10%)
5. Equipment and manpower for repair and maintenance (Point 10%)
A proposal shall be rejected at this stage if it is fail to achieve the minimum
technical score, which is 70%.
Total weight given to Technical Proposal is 70%
Total weight given to Financial Proposal 30%
The lowest financial proposal (FP) will be given a financial score of 100 points.
The financial score (FS) the other financial proposals will be computed as:

FS=100xFP/F where F is the bid price of the proposal under consideration


Proposal will be ranked to total score (S) of their combined technical score (TS)
and financial Score (FS) using the given weight.
S=(TSxT/100)+(FSxF/100) where T is the weight given to the technical
proposal and F is the weight given to the Financial proposal.
The bidder achieving the highest combined total score will be invited for
negotiation.