1 City Government of Addis Ababa
1 City Government of Addis Ababa
1 City Government of Addis Ababa
0005/2006
/ /
- 10,000.00
1.
2.
3.
4.
5.
()
6. 26 (June 3) 2006 .
400 430
Food Description
Physi
Qty
w Unit
Unit price
With vat
Remar
with Vat
total
price
1
60 KVA Generator
Pce
with Accessories
10 KVA Generator
Pce
10
with Accessories
Description of Service
Qty
Physi
Place where
Final
cal
service
completio
Unit
Installation
11
n date (s)
At the final
of service
Within one
destination
week
At the final
Within two
destination
days
Perso
At the final
Within one
destination
week after
Pcs
system
Test and commissioning
Commissio
ning
purchasers nominated
Training
11
Pcs
offer. Phrases such as refer to catalogue etc are not acceptable. The
guaranteed value should be supported by catalogues and submittal of
catalogues which describes each item is mandatory. If the guaranteed value is
not supported by catalogues the offer will be rejected.
Guaranteed Value
Required
Bidder
Required
Required
60KVA
Required
Required
Required
In line
Direct
Turbocharged
Required
Required
400/230V
50 Hz
0.8
3
Star/Y
Self exciter
H type
2500m a.s.l
250C
Guaranteed Value
Required
Bidder
Required
Required
10KVA
Required
Required
Required
In line
Direct
Natural
Required
Required
400/230V
50 Hz
0.8
3/1
Star/Y
Self exciter
H type
2500m a.s.l
250C
Therefore the technical offer of the bidders shall be evaluated as per the
following
1. General
2. Engine
tipo
turbina
condiciones
2.2.
de
debe
ser
seguridad
adaptado
en
la
para
manterer
temperatura
las
ambiente
especificada.
Exhaust System
El conjunto de escape sera dimensionado para cumplir con los
requerimientos de motor del fabricante en cuanto a cada de la
presin.
2.3.
Starting System
El motor estar equipado a 12 or 24v D.C y arranque electric
con con conjunto de arranque-parada automtica y manual. El
cargador de bacteria incluir control de carga y proteccin de
2.4.
sobrecarga.
Speed Governing
2.5.
2.6.
normal:
Baja presin del aceite lubricante
Elevada temperatura de agua refrigerante
Sobrevelocidad del motor con manivela
2.7. Engine Mounting
El motor diesel se montar sobre bancada de acero y sobre base
antivibracin. El chasis tundra la Resistencia suficiente para
cumplir lo siguiente:
Resistir la fuerza
hecha
durante
su
manipulacin
transporte.
Limitar la torsion y movimientos de flexin
Prevenir la vibracin en el rango dado,
3. Alternator
3/single phase sncrono, de rodamiento individual. It shall be
brushless, revolving field type screen protected. Its rated site output
shall not be less than the required capacity at the rated speed and P.F
at the given site condition. The insulation class of alternator, exciter,
and auxiliary windings shall be H type. Provisto de sistema de
excitacin que pueda funcionar sobre las siguientes condiciones:
3.1.
Voltage Regulation
El sistema de regulacin automatic del voltaje mantendr la
corriente al +- 1% del voltaje diseado,para cualquier carga de
cero a cien a cualquier factor de potencia. Tambin sera capaz
de restablecer el voltaje en cualquier situacin en un mximo de
2 segundosIt shall also re-establish the voltage at rated value,
with in maximum of 2 seconds of a sudden load change form no
load to full load or vice versa.
Instruments and Relays
All instruments shall be tropicalized and their accuracy class
3.2.
3.3.
3.5.
4.2.
Power factor
: 0.8
Phase
: 3/1
Alternator connection
: Start/Y
Excitation
: Self excited
Insulation class for stator and rotor
:H
5. Control Board
The control Panel of generating sets shall incorporate all
instrumentations relays mentioned above.
6. Loose Items
Lead acid battery with connecting cable
7. Other
o Operation and maintenance manuals.
o Wiring diagrams.
o Spare part catalogue.
o Factory test certificate should be submitted with the generator
o ISO certificate should be submitted with the bid
o Manufacturer standard tools
8. Specific fuel consumption of the engine in L/Kwhr at 100, 75, and
50% of rated load should be stated.
9. De rating factor for (alternator and Engine) showing the maximum
power at different altitude and temperatures should be attached
10. List of recommended spare parts for 3000hrs operation shall be
prepared and filling out price of each item.
11. Manufacturer broachers and other supporting documents relevant
for the purpose should be attached.
12. Cost of installation and installation material should be included in
the quotation.
13. Bidders should produce documentary evidence which justify past
performance and capable of similar assignment.
14. Bidders should submit the manufacturers authorization to
demonstrate that it has been duly authorized by the manufacturer to
supply these goods in the purchasers country.
15. All pages of the bid shall be signed by the bidder or a person duly
authorized.
N.B. The rated site output shall be analyzed taking into account the
continuous prime power.
16. Inspection and Tests
Inspection and testes shall be carried out by the purchasers
nominated agent at its receiving point.
to
Only bids that meet mandatory criteria will be subjected to point rating
as applicable.
1. Technical Specification. (Point 50%)
2. Previous similar Experience (Number of contracts performed). (Point
20%)
3. Delivery time. (Point 10%)
4. Warranty period. (Point 10%)
5. Equipment and manpower for repair and maintenance (Point 10%)
A proposal shall be rejected at this stage if it is fail to achieve the minimum
technical score, which is 70%.
Total weight given to Technical Proposal is 70%
Total weight given to Financial Proposal 30%
The lowest financial proposal (FP) will be given a financial score of 100 points.
The financial score (FS) the other financial proposals will be computed as: