Professional Documents
Culture Documents
Cable Tray Questions
Cable Tray Questions
Note: There are several acronyms that are used in the field to indentify rigid steel
conduit. The National Electrical Code (NEC) uses the acronym RMC which
includes rigid steel conduit, rigid aluminum conduit, stainless steel conduit and red
brass conduit. The acronym GRC galvanized rigid conduit is also frequently
used. The UL Standards refer to Electrical Rigid Metal Conduit Steel or ERMC-S.
In the following FAQs, we use the term Galvanized Steel RMC when we need to be
specific about the properties or requirements of rigid steel conduit that is
galvanized.
What are the differences between electrical metallic tubing (EMT), rigid steel
conduit (RMC), and intermediate metal conduit (IMC)? Answer
What National Electrical Code (NEC) Articles cover IMC, RMC, and EMT? Answer
What Standards apply to steel conduit/tubing? Answer
Can RMC, IMC and EMT be direct-buried? Answer
Can steel raceways be installed as a watertight system? Answer
Can RMC, IMC and EMT be installed in concrete? Answer
Do RMC, IMC and EMT comply with the requirements of NFPA 130? Answer
What is the coefficient of expansion for steel conduit/EMT and why is this
significant? Answer
What are the metric designators for steel conduit/EMT? Answer
What is the fire rating of steel conduit/EMT? Answer
Can IMC be used as a service mast? Answer
Does IMC provide as much physical protection as rigid? Answer
How do you thread IMC? Answer
What type of thread is cut on RMC and IMC? Answer
How can field-cut threads be protected against corrosion? Answer
Does RMC conform to IEC standards? Answer
Is RMC the same as schedule 40 pipe? Answer
Can EMT be used over 600 volts? Answer
1. The Steel Tube Institute Guidelines for Installing Steel Conduit/Tubing General
Product Information addresses this question. Click here to link to the section
containing a downloadable pdf file.
Back to Questions
2. Raceway Articles were renumbered in the 2002 NEC. The following list shows
the Article numbers that apply to IMC, RMC, and EMT, followed by the former Article
number in parentheses.
Back to Questions
3. Steel Tube Institute members list their products to UL standards and also
manufacture them in accordance with ANSI C80 standards (American National
Standards Institute). ASTM International does not publish standards which
specifically cover steel electrical conduit and couplings. Therefore, ASTM
specifications do not apply to metal conduit for use as a metal raceway for the
installation of wires and cables in accordance with the National Electrical Code.
The following standards apply to steel conduit and tubing:
WW-C-581 Class 1 Type A; replaced with UL Standard for Electrical Rigid Metal
Conduit - Steel, UL 6
WW-C-563 replaced with UL Standard for Electrical Metallic Tubing -Steel, UL 797
Back to Questions
4. The 2011 National Electrical Code (NEC) allows the direct burial of all three
products as noted in their respective Articles:
Galvanized Steel RMC Section 344.10 (B) Corrosion Environments. Galvanized steel
RMC, elbows, couplings, and fittings shall be permitted to be installed in concrete,
in direct contact with the earth, or in areas subject to severe corrosive influences
where protected by corrosion protection and judged suitable for the condition."
IMC Section 342.10 (B) Corrosion Environments. Galvanized steel IMC, elbows,
couplings, and fittings shall be permitted to be installed in concrete, in direct
contact with the earth, or in areas subject to severe corrosive influences where
protected by corrosion protection and judged suitable for the condition."
EMT Section 358.10 (B) Corrosion Protection. Galvanized steel EMT, elbows,
couplings, and fittings shall be permitted to be installed in concrete, in direct
contact with the earth, or in areas subject to severe corrosive influences where
protected by corrosion protection and approved as suitable for the condition."
Members of the Conduit Committee of the Steel Tube Institute apply a zinc coating
to galvanize steel RMC, IMC and EMT. Therefore, these products are protected by
corrosion protection as the Code requires. However, in severe corrosive
environments, the designer or AHJ may decide to require additional or
supplementary protection.
(Note: Soils producing severe corrosive effects have low electrical resistivity,
expressed in ohm-centimeters. Local electric utilities commonly measure the
resistivity of soils. The authority having jurisdiction (AHJ) has the authority to
determine the necessity for additional protection.) EMT in direct contact with the
soil generally requires supplementary corrosion protection. However, local
experience in some areas of the country has shown this to be unnecessary.
Back to Questions
5. No raceway system is really "watertight", including those that are glued or have
sealed joints. Normally raceways will collect condensation. The raceway is designed
to allow this moisture to drain out.
The 2011 NEC permits Galvanized steel EMT, IMC and RMC to be installed in all
wet locations both inside and outside. NEC Sections 342 (345).10(D), 344
(346).10(D) and 358 (348).10(C) caution the installer that all hardware items such
as straps, bolts, screws etc. be of a corrosion resistant material when used to
support raceways in wet locations. When thread less fittings are used with RMC and
IMC, they must be identified and listed for the application. The UL standard for
Conduit, Tubing and Cable Fittings, UL 514B, requires that thread less fittings
intended for use in wet locations be marked "Wet locations" on the fitting or its
smallest unit shipping container. Thread less fittings intended for embedment in
poured concrete are marked "Concrete-tight" or "Concrete-tight when taped".
Fittings listed as wet locations are also "Concrete-tight", but not all concrete-tight
fittings are wet locations fittings. For more information, see Section 4.3.3, Fittings
For Use With RMC, IMC, and EMT in the publication Guidelines for Installing Steel
Conduit/Tubing
If the presence of water is a problem, one of the following steps may help: 1. Install
a typical Quality concrete-polymer underground open bottom junction box over a
gravel sump. This can be done by excavating a hole approximately 3' X 3; filling it
with 1 to 2 inch gravel and placing the Quality box flush with the ground prior to
entering the building, or at the lowest location in the conduit run. 2. Install type
ECDB or equivalent drain fittings to permit the water to drain out of the conduit.
These would normally be installed in all above the ground locations prior to entering
each building or piece of equipment.
The inside of all above grade raceways installed in a wet location are also
considered to be a wet location. Section 300.9 requires conductors and cables
installed in these locations to be listed for use in wet locations in accordance with
310.10(C).
NEC 300.6(C) requires all metallic raceways installed indoors in a wet location to
be mounted so there is at least a 1/4 inch air space between the raceway and the
supporting surface to minimize the accumulation of moisture.
Back to Questions
6. The National Electrical Code (NEC) allows all three products to be installed in
concrete, as noted in their respective Articles: (Also see NEC 300.6(A)(3).
Galvanized RMC Section 344.10 (B) Corrosion Environments. Galvanized steel RMC,
elbows, couplings, and fittings shall be permitted to be installed in concrete, in
direct contact with the earth, or in areas subject to severe corrosive influences
where protected by corrosion protection and judged suitable for the condition."
IMC Section 342.10 (B) Corrosion Environments. "IMC, elbows, couplings, and
fittings shall be permitted to be installed in concrete, in direct contact with the
earth, or in areas subject to severe corrosive influences where protected by
corrosion protection and judged suitable for the condition."
EMT Section 358.10 (B) Corrosion Protection. "Ferrous or nonferrous EMT, elbows,
couplings, and fittings shall be permitted to be installed in concrete, in direct
contact with the earth, or in areas subject to severe corrosive influences where
protected by corrosion protection and approved as suitable for the condition."
Members of the Conduit Committee of the Steel Tube Institute apply a zinc coating
to galvanize steel RMC, IMC and EMT. Therefore, these products are protected by
corrosion protection as the Code requires. However, in severe corrosive
environments, the designer or AHJ may decide to require additional or
supplementary protection. If supplementary corrosion protection is required or
desired, it can be provided by a factory-applied PVC coating, paint approved for the
purpose, or tape wraps approved for the application.
When steel conduit/EMT emerges from concrete into soil, we recommend that
supplementary corrosion protection be applied a minimum of 4 inches on each side
of the point where the conduit or EMT emerges. This link will take you to an
individual page from the STI Installation Guide pertaining to concrete installation.
The UL Directory states the following for EMT: "Galvanized steel electrical metallic
tubing installed in concrete on grade or above generally requires no supplementary
corrosion protection. Galvanized steel electrical metallic tubing in concrete slab
below grade level may require supplementary corrosion protection."
Where the concrete slab is installed on grade, it is important that the raceway be
placed in between layers of rebar and above the bottom of the slab to insure full
encasement. However, there are structural concerns that must be satisfied. These
concerns are related to size of the conduit or tubing to be encased and the
thickness of the slab.
Back to Questions
7. The requirements in the 2010 edition of NFPA 130 were changed from the 2007
edition of NFPA 130.
NFPA 130 (2007 Edition): Section 5.4 Wiring Requirements state that "Materials
manufactured for use as conduits, raceways, ducts, boxes, cabinets, equipment
enclosures, and their surface finish materials shall be capable of being subjected to
temperatures up to 500C (932F) for 1 hour and shall not support combustion
under the same temperature condition."
Since the melting point of zinc is around 800F, the galvanizing may be
compromised but the conduit and EMT would still be intact after the E119 fire and
would not be "capable of supporting combustion". We cannot verify the condition of
the conductors within the conduit. However, Fire resistive Circuit integrity cables
can be used within conduit to obtain a 2-hour fire rating.
NFPA 130 (2010): Section 5.4.2 states that conduits, raceways, ducts, boxes,
cabinets, and equipment enclosures shall be constructed of noncombustible
materials in accordance with the requirements of ASTM E 136. Steel conduit and
steel EMT are noncombustible products and comply with this requirement.
Back to Questions
Back to Questions
9. The Trade Sizes and Metric Designator equivalents for RMC, IMC, and EMT are:
Trade Size
1/2
3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6
16
21
27
35
41
53
63
78
91
103
129
155
Metric Designator
Note: The Trade Sizes and Metric Designators are for identification purposes only
and are not actual dimensions. Product dimensions do not change.
Back to Questions
10. Steel conduit and tubing are considered noncombustible by the building codes.
They do not have fire ratings. This question is usually asked relative to the
penetration of a fire-rated assembly or use in an emergency circuit, fire pump, or
mass transit vehicle (see Question 4 for information on NFPA 130 "Standard for
Fixed Guide way Transit and Passenger Rail Systems").
1. Penetrations
The NEC and building codes require the sealing of openings around raceways that
penetrate a fire rated assembly. This requirement is to prevent smoke, gases and
flames from migrating from one area to another. There are many listed penetration
fire stopping systems that can be used to seal openings; the listing instructions
should be strictly followed.
Most building codes permit the openings around galvanized steel RMC, IMC and
EMT in concrete or masonry to be filled with cement, mortar, or grout. However,
since local codes sometimes vary, these requirements should be checked prior to
installation.
2. Emergency circuits (NEC 700.10(D)(1) and Fire Pump Circuits (NEC 695.6(A)(2)(d)
Prior to installing these circuits, the NEC and local or state code requirements
should be reviewed. Steel raceways withstand fire (see Question 4); however,
ordinary conductor insulation may be compromised when exposed to elevated
temperatures and a short circuit can be created. This is the reason for special
protection of emergency and fire-pump circuits. Methods of fire protection include
enclosing the raceways in a fire-rated enclosure, embedding them in concrete,
wrapping them with a listed wrap system for protection from fire or installing them
as part of a listed Electrical Circuit Protective System. The UL Fire Resistive Directory
contains information on listed fire-rated assemblies that include steel conduit and
EMT. It is the entire assembly that has the fire-rating, not the individual component.
The NEC does not require these thermal protection methods where conduit is
installed in a fully sprinkle red building.
Back to Questions
11. Yes, according to Section 230.28 of the 2011 NEC the only requirement is that
the service mast "...shall be of adequate strength or be supported by braces or guys
to withstand safely the strain imposed by the service drop." IMC meets this
requirement. The local utility should be consulted for service mast requirements.
Back to Questions
12. Yes, even though IMC is lighter and has a thinner wall than rigid steel conduit, it
provides equivalent protection to conductors. This is achieved through the steel
processing during manufacturing. The NEC allows IMC to be used in all of the
same atmospheres and occupancies as rigid steel conduit. Articles 342 for
Intermediate Metal Conduit and 344 (for Rigid Metal Conduit contain identical
installation requirements. Both products are UL listed to their respective standards.
Back to Questions
13. Cutting and threading of IMC is covered extensively in the Steel Tube Institute
publication Guidelines for Installing Steel Conduit/Tubing under Section 4, General
Installation Practices. You can jump to that section by clicking here to download a
puff file. Back to Questions
Back to Questions
14. The NEC requires that the threads of both RMC and IMC be cut with a 3/4 inch
taper per foot (1 in 16) per ANSI/ASME B.1.20.1 Standards for Pipe Threads, General
Purpose (Inch). This applies to both factory and field threads. This is the same taper
as standard plumbing pipe.
Back to Questions
15. Factory cut threads have corrosion protection applied at the factory. Field cut
threads are required to be coated "with an approved electrically conductive,
corrosion-resistant compound "where corrosion protection is necessary" (see NEC
2011 300.6(A). Where installed in wet or outdoor locations, we recommend that all
field cut threads and any threads exposed after installation be protected against
corrosion. We recommend that all field cut threads be protected against corrosion
where they will be installed in wet or outdoor locations. The thread surface should
be protected with conductive rust resistant coating. Zinc-rich paint is a typical
coating, but there are other conductive coatings that can be used.
Field threads should be cut one thread short. This will insure a good connection and
allow the entire thread surface to be inside the coupling.
Back to Questions
16. The Rigid Steel Conduit used in the U.S. is manufactured to UL Safety Standard
No. 6 and to ANSI C80.1. There is one IEC standard entitled Extra Heavy-Duty Rigid
Conduit (IEC 981) which is very similar to the Rigid Steel Conduit listed to UL 6 with
the exception of some dimensional differences. At the current time, no one lists
product to IEC 981.
Back to Questions
17. No. The term Schedule 40 originated with an ASTM specification and has come
into general usage. It is still addressed in a number of ASTM specifications, whose
requirements typically include dimensional and strength parameters.
Rigid conduit is intended for electrical applications, not structural ones. Its
requirements are governed by UL and ANSI specifications, not by ASTM. The main
issue here is that, whereas dimensions may be similar between the two, rigid
conduit is not intended for, is not designed for, and is not tested for any strength or
structural requirements
Back to Questions
Part II of Article 300 (Wiring Methods) of the National Electrical Code covers
"Requirements for Over 600 Volts, Nominal". In Section 300.37 of Part II entitled
"Aboveground Wiring Methods", EMT is listed as one of the permitted wiring
methods.
Back to Questions
19. Yes, RMC, IMC and EMT are all permitted as an equipment grounding conductor
in accordance with NEC 250.118. It is permitted to add a supplementary
equipment grounding conductor sized in accordance with NEC 250.122. This is a
systems design consideration. If a supplementary equipment grounding conductor
is used, it is still very important to comply with NEC 300.10 and 300.12, since
approximately 90% to 95% of the current will flow on the conduit and not in a
supplementary conductor. For information on the equipment grounding capabilities
of RMC, IMC and EMT, click here for a link to the section with the results of a
research study performed by the Georgia Institute of Technology.
Back to Questions
20. Yes. A copy of the study conducted by Georgia Institute of Technology titled
Modeling and Evaluation of Conduit Systems for Harmonics and Electromagnetic
Fields is the basis for the Grounding and Electromagnetic Interference (GEMI)
Analysis software, which is available for downloading.
Back to Questions
21. Steel conduit and tubing offer several advantages over alternative wiring
methods:
EMI Shielding
Physical protection of conductors
Proven equipment grounding conductor
Low coefficient of expansion - infrequent need for expansion fittings
Impact resistant -high tensile strength
Noncombustible
Adaptable to future wiring changes
Low life-cycle costs
Recyclable (For more documentation click here
Back to Questions
Back to Questions
23. Yes, per 2011 NEC Article 358 all fittings are required to be listed (358.6) and
suitable for a wet location (358.42). In358.42, it is stated that "Couplings and
connectors used with EMT shall be made up tight. Where buried in masonry or
concrete, they shall be concretetight type. Where installed in wet locations, they
shall comply with 314.15(A)." Article 314 includes installation requirements for
fittings used to join raceways and to connect raceways and cables to boxes and
conduit bodies. 314.15(A) states that in damp or wet locations, boxes, conduit
bodies, and fittings "shall be placed or equipped so as to prevent moisture from
entering or accumulating within the box, conduit body, or fitting. Boxes, conduit
bodies and fittings installed in wet locations shall be listed for use in wet locations."
Back to Questions
24. Unlike other materials, steel contains recycled material and is also fully
recyclable. In fact, according to the Steel Recycling Institute (SRI), steel is the
world's most recycled material. All of our member conduit producers use recycled
steel in their conduit and tubing products
The amount of recycled material in steel conduit/tubing products depends upon the
process used by our various steel suppliers.
Back to Questions
25. If you have other questions or need additional information regarding steel
conduit, its uses, benefits or installation, please contact Richard Loyd. Email:
dickonel@aol.com Phone: 480-802-9228
Back to Questions